HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

Similar documents
HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

HGM1750 Genset Security Module USER MANUAL Smartgen Technology

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

HSC940 Genset Controller CONTENTS 1 OVERVIEW PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION KEY FUNCTIONS...

HGM6000K Series Automatic Generator Module OPERATING MANUAL Smartgen Electronic

USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO.,LTD

HGM6000K Series Automatic Generator Module USER MANUAL Smartgen Technology

HGM6320T AUTOMATIC GENERATOR CONTROLLER USER MANUAL

HGM6320T AUTOMATIC GENERATOR CONTROLLER USER MANUAL

HGM6310D/6320D AUTOMATIC GENERATOR MODULE USER MANUAL

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

HGM6100K Series Automatic Generator Module OPERATING MANUAL Smartgen Electronics

HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL

Generator Controller Manual

DEEP SEA ELECTRONICS PLC

702 AUTOMATIC START MODULE OPERATING INSTRUCTIONS

DEEP SEA ELECTRONICS PLC

HGM6410/6420 AUTOMATIC GENERATOR MODULE WITH J1939 INTERFACE SOFTWARE MANUAL

HGM9510 GENSET PARALLEL (WITH GENSET) UNIT USER MANUAL

HGM6400 Automatic Genset Controller (With J1939 Interface) USER MANUAL Smartgen Technology

GENSET CONTROL MODULE LEVEL 0 A120A. User selectable time delays for engine start and engine stop (cool down).

GCU-10. Automatic Engine Control Unit Operators Manual

DEEP SEA ELECTRONICS PLC

HGM6410/6420. Automatic Generator Module. With J1939 Interface OPERATING MANUAL. Smartgen Electronics

GENSET CONTROL MODULE

Deep Sea Electronics Plc

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

HAT220A ATS CONTROLLER USERS MANUAL

HGM6100N SERIES (HGM6110N/6120N/6110NC/6120NC/6110CAN/6120CAN) GENSET CONTROLLER USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

DEEP SEA ELECTRONICS PLC

Flight Systems. Replacement for KASSEC DESCRIPTION

DEEP SEA ELECTRONICS PLC

GENSET CONTROL MODULE A121A / A241A

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL

Auto Mains Failure AMF Controller AE10113

Te 803 Electronic Controller. Service, Operation & Technical Information Manual

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

HGM9520 Genset Parallel (With Mains) Unit USER MANUAL. Smartgen Technology

DKG-114 MANUAL AND REMOTE START UNIT

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

1. AC VOLTS: Displays generator output in voltage. 2. AC FREQUENCY: Displays the speed of the generator set in Hertz.

DEEP SEA ELECTRONICS PLC

PSM72H Push-Button Start Module

HGM7110DC DC Genset Controller USER MANUAL ZHENGZHOU SMARTGEN TECHNOLOGY CO.,LTD

USER MANUAL FOR GC500 GENSET CONTROLLER SEDEMAC ABSTRACT

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

The measurements module provides the following engine features information:

ENGEN -100/ENGEN -200 ENGINE GENERATOR CONTROLLER

GSC300 Auto Start Engine Controller

Deep Sea Electronics Plc

OPERATING INSTRUCTION: DGC-6D/6D1I

GSC300. Auto Start Engine Controller. Installation and User Manual for the GSC300 Auto Start Engine Controller. Full Version

STANDARD OWNER S MANUAL

Cat/DCG-6D1I/07-08/03/Ver 1 Page 2/10

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

Manual and Remote Start Unit with Key Switch, 72x72 DIN Size

Generator Sets Controller 210. Operation Manual. Ver1.0

GSC300 Auto Start Engine Controller

DKG-317 MANUAL AND REMOTE START UNIT

Starting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F

EAOM-10.2 AUTOMATIC TRANSFER SWITCH & START UNIT FOR DIESEL GENERATORS

AUTOMATIC STAND-BY AND PEAK-LOAD CONTROL

DEEP SEA ELECTRONICS PLC DSE3210 Configuration Suite Software Manual

DKG-215 MANUAL AND REMOTE START UNIT

ENGINE PROTECTION BOARD PDM1

DEEP SEA ELECTRONICS PLC

DSEULTRA DSE6000 Quick Start Guide Document Number

HAT700 Series HAT700/HAT700I/HAT700B/HAT700BI/HAT700S ATS CONTROLLER USER MANUAL

DKG-207 AUTOMATIC MAINS FAILURE AND REMOTE START UNIT

Deep Sea Electronics Plc

AUTOSTART 705S V1.00 AUTOSTART 710S / 720S / 730S V1.04 Programming Reference and Check Sheets

