Faults Mitigation Control Design for Grid Integration of Offshore Wind Farms and Oil & Gas Installations Using VSC HVDC

Similar documents
FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Temporary Rotor Inertial Control of Wind Turbine to Support the Grid Frequency Regulation

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Modelling and Simulation of DFIG with Fault Rid Through Protection

Fault Rid Through Protection of DFIG Based Wind Generation System

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

CONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS

Statcom Operation for Wind Power Generator with Improved Transient Stability

Pumped storage for balancing wind power fluctuations in an isolated grid

Squirrel cage induction generator based wind farm connected with a single power converter to a HVDC grid. Lluís Trilla PhD student

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Wind Farm Evaluation and Control

Experience on Technical Solutions for Grid Integration of Offshore Windfarms

IMPROVEMENT IN DOUBLY FED INDUCTON GENERATOR UNDER FAULT USING INDUCTOR

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE

A Variable Speed Wind Generation System Based on Doubly Fed Induction Generator

DUAL BRIDGE RECTIFIER FOR PMSG VARIABLE SPEED WIND ENERGY CONVERSION SYSTEMS

Design and Control of Lab-Scale Variable Speed Wind Turbine Simulator using DFIG. Seung-Ho Song, Ji-Hoon Im, Hyeong-Jin Choi, Tae-Hyeong Kim

ABB POWER SYSTEMS CONSULTING

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

Effect of crowbar resistance on fault ride through capability of doubly fed induction generator

Use of STATCOM for Improving Dynamic Performance of Wind Farms Connected in Power Grid

ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG

Possibilities of Distributed Generation Simulations Using by MATLAB

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

Coordinated Control of DFIG under Grid Fault Condition in Wind Energy Conversion System

Low-Frequency AC Transmission for Offshore Wind Power

DC Voltage Droop Control Implementation in the AC/DC Power Flow Algorithm: Combinational Approach

Full-Scale Medium-Voltage Converters for Wind Power Generators up to 7 MVA

LVRT of DFIG Wind Turbines - Crowbar vs. Stator Current Feedback Solution -

IJSER. 1. Introduction. 2. Power flow of Doubly fed Induction Generator (DFIG) K. Srinivasa Rao 1 G. Kamalaker 2

ASSESSING BEHAVOIR OF THE OUTER CROWBAR PROTECTION WITH THE DFIG DURING GRID FAULT

Modeling of doubly fed induction generator (DFIG) equipped wind turbine for dynamic studies

Study of DFIG based Wind Turbine for Reactive Power Generation Capability

Design and Modelling of Induction Generator Wind power Systems by using MATLAB/SIMULINK

Wind Generation and its Grid Conection

Critical Clearing Time and Voltage Stability of DG Integration in Lebanon: A Simulation Using MATLAB/SIMULINK

Simulated Switching Transients in the External Grid of Walney Offshore Wind Farm

Published by: PIONEER RESEARCH & DEVELOPMENT GROUP ( 201

Reactive power support of smart distribution grids using optimal management of charging parking of PHEV

Workshop on Grid Integration of Variable Renewable Energy: Part 1

Integration of Large Wind Farms into Electric Grids

Anupam *1, Prof. S.U Kulkarni 2 1 ABSTRACT I. INTRODUCTION II. MODELLING OF WIND SPEED

Keywords: DFIG wind turbine, MPPT, Voltage stability control, Power factor control, PSCAD simulation, Voltage oriented vector control.

