Cleaning Flooded Gear

Similar documents
Cleaning Flooded Gear

Introduction CAUTION. S&C Power Operated Metal-Enclosed Switchgear Outdoor Distribution (4.16 kv, through 34.5 kv)

Introduction CAUTION CAUTION. S&C Power Operated Metal-Enclosed Switchgear Indoor and Outdoor Distribution (4.16 through 34.5 kv)

S&C Vista Underground Distribution Switchgear

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Instructions for Installation and Operation

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

Installation, Operation, and Maintenance

Installation and Operation

INSTRUCTIONS Ç CAUTION. S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, and SMD-3. For Field Assembly and Installation NOTE INSTRUCTION SHEET

S&C Manual PME Pad-Mounted Gear

SPECIFICATION BULLETIN

Installation and Operation

Instructions for Installation and Operation

Installation and Operation

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

Instructions for Installation

Installation And Operation

Instructions for Installation

Installation. S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Table of Contents

INSTRUCTION MANUAL Metal-Enclosed Switchgear Indoor and Outdoor Distribution 2400 volts through 34,500 volts

Inspection and Maintenance

S&C Source-Transfer Vista Underground Distribution Switchgear

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

S&C Circuit-Switchers Mark VI Installed on S&C Mounting Pedestals 84- through 102-inch Phase Spacing Outdoor Transmission (69 kv through 138 kv)

Installation. S&C Omni-Rupter Switches Outdoor Distribution 14.4 kv and 25 kv

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

SPECIFICATIONS. S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATION BULLETIN Indoor Distribution (4.8 kv and 13.

Installation. Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Table of Contents. Instruction Sheet

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

www. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003

University of Houston Master Construction Specifications Insert Project Name

Three-Phase Pole Mounted Recloser

Installation. S&C Circuit-Switchers Mark VI 69-kV 51-inch Phase Spacing Single Pedestal Design Outdoor Transmission.

S&C Switch Operators Types AS-1A and AS-10

WARNING. TYPE PSI/II PAD-MOUNT SWITCHGEAR with Non-Loadbreak Fuse Mountings 15kV 25kV INSTRUCTIONS. Qualified Persons. For Installation and Operation

Installation Instructions Electric Heaters 5 20 kw

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

INSTRUCTIONS For Field Assembly, Installation, and Maintenance

INSTRUCTIONS Ç CAUTION. S&C Manual PMH Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) For Installation TABLE OF CONTENTS

Installation Instructions Electric Heaters 5 20 kw

Installation Instructions

A. Submit manufacturer's literature and technical data before starting work.

INSTRUCTIONS For Field Assembly and Installation

INSTRUCTIONS Ç CAUTION Ç IMPORTANT

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

Medium Voltage Metal-Enclosed Switches

15-kV Live Terminal Primary Metering Station Pad-Mounted Outdoor

Typical Specification

Installation, Maintenance, and Operation Manual

Operation. S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles. Table of Contents

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

MASTERCLAD. Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class Instruction Bulletin. Retain for future use.

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

Medium Voltage Metal-Enclosed Switches

DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak

GTX UNIT SUBSTATION Installation, Maintenance & Operation Manual

INSTRUCTION MANUAL #103

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Specifications. S&C Mini-Rupter Switches Indoor Distribution (4.16 kv through 25 kv) Manually Operated Styles

15-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 140 Amp (Max) Clip-Mounted Current-Limiting Fuses

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

CABINET - CURRENT TRANSFORMER Indoor - Outdoor 240 Volts Amperes Maximum

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

Cutler-Hammer INSTRUCTIONS FOR MAGNUM DS METAL-ENCLOSED LOW-VOLTAGE SWITCHGEAR ASSEMBLIES WITH MAGNUM DS BREAKERS IB E

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH

ibusway for Data Center

Product Specifications for Aluminum Vertical Break Switches

MASTERCLAD Metal-Clad Indoor Switchgear

Installation and Operation

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

MATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Metal-Clad Indoor Switchgear

S&C Mini-Rupter Switches Application The Standard Mounting Arrangement Scheme for S&C Mini-Rupter Switches Typical ED, reduced from full 11 size.

