Prefabricated transformer substations Up to 36 40.5 kv IEC 67-0 Location: Date: Speaker: Reliable innovation. Personal solutions.
Contents I. Introduction II. Main features III. Product range Design Range References 60 Transformer Substations
I. Introduction Preface Prefabricated transformer substations The prefabricated transformer substations are products which are IEC / EN 67-0 compliant. They are built as standard, tested and are supplied as a unit. World biggest prefabricated transformer substation manufacturer More than 90,000 transformer substations installed worldwide More than 0,000 underground substations Manufactured 00% in Europe Application: DNS (Distribution Network Solutions for secondary distribution) A. Distribution transformer B. MV and LV electrical equipment C. MV and LV interconnection D. Auxiliary equipment and circuits E. Enclosure Your business and DNS applications Segments Smart Grid Transmission & Distribution Generation Infrastructures Industrial Tertiary Wind Solar Dispatchable RES 3 Transformer Substations
II. Main features Safety People and third parties protection: Internal arc tested (IAC class) Physical protection in transformer accesses (live parts not accessible, even in overload conditions) Dielectric liquid collector: Protection against insulator leakage Reliability Factory- assembled and equipped as a unit. Low thermal load: Minimum quantity of dielectric liquid in the transformers High mechanical and electrical endurance Efficiency Protection against pollution, other environmental factors, impacts, vandalism Longer life, endurance and robustness than non-prefabricated solutions Minimal civil works and easy transportation Sustainability Minimal environmental, visual and acoustic impact. Reduced size and versatility Equipment adaptable to the evolution of the network Continuous innovation Aesthetic integration into the environment Auxiliary low voltage feeder inlet to enter cables from a generator set Smart-grid ready substations 4 Transformer Substations
Prefabricated transformer substations (/) Concrete Compact kiosk: miniblok Compact underground: minisub Kiosk: ormaset ormaset.p Rural kiosk: ctr ctc CEADS (Compact equipment assembly): mb Other specific tested configurations : Walk-in: pfu.4 iec Underground: pfs.48 iec ormadis.s 5 Transformer Substations
Prefabricated transformer substations (/) Concrete Metallic Walk-in (PAMI & PUIE): cto Rural kiosk (PRCS): ctc.r Rural kiosk (PSS): ctc.ra & rb Kiosk: ormaset.m Outdoor compact: mb.m 6 Transformer Substations
Compact kiosk: miniblok Concrete Kiosk-type compact Prefabricated Transformer Substation used in Medium Voltage (MV) electrical distribution networks up to 36 kv Ground level installation Outdoor operation Tested and supplied from factory as a unit Internal arc tested Minimal visual impact Oil collecting pit Auxiliary LV feeder access for cables coming from a generator set Experience: Over 4,000 units installed Consists of: MV associated (A) type compact equipment assembly (CEADS) Monoblock concrete enclosure with removable roof Range Design 3....3 Concrete enclosure. Optional: Operating isolating platform mb: Associated compact equipment assembly. MV switchgear (RMU) cgmcosmos-lp (up to 4 kv) cgm.3-lp (up to 36 kv). Transformer up to 630 kva.3 LV board miniblok.4 miniblok.36 3 Ormazabal protection, control and metering units 7 Transformer Substations
Compact kiosk: miniblok Technical details miniblok miniblok.4 miniblok.36 Rated Voltage Ur [kv] 4 36 Rated frequency fr [Hz] 50 Internal arc classification IAC 6 ka / 0, 5 s Transformer Power [kva] 50 / 400 / 630 MV Switchgear Rated current Busbars Ir [A] 400 / 630 Output Ir [A] 400/630 (l) 00 (p) Short-time current Ik [ka] 6 / 0 Low voltage board Rated voltage Ur [V] 440 Rated current Busbar Ir [A] 000 Outputs Ir [A] 4 x 400 Width [mm] 00 Depth [mm] 00 Height [mm] 40 Visible height [mm] 600 Weight (with a 630 kva transformer) [kg] 7400 7550 Standards EN 5053 IEC / EN 67-0 Compact equipment assembly (CEADS) HV switchgear: Prefabricated transformer substations 8 Transformer Substations