Voltage Control Strategies for Distributed Generation

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

POWER TRANSMISSION OF LOW FREQUENCY WIND FIRMS

Modeling of Active Crowbar Protection Scheme for Various Types of Fault in Wind Energy Conversion System using DFIG

Simulation and Analysis of a DFIG Wind Energy Conversion System with Genetic Fuzzy Controller

CHAPTER 5 ACTIVE AND REACTIVE POWER CONTROL OF DOUBLY FED INDUCTION GENERATOR WITH BACK TO BACK CONVERTER USING DIRECT POWER CONTROL

Asian Journal on Energy and Environment ISSN Available online at

FAULT ANALYSIS FOR VOLTAGE SOURCE INVERTER DRIVEN INDUCTION MOTOR DRIVE

Low-Voltage Ride-Through Capability Improvement of DFIG-Based Wind Turbines

Laboratory Tests, Modeling and the Study of a Small Doubly-Fed Induction Generator (DFIG) in Autonomous and Grid-Connected Scenarios

(by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen)

Control of Grid Voltage and Power of Doubly Fed Induction Generator wind turbines during grid faults

Available online at ScienceDirect. Energy Procedia 42 (2013 ) Mediterranean Green Energy Forum MGEF-13

HVDC POWER FROM SHORE. B. WESTMAN* K. ERIKSSON* G. PERSSON* A. MÆLAND** ABB Sweden*, Norway**

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011

Grid Code Testing of Wind Turbines by VSC-based Test Equipment

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz

A New Control Algorithm for Doubly Fed Induction Motor with Inverters Supplied by a PV and Battery Operating in Constant Torque Region

EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION

J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy***

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode

Design and Implementation of Reactive Power with Multi Mode Control for Solar Photovoltaic Inverter in Low Voltage Distribution System

Power Quality Improvement Using Statcom in Ieee 30 Bus System

Stability Study of Grid Connected to Multiple Speed Wind Farms with and without FACTS Integration

A Comparative Study of Constant Speed and Variable Speed Wind Energy Conversion Systems

Model Predictive Control of Back-to-Back Converter in PMSG Based Wind Energy System

ENHANCEMENT OF TRANSIENT STABILITY OF SMART GRID

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

Modelling and Simulation of DFIG based wind energy system

Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM Using Fuzzy Logic Controller

Wind Power Integration in Isolated Grids enabled by Variable Speed Pumped Storage Hydropower Plant

Control Strategy for DFIG Wind Turbine to Enhance LVRT under Various Faults

CHAPTER 5 ROTOR RESISTANCE CONTROL OF WIND TURBINE GENERATORS

Diversifying into Marine Energy. ABB March 2015

International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. (An ISO 3297: 2007 Certified Organization)

Performance of Low Power Wind-Driven Wound Rotor Induction Generators using Matlab

A.Arun 1, M.Porkodi 2 1 PG student, 2 Associate Professor. Department of Electrical Engineering, Sona College of Technology, Salem, India

ABB Wind Power Solution

STUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM

Transient Stability Improvement of a FSIG Based Grid Connected wind Farm with the help of a SVC and a STATCOM: A Comparison

Introduction CONTENT Future of offshore wind energy in Europe Offshore wind energy in Spain Alternatives to the transmission system to the grid Compar

Stability Enhancement of DFIG Fed Wind Energy Conversion System Using Crowbar Protection Scheme

Facility Employing Standard Converters for Testing DFIG Wind Generators up to 30kW

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

IJREE - International Journal of Research in Electrical Engineering ISSN:

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

STEADY STATE ELECTRICAL DESIGN, POWER PERFORMANCE AND ECONOMIC MODELING OF OFFSHORE WIND FARMS

Dynamic Behaviour of Asynchronous Generator In Stand-Alone Mode Under Load Perturbation Using MATLAB/SIMULINK

Grid voltage control by using DFIG during grid faults

Offshore Wind Connections HVDC for Offshore Grids

Transcription:

SPEEDAM 2010 International Symposium on Power Electronics, Electrical Drives, Automation and Motion Faults Mitigation Control Design for Grid Integration of Offshore Wind Farms and Oil & Gas Installations Using VSC HVDC Bing Liu, Member, IEEE, Jia Xu, Raymundo E. Torres-Olguin, Tore Undeland, Fellow, IEEE Department of Electric Power Engineering, Norwegian University of Science and Technology Abstract This paper presents an analysis and new fault mitigation methods of grid integration of offshore wind farms and oil & gas installations using Voltage Source Converter (VSC) HVDC transmission system. On the fault occurrence in the onshore AC grid, the proposed DC link voltage controller initiates fast output power drop of the wind farm, in order to avoid the overvoltage in the DC transmission link. On the faults occurrence in the oil & gas installation, the proposed control employs a voltage-dependent limiter, to limit the maximum amount of active power from the offshore VSC. Simulation results in PSCAD / EMTDC show the satisfied performance of the proposed control strategy for the case of one 300 MW VSC transmission system connecting an offshore wind farm and oil & gas installations to the grid. Keywords Voltage Source Converter (VSC), Offshore wind farm, Oil & Gas Installation, Grid Integration. I. INTRODUCTION Offshore wind farms promise to become an important energy source in the near future, because of several favourable characteristics such as higher wind speeds, less turbulence and availability of large areas. However, long distances from wind farms to the shore pose challenges to the design of offshore power transmission links, such as the requirements on low electricity loss and the high grid faults toleration ability, which are critical for the economic feasibility of huge offshore wind projects. Since the most of planning offshore wind farms are 100 km away from onshore, HVDC transmission solutions will be feasible and more competitive than the AC solutions [1]. Two major HVDC solutions for the offshore power transmission are the Line-Commutated-Converter (LCC) HVDC transmission system using thyristors and VSC HVDC system using IGBTs. The LCC HVDC solution has relatively less loss and longer commercial operation experience. However, the huge size and weight of LCC converter station is the major drawback for offshore applications [1] [2]. The VSC HVDC has recently gained growing interest due to its simplified modularity, the independence of AC network, and the decoupled active and reactive power control capability. The configuration and control topologies of the VSC- HVDC transmission system for the offshore wind farms were presented in previous publications [3] [4]. Because some oil and gas installations are geologically close to high wind resource areas [10]. It is feasible to integrate the offshore oil & gas installations and the wind farms using single HVDC transmission link to onshore grid, which potentially can abate significant CO 2 emission caused by gas turbines or diesel generators at oil & gas installations. In [5] [6], the control and performance of VSC HVDC system during a balanced phase to ground fault at onshore AC grid were studied, however, it is hard to find any detailed study on the offshore AC grid balanced faults. Furthermore, in some of previous publications, the wind farm with variable speed wind turbines is simplified as a controlled current source or synchronize generator. Obviously, the operation and response of variable speed wind turbines under network disturbance will be significantly different from any current source, for example, the wind turbine drive train oscillations may cause oscillating power variations to the grid. Thus the model presented in this paper consists of wind air dynamic model and two mass drive drain model, which can be used for studying how the wind speed variations and mechanical oscillations influence the offshore AC grid. This paper is organized as follows: First, a VSC HVDC transmission topology is proposed for grid integration of oil & gas installations and offshore wind farms. Second, the HVDC system mathematic model and the control strategy during the normal operation will be presented. Third, the control approaches to ride through various faults both in offshore and onshore AC grid will be investigated. At last, some simulation results in PSCAD will be presented to illustrate the stable performance of the proposed several control strategies to override faults. I. SYSTEM CONFIGURATION Figure 1 shows the single line diagram of the VSC HVDC system for the control strategy analysis. It comprised a wind farm with variable speed wind turbine, several oil & gas installations, and a VSC HVDC link. Fig. 1 Single line diagram of the VSC HVDC transmission system for the control strategy analysis 978-1-4244-4987-3/10/$25.00 2010 IEEE 792

The oil & gas installation has both passive loads and induction machines. The offshore side VSC collects and transmits active power to onshore grid side VSC by dc cables. The variable speed operation of wind turbines can be achieved with the back-to-back converter and pitch control. A crowbar is connected to the convert to protect DC capacitor over voltage and rotor over current. Stator voltage-oriented vector control method is used to control the back-to-back converter [7]. The detailed control strategy of wind turbine with Doubly Fed Induction Generator (DFIG) will not be explained in this paper, since it was well documented in several references [3] [7]. Extra power command Reference power Speed- Power Relationship Generator power Paero Nominal rotor speed Rotor speed - - + Drive train representation Pitch Controller β system, shown as follows: Offshore AC Frequency Controller Several frequency control strategies of VSC-HVDC systems were proposed in [9]. However, the fixed frequency control strategy is favorable for transmitting the offshore wind energy. First, with the fixed offshore AC grid frequency, the offshore VSC behaves as infinite voltage source and absorb the fast changing wind power generation, so a bi-direction power transmission can be achieved. Second, with the fixed frequency the extra power control loop is not needed, therefore, the fast communication system among the offshore wind farms, the oil & gas installation and VSC is not necessary. The diagram of the frequency control strategy for the offshore side VSC is also shown in Figure 3. A fixed nominal frequency (f ref ) is supplied to the VSC output voltage (V vsc ); therefore, the VSC is controlled as a voltage source with constant frequency and phase angle. The AC voltage controller consists of one PI regulator and feedback from measurement, as shown in Fig. 3. Torque controller Converter representation Aerodynamic representation Fig. 2 DFIG wind turbine control topology An equivalent model of wind farms is developed based on aggregating wind turbines, which consists of air dynamic and mechanical model, generator and power converter control [8], as shown in Figure 2. The parameters of each power system component will be presented in the simulation results session. II. SYSTEM CONTROL The control objective of VSC transmission system are: 1), to collect and transmit power according wind generation and oil & gas installation load situation, 2), to maintenance DC link voltage to a reasonable range, and 3), to provide reactive power compensation if necessary. 4), to regulate the offshore AC grid voltage and frequency. To achieve the upper mentioned objectives, there are different control strategies for offshore side VSC and onshore side VSC. The offshore side VSC regulates the voltage and frequency of the offshore AC grid, while onshore grid side VSC maintenances DC link voltage and provide reactive power. Comparing with LCC HVDC solutions, one of the advantages of VSC HVDC is the bi-direction power transmission; in another word, the power transmission can change its direction automatically according the offshore wind generation supplying and load demanding situation, as simulation result shown in Fig. 7. A: Normal operation As the control strategy of onshore side VSC has been well explained in several references [5] [7], this paper focuses on several controllers employed in the offshore VSC-HVDC Fig. 3: The proposed control block diagram for offshore side VSC AC current limitation B: Onshore AC Grid Fault Mitigation Control It is critical to supply continuous power to oil & gas installations, which requires offshore AC grid to ride through certain onshore grid faults. During onshore grid fault, the active power transmitted to onshore by DC cable will be significant reduced due to onshore AC voltage dip, while the wind farm keeps on supplying active power to offshore VSC, the HVDC DC link voltage dynamic can be shown in equation [1]: 2 dvdc CS = 2PW 2PC 2 PP = ΔP (1) dt Where P is the surplus power generated by wind farm, and where P W, P C, P P is active power of wind farm, offshore VSC, and oil platforms representatively. If no any control on DC link implemented, the HVDC DC link voltage will increase rapidly, which will be out of reasonable range and bring equipments damage. There are several methods for grid fault ride-through mentioned in [6]. It is possible either to use DC chopper to dissipate superfluous power by breaking resistors, or to reduce wind farm output power after detecting the DC link voltage surge. The wind power deduction method will be used in this paper, because the variable speed wind turbines facilitate the possibility of energy storage into the rotating rotor, thus the surplus energy can be stored into the rotor instead of being dissipated to the breaking resistors. 793

The exact design of the V ac versus V vsc curve in Figure 5 is depends on the detailed VSC design and how fast the wind generation recovers from faults, in order to reach the active power balance in the offshore AC grid. Fig. 4 the proposed DC Link Voltage Controller (DLVC) during onshore AC grid fault The proposed HVDC DC Link Voltage Controller (DLVC) is shown in Fig. 4. The Fig. 9 shows a comparison between systems with the DLVC controller and without DLVC controller basing on ssimulation results. Normally the wind power reference P Wref is decided by maximal power track calculation. When DC link voltage (V DC ) exceeds certain value (V DC_ref ), the V DC deviation loop is activated by sending its output to wind turbine power reference. By this way, the wind power output will be reduced by change modulation index to Rotor Side Converter (RSC). Thus, a new power balance will be established to regulate the HVDC DC link voltage. Another alternative option of DC link voltage regulation is to reduce the current from wind farm by frequency control, which is mentioned in [6]. However, the fast deviation of frequency is hard to be detected in a short period, so it might be not feasible for this response speed demanding application. C: Offshore AC Grid Fault Mitigation Control The offshore side VSC collects and transmits the wind power to oil & gas installations and onshore, while maintaining the AC grid voltage (V ac ) and frequency. Figure 3 shows the control structure of the offshore side VSC. The offshore AC grid faults most likely occur in oil & gas installations than in wind farm. During the fault, there will be a voltage drop with a low retained voltage at the offshore AC bus. Therefore, a large transient current caused by power balance will most probably occur, which might damage the IGBTs and other equipments. In one aspect, the transient current should be limited to avoid the equipment damage. In another aspect, the VSC should supply over current as much as possible within its limitation, in order to allow protection system detect and trigger the faults in time. Since there is no inner current control loop implemented in offshore side VSC, the AC voltage of VSC (V vsc ) has to be appropriately limited. Therefore, an offshore AC grid voltage independent limiter is implemented in the ac voltage control loop via the modulation index (M) of the VSC, shown in Figure 3. When the faults occur, the low offshore AC grid voltage (V ac ) is detected, and the V vsc is set to a low value, in order to limit the VSC current. During the faults recovery period, the VSC voltage V vsc limitation increase linearly with the offshore AC voltage, as shown in Figure 5. Fig. 5: Vac vs Vvsc relationship in voltage dependent limiter III. SIMULATION RESULT To evaluate the proposed control system, a model of VSC- HVDC transmission system is simulated in PSCAD / EMTDC, shown in Figure 1. The simulated topology consists of a 300 MW variable speed wind turbines based wind farm and a 100 MW oil & gas installation, which is connected to VSC-based HVDC transmission system of 150 km length and transmission voltage of ± 120 kv. A: Normal operation simulation System control and operation during normal operation with series step change of both wind speed and oil & gas installation load were simulated. The simulation events are listed at table 1. The Fig. 9 shows the simulation result. At t = 2 s and t = 4 s, the wind speed changes from 11 m/s to 12 m/s, and changes back to 11 m/s, the active power generated by wind farm and power transmit to onshore were changed correspondingly. Notice that there is no any affection on power supplying to oil & gas installation. At t = 3 s and t = 5 s, the load switching of platform shown in Fig. 6 (d) have no affection on wind farm power output as shown in Fig. 6 (b). Fig. 6 (c) shows that the power transmitted to onshore grid reduces and increases correspondingly with platform load variation. The Fig. 6 (g) and Fig. 6 (h) clearly shows the regulation of offshore AC voltage and frequency during variation of wind speed and platform load. TABLE I SIMULATION EVENTS Sec. Events 2 Wind speed increases from 11 to 12 m/s 3 An oil installation rated 60 MW (0.12 pu, pf 0.85 ) is connected 4 Wind speed decreases to 11 m/s 5 An oil installation rated 60 MW (0.12 pu, pf 0.85 ) is disconnected Furthermore, the wind step change was replaced by the existing wind source for 10 seconds, with mean wind speed = 12 m/s at hub height and a random noise generation, shown in Fig. 7 (a). The active power of wind farm varies correspondingly with certain delay, shown in Fig. 7 (b). Because of the proposed fix control strategy in offshore AC grid, the surplus power is absorbed and transmitted by offshore side VSC. If the wind power generation is less than the load of the oil & gas installations, the power flow in VSC HVDC reversed from the onshore grid to the offshore automatically. 794

Fig. 6 Simulation result with step change of wind speed and platform load. Fig. 8 Simulation result during a three phase fault on the onshore side AC grid (with DLVC implemented). Fig. 7 Simulation result with variation of wind speed and platform load. B: Onshore AC Grid Fault Simulation Further study focuses on the operation and performance during a solid three phase to ground fault on onshore AC grid, and the simulation results are shown in Fig. 8. The fault was applied at 1.5 s and cleared at 1.6 s. When the fault occurred, Onshore AC voltage collapsed to 0.11 p.u., shown in Fig. 8 (a). During the fault, the active power transmission reduced significantly as show in Fig. 8 (c), while wind farm still produce power as illustrated in Fig. 8 (b). During the faults, the power consumption of oil & gas installation keeps on normal value, to guarantee the continuous oil production. When the fault is cleared, the onshore AC voltage and HVDC DC link voltage recovers after some transient. The power transmission resumes and HVDC DC voltage return to nominal value. Simulations were carried out using DLVC controller mentioned in section II. When the HVDC DC voltage increases to 1.05 p.u., the extra control loop shown in Fig. 4 will be activated. The control signal is sent to wind farm power reference to reduce its power output. As we can see in Fig. 8 (b), the active power generation of wind farm is reduced from 0.88 p.u. to 0.65 p.u., while the HVDC DC link voltage (Fig. 8 (g)) keeps in a reasonable range. 795

The wind turbine rotating speed will be increased, because the unbalanced mechanical torque and DFIG air-gap torque leads to acceleration of wind turbine rotor. The simulations were repeated for different values of offshore VSC reference voltage limitation V vsc_max. When the V vsc_max is equal to 1.5 times the rated VSC AC voltage, the offshore VSC current surged to 2.8 p.u. (Fig. 11 b). When the V vsc_max is equal to 1.1 times the rated VSC ac voltage, the offshore VSC current is within 1.0 p.u. during fault and surged to 1.5 p.u. during recovery period (Fig. 12 b). Simulation results in Figure 11 and 12 show that the VDL significantly affects the system dynamics during the fault and recovery period. Simulations in Figure 11 and 12 also show that the wind farm DFIGs and induction motors in oil platforms will supply most of fault current, while VSC current was kept as relatively lower value. So it is interesting to see that how the fault current will be supplied if the wind turbine is equipped with full size converters, as over current capability of converter is limited close to the rating current. Furthermore, if the VSC supplies the offshore oil & gas installation, another potential challenge could be how to set the protection system parameters to distinguish the AC grid faults current from the motor start current in the oil installation. Fig. 9 Simulation results during a three phase fault on onshore side AC grid (Blue: without DLVC implemented, Green: with DLVC controller). The simulation case has been repeated without the DLVC controller, as shown by blue curves in Fig 9. When the configuration without DLVC controller is used, the active power from wind farm (blue solid curve in Figure 9a) almost keeps unchanged, thus the dc voltage farm (blue solid curve in Figure 9a) surged to a high level (1.36 p.u.) until the fault clearance. At the same time, with DLVC controller presence, the HVDC DC voltage, offshore AC voltage and offshore AC frequency (green solid curves in Figure 9a and 9b) peak values are smaller than the configuration without DLVC controller. C: Offshore AC Grid Fault Simulation The simulations results of a solid three phase to ground fault on offshore AC grid are shown in Fig. 10. The fault is applied at 1.50 s and cleared at 1.60 s. When the fault occurs, the offshore AC voltage collapses to almost 0.1 p.u. as shown in Fig. 10 (a). During the fault, the wind farm active power output and HVDC active power transmission reduce significantly as show in Fig. 10 (b) and (c). When the fault is cleared, the offshore AC voltage recovers after some transient as the power transmission resumes. Simulations were carried out implementing VDL mentioned in section II, which influences the recovery ramping of active VSC power. In this case, the wind farm power recovers faster than active VSC power. Therefore the power unbalance brought frequency surge after 1.70 second (Fig. 10 (h)). The active VSC power recovery ramping can be further adjusted to reach more accurate power balance and thus less frequency variation. Fig. 10 Simulation result during a three phase fault on the offshore side AC grid (with VDL limiter implemented). In this extremely serious fault scenery simulated, the active power supplied to oil & gas installations has dropped to near 0 p.u. Therefore, the uninterruptible power supply needs to be installed in the platform to keep continuous operation. 796

First, the principle of the proposed VSC HVDC system and its control strategy has been described. The system dynamic performances during variable wind speed and load switching have been demonstrated by PSCAD simulation. Second, the system performance during onshore AC grid three phases to ground fault has been studied. With the proposed DC link voltage controller, the system is likely to survive during such fault conditions. At last, the offshore AC grid three phases to ground fault was studied, and the simulation results show the proposed VDL limiter implemented will help the system recovery by influencing the recovery ramping of active VSC power. APPENDIX TABLE II SYSTEM PARAMETERS Fig. 11 Currents of wind farm, offshore VSC and oil platform (with ac voltage limitation 1.5 p.u. at offshore VSC) Rated (base) apparent power 300 MVA 1.0 pu Rated (base) voltage, offshore AC 115 kv 1.0 pu Rated (base) voltage, HVDC link 120 kv 1.0 pu System Frequency f ref 50 HZ 1.0 pu 150-km dc transmission line [3] Resistance per km 0.0217 Inductance per km 0.792mH ACKNOWLEDGMENT The authors would like to thank Ms. Vibeke Skjetne of ABB Elektro & Drives System, Oslo, Norway, for advice and helpful discussions. Fig. 12 Currents of wind farm, offshore VSC and oil platform (with ac voltage limitation 1.1 p.u. at offshore VSC) IV. CONCLUSIONS Several faults mitigation control strategies for the offshore VSC HVDC grid integrating offshore wind farm and oil & gas installations has been proposed and evaluated in this paper, for example, the DC link voltage controller for onshore grid faults and the voltage dependent limiter for offshore AC grid faults. REFERENCES [1] E. Koldby, M.Hyttinen, Challenges on the road to an offshore HVDC grid, in Proc. Nordic Wind Power Conference, Bornholm, Denmark, 2009. [2] E. Berge1 et al, Modelling of offshore wind resources. Comparison of a mesoscale model and measurements from FINO1 and North Sea oil rigs, in EWEC 2009. [3] D. W. Xiang et al, Coordinated control of an HVDC link and doubly fed induction generators in a large offshore wind farm,, IEEE transactions on power delivery, 21 (1). pp. 463-471. 2006 [4] Cuiqing Du et al, A New Control Strategy of a VSC HVDC System for High-Quality Supply of Industrial Plants, IEEE Transactions on Power Delivery, Vol. 22, No. 4, October 2007 [5] L. Xu, L. Yao and C. Sasse, Grid integration of large DFIG-based wind farms using VSC transmission, IEEE Trans. Power Syst., Vol. 22, No.3 August 2007 [6] C. Felts et al, Enhanced fault ride-through method for wind farms connected to the Grid Though VSC-Based HVDC Transmission, IEEE Transactions on Power Systems, Vol.24, No.3, August 2009 [7] Bing Liu, The Implementation of Variable Speed Wind Turbine Aerodynamic and Drive Train Modeling for Transient Analysis, EAWE the 4th PhD seminar in Wind energy, 2008 [8] S. Muller, M. Deicke, and R. W. De Doncker, Doubly fed induction generator systems for wind turbines, IEEE Ind. Appl. Mag., vol. 8, no. 3, pp. 26 33, May/Jun. 2002. [9] Cuiqing Du, Comparison of Different Frequency Controllers for a VSC-HVDC Supplied System, IEEE Transactions on Power Delivery, VOL. 23, NO. 4, October 2008 [10] E. Berge1, Ø. Byrkjedal1, Y. Ydersbond and D. Kindler, Modelling of offshore wind resources. Comparison of a mesoscale model and measurements from FINO 1 and North Sea oil rigs, in EWEC 2009 [11] PSCAD User's Manual, Manitoba HVDC Research Center, 4/2005. 4 [12] IEC 60919: Performance of HVDC systems 797