Product Data. FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil

Similar documents
Product Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES

Product Data FFMA BASE SERIES FAN COIL SIZES 018 TO 037 FEATURES

Product Data. FFMA Base Series Fan Coil Sizes 018 thru 037 FEATURES

Product Data. CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) FMA4P1800AL 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

FMU4X, FMC4X FMU4Z, FMC4Z

CFM (L/s) Dimensions. Filter Size Ship Wt. HxWxDin.(mm) 1800Aǂ 1-1/2 18, (212) 675 (319) 36-1/2 x 20-1/2 x (45) FMA4P (928 x 521 x 381)

CFM (L/s) Dimensions. Filter Size Ship Wt. H x W x D in. (mm) 1800Aǂ 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

CFM (L/s) Min Max 450 (212) 600 (283) 750 (354) Dimensions H x W x D in. (mm) 675 (319) 36 1/2 x 20 1/2 x (425)

CFM (L/s) Dimensions. Filter Size in. Ship Wt. H x W x D in. (mm) 1800A 1 1/2 18, (212) 675 (319) 36 1/2 x 20 1/2 x 15

Product Data FF1E LEGACY LINE FAN COIL SIZES 018 THRU 037 FEATURES

Product Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES

Product Data. FF1E Base Series Fan Coil Sizes 018 thru 036 FEATURES

Product Data PF1MNC DIRECT EXPANSION FAN COIL SIZES 018 THRU 061 FEATURES/BENEFITS AVAILABLE SIZES: 18,000 to 61,000 BTU unit ELECTRICAL RANGE:

STANDARD FEATURES S S S S S S S S S S S S S S S S S S S S S S S S

Product Data. FA4A FB4A FC4B Direct Expansion Fan Coil. Sizes 018 thru 070. Air Handling Technology At Its Finest

Product Data. FX4C, FC4D Comfort Series Fan Coil Sizes 018 thru 060 AIR HANDLER TECHNOLOGY AT ITS FINEST

Product Data. CC5A, CD5A Heating/Cooling Coil. Sizes A018 thru W060 COMMON FEATURES

APARTMENT FAN COILS AVAILABLE WITH FACTORY INSTALLED 5, 7, & 11 kw ELECTRIC HEAT, or NO HEAT R -22 SYSTEMS

Operating Net Capacity BTU/h. Input BTU/h Efficiency. lbs (kg) PGR524040KGP* 23, ,000/26, /8 x 47 x 31-7/16

APARTMENT FAN COILS AVAILABLE WITH FACTORY INSTALLED 5, 7, & 11 kw ELECTRIC HEAT, or NO HEAT R-410A and R-22 SYSTEMS

Tons BTU/h S.E.E.R* E.E.R** HSPF

DIRECT EXPANSION COMMERCIAL PACKAGED AIR HANDLING UNITS, 6 25 TONS

N4A6. Product Specifications

FEM4X, FSM4X, FSU4X. Product Specifications

CSA6. Product Specifications. SoftSound SXC 2600

FEM4P, FSM4P, FSU4P. Product Specifications

CPC Commercial. 7½- to 12½-Ton Three-Phase. up to 11.5 EER. Cooling Capacity: 90, ,000 BTU/h. Packaged Air Conditioners

Product Data PH3Z 13 SEER SINGLE -PACKAGED HEAT PUMP SYSTEM WITH R -22 REFRIGERANT SINGLE AND THREE PHASE 2-5 NOMINAL TONS ( )

PHR5. Product Specifications

VHIA High-Static Ducted Indoor Units - 60HZ

Product Data PH13NA PH13PA FEATURES AND BENEFITS. 13SEERSplitSystemHeatPump with R---410A Refrigerant 1.5 To 5 Nominal Tons AVAILABLE SIZES:

N4A4 C. Product Specifications

WCA4**4. Product Specifications

PACKAGED HEAT PUMP AIR HANDLER UNITS, 6 25 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