Compact kiosk: miniblok References Main countries with miniblok installed: Utility End Users RES Spain Argentina Chile Brazil Colombia Dominican Republic Switzerland Paraguay 9 Transformer Substations
Compact underground: minisub Concrete Underground-type compact Prefabricated Transformer Substation used in Medium Voltage (MV) electrical distribution networks up to 36 kv Tested and supplied from factory as a unit Natural ventilation (class 0) Internal arc tested Integration into the environment Oil collecting pit Experience: Over,000 units installed worldwide Design. 3..3.. Consists of: MV associated (A) type compact equipment assembly (CEADS) Monoblock concrete enclosure with removable cover Concrete enclosure. Staff access Range. Ventilation (h or v) mb: Associated compact equipment assembly. MV switchgear (RMU) cgmcosmos-lp (up to 4 kv) cgm.3-lp (up to 36 kv). Transformer up to 630 kva.3 LV board minisub-h: Horizontal ventilation minisub-v: Vertical ventilation 3 Ormazabal protection, control and metering units 0 Transformer Substations
Compact underground: minisub Technical details minisub minisub.4 minisub.36 Rated Voltage Ur [kv] 4 36 Rated frequency fr [Hz] 50 Internal arc classification IAC 6 ka / 0, 5 s Transformer Power [kva] 50 / 400 / 630 MV Switchgear Rated current Busbars Ir [A] 400 / 630 Output Ir [A] 400/630 (l) 00 (p) Short-time current Ik [ka] 6 / 0 Low voltage board Rated voltage Ur [V] 440 Rated current Busbar Ir [A] 000 Outputs Ir [A] 4 x 400 Ventilation [mm] h v Width [mm] 4450 3460 Depth [mm] 460 Height [mm] -40 Ventilation height [mm] 0 +485 Weight (with a 630 kva transformer) [kg] 6700 4 kv / 6850 36 kv 500 4 kv / 5350 36 kv Standards EN 5053 IEC / EN 67-0 Compact equipment assembly (CEADS) HV switchgear: Prefabricated transformer substations Transformer Substations
Compact underground: minisub References Utility Main countries with minisub installed: Spain Argentina Portugal Turkey Transformer Substations
CEADS Compact equipment assembly: mb Compact equipment assembly designed to be installed both in prefabricated transformer substations and in buildings made for that purpose, used in MV electrical distribution networks up to 36 kv (EN 5053) CEADS type A (associated) Fully factory assembled Tested and supplied from factory as a unit Internal arc tested To be integrated in miniblok and minisub compact TS Experience: Over 8,500 units installed worldwide Design 4 6 3 5 Range MV switchgear (RMU) cgmcosmos-lp (up to 4 kv) cgm.3-lp (up to 36 kv) Transformer up to 630 kva 3 LV board mb.4 mb.36 4 Ormazabal protection, control and metering units 5 Self- supporting frame 6 Direct MV and LV interconnections 3 Transformer Substations
CEADS Compact equipment assembly: mb Technical details mb mb.4 mb.36 Rated Voltage Ur [kv] 4 36 Rated frequency fr [Hz] 50 Internal arc classification IAC 6 ka / 0, 5 s Transformer Power [kva] 50 / 400 / 630 MV Switchgear Rated current Busbars Ir [A] 400 / 630 Output Ir [A] 400/630 (l) 00 (p) Short-time current Ik [ka] 6 / 0 Low voltage board Rated voltage Ur [V] 440 Rated current Busbar Ir [A] 000 Outputs Ir [A] 4 x 400 Width [mm] 890 890 Depth [mm] 673 84 Height [mm] 53 59 Weight [kg] 600 (50 kva) 950 (400 kva) 400 (630 kva) 800 (50 kva) 00 (400 kva) 550 (630 kva) Standards EN 5053 IEC / EN 67- Compact equipment assembly (CEADS) HV switchgear: Common specifications for HV switchgear and control gear 4 Transformer Substations
CEADS Compact equipment assembly: mb References Utility End Users RES 5 Transformer Substations