Model H30 Operation Manual

Energy Division

DKG-509 AUTOMATIC MAINS FAILURE UNIT

ECONOMISER SERIES E2T USER MANUAL

TG350 User Manual. Manual Revision: Min. FW Revision: Date Released: 09/01/ DYNAGEN Technologies Inc

DEEP SEA ELECTRONICS DSE7110 MKII / DSE7120 MKII Configuration Suite PC Software Manual

OPERATING INSTRUCTIONS MCP-MT1

DKG-109J AUTOMATIC MAINS FAILURE UNIT

Dash8-200/300 - Auxiliary Power Unit APU CONTROLS AND INDICATORS. Page 1

DEEP SEA ELECTRONICS

GSC300. Auto Start Engine Controller. Installation and User Manual for the GSC300 Auto Start Engine Controller. Full Version

OPERATING INSTRUCTIONS ECON-M

DKG-707 MULTI GENSET PARALLELLING UNIT WITH J1939 INTERFACE

Te 804 Electronic Controller. Service, Operation & Technical Information Manual

ES52 Auto Start Engine Controller Installation and User Manual for the ES52 Auto Start Engine Controller.

ICON 2 1. FEATURES AND CHARACTEIRICS

DEEP SEA ELECTRONICS PLC DSE3210 CONTROLLER OPERATORS MANUAL

DEEP SEA ELECTRONICS

PowerCommand 2100 digital generator set control

GENSET PRODUCTS 013 2

Generator Start Control Module

Specification. Terminals Detail. AUTO (Remote Start) Operation. TEST Operation. OFF Operation

Bombardier Challenger Auxiliary Power Unit

DKG-109 AUTOMATIC MAINS FAILURE UNIT

ST315B. User Handbook STAFFOR. ST315B Temperature Programmer. See separate handbook for Installation Instructions Issue: 2.00

Generator Start Control Module

Transcription:

HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

CONTENT 1 SUMMARY... 4 2 FEATURES... 4 3 SPECIFICATION... 4 4 DISPLAY SYMBOL AND OPERATION... 5 5 ALARM... 7 6 PARAMETERS TABLE (ONLY ADJUST VIA PC)... 8 7 TERMINAL... 10 8 CASE DIMENSIONS (HOLE: 67MM 67MM)... 11 9 TYPICAL CONNECTIONS... 11 HGM72 Automatic Generator Module ISSUE 2010-06-01 Version 1.2 Page 3 of 11

1 SUMMARY The Module HGM72 is an Automatic Engine Control Module. It selects 3 kinds of working state, can pass panel light touch buttons artificially start/stop genset, also can through remote start signal input automatic starting generator, and can detect fault (low oil pressure, high water temperature, emergency stop alarm, over speed) automatically disconnect fuel relays and stop electromagnet to electric suction close. Panel LED indicator fault state, provide real and effective fault alarm signal. 2 FEATURES The power supply a wide range (8~35) VDC, can adapt different starting battery voltage environment. With low oil pressure, high water temperature, overspeed, and emergency stop, start failures and so on protection and instructions. Can provide charging generator excitation function. With idle speed control and ETS solenoid function. Speed signal depend on frequency of generator. Panel LED display various operation and alarm state. 2 relay fixed output port (fuel output, starting output). 3 a programmable output port, can set common alarm output, preheat output, idle control, stop output, and other functions. Provide PC programming port, genset work necessary various delay, output port definition, power threshold can via PC settings, PC only need a USB port. Built-in watch dog can never be dead halt, ensuring smooth program execution. Modular configuration design, Flame Retardant ABS plastic shell, inserted type connection terminals, flush type installation, compact structure, easy installation. 3 SPECIFICATION a) DC supply: (8~35) V. b) Single-phase AC input: AC (15~300) V (+ 20%) 50Hz/60Hz. c) Five relay output(b+, 5A): Crank output Fuel output HGM72 Automatic Generator Module ISSUE 2010-06-01 Version 1.2 Page 4 of 11

Configurable output1 Configurable output2 Configurable output3 HGM72 Automatic Generator Module d) 3 Digit input port: connect to (B-) is active. e) Power Consumption: standby mode(12v: 0.3W, 24V: 0.4W),working (12V: 1W, 24V: 1.1W). f) Operating Temperature Range: (-30~+70) C. g) Dimensions: 72mm 72mm 52mm. h) Panel cutout: 67mm 67mm. i) Weight: 0.2kg. 4 DISPLAY SYMBOL AND OPERATION a) PUSH BUTTON Symbol Defined Description Manual start button Push this button, generator will start, and the module comes into manual state. Auto state button Push this button, the module comes into auto state. Stop button Push this button, generator will stop, and the module comes into stop state. b) LED Symbol Defined Description Running Running led Lighten when engine start successfully. Emergency Emergency stop alarm Lighten when emergent stop input is led active. High Water High Water Temp alarm Lighten when high water Temp led temperature alarm is appearing. Low Oil Low Oil pressure alarm Lighten when the module detects that the engine oil pressure has Pressure led fallen below the low oil pressure pre-alarm setting level. Lighten when the engine speed has Over speed Over speed alarm led risen above the over speed pre alarm setting. Charge Failure Charge Failure alarm led Lighten if the module does not detect a voltage from the alarm light terminal on the auxiliary charge HGM72 Automatic Generator Module ISSUE 2010-06-01 Version 1.2 Page 5 of 11

Low Battery Over Crank Common Alarm Low Battery alarm led Over Crank alarm led Common Alarm led alternator. Lighten if the module detects that the plant DC supply has fallen below the low voltage setting level. Lighten when over crank alarm is appearing. Lighten when emergency stop, high temperature, low oil pressure, over speed, under speed, charge failure, battery over voltage, battery under voltage, crank failure, stop failure, and no generator is appearing. c) OPERATION Module has three states: stop state (OFF), man state (MAN), auto state (AUTO). 1) Man Start ( ) When push Man start button ( ), preheat will first output, and start preheat delay, when preheat delay is end, fuel output 1 second, preheat output will stop, and crank output is start. Here engine will start, when crank successfully, crank output stop. Then engine comes into the safe time. When the safe time is end, then engine comes into the idle time. When the safe time is end, then idle output is out and engine will run at full tilt. 2) Auto State ( ) When push ( ) button, the module will enter automatic state. Here if remote start input is active (connect to B-), the engine will start after the delay of start engine. Preheat will first output, and start preheat delay, when preheat delay is end, fuel output 1 second, preheat output will stop, and crank output is start. Here engine will start, when crank successfully, crank output stop. Then engine enter the safe delay. When the safe delay is end, then engine enter the idle delay. When the safe delay is end, then idle relay is close and genset raise high speed. Note: In the process of starting interval delay, fuel output disconnect, starting interval delay after three seconds, preheat and ETS solenoid output, and ETS solenoid stop disconnect after starting interval delay, fuel HGM72 Automatic Generator Module ISSUE 2010-06-01 Version 1.2 Page 6 of 11

output, preheat output before genset start off. When remote start input is inactive, the engine enter the idle process after the delay of engine stop, idle relay disconnect, fuel relays output after the idle delay, ETS solenoid output, genset will automatically stop, ETS solenoid disconnect when genset stop steady. 3) Stop State ( ) Push the ( ) button when engine is running, the button beside led will lighten, enter idle process, idle relay disconnect, idle delay ended, fuel disconnect, ETS solenoid output, genset stop, ETS solenoid disconnect when genset stop steady. When genset fault alarm is appear, push the ( ) button (keep after 1 second loosen) can relieve the alarm. If exceed 1 second, panel all lights will all bright (test lamps function). When engine is waiting state, push ( ) button 1 second above, ETS solenoid will output and all led will be Lighten. Loosen the stop buttons, ETS solenoid output disconnect instantly, and test lamps function is over. When engine is waiting state, only emergent stop alarm can be check. 5 ALARM a) Low Oil Pressure: check after the safe delay, the duration of 2 seconds above, the module will alarm and stop engine. b) High Temperature: check after the safe delay, the duration of 3 seconds above, the module will alarm and stop engine. c) Over speed: check after the preheat delay, the duration of 1.5 seconds above, the module will alarm and stop engine. d) Under speed: check when engine run at full tilt, the duration of 15 seconds above, the module will alarm and stop engine. e) Charge Failure: check when engine run at full tilt, the duration of 3 seconds above, and the module will warn but don t stop engine. f) Over Crank: when engine crank fail over the times of configure, the module will alarm and stop engine. g) Stop Failure: when engine is stop fail, the module will warn. h) No generator: check after the idle delay, when generator frequency for zero and the duration of 5 seconds above, the module will alarm and stop engine. HGM72 Automatic Generator Module ISSUE 2010-06-01 Version 1.2 Page 7 of 11

i) Battery over voltage: The DC supply has risen above the high volts setting level for the duration of the high battery volts 20 seconds. j) Battery under voltage: The DC supply has low above the under volts setting level for the duration of the low battery volts 20 seconds. k) Emergency Stop: When emergency stop input, ETS solenoid stop immediately output, and then fuel disconnect, preheat and start signal emit emergency stop alarm signal. l) Common Alarm: when any alarm or warn is appear, this alarm will active. When the over speed, under speed, high temperature, low oil pressure, emergency stop, no generator, crank failure, stop failure alarm, battery over voltage, battery under voltage, common alarm LED illuminate, and common alarm output. 6 PARAMETERS TABLE (ONLY ADJUST VIA PC) Num Parameter Range Default Remark 1 Start delay (0-3600)s 1 It s the delay from remote start signal is active or mains is failure, to start generator. 2 Stop delay (0-3600)s 5 It s the delay from remote start signal is inactive or mains is normal, to stop generator. 3 Number of Crank (1-9) 3 Numbers of crank cycles. This is the maximum amount of 4 time that the module will Cranking (3-60)s 5 energize the starter motor for time during starting attempts once the starter has engaged. 5 6 Crank rest time Safe running time (3-60)s 10 (1-60)s 10 This is the amount of time the module will wait for between start attempts. This is to allow the starter motor to cool and the starter batteries to recover. This timer dictates how long the module will ignore the Low oil pressure, High Engine Temperature, Under speed, Under volts and any other inputs configured as active from safety on. HGM72 Automatic Generator Module ISSUE 2010-06-01 Version 1.2 Page 8 of 11

Num Parameter Range Default Remark 7 8 9 10 Start idle time Stop idle time ETS solenoid hold Fail to stop delay (0-3600)s 0 (0-3600)s 0 (0-120)s 30 (0-120)s 0 11 Preheat time (0-300)s 0 12 13 14 Gens over freq Gens under freq Condition of Crank (0-75)Hz 57 (0-59)Hz 0 (0-1) 0 This is the amount of time that the start Idle speed is held active. These allow the engine to hold low speed. This is the amount of time that the stop Idle speed is held active. These allow the engine to hold low speed. This timer is used if the unit is configured to operate an Energize to stop engine. It dictates the duration that the ETS output will remain active after the module has detected the engine has come to rest. If the ETS output is not configured, this timer will still operate, preventing an immediate restart. Once the module has given a shutdown signal to the engine it expects the engine to come to rest. It monitors the Oil pressure and speed sensing sources and if they still indicate engine movement when this timer expires a Fail to stop alarm signal is generated. This timer dictates the duration that the pre-heat output will be active before an attempt is made to start the engine. Once this timer has expired cranking will commence. When generator frequency is over than the point and hold great than 3 seconds, generator over frequency is active. When generator frequency is low than the point, generator low frequency and hold great than 15 seconds is active. 0: Freq 1: Freq+ Oil pressure HGM72 Automatic Generator Module ISSUE 2010-06-01 Version 1.2 Page 9 of 11

Num Parameter Range Default Remark 15 16 17 18 19 20 21 22 Freq disconnect Battery over volt Battery under volt Charge failure volt Configurable output1 Configurable output2 Configurable output3 Module address 7 TERMINAL (5-30)Hz 10 (0-35)V 35.0 (0-30)V 8.0 (0-30)V 4.0 (1-8) 5 (1-8) 6 The same of 19 (1-8) 1 The same of 19 (1-254) 1 a) Terminal 1(B-): connect to the cathode of battery. b) Terminal 2(B+): connect to the anode of battery. When generator frequency is large than this point, starter will disconnect. When generator battery voltage is over than the point and hold for 20 seconds, battery over voltage signal is active. It s a warning alarm. When generator battery voltage is less than the point and hold for 20 seconds, battery under voltage signal is active. It s a warning alarm. During generator is running, when charge alternator WL/D+ voltage is low than this point and remain for 5 seconds, generator will warning alarm. 1. Common alarm 2. Preheat control 3. Fuel output 4. Crank output 5. Idel control 6. Energized to stop output 7. Over speed alarm output 8. Running 9. Close ATS 10. Open ATS Address of module for communication c) Terminal 3(Em. stop input): emergent stop input, connect to (B-) is active. d) Terminal 4(Fuel Output): Fuel Output, (B+, 5A). e) Terminal 5(Start Output): Start Output, (B+, 5A). f) Terminal 6(Remote Start Input): Remote Start Input, connect to (B-) is active. HGM72 Automatic Generator Module ISSUE 2010-06-01 Version 1.2 Page 10 of 11

g) Terminal 7(D+): Connect to the terminal WL (or D+) of charger. h) Terminal 8(LOP Input): Low oil pressure input, connect to (B-) is active. i) Terminal 9(HWT. Input): High temperature input, connect to (B-) is active. j) Terminal 10(L), 11(N): Alternator Input. k) Terminal 12(Configurable Output1): Configurable output, (B+, 5A). l) Terminal 13(Configurable Output2): Configurable output, (B+, 5A). m) Terminal 14(Configurable Output3): Configurable output, (B+, 5A). n) PC (LINK): Connect to PC by SG72. 8 CASE DIMENSIONS (HOLE: 67mm 67mm) 9 TYPICAL CONNECTIONS HGM72 Automatic Generator Module ISSUE 2010-06-01 Version 1.2 Page 11 of 11