V33A Standard/High Efficiency 360 Cassette Indoor Models - 60HZ

GPC14H 2- to 5-Ton Packaged Air Conditioner Up to 14 SEER

VMDB Concealed Medium Static Ducted Indoor Models - 60HZ

S5BP Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

V33B High Efficiency 360 Cassette Indoor Models - 60HZ

VMDA Concealed Medium Static Ducted Indoor Models - 60HZ

VWMB Wall-Mounted Non-Ducted Indoor Models - 60HZ

GPC14H. 2- to 5-Ton Packaged Air Conditioner 14 SEER. Cooling Capacity: 24,000-57,500 BTU/H

BAC / BHC Product Specifications

S6BQ Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Split System 2-Stage Air Conditioner. 7 1/2 and 10 Ton rated at 11.2 EER and 12.

Product Data. Features/Benefits. OMNIZONE 50XCR06-24 Remote Air-Cooled Indoor Self-Contained Systems with PURON Refrigerant (R-410A)

ELECTRIC HEAT AIR HANDLERS

DIRECT EXPANSION COMMERCIAL PACKAGED AIR HANDLING UNITS, 6 25 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Product Data. Features/Benefits. Omnizone 50XCA06-14 Air-Cooled Indoor Self-Contained Systems with Puron Refrigerant (R-410A) 5 to 12 Nominal Tons

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS DESCRIPTION FEATURES MODELS: AHR18 THRU 60* WARRANTY

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

technical sales guide - 60Hz Ducted Split Units HIGH AMBIENT OPERATION 52 UPTO

PRPAC14 PRODUCT SPECIFICATIONS 14 SEER ELECTRIC/ELECTRIC PACKAGED UNIT REFRIGERANT SYSTEM CABINET CONSTRUCTION BLOWER INSTALLATION WARRANTY

ARUF Series. Multi-Position, Multi-speed Air Handler with PSC Motor 1½ to 5 Tons. Contents. Product Features

DIRECT EXPANSION COMMERCIAL PACKAGED AIR HANDLING UNITS, 6-25 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

48CWA2-00 Chilled Water Fan Coil With or Without Electric Heat 2-Pipe Heat / Cool Fan Coil 48,000 BTUH

Q7RE Series Single Packaged Heat Pump, Single Phase

HMG*T TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler Residential System 18,000-60,000 Btuh (Heat Pump & Air Conditioner)

HMG Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler. 13 SEER Residential System 18,000-60,000 Btuh (Heat Pump & Air Conditioner)

TECHNICAL GUIDE DESCRIPTION MODELS: D4HH 024 THRU 180 HORIZONTAL FEATURES SINGLE PACKAGE AIR CONDITIONERS HORIZONTAL INDOOR & CONDENSER AIR FLOW

TSA6. Product Specifications. SmartComfort TXC 5600

Q7RE Series Single Packaged Heat Pump, Single Phase

CPC Commercial. 15- & 20-Ton, Three-Phase Packaged Air Conditioner. 20-Ton Cooling Capacity: 240,000 BTU/h

DIRECT EXPANSION COMMERCIAL PACKAGED AIR HANDLING UNITS, 6 25 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

S/T Ratio. Input BTU/h

PCB COMMERCIAL SERIES

Dimensions Filter Size in. (mm) lbs. (kg) FVM4X2400B 135 (61) FVM4X2400BT

14 SEER, 12 EER PACKAGE AIR CONDITIONER, 2 to 5 TONS 208/ Single Phase

PACKAGED HEAT PUMP AIR HANDLER UNITS, 6 25 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Q6SP Series Rev A TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 7.5 and 10 Ton Packaged Electric Heat Pump Units with R-410A 11.