Kiosk: ormaset Concrete Kiosk-type Prefabricated Transformer Substation used in Medium Voltage (MV) electrical distribution networks up to 36 kv Ground level installation (half-buried) Outdoor operation Independent accesses: MV switchgear and transformer + LV board Tested and supplied from factory as a unit Minimal visual impact Oil collecting pit Auxiliary LV feeder access for cables coming from a generator set Experience: Over 550 units installed worldwide Design 3 4 5 Monoblok concrete enclosure Range MV switchgear cgmcosmos (up to 4 kv) cgm.3 (up to 36 kv) 3 Transformer up to 000 kva 4 5 LV board Ormazabal protection, control and metering units ormaset.4 ormaset.36 6 Transformer Substations
Kiosk: ormaset Technical details ormaset ormaset.4 ormaset.36 Rated Voltage Ur [kv] 4 36 Rated frequency fr [Hz] 50 Transformer Power (max) [kva] 000 MV Switchgear Rated current Busbars Ir [A] 400 / 630 Output Ir [A] 400/630 (l) 00 (p) Short-time current Ik [ka] 6 / 0 Low voltage board Rated voltage Ur [V] 40 Rated current Busbar (max) Ir [A] 600 Width [mm] 3475 Depth [mm] 070 Height [mm] 350 Visible height [mm] 4500 Weight (without transformer) [kg] 7300 Standards IEC / EN 67-0 HV switchgear: Prefabricated transformer substations 7 Transformer Substations
Kiosk: ormaset References Main countries with ormaset installed: Utility End Users RES Spain Portugal Poland Turkey 8 Transformer Substations
Kiosk: ormaset.p Concrete Kiosk-type Prefabricated Transformer Substation used in Medium Voltage (MV) electrical distribution networks up to 4 kv Ground level installation (half-buried) Outdoor operation Independent accesses: MV switchgear and transformer + LV board Supplied from factory as a unit Minimal visual impact Oil collecting pit Design 4 3 5 Range Monoblok concrete enclosure Length 830mm Length 400mm Length 900mm MV switchgear cgmcosmos / ga-gae (up to 4 kv) 3 Transformer up to 630 kva 4 LV board ormaset.p-73 : 730 mm width series ormaset.p-0 : 00 mm width series 5 Ormazabal protection, control and metering units 9 Transformer Substations
Kiosk: ormaset.p Technical details ormaset.p Rated Voltage Ur [kv] 4 Rated frequency fr [Hz] 50 Transformer Power (max) [kva] 630 MV Switchgear Rated current Busbars Ir [A] 400 / 630 Output Ir [A] 400/630 (l) 00 (p) Short-time current Ik [ka] 6 / 0 Low voltage board Rated voltage Ur [V] 40 Rated current Busbar (max) Ir [A] 600 73/83 0/40 0/90 Width [mm] 730 00 00 Depth [mm] 830 400 900 Height [mm] 45 45 45 Visible height [mm] 65 65 65 Weight [kg] 6900 700 700 Standards IEC / EN 67-0 HV switchgear: Prefabricated transformer substations 0 Transformer Substations
Kiosk: ormaset.p References Utility End Users Main countries with ormaset.p installed: Poland Germany Switzerland Transformer Substations
Rural kiosk: ctr Concrete Kiosk-type compact Prefabricated Transformer Substation used in Medium Voltage (MV) rural distribution networks up to 36 kv Ground level installation Outdoor operation Tested and supplied from factory as a unit Minimal visual impact Oil collecting pit Auxiliary LV feeder access for cables coming from a generator set Experience: Over 5,000 rural kiosks installed Design 3..3. Consists of: MV associated (A) type compact equipment assembly (CEADS) Monoblock concrete enclosure with removable roof Concrete enclosure Range Associated compact equipment assembly. MV switchgear cgmcosmos (up to 4 kv) cgm.3 (up to 36 kv). Transformer up to 630 kva.3 LV board ctr. ctr.3 3 Ormazabal protection and control unit: ekor.rpt-k Transformer Substations
Rural kiosk: ctr Technical details ctr ctr. ctr.3 Rated Voltage Ur [kv] 4 36 Rated frequency fr [Hz] 50 Transformer Power [kva] 00 / 60 / 50 MV Switchgear Rated current Ir [A] 00 Short-time current Ik [ka] 6 Low voltage board Rated voltage Ur [V] 40 Rated current Busbar Ir [A] 630 Outputs Ir [A] 3 x 400 Width [mm] 700 Depth [mm] 600 Height [mm] 975 00 Visible height [mm] 500 Weight (with a 50 kva transformer) [kg] 450 4350 Standards EN 5053 IEC / EN 67-0 Compact equipment assembly (CEADS) HV switchgear: Prefabricated transformer substations 3 Transformer Substations
Rural kiosk: ctr References Utility Main countries with ctr installed: Spain Argentina Turkey 4 Transformer Substations
Rural kiosk: ctc Concrete Kiosk-type under pole Prefabricated Transformer Substation used in Medium Voltage (MV) rural distribution networks up to 36 kv Ground level installation Outdoor operation Tested and supplied from factory as a unit Minimal visual impact Oil collecting pit Breaking and protection remain on the pole Experience: Over 5,000 rural kiosks installed Design 4 3 4 Consists of: Electrical equipment: MV/LV distribution transformer and LV board Monoblock concrete enclosure with removable roof Range 3 Concrete enclosure Distribution transformer up to 50 kva LV board 4 Accesses ctc: - 4-36 kv 5 Transformer Substations
Rural kiosk: ctc Technical details ctc Rated Voltage Ur [kv] / 4 / 36* Rated frequency fr [Hz] 50 Transformer Power [kva] 50 Low voltage board Rated voltage Ur [V] 440 Rated current Ir [A] 630 Width [mm] 330 Depth [mm] 70 Height [mm] 080 Visible height [mm] 600 Weight [kg] 4600 (*) Requires personalized project Standards IEC / EN 67-0 HV switchgear: Prefabricated transformer substations 6 Transformer Substations
Rural kiosk: ctc References Utility Main countries with ctc installed: Spain Argentina 7 Transformer Substations
Walk-in PAMI (Poste à aire de manœuvre intérieure): cto Concrete Walk-in type Prefabricated Transformer Substation with reduced dimensions used in Medium Voltage (MV) electrical distribution networks up to 4 kv. Generally in France for public distribution networks non exploited by EDF.. Ground level installation Indoor operation Tested and supplied from factory as a unit Minimal visual impact Reduced occupied space Easy installation Ergonomic design: easy indoor access and operation Experience: about 700 cto installed 4 3... Monoblok concrete enclosure Access front door Access cover MV switchgear cgmcosmos (up to 4 kv) 3 Transformer up to 630 kva 4 LV board 8 Transformer Substations
Walk-in PAMI (Poste à aire de manœuvre intérieure): cto Technical details cto Rated Voltage Ur [kv] 4 Rated frequency fr [Hz] 50 Transformer Power [kva] 50-630 MV Switchgear Rated current Busbars Ir [A] 400 Output Ir [A] 400 (l) 00 (p) Short-time current Ik [ka] 6 / 0 Low voltage board Rated voltage Ur [V] 40 Rated current Busbar (max) Ir [A] 00 Width [mm] 530 Depth [mm] 00 Height [mm] 300 Visible height [mm] 700 Weight (with a 630 kva transformer) [kg] 7300 Standards IEC / EN 67-0 HV switchgear: Prefabricated transformer substations 9 Transformer Substations
Walk-in PAMI (Poste à aire de manœuvre intérieure): cto References Utility End Users Main countries with cto installed: France Gabon 30 Transformer Substations
Walk-in PUIE (Poste Urbain Intégré à son Environnement): cto Concrete Walk-in type Prefabricated Transformer Substation with reduced dimensions public distribution networks up to 4 kv in France. used in. According to standard: HN 64-S-56 et amendement de janvier 009 Consists of: Electrical equipment: cgmcosmos.c-i+spt : 4 kv / 400 A /,5 ka s Transformer: transforma.tpc 400-630 kva LV board: TIPI type ITI board for remote control Monoblock concrete enclosure with removable roof 4 3... Monoblok concrete enclosure Access front door Access cover MV switchgear cgmcosmos (up to 4 kv) 3 Transformer up to 630 kva 4 LV board 3 Transformer Substations
Rural kiosk (PRCS type: Poste rural compact simplifié): ctc.r Concrete Kiosk-type compact Prefabricated Transformer Substation used in Medium Voltage (MV) rural distribution networks up to 4 kv in France According to specification ERDF HN 64-S-57 version B and NF C -0 Ground level installation Outdoor operation Tested and supplied from factory as a unit Minimal visual impact Experience: Over 3,500 ctc.r installed Design Consists of: MV/BT transforma.tpc (50, 00 or 60 kva) according to HN64-S-57. LV board (TIPI or fused board) Base and side walls of concrete with metallic covers and grids. 3. Concrete enclosure Range.. 3 Removable front cover Foldable upper cover TPC transformer up to 60 kva LV board 3 Transformer Substations
Rural kiosk (PRCS type: Poste rural compact simplifié): ctc.r Technical details ctc.r Rated Voltage Ur [kv] 7.5 / 4 Rated frequency fr [Hz] 50 Transformer Power (max) [kva] 50 / 00 / 60 Low voltage board Rated voltage Ur [V] 40 Rated current Ir [A] 50 A (60 kva) 50 kva 00 kva 60 kva Width [mm] 480 Depth [mm] 680 Height [mm] 75 Visible height [mm] 455 Weight [kg] <600 <800 <000 Standards HN 64-S-57 Version B NF C -0 IEC / EN 67-0 HV switchgear: Prefabricated transformer substations 33 Transformer Substations
III. Product range Rural kiosk (PRCS type: Poste rural compact simplifié): ctc.r References Utility Main country with ctc.r installed: France 34 Transformer Substations
Rural kiosk (PSS-A or -B type: Poste au sol simplifié): ctc.ra & rb Concrete Design Kiosk-type compact Prefabricated Transformer Substation used in Medium Voltage (MV) rural distribution networks up to 4 kv in France.. According to specification ERDF HN 64-S-36 version D and NF C -0 Ground level installation Outdoor operation Tested and supplied from factory as a unit Minimal visual impact Experience: About 900 ctc.ra & rb installed. 4 3 4. Consists of: MV/BT transforma.tpc (00, 60 or 50 kva) according to HN64-S-4. LV board (TIPI type) In ctc.rb: cgmcosmos switchgear up to 4 kv Base and side walls of concrete with metallic covers and grids Range ctc.ra.. ctc.rb Concrete enclosure Removable front cover Foldable upper cover TPC transformer up to 50 kva 3 MV switchgear cgmcosmos (up to 4 kv) ctc.ra ctc.rb 4 LV board 35 Transformer Substations
Rural kiosk (PSS-A or -B type: Poste au sol simplifié): ctc.ra & rb Technical details ctc.ra & rb Rated Voltage Ur [kv] 7.5 / 4 Rated frequency fr [Hz] 50 Transformer Power (max) [kva] 00 / 60 / 50 Low voltage board Rated voltage Ur [V] 40 MV Switchgear (ctc.rb) Short-time current Ik [ka] 8 ctc.ra ctc.rb Width [mm] 40 300 Depth [mm] 60 60 Height [mm] 00 00 Visible height [mm] 500 500 Weight [kg] <380 <4980 Standards HN 64-S-36 Version D HN 5-S-4 NF C -0 IEC / EN 67-0 HV switchgear: Prefabricated transformer substations 36 Transformer Substations
Rural kiosk (PSS-A or -B type: Poste au sol simplifié): ctc.ra & rb References Main country with ctc.ra & rb installed: Utility ctc.ra ctc.rb France 37 Transformer Substations
Kiosk: ormaset.m Metallic Kiosk-type Prefabricated Transformer Substation used in Medium Voltage (MV) electrical distribution networks up to 36 kv Ground level installation Outdoor operation Independent accesses: MV switchgear and transformer + LV board Tested and supplied from factory as a unit Mobility and temporary uses Optional base with sleigh for easier relocation: ormaset.m-s type 4 Design 3 Range Metallic enclosure MV switchgear cgmcosmos (up to 4 kv) cgm.3 (up to 36 kv) 3 Transformer up to 000 kva 4 LV board ormaset.m-4 ormaset.m-36 38 Transformer Substations
Kiosk: ormaset.m Technical details ormaset.m ormaset.m-4 ormaset.m-36 Rated Voltage Ur [kv] 4 36 Rated frequency fr [Hz] 50 Transformer Power (max) [kva] 000 MV Switchgear Rated current Busbars Ir [A] 400 / 630 Output Ir [A] 400/630 (l) 00 (p) Short-time current Ik [ka] 6 / 0 Low voltage board Rated voltage Ur [V] 400 Rated current Busbar (max) Ir [A] 600 Width [mm] 3600 Depth [mm] 336 Height [mm] 300 Weight [kg] <4800 (630 kva) <5500 (000 kva) Standards IEC / EN 67-0 HV switchgear: Prefabricated transformer substations 39 Transformer Substations
Kiosk: ormaset.m References Utility End Users Main country with ormaset.m installed: France 40 Transformer Substations
Outdoor compact: mb.m Metallic Outdoor compact prefabricated transformer substation used in Medium Voltage (MV) electrical distribution networks up to 40.5 kv. Design Ground level installation Outdoor operation Tested and supplied from factory as a unit Internal arc tested IAC AB 0 ka s Corrosivity C4 H (ISO 944-A) Transportable in sea container HC 40 (up to 3 units) 3 Range mb.m 4 mb.m 36 mb.m 40,5 PV applications s: mb.m-pv Medium-voltage outdoor switchgear cgmcosmos / ga (up to 4 kv) cgm.3 (up to 40,5kV) transformer up to,5 MVA Optional: IPