DETAILED EQUIPMENT SPECIFICATION MR SERIES WATER SOFTENERS

Similar documents
DETAILED EQUIPMENT SPECIFICATION MHC SERIES WATER SOFTENERS

DETAILED EQUIPMENT SPECIFICATION MDAS SERIES DEALKALIZERS

INDUSTRIAL GRADE WATER SOFTENERS LWTS INDUSTRIAL SERIES

CAT231.1 PRESSURE GAUGE AND TEST TAP KIT SKID MOUNTING 220V, 50HZ, 1Ø OPERATING CONDITIONS 25 TO 100 PSI 100 F MAX IMUM TEMPERATURE SERIES METER

INDUSTRIAL GRADE WATER SOFTENERS LWTSF INDUSTRIAL SERIES

CAT231.1 SHUT OFF KIT (SOK) TO PREVENT BYPASS PRESSURE GAUGE AND TEST TAP KIT SKID MOUNTING 220V, 50HZ, 1Ø

PRESSURE GAGES AND TEST TAPS

SECTION 1. Fleck Fiberglass Softeners. *Shown with factory SKID & Interconnecting Plumbing

DETAILED EQUIPMENT SPECIFICATION MRO-4 SERIES REVERSE OSMOSIS SYSTEMS

DETAILED EQUIPMENT SPECIFICATION HIGH PURITY LABORATORY WATER SYSTEM

Fleck Top Mount Section 1 Fiberglass Softeners

Fleck Epoxy Lined Section 2 Steel Softeners

TNT SERIES WATER CONDITIONERS

Fleck Fiberglass Section 9 Chloride Dealkalizers

Clean and soft water for business needs. Commercial softening equipment. COMMERCIAL WATER SOFTENERS

Commercial Softeners

Technical Manual. Models: Standard Softeners High Efficiency Softeners Combination Softeners S150 S250 S250 OD S350 S550 S650 S650 OD Q850 Q850 OD

SECTION H4 BOILERMATE DEAERATORS

BNT 85 /185 Valve Operation Manual

INSTALLATION, OPERATING AND SERVICE MANUAL

SECTION H3 TRAYMASTER SERIES DEAERATORS

SAMPLE SPECIFICATIONS

AQT-56SE ELECTRONIC SERIES PROGRAMMING MANUAL CONTROL VALVES

WATER SOFTENER SEMI AUTOMATIC INSTALLATION & OPERATING INSTRUCTIONS. Serial No :

CLEAVER-BROOKS. SAB/Q Heavy Duty Co-Current Commercial and Industrial Water Softeners

IWT 565 Series Valve Operation Manual

65 Series. Valve Operation Manual

Signature Series. Duplex Softener Service Manual

AQT-275 SERIES SERVICE MANUAL CONTROL VALVES

BLAKE WATER SOLUTIONS U.S. NORTHEAST REGION DISTRIBUTION CATALOG REV 09/09

MASTER. Water Conditioning Corp. Installation and Operation Manual. MCA Combination Series Residential Units

Water Specialist 1 Control Valve Series Model: WS1CS 1.25 Control Valve Series Model: WS1.25CS

Performance Specifications

Installation and Operations Manual

Series 774 Automatic Skid Package

FreezeFree TM Nitro Anti-Icing System GENERAL SPECIFICATIONS

MGTE Series 1 1/2 Metered & Time Clock

DCS7 Water Softener - Product Manual

AquaMatic Series. A100 and A200 Stager Controls

P/N: (Rev. G 1/19/10)

Water Specialist CI Control Valve Programming and Cover Drawing Manual

FLOOD PROTECTION SHUT DOWN VALVE (3 and smaller)

Duplex Commercial Pressurizer -DCP

ProFloSE. Downflow Brining Service Manual. IMPORTANT: Fill in pertinent information on page 2 for future reference.

Rayne Guardian Water Conditioner This manual contains information on setting the controller and normal operating maintenance required by the owner

Installation and Operation Manual

VALVE. Water Treatment Controls ~~~~ SERVICEMANUAL ----

OPERATION AND MAINTENANCE MANUAL PF-20 Series. Permanent Media Filters PUROFLUX FILTRATION AND CONTROL SYSTEMS

Model 7000XTR. Service Manual. IMPORTANT: Fill in Pertinent Information on Page 3 for Future Reference

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

3200ET TIMER. Service Manual. IMPORTANT: Fill in pertinent information on page 2 for future reference.

AQT-56 POWERFLO SERIES SERVICE MANUAL CONTROL VALVES

COMMERCIAL UST ADD WATER BULLETIN; ISSUE 1

ROGERS MACHINERY COMPANY, INC

WATER SOFTENER SERIES DAY TIMER INSTALLATION & OPERATING INSTRUCTIONS. Serial No :

Water Specialist 1 Control Valve Series Model: WS1CI 1.25 Control Valve Series Model: WS1.25CI

Plastic Valve Nest Epoxy Lined Section 7 Steel Filters - 18 thru 48

6700XTR Upflow. Service Manual. IMPORTANT: Fill in Pertinent Information on Page 3 for Future Reference

General Operation. To set Time of Day. To set Time of Regeneration / Backwash

SIMPLEX PREMIUM WATER SOFTENER INSTALLATION AND USER GUIDE

Weld tabs are standard on all media tanks and screen filter housings.

Value Super Filter Max Installation Manual

Iron Gate Air Pump System Manual

AMERICAN RECIRCULATING SAND FILTER SYSTEMS

Specifications. Autotrol 255 Valve. Autotrol 255 Series Valve Specifications. Flow Rates (Valve Only) Regeneration Operation

SECTION FACILITY FUEL - NATURAL GAS PIPING AND SYSTEMS

H-125 HE SERIES. Owner s Manual HIGH EFFICIENCY SYSTEM. Manufactured by: HELLENBRAND, INC. Web:

Owner s Manual. PS48/PS80 Advantage Series Salt Based Water Softeners

HYDRO ION Water softener Type: VAD CS

SPECIFICATIONS EFFLUENT/SUMP SIMPLEX SYSTEM ZOELLER SUBMERSIBLE DEWATERING OR EFFLUENT PUMPS

SPECIFICATIONS EFFLUENT/SUMP DUPLEX SYSTEM ZOELLER SUBMERSIBLE DEWATERING OR EFFLUENT PUMPS

TECHNICAL SHEET AUTOTROL PERFORMA CV CONTROL VALVE - LOGIX SERIES WATER PURIFICATION VALVES - AUTOTROL

Water Specialist 1 Control Valve Series Model: WS Control Valve Series Model: WS1.25

SPECIFICATIONS SEWAGE/SUMP DUPLEX SYSTEM ZOELLER COMPANY SUBMERSIBLE SEWAGE OR DEWATERING PUMPS

COMMERCIAL / INDUSTRIAL WATER SOFTENERS

A. The latest published edition of a reference shall be applicable to this Project unless identified by a specific edition date.

WS1 & 1.25 Man u al. Introduction. The following general warnings and the specifications in Table 1 must appear in the OEM s System Manual.

XFL70 FLOW RATE (LPM) Flow Rate (GPM)

Duplex Jobsite Wired Basin Package Non-Sparking Stainless Rail Non-Sparking, Class I, Group D, Division 1, with Steel Cover

FLECK 5600 SERVICE MANUAL. waterpurification.pentair.com

Water Specialist PR Control Valve Programming and Cover Drawing Manual

Simplex Jobsite Wired Basin Package Non-Sparking Stainless Rail Non-Sparking, Class I, Group D, Division 1, w/fiberglass Cover

Owner s Manual AMERICAN AQUA Saline, MI (734) Howell, MI (517) Adrian, MI (517)

Pump Specifications FL100 Series Submersible Effluent Pump

COMBINATION PRESSURE REDUCING AND SOLENOID SHUTOFF CONTROL VALVES 2.01 COMBINATION RESSURE REDUCING AND SOLENOID SHUTOFF CONTROL VALVE

wd-2

SILVER COMPOSITE SERIES VALVE Manufactured After June, 2000

SOLENOID CONTROL VALVE

SECTION PIPING SPECIALTIES PART 1 GENERAL 1.1 SUMMARY

Commercial Water Treatment Catalog

Logix Magnum IT and Cv Valves. Installation and Service Manual

Owner s Manual. Manufactured by: HELLENBRAND, INC. 404 Moravian Valley Road Waunakee, Wisconsin

NUGEN Pure Water Systems Fusion XT. Installation Instructions and Owners Manual

Water Specialist EI Control Valve Programming and Cover Drawing Manual

NOTE: All dimensions shown are rounded up to the nearest inch to get even dimensions. TM.400NMTVP doc Page 1 of 5

ADVANCE. Backwashing Filters and Tannin Filter. Installation Instructions & Owner s Manual

Pump Specifications FL50 Series 1/2 hp Submersible Effluent Pump

MODULATING FLOAT CONTROL VALVE

LEAD FREE * LFF113RFP Flood Protection Shut Down Valve

Assembled Engineered Systems. Softeners Filters Specialty Systems

Transcription:

5356 Hillside Avenue Indianapolis, IN 46220 P: +1 888-56-Water (569-2837) F: +1 317-255-4727 info@nancrede.com www.nancrede.com DETAILED EQUIPMENT SPECIFICATION MR SERIES WATER SOFTENERS 1.0 SCOPE 1.1 Provide as indicated a factory assembled vertical pressure type water softener system shipped with manifold piping attached to the resin tank for ease of installation and start up. The system shall be of an approved design as fabricated by a manufacturer regularly engaged in the production of water treatment equipment. All equipment and material shall be supplied in compliance with the specifications as intended for a complete and operational system. 1.2 Qualified manufacturers of water treatment equipment of the type specified are Marlo, Inc. or engineers approval equal. 2.0 GENERAL DESCRIPTION 2.1 The system, in compliance with equipment specifications, is described as an automatic (single) (parallel twin) (alternating twin) (parallel triple) (alternating triple) water softener system meeting the performance and design data requirements as hereinafter specified. 2.2 The system specifications are based on Marlo Model. 3.0 PERFORMANCE & DESIGN DATA 3.1 INFLUENT WATER ANALYSIS Total Hardness GPG as CaCO 3 Iron (Fe) ppm Turbidity (NTU) ph 3.2 EFFLUENT WATER QUALITY ZERO GPG Hardness (ASTM Soap Test Method) 3.3 DESIGN PARAMETERS Continuous System Flow & Pressure Drop GPM @ psi Peak System Flow & Pressure Drop GPM @ psi Daily Water Usage Gallons/Day Daily Hours of Water Demand Hours/Day Operating Temperature Range F Maximum Operating Pressure Range (System) PSIG Electrical Requirements V Hz 3.3 EQUIPMENT SCHEDULE Softener Tanks Qty. Dia. in. Side Shell in. Service Valves Size in. Type. Softening Resin Qty. cu. ft. 1

4.0 EQUIPMENT Brine Maker Qty. Dia. in. Height in. Salt Storage lbs. Regeneration Type (Time clock) (Metered) Water Meter (s) Qty Size in. Type. 4.1 Tank Softener tank(s) shall be of welded construction of tank-quality carbon steel. The tank(s) shall have threaded openings for pipe connections and an 11 x 15 manhole in the top head (for tanks 30 diameter and smaller; two 4 x 6 handholes shall be provided in the top head and lower side shell). The tank(s) shall be rated for 100 psig working pressure and 150 psig test pressure. Support legs shall be the strap-type permanently welded to the lower tank head. The tank(s) shall have their exterior and interior protected with a hot dipped galvanized application after fabrication. A minimum freeboard of 50% shall be provided for backwash expansion above the normal ion exchange resin bed level. 4.2 Tank Option Provide pressure vessel in accordance with ASME Section VII. Working pressure to be 100, 125 or 150 pounds, hydrotested to 150, 187.5 or 225 psig stamped and certified. 4.3 Tank Option Provide cold-set epoxy internal lining with a minimum of 10 12 mils DFT and a rust resistant prime coat external coating 2 3 mils DFT. 4.4 Tank Option Provide safety blue epoxy finish paint 6 8 mils DFT over exterior tank and valve surfaces. 4.5 Upper Distributor The upper distribution system shall be a single point baffle constructed of Schedule-40 galvanized steel pipe and fittings. 4.6 Lower Distributor The lower distributor system shall be of the hub and radial type design, constructed of PVC with slotted full flow non-clogging replaceable ABS strainers and covered with a subfill of 1/8 x 1/16 washed gravel. 4.7 Main Operating Valves The main operating valves shall be a nest of individual diaphragm valves. The valves shall have cast iron bodies, Buna-N diaphragm and stainless steel and brass internal parts. The valves shall be slow opening and closing, and free of water hammer. There shall be no contact of dissimilar metals within the valves and no special tools shall be required to service the valves. Valves can be operated either hydraulically or pneumatically. 4.8 Brine System The brine system shall be platform type with a dry salt storage compartment and a saturated brine compartment sufficient for at least four regenerations at full salting. The tank shall be of polyethylene construction. It shall be equipped with a float operated plastic brine valve and allow for simple adjustment of salt dosage without removal of salt or salt shelf system. 2

4.9 Resin Resin shall be of a premium grade high capacity synthetic sulfonamide styrene divinyl benzene type, to be furnished in the sodium form. It shall be stable over the entire ph range, have good resistance to bead fracture, and be insoluble in all common solvents. The resin shall be capable of 30,000 grains per cubic foot capacity when regenerated with 15 lbs. NaCI. 4.10 Flow Control An automatic backwash control shall be provided to maintain a proper backwash and fast flush flows over wide variations of operating pressure. Controller shall contain no moving parts, and require no filed adjustment. 4.11 Piping and Fittings The main operating valves and manifold piping shall be factory assembled and shipped attached to the resin tank for ease of installation and start-up. Piping shall be Schedule-40 galvanized steel. Galvanized fittings shall be standard Class 150 threaded malleable iron. 4.12 Control System A NEMA 12 rated, factory mounted and wired electrical enclosure with all timing and sequencing controls for each softener shall be manufactured and provided by the same vendor providing the water treatment hardware. The controls shall include an automatic regeneration timer having the capability of providing site adjustable regeneration steps of backwash, brine injection, brine displacement, flush and return to service. Indicator lights on the panel door shall display the current status of the system. A multi-ported pilot control stager shall be factory wired and pre-tubed to automatically pressure activate the main operating valves through the steps of regeneration. An indicator on the stager indicates the cycle of operation at all times. Complete function and control of all regeneration steps can be performed manually in the event of a power failure. 5.0 REGENERATION INITIATION OPTIONS (Choose One) 5.1 Time Clock The 12-Day electrical time clock controller shall be fully adjustable to initiate regeneration at any hour of the day and any day of the week. 5.2 MF-ET Automatic Reset Meter (Single Tank) The single water softener shall be equipped with a single, impeller type water meter in the outlet piping. When the user specified volume is reached, the meter register will send a 120 volt signal to the control system that will direct the softener to begin regeneration immediately or delayed to a user set time. Meter register shall be mounted in a NEMA-3R environmental enclosure and have digital display of continuous flow rate and volume totalization. 5.3 MF-ET Automatic Reset Meter (Twin Alternating) The twin water softener shall be equipped with a single, impeller type water meter in the common outlet header. When the user specified volume is reached, the meter register will send a 120 volt signal to an alternator stager that will direct the softener presently on-line to begin regeneration immediately while placing the stand-by softener into service mode. System shall produce a continuous supply of soft water. Meter register shall be mounted in a NEMA-3R environmental enclosure and have digital display of continuous flow rate and volume totalization. 3

5.4 MX Electronic Programmable Controller The system shall consist of (two) or (three) media tanks each having a dedicated paddle wheel type flow sensor in the softener outlet piping and operate in either of these user selected modes: Alternating One (1) media tank will be in standby or regeneration and one (1) or two (2) media tanks will be on-line. At a user-specified volume the standby tank will go on-line and the exhausted tank will go into regeneration. After regeneration this tank will go into standby until its rotation to go back on-line. Parallel - All media tanks are on-line simultaneously. As each media tank s user specified volume is reached it shall immediately be taken off-line, regenerated and placed immediately back on-line. Additive Flow - One (1) media tank, designated as the primary, will remain on-line at all times. Variation of treated water flow demand shall automatically cause one additional media tank (up to two additional media tanks) to change status from standby to on-line and back to standby as needed. When the primary media tank regenerates, the next media tank in sequence shall become the primary. As each media tank user set volume is reached, it will immediately be taken off-line, regenerated and placed immediately back on-line or standby depending on treated water flow demand. The controller shall be capable of continuously determining the exhaustion rate of each media tank thus automatically avoiding the possibility of a simultaneous regeneration attempt. Simultaneous regenerations are not possible. The exchange capacity of each softener can be the same or different. Flow rate or peak flow rate indication shall be continuously displayed for each unit. The continuous flow range is 0 999 flow units per minute (gallons, cu-ft., liters, cu-m, etc.). Cumulative volume totalization to eight (8) digits shall be continuously displayed for each unit. 6.0 SKID MOUNT, PREPIPE AND PREWIRE OPTION The softener mineral tanks shall be skid mounted on a 4 channel iron skid (7.25 lbs. per foot, ASTM grade A-36). The skid shall be cross-braced with 4 channel or angle iron. All steel surfaces shall be finish coated to match exterior of softener tanks. All interconnecting piping shall be the same material as the valve nest manifold piping and shall be assembled by the manufacturer. This shall include inlet and outlet bronze isolation valves for each tank and a bronze system bypass valve. Inlet, outlet and drain headers shall be provided and terminated at the skid edge. All piping shall be suitably supported by channel supports anchored to the skid. Electric wiring, where applicable, shall be complete between all inter unit controls and require only a single power source connection. The inter unit wiring shall be contained in waterproof conduit. All inter-tank hydraulic or pneumatic tubing shall be installed as part of the skid package. The mineral tanks are to be bolted to the skid. Permanent attachment, or welding, will not be acceptable. The entire skid mounted system shall be leak and electrically tested as a unit by the manufacturer before shipment. 7.0 ACCESSORIES 7.1 Water test kits for hardness test shall be supplied to conduct soap drop test. 7.2 Pressure Gauges for hard water inlet and soft water outlet. 7.3 Sampling Cocks for hard water inlet and soft water outlet. 4

8.0 INSTRUCTIONS A complete set of installation, operating and maintenance manualsshall be provided. 9.0 FIELD SERVICE The services of a factory authorized service representative shall be made available to supervise, inspect and provide operator training as required for initial start-up and system operation. 10.0 GUARANTEES Attrition loss of mineral is guaranteed not to exceed 3% per year for a period of three (3) years. All mechanical and electrical equipment is guaranteed for one (1) year against any defects in workmanship or materials. Any part proving defective shall be replaced or repaired within this period at manufacturer s option. The manufacturer guarantees that under actual operating conditions the mineral shall not be washed out of the system during the service run or backwashing period; and that the turbidity and color of the effluent, by reason of passing through the softener system, shall not be greater than the incoming water; and that the underdrain system, gravel and minerals shall not become fouled, either with turbidity or by dirt, rust or scale from the softening system while operating as noted in manufacturer s instructions. 5