TECHNICAL GUIDE SINGLE PIECE STANDARD ECM AIR HANDLERS. DESCRIPTION

MHWW-24-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 24,000 BTUH. Rev. 1.3

135 (61) FVM4X2400AT. (416 x 546) FVM4X3600A FVM4X3600AT FVM4X4800A FVM4X4800AT FVM4X6000A FVM4X6000AT 1400 (661) 1600 (755) 2000 (944)

Product Data. Features/Benefits. 38HDL Cooling Only Condensing Unit. 1 1 / 2 to 5 Nominal Tons

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT:

CAS. Product Specifications

BAC / BHC SERIES 6 to 20 Ton Air Handlers

PRAC14 PRODUCT SPECIFICATIONS

Product Data. S Up to 19 SEER / up to 12.5 EER S Microtube Technologyt refrigeration system Sound

R4H4. Product Specifications

Rheem High Efficiency Air Handler

PRPHP14 PRODUCT SPECIFICATIONS 14 SEER HEAT PUMP PACKAGED UNIT REFRIGERANT SYSTEM CABINET CONSTRUCTION BLOWER CONTROLS INSTALLATION ACCESSORIES

FEM, FSM, FSU. Product Specifications

R4A3. Product Specifications EFFICIENT 13 SEER AIR CONDITIONER ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT

R4A5. Product Specifications EFFICIENT 14 SEER/ EER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT

Product Data. 40RUQ SplitSystemHeatPump Indoor Unit (Air---Handling Unit) With Puron R Refrigerant 60 Hz FEATURES/BENEFITS

Product Data PH15NB. 15SEERSplitSystemHeatPump with R---410A Refrigerant 1.5 To 5 Nominal Tons AVAILABLE SIZES:

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 20 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

B6BMMX Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Air Handler Residential System 18,000-60,000 Btuh (Heat Pump & Air Conditioner)

TECHNICAL GUIDE SINGLE PIECE STANDARD ECM AIR HANDLERS. DESCRIPTION FEATURE

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

BCE5E PRODUCT SPECIFICATIONS ENHANCED AIR HANDLER APPLICATION INSTALLATION CABINET COILS COMPONENTS WARRANTY

BAC / BHC SERIES 6 to 20 Ton Air Handlers

R4A4. Product Specifications EFFICIENT 14 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT

P7RD-A Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. Single Packaged Air Conditioner

Rheem High Efficiency Air Handler

FORM NO. HSC-543 AIR HANDLERS

SSZ14. High-Efficiency. Split System Heat Pump. Cooling Capacity: 18,000 to 57,600 BTU/h. Up to 15 SEER & 8.5 HSPF

Bosch BOVA Split System Heat Pump

Product Data. 40RUA / 40RUS 6to30TonDirectExpansionwithPuron R Refrigerant 7.5to30TonChilledWater Packaged Air---Handling Units 60 Hz

Product Data. 40RUA 18.3 to 59.2 kw Direct Expansion Packaged Air---Handling Units 50 Hz

Transcription:

FPMA Sizes 018 thru 036 FPMB Sizes 018 thru 030 Base Series Horizontal Fan Coil A13303 Fig. 1 - FPM(A,B)NU Uncased Horizontal Fan Coil (FPMANU model shown) Fig. 2 - FPM(A,B)NC Cased Horizontal Fan Coil (Unit pictured upside down) Product Data A13304 The FPM(A,B) Series Fan Coil unit is primarily designed for multi-family applications as a horizontal only indoor fan coil for split -system heat pumps for use with Puron refrigerant. The FPM(A,B) series fan coil is available in cased or uncased versions from the factory. Accessory field -installed electric heat kits are available in 3, 5, 6, 7.5 or 10 kw sizes. The electric heat, however, cannot be run simultaneously with refrigerant heat. The factory electric heat kits for the FPM(A,B) come with a control to prevent both electric heat and heat -pump heat from operating simultaneously. The FPMA comes with a piston refrigerant metering device. The FPMB comes with a factory installed Puron TXV. These fan coils come configured for Puron refrigerant. However, they can be used for R -22 applications with the addition of an R -22 TXV kit. The uncased version can be installed in a furred -in ceiling or in a field fabricated casing or duct. The cased version can be installed in a furred -in ceiling or with ducted return. Return air must be pass through a filter in all applications. Local codes may limit free -air -return type installations to single -level applications. A louvered return air panel, which is sized for unit access and accepts either 1 -in. or 2 -in. air filters, is available as an accessory. A solid access panel also is available. Please note that when using the cased model, FPM(A,B)NC, in horizontal return applications, a bottom cover will need to be field fabricated. Designated mounting locations are provided on the equipment. The factory cased version is fully insulated to meet applications in conditioned space. It also should be noted that the unique cabinet design of the cased coil meets the requirement of 2% cabinet leakage rate when tested at 1.0 -in. of static pressure. This unit is not approved for installation in unconditioned spaces. PSC blower motors have been selected to provide the proper air handling for both heating and cooling. Refrigerant line connections are made on the side of the unit while the high and low voltage connections are made from either the right or left side of the fan coil. Sweat-type refrigerant connections on both liquid and vapor lines make for swift, low -cost installation. On cased units, the refrigerant lines can be run out the back or side of the unit while electrical connections can be run out either side or back of the casing. Primary and secondary drain connections exit from the back or side of the cabinet.

STANDARD FEATURES Environmentally -Sound Refrigerant Technology S Designed for Puron refrigerant, the chlorine-free non -ozone depleting refrigerant Quality Assisting, Ease of Installation S Cased version meets requirements of a 2% cabinet leakage rate when tested at 1.0 -in. w.c. of static pressure. S Provisions made for suspending from ceiling joints S Multiple electrical, refrigerant lineset and drain line entry for application flexibility S Sweat connections for leak free service S Cabinet construction features innovations designed to prevent cabinet sweating Heat Transfer Technology S Grooved copper tubing S A -coil design for maximum surface area Controls and Electrical Features S 40VA 208/230v transformer MODEL NUMBER NOMENCLATURE 1 2 3 4 5 6 7 8 9 10 11 12 F P M A N U 0 1 8 0 0 0 Product F=FanCoil Type P = Ceiling Fan Coil Heating Size 000 = No Factory---Installed Electric Heat Position M = Multi---Family Series A = Piston Ceiling Fan Coil Capacity B=TXVCeilingFanCoil 018 = 18,000 024 = 24,000 Electrical 030 = 30,000 N = 208/230v, 1ph--- 60 Hz 036 = 36,000 Cabinet U=Uncased C=Cased the environmentally sound refrigerant Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program For verification of certification for individual products, go to www.ahridirectory.org. 2

DIMENSIONS Liquid line comection copper (sweat) 26-3 /8 [670 m m] Auxiliary drain connection 3/4 [20 mm] male pipe thread (npt) Primary drain conncetion 3/4 [20mm] male pipe thread (npt) 10-1/4 [26 260 mm ] D 1 [25 mm ] A B Vapor line comection copper (sweat) Low voltage connection 7-7 /8 [20 200 mm ] 16-1 /4 [41 412 m m] High voltage connection 1-3/8 [35 mm] dia knock outs Supply duct opening 5 [12 127 m m] C Fig. 3 - FPM(A,B)NU Uncased Horizontal Fan Coil Dimensional Drawing (FPMANU model shown) A150454 FPM(A,B)NU DIMENSIONAL DATA Model Size Dimensions- inches [mm] A B C D Unit Operating Weight lbs (kg) 18 37-1/4 [946] 34-11/16 [881] 30 [762] 6-1/2 [165] 75 (34) 24 37-1/4 [946] 34-11/16 [881] 30 [762] 6-1/2 [165] 75 (34) 30 49-1/4 [1251] 46-11/16 [1186] 42 [1067] 6-1/2 [165] 93 (42) 36 49-1/4 [1251] 46-11/16 [1186] 42 [1067] 6-1/2 [165] 93 (42) 3

DIMENSIONS (CONT.) Supply Duct Opening Fig. 4 - FPM(A,B)NC Cased Horizontal Fan Coil Dimensional Drawing (FPMANC model shown) A150455A FPM(A,B)NC DIMENSIONAL DATA Model Size Dimensions- inches [mm] A B C D Unit Operating Weight lbs (kg) 18 39-3/4 [1010] 30--- 3/8 [771] 28 [711] 43--- 3/8 [1101] 109 (49) 24 39-3/4 [1010] 30--- 3/8 [771] 28 [711] 43--- 3/8 [1101] 109 (49) 30 51--- 3/4 [1315] 42--- 3/8 [1076] 40 [1016] 55--- 3/8 [1406] 135 (61) 36 51--- 3/4 [1315] 42--- 3/8 [1076] 40 [1016] 55--- 3/8 [1406] 135 (61) 4

SPECIFICATIONS Unit Size FPMAN(C,U) 18 24 30 36 Nominal Cooling Capacity (BTUH) 18,000 24,000 30,000 36,000 COIL Puron (R--- 410A) - Refrigerant Metering Device (Piston)* 50 (1.27mm) 56 (1.42mm) 67 (1.7mm) 70 (1.78mm) Coil Configuration A --- Coil BLOWER & MOTOR Air Discharge Horizontal Blower Type Dual Blower Direct Drive CFM (Nominal) 600 800 1000 1200 Motor Type PSC PSC PSC PSC Motor HP 1/8 1/8 1/3 1/3 Rated RPM 1075 1075 1600 1600 Motor Speeds 3 3 3 3 FILTER Field Installed --- in. (mm) Qty. 2 --- 16x20x1 (406x508x25) Qty. 2 --- 16x20x1 (406x508x25) Qty. 2 --- 20x20x1 (508x508x25) Qty. 2 --- 20x20x1 (508x508x25) CONNECTIONS Suction Sweat --- in. (mm) 3/4 In. (19 mm) Liquid Sweat --- in. (mm) 3/8 In. (9.5 mm) Condensate (MPT) --- in. (mm) 3/4 In. (19 mm) ELECTRICAL DATA Voltage 208/230 208/230 208/230 208/230 Hertz 60 60 60 60 Minimum Circuit Ampacity 1.32 1.32 2.2 2.2 Maximum Circuit Protector 15 (A) 15 (A) 15 (A) 15 (A) * The piston included with the fan coil is unique to this product and CANNOT be replaced with the piston shipped with outdoor unit. Refer to the AHRI ratings tocheckifyourcombinationcanusethepistonshippedwiththefancoilifanaccessorytxvisrequired. Unit Size FPMBN(C,U) 18 24 30 Nominal Cooling Capacity (BTUH) 18,000 24,000 30,000 COIL Puron (R--- 410A) - Refrigerant Metering Device TXV Coil Configuration A --- Coil BLOWER & MOTOR Air Discharge Horizontal Blower Type Dual Blower Direct Drive CFM (Nominal) 600 800 1000 Motor Type PSC PSC PSC Motor HP 1/8 1/8 1/3 Rated RPM 1075 1075 1600 Motor Speeds 3 3 3 FILTER Field Installed --- in. (mm) Qty. 2--- 16x20x1 (406x508x25) Qty. 2--- 16x20x1 (406x508x25) Qty. 2--- 20x20x1 (508x508x25) CONNECTIONS Suction Sweat --- in. (mm) 3/4 In. (19 mm) Liquid Sweat--- in. (mm) 3/8 In. (9.5 mm) Condensate (MPT) --- in. (mm) 3/4 In. (19 mm) ELECTRICAL DATA Voltage 208/230 208/230 208/230 Hertz 60 60 60 Minimum Circuit Ampacity 1.32 1.32 2.2 Maximum Circuit Protector 15 (A) 15 (A) 15 (A) 5

PERFORMANCE DATA AIRFLOW PERFORMANCE (Standard CFM) Use for Selecting Electric Heat Speed Model 18 24 30 36 CFM Dry Coil without Filter or Electric Heat Motor Speed External Static Pressure-Inches W.C. [kpa] 0[0] 0.05 [.01] 0.1 [.02] 0.15 [.04] 0.2 [.05] 0.25 [.06] 0.3 [.07] Low 762 724 686 642 598 513 448 Medium 1033 981 932 876 819 735 667 High 1062 1007 953 888 825 764 722 Low 762 724 686 642 598 513 448 Medium 1033 981 932 876 819 735 667 High 1062 1007 953 888 825 764 722 Low 1200 1152 1116 1073 1039 989 924 Medium 1331 1285 1242 1205 1165 1121 1050 High 1449 1402 1361 1322 1284 1235 1198 Low 1200 1152 1116 1073 1039 989 924 Medium 1331 1285 1242 1205 1165 1121 1050 High 1449 1402 1361 1322 1284 1235 1198 AIRFLOW PERFORMANCE (Standard CFM) Use for Selecting Cooling and Heat Pump Speed Model 18 24 30 36 CFM Wet Coil without Filter or Electric Heat Motor Speed External Static Pressure-Inches W.C. [kpa] 0[0] 0.05 [.01] 0.1 [.02] 0.15 [.04] 0.2 [.05] 0.25 [.06] 0.3 [.07] Low 747 671 623 575 528 469 397 Medium 996 912 833 765 683 609 518 High 1051 974 888 816 742 665 576 Low 747 671 623 575 528 469 397 Medium 996 912 833 765 683 609 518 High 1051 974 888 816 742 665 576 Low 1211 1150 1069 1017 958 906 849 Medium 1313 1261 1216 1151 1105 1051 984 High 1428 1377 1315 1244 1198 1148 1089 Low 1211 1150 1069 1017 958 906 849 Medium 1313 1261 1216 1151 1105 1051 984 High 1428 1377 1315 1244 1198 1148 1089 --- Shaded boxes represent airflow outside the required 300-450 cfm/ton. NOTES: 1. Airflow data is without filter or electric heat accessory. Heater adds 0.05 static. 2. Use dry coil data for determining electric heater airflow. 3. Use wet coil data for determining cooling airflow. REQUIRED CFM RANGE CFM Size Min Max 18 450 675 24 600 900 30 750 1125 36 900 1350 6

GROSS COOLING CAPACITIES (mbh) Unit Size 18 24 30 36 INDOOR COIL AIR PERFORMANCE DATA (CONT.) SATURATED TEMPERATURE LEAVING EVAPORATOR F ( C) 35 (2) 40 (4) 45 (7) 50 (10) 55 (13) CFM EWB TC SHC BF TC SHC BF TC SHC BF TC SHC BF TC SHC BF 72 (22) 40 21 0.00 36 19 0.00 32 17 0.01 27 15 0.03 22 12 0.04 525 67 (19) 33 22 0.04 29 19 0.04 24 17 0.04 19 15 0.04 14 12 0.05 62 (17) 26 22 0.05 22 20 0.05 18 17 0.05 14 14 0.08 12 12 0.23 72 (22) 45 24 0.00 40 21 0.00 35 19 0.03 30 16 0.04 24 14 0.05 600 67 (19) 36 24 0.05 32 22 0.05 27 19 0.05 22 16 0.06 15 14 0.06 62 (17) 29 24 0.06 25 22 0.06 20 19 0.06 16 16 0.09 13 13 0.25 72 (22) 49 26 0.00 44 23 0.00 38 20 0.04 32 18 0.05 26 15 0.06 675 67 (19) 40 26 0.06 35 24 0.06 29 21 0.07 23 18 0.07 17 15 0.07 62 (17) 32 27 0.07 27 24 0.07 22 21 0.07 17 17 0.10 14 14 0.26 72 (22) 54 27 0.00 48 25 0.00 42 22 0.04 36 19 0.06 29 16 0.06 700 67 (19) 44 28 0.06 39 25 0.07 33 22 0.07 26 19 0.07 18 16 0.07 62 (17) 35 29 0.07 30 26 0.07 24 23 0.07 19 19 0.11 16 16 0.26 72 (22) 59 30 0.00 53 27 0.01 47 24 0.06 39 21 0.07 31 18 0.08 800 67 (19) 48 31 0.08 42 28 0.08 36 25 0.08 28 21 0.09 20 18 0.09 62 (17) 39 32 0.09 33 28 0.09 26 25 0.09 22 22 0.13 18 18 0.28 72 (22) 64 33 0.00 57 30 0.03 50 26 0.07 43 23 0.09 34 19 0.09 900 67 (19) 52 34 0.09 46 30 0.10 39 27 0.10 31 23 0.10 22 20 0.10 62 (17) 42 35 0.10 35 31 0.10 29 28 0.10 24 24 0.15 20 20 0.29 72 (22) 64 31 0.04 59 29 0.05 53 26 0.05 45 23 0.06 37 20 0.06 875 67 (19) 53 33 0.06 48 31 0.06 41 28 0.06 34 25 0.06 25 21 0.06 62 (17) 43 35 0.06 38 32 0.06 32 30 0.06 27 27 0.14 23 23 0.28 72 (22) 69 34 0.05 63 31 0.06 57 28 0.07 49 25 0.07 40 22 0.07 1000 67 (19) 57 36 0.07 51 33 0.07 44 30 0.07 36 27 0.07 27 24 0.07 62 (17) 47 38 0.07 41 36 0.07 34 33 0.08 30 30 0.17 25 25 0.30 72 (22) 72 35 0.07 66 33 0.07 59 30 0.08 51 27 0.08 42 23 0.08 1100 67 (19) 60 38 0.08 54 35 0.08 46 32 0.08 38 29 0.08 29 25 0.08 62 (17) 49 41 0.08 43 38 0.08 37 36 0.09 32 32 0.19 27 27 0.31 72 (22) 69 34 0.06 63 32 0.07 56 29 0.07 49 26 0.08 40 22 0.08 1050 67 (19) 57 37 0.08 51 34 0.08 44 31 0.08 36 28 0.08 27 24 0.08 62 (17) 46 39 0.08 40 37 0.08 34 34 0.08 30 30 0.18 25 25 0.30 72 (22) 73 36 0.08 67 34 0.08 60 31 0.09 52 28 0.09 42 24 0.09 1200 67 (19) 61 40 0.09 54 37 0.09 47 34 0.10 39 30 0.10 29 27 0.09 62 (17) 50 43 0.09 43 40 0.09 37 37 0.10 33 33 0.21 28 28 0.33 72 (22) 77 39 0.10 71 36 0.10 63 33 0.10 55 30 0.11 45 26 0.11 1350 67 (19) 64 42 0.11 57 40 0.11 50 36 0.11 41 33 0.11 31 29 0.11 62 (17) 52 46 0.11 46 43 0.11 41 41 0.13 36 36 0.24 30 30 0.35 CFM --- Cubic Ft per Minute EWB --- Entering Wet Bulb _F (_C) LWB --- Leaving Wet Bulb _F (_C) TC --- Gross Cooling Capacity 1000 Btuh SHC --- Gross Sensible Capacity 1000 BF --- Bypass Factor MBH --- 1000 Btuh Btuh NOTES: 1. Contact manufacturer for cooling capacities at conditions other than shown in table. 2. Formulas: Leaving db = entering db -sensible heat cap. 1.09 x CFM Leaving wb = wb corresponding to enthalpy of air leaving coil (h lwb ) h lwb =h ewb -total capacity (Btuh) 4.5xCFM where h ewb = enthalpy of air entering coil. Direct interpolation is permissible. Do not extrapolate. 3. SHC is based on 80_F (27_C) db temperature of air entering coil. Below 80_F (27_C) db, subtract (Correction Factor x CFM) from SHC. Above 80_F (27_C) db, add (CorrectionFactorxCFM)toSHC. 4. Bypass Factor = 0 indicates no psychometric solution. Use bypass factor of next lower EWB for approximation. BYPASS FACTOR SHC CORRECTION FACTOR ENTERING AIR DRY-- BULB TEMPERATURE (_F) 79 78 77 76 75 Under 75 81 82 83 84 85 Over 85 ENTERING AIR DRY-- BULB TEMPERATURE (_C) 26 25 25 24 24 Under 75 27 28 28 29 29 Over 85 Correction Factor 0.10.098 1.96 2.94 3.92 4.91 Use 0.20 0.87 1.74 2.62 3.49 4.36 formula shown 0.30 0.76 1.53 2.29 3.05 3.82 below Interpolation is permissible. Correction Factor = 1.09 x (1 --- BF) x (db --- 80) 7

ESTIMATED SOUND POWER LEVEL (dba) PERFORMANCE DATA (CONT.) CONDITIONS OCTAVE BAND CENTER FREQUENCY UNIT SIZE CFM Ext Static Pressure 63 125 250 500 1000 2000 4000 18 600 0.18 47.9 51.6 46.6 49.6 47.6 38.7 34.7 24 800 0.18 47.9 51.3 50.7 51.1 46.9 41.6 35.7 30 1000 0.24 47.9 55.7 50 54.3 51.9 43.8 39.3 36 1200 0.24 47.9 55.6 49.2 53.1 49.6 43.4 38.2 * Estimated sound power levels have been derived using the method described in the 1987 ASHRAE HVAC Systems & Applications Handbook, Chapter 52, p. 52.7. ELECTRIC DATA WITH OPTIONAL FIELD-INSTALLED ELECTRIC HEAT HEAT KIT MODEL USED ON SIZE NOMINAL HEAT CAPACITY @ 240V HEATER CAPACITY (MBH) MINIMUM CIRCUIT AMPACITY (MCA) MAX. FUSE OR BREAKER HEAT KIT AMPACITY (HACR) MIN. WIRE SIZE (AWG) MIN. GROUND WIRE SIZE MAX. WIRE LENGTH (Ft) KW 208 240 208 240 208 240 208 240 208 240 208 240 EHK3-03B 3 7.7 10.2 14.8 16.9 20 20 12 12 10 10 72 73 EHK3-05B 5 12.8 17.1 23.9 27.3 30 30 10 10 10 10 72 73 EHK3-06B 18 6 15.4 20.5 28.4 32.6 35 35 8 8 10 10 98 96 EHK3-08B 7.5 19.3 25.7 35.2 40.4 50 50 8 8 10 10 78 79 EHK3-10B 10 24.7 32.8 44.6 51.3 60 60 6 6 10 10 94 96 EHK3-03B 3 7.7 10.2 14.8 16.9 20 20 12 12 10 10 72 73 EHK3-05B 5 12.8 17.1 23.9 27.3 30 30 10 10 10 10 72 73 EHK3-06B 24 6 15.4 20.5 28.4 32.6 35 35 8 8 10 10 98 96 EHK3-08B 7.5 19.3 25.7 35.2 40.4 50 50 8 8 10 10 78 79 EHK3-10B 10 24.7 32.8 44.6 51.3 60 60 6 6 10 10 94 96 EHK3-03B 3 7.7 10.2 15.8 17.9 20 20 12 12 10 10 67 69 EHK3-05B 5 12.8 17.1 24.9 28.3 30 30 10 10 10 10 69 71 EHK3-06B 30 6 15.4 20.5 29.4 33.5 35 35 8 8 10 10 94 93 EHK3-08B 7.5 19.3 25.7 36.1 41.4 50 50 8 8 10 10 76 77 EHK3-10B 10 24.7 32.8 45.5 52.3 60 60 6 6 10 10 92 94 EHK3-03B 3 7.7 10.2 15.8 17.9 20 20 12 12 10 10 67 69 EHK3-05B 5 12.8 17.1 24.9 28.3 30 30 10 10 10 10 69 71 EHK3-06B 36 6 15.4 20.5 29.4 33.5 35 35 8 8 10 10 94 93 EHK3-08B 7.5 19.3 25.7 36.1 41.4 50 50 8 8 10 10 76 77 EHK3-10B 10 24.7 32.8 45.5 52.3 60 60 6 6 10 10 92 94 * Copper wire must be used. If other than uncoated (non---plated), 75_C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code (ANSI/NGPA 70). * Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%. OTHER ACCESSORIES Kit Number Description Used on sizes KFAGP0101LGL Louvered Panel with Filter Rack 18, 24 KFAGP0201LGL Louvered Panel with Filter Rack 30, 36 KFAGP0101COV Access Panel 18, 24 KFAGP0201COV Access Panel 30, 36 KSATX0601HSO TXV Kit R-22 18, 24, 30, 36 KSATX201PUR TXV Kit Puron (R-410A) 18, 24, 30 KSATX301PUR TXV Kit Puron (R-410A) 36 KFAET0150ETK PVC Condensate Trap Kit (50 pack) All E2015 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 06/15 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. PDSFPMA--- 03 Replaces: PDSFPMA---02 8