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

S&C M Series Switch Operators Reciprocating and Rotating Switch Operation

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

S&C Recloser Bypass Disconnects

Bayside Model BU2050 Installation, Maintenance, and Operation Manual

OPERATION AND MAINTENANCE OF TRAYER 4000 SERIES PADMOUNTED VACUUM FAULT INTERRUPTER

UNDERGROUND SERVICES - SECONDARY

TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV

Installation Instructions LINK---C

Switchgear Skid, C1192

Publication No.: PSG

Operation. S&C Source-Transfer Vista Underground Distribution Switchgear. Pad-Mounted, Dry-Vault-Mounted, Wet-Vault-Mounted, and UnderCover Styles

Transcription:

S&C Manual PMX Modular Metal-Enclosed Switchgear Outdoor Distribution (13.8 kv and 25 kv) Cleaning Flooded Gear Table of Contents Section Page Section Page Introduction.... 2 Safety Information Understanding Safety-Alert Messages.............. 3 Following Safety Instructions.... 3 Replacement Instructions and Labels.... 3 Cleaning Procedure...5 Replacement Parts and Lubricants... 8 July 13, 2009 S&C Electric Company Instruction Sheet 627-800

Introduction Ç CAUTION The equipment covered by this publication must be inspected and maintained by qualified persons who are thoroughly trained and who understand any hazards that may be involved. This publication is written only for such qualified persons and is not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment. This publication provides cleaning recommendations for S&C Manual PMX Modular Metal-Enclosed Switchgear that has been flooded. Before the gear can be returned to service, contaminants must be removed; insulators, bushings, bus, and barriers must be cleaned; and moving contacts and switch quick-make, quick-break mechanisms must be lubricated. Equipment and cables must be de-energized and grounded in each module prior to starting work. Applicable instruction sheets, drawings, and wiring diagrams along with documentation for low-voltage components of the switchgear not of S&C manufacture can be found in an envelope labeled INSTALLATION AND OPERATION INFORMATION KIT, located in a holder inside the appropriately labeled switchgear module door. If cleaning or maintenance is required beyond the scope of this publication, or if replacement parts and lubricants are needed, contact the nearest S&C Sales Office. Have the complete catalog number of the gear and date of shipment (as shown in the nameplate) available for reference. 2 S&C Instruction Sheet 627-800

Safety Information Understanding Safety-Alert Messages There are several types of safety-alert messages which may appear throughout this instruction sheet as well as on labels and tags attached to the S&C PMX Modular Manual Metal-Enclosed Switchgear. Familiarize yourself with these types of messages and the importance of the various signal words, as explained below. Ç DANGER DANGER identifies the most serious and immediate hazards which will likely result in serious personal injury or death if instructions, including recommended precautions, are not followed. Ç WARNING WARNING identifies hazards or unsafe practices which can result in serious personal injury or death if instructions, including recommended precautions, are not followed. Ç CAUTION CAUTION identifies hazards or unsafe practices which can result in minor personal injury or product or property damage if instructions, including recommended precautions, are not followed. NOTICE NOTICE identifies important procedures or requirements that, if not followed, can result in product or property damage if instructions are not followed. Following Safety Instructions NOTICE Read this instruction sheet thoroughly and carefully before cleaning your S&C PMX Modular Manual Metal- Enclosed Switchgear. If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Authorized Distributor, or call S&C Headquarters at (773) 338-1000, Monday through Friday between 8:30 AM and 5:00 PM Central Standard Time. (In Canada, call S&C Electric Canada, Ltd. at (416) 249-9171, Monday through Friday between 8:00 AM and 5:00 PM Eastern Standard Time.) Replacement Instructions and Labels If you need additional copies of this instruction sheet, contact your nearest S&C Sales Office or S&C Authorized Distributor, or call S&C Headquarters. It is important that any missing, damaged, or faded labels on the equipment be replaced immediately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C Authorized Distributor, S&C Headquarters, or S&C Electric Canada. S&C Instruction Sheet 627-800 3

Safety Information Ç DANGER When access to high-voltage bays is required, it should be restricted to qualified persons who observe the following procedures: 1. Adhere to prescribed safety rules at all times. 2. Be certain that fuses, interrupter switches, their mechanisms, and any other devices are disconnected from all power sources and grounded before that device is inspected, serviced, or repaired. 3. Always assume that both sets of terminals on any interrupter switch or fuse are energized unless proven otherwise by test, by visual evidence of open-circuit conditions on both terminals ends, or by grounding. 4. Test for voltage. Qualified persons should be certain that they have and know how to operate the correct test equipment for determining the voltage on both sets of terminals on any fuse or interrupter switch. 5. After the gear has been completely disconnected from all sources of power and tested, properly connect suitable grounding leads to both sides of the equipment, that is, to the incoming and outgoing phases of the equipment to be maintained. 6. Padlock and tag equipment in accordance with the user s standard operating procedures. SPECIAL WARNING: All voltage transformers and voltage sensors must be disconnected when external voltage is used to test any secondary-side wiring or devices, to void energizing the high-voltage conductors through the voltage transformers or sensors. Remove the primary fuses of the voltage transformers and disconnect the secondaries by removing the secondary fuses or by disconnecting the secondary leads. Do not disconnect the burden or the voltage limiter from the voltage sensor until the switchgear is de-energized; otherwise the voltage sensor will be damaged. For voltage sensors, the secondary leads must be shorted by inserting screws into shorting-type terminal blocks. 7. When the equipment to be cleaned is not of S&C manufacture, follow instructions supplied by the manufacturer of the equipment. 8. Make certain that ground connections from the ground bus (or ground pad on a single-module assembly) to the permanent station or system ground facility are made. No equipment should be returned to service unless such grounds are properly made. NOTE: Occasionally low-voltage components may require maintenance. In the servicing or repair of space heaters, voltage-transformer secondary wiring, and any other components located in a high-voltage module, all of the preceding safety procedures apply. The maintenance of other low-voltage components (such as voltmeters, ammeters, relays, etc.), isolated from high voltage, may be performed under the safety rules for equipment rated 600 volts or less. If maintenance is to be performed on ammeters, short-circuit the secondary connections of the associated current transformer at the shorting-type terminal block prior to removal of the ammeter. This may require access to a high-voltage module, in which case the foregoing procedures apply. When returning the equipment to service, the following procedures should be observed: 1. Reconnect any low-voltage terminals that may have been disconnected when servicing the gear. 2. Make certain that fuses (or switch blades in lieu of fuses) are closed and securely latched. 3. Open any grounding switch, or remove other grounding means, before energizing the associated interrupter switch(es). 4. Close and securely latch each switchgear-module door before energizing the circuit or operating any switching device. 5. Lock interrupter switches in the open or closed position as dictated by the electric power system design. 6. Padlock all doors, switch-operating handles, and covers before leaving the installation site, even momentarily. Observe this procedure even in those cases where the gear is accessible only to qualified persons. 4 S&C Instruction Sheet 627-800

Cleaning Procedure This procedure must be followed in the order indicated. Step Procedure 1 Remove the barriers in each module 2 Remove and discard the arc compressors from each Mini-Rupter Switch 3 Thoroughly rinse the interior of each module with clean water. Do not use a pressure washer 4 Clean the bus, Cypoxy bus support insulators and bushings, and barriers as follows: a) Wash with phosphate-free mild soap such as Joy Dishwashing Liquid and water. Do not use industrial-strength cleaning solutions such as Formula 409 or Simple Green, which contain solvents. Solvent vapors can attack arc compressor components and fuse pull rings, resulting in reduced interrupting performance or weakened parts b) Rinse thoroughly with clean water c) Dry with compressed air 5 Lubricate each Mini-Rupter Switch quick-break mechanism with WD-40. Do not get WD-40 on insulators or bushings 6 Lubricate each Mini-Rupter Switch contact with Nye Rheolube. Do not use lubricants which contain solvents 7 Install new arc compressors on each Mini-Rupter Switch 8 Replace low-voltage devices such as meters, relays, switches, fault indicators, and fuses 9 Follow the equipment manufacturers recommendations with respect to cleaning and reuse of medium-voltage devices such as voltage transformers, current transformers, terminators, and surge arresters 10 Reinstall the barriers S&C Instruction Sheet 627-800 5

Cleaning Procedure Step Procedure 11 For each live-front entrance and feeder module furnished with fuses, open each fuse and remove it from its hinge For each SM-20 and SM-40 Power Fuse, do the following: a) Remove the end fittings and Silencer. Wash them with phosphate-free mild soap such as Joy Dishwashing Liquid and water. Do not use industrial-strength cleaning solutions such as Formula 409 or Simple Green, which contain solvents. Solvent vapors can attack fuse pull rings, resulting in reduced interrupting performance or weakened parts b) Thoroughly rinse the end fittings and Silencer with clean water c) Dry the end fittings and Silencer with compressed air d) Make that the latch on the upper end fitting pivots freely. If not, replace the end fittings e) Apply No-Ox-Id sure A to the contact rod assembly. Do not get No-Ox-Id A on the latch or pull ring f) Apply a light film of Amojel petroleum jelly to the surfaces of the latch and pull ring where they touch during operation g) Discard the SMU-20 or SMU-40 Fuse Unit. Also discard all spare fuse units For each SM-4Z and SM-5S Power Fuse, do the following: a) Remove the Silencer or Snuffler exhaust control device. Wash it with phosphate-free mild soap such as Joy Dishwashing Liquid and water. Do not use industrial-strength cleaning solutions such as Formula 409 or Simple Green, which contain solvents b) Thoroughly rinse the exhaust control device with clean water c) Dry the exhaust control device with compressed air d) Discard the SM-4Z or SM-5S Holder and SM-4 or SM-5 Refill Unit. Also discard all spare refill units For each Fault Fiter Electronic Power Fuse, do the following: a) Remove the holder. Wash it with phosphate-free mild soap such as Joy Dishwashing Liquid and water. Do not use industrial-strength cleaning solutions such as Formula 409 or Simple Green, which contain solvents. Solvent vapors can attack fuse pull rings, resulting in reduced interrupting performance or weakened parts b) Thoroughly rinse the holder with clean water c) Dry the holder with compressed air d) Make sure that the latch on the holder pivots freely. If not, replace the holder e) Apply No-Ox-Id A to the contact rod assembly. Do not get No-Ox-Id A on the latch or pull ring f) Apply a light film of Amojel petroleum jelly to the surfaces of the latch and pull ring where they touch during operation g) Discard the interrupting module and control module. Also discard all spare interrupting and control modules 6 S&C Instruction Sheet 627-800

Cleaning Procedure Step Procedure 12 For each entrance and feeder module furnished with enhanced fuse handling, unlatch and pivot each TransFuser Mounting and remove the fuse For each SME-20 and SME-40 Power Fuse, do the following: a) Remove the end fittings and Silencer. Wash them with phosphate-free mild soap such as Joy Dishwashing Liquid and water. Do not use industrial-strength cleaning solutions such as Formula 409 or Simple Green, which contain solvents b) Thoroughly rinse the end fittings and Silencer with clean water c) Dry the end fittings and Silencer with compressed air d) Make sure that the latch on the lower end fitting pivots freely. If not, replace the end fittings e) Apply No-Ox-Id A to the contact rod assembly and its mating contact. Do not get No-Ox-Id A on the latch f) Discard the SMU-20 or SMU-40 Fuse Unit. Also discard all spare fuse units g) Lubricate the TransFuser roller tracks with Nye Rheolube and check for free movement. Do not use lubricants which contain solvents For each SME-4Z Power Fuse, do the following: a) Remove the Silencer. Wash it with phosphate-free mild soap such as Joy Dishwashing Liquid and water. Do not use industrial-strength cleaning solutions such as Formula 409 or Simple Green, which contain solvents b) Thoroughly rinse the Silencer with clean water c) Dry the Silencer with compressed air d) Discard the SME-4Z Holder and SM-4 Refill Unit. Also discard all spare refill units e) Lubricate the TransFuser roller tracks with Nye Rheolube and check for free movement. Do not use lubricants which contain solvents For each Fault Fiter Electronic Power Fuse, do the following: a) Remove the holder. Wash it with phosphate-free mild soap such as Joy Dishwashing Liquid and water. Do not use industrial-strength cleaning solutions such as Formula 409 or Simple Green, which contain solvents b) Thoroughly rinse the holder with clean water c) Dry the holder with compressed air d) Make sure that the latch on the holder pivots freely. If not, replace the holder e) Apply No-Ox-Id A to the contact rod assembly and its mating contact. Do not get No-Ox-Id A on the latch f) Discard the interrupting module and control module. Also discard all spare interrupting and control modules g) Lubricate the TransFuser roller tracks with Nye Rheolube and check for free movement. Do not use lubricants which contain solvents 13 Perform a 60-Hz dielectric test on the switchgear using the test values shown in S&C Instruction Sheet 627-500 S&C Instruction Sheet 627-800 7

Replacement Parts and Lubricants Part Number 9999-044 Nye Rheolube, ¼-Ounce Tube Description 9999-130 Nye Rheolube, 7-Pound Can 0352-006 No-Ox-Id A, 5-Gallon Can 0352-313 Amojel Petroleum Jelly, 5-Gallon Can 0825-435 Penetrox A, 4-Ounce Tube SA-40726 Mini-Rupter Switch Arc Compressor Replacement Kit 1023-332 Aluminum Bus Hardware, ½ 13 x 1½ Hexhead Cap Screw, Galvanized 1023-812 Aluminum Bus Hardware, ½ 13 Hex Nut, Galvanized CD-2262-2 Aluminum Bus Hardware, ½ Belleville Washer 1323-304 Copper Bus Hardware, ½ 13 x 1½ Hexhead Cap Screw, Stainless Steel 1323-811 Copper Bus Hardware, ½ 13 Hex Nut, Stainless Steel 2140-013 Copper Bus Hardware, ½ Flat Washer, Brass 1340-058 Copper Bus Hardware, ½ Lockwasher, Stainless Steel Live-Front Module Fuse-Unit End Fittings and Holders 3097 SM-20 Fuse-Unit End Fittings 3090 SM-40 Fuse-Unit End Fittings 86632R2 86633R2 86642R2 86643R2 SM-4Z Holder, 13.8 kv SM-4Z Holder, 25 kv SM-5S Holder, 13.8 kv SM-5S Holder, 25 kv 99112 Fault Fiter Holder, 13.8 kv 99113 Fault Fiter Holder, 25 kv Enhanced Fuse Handling Module Fuse-Unit End Fittings and Holders 3093 SME-20 Fuse-Unit End Fittings 3094 SME-40 Fuse-Unit End Fittings 90362 SME-4Z Holder, 13.8 kv 90363 SME-4Z Holder, 25 kv 3132 Fault Fiter Holder, 13.8 kv 3133 Fault Fiter Holder, 25 kv Printed in U.S.A. 8 S&C Instruction Sheet 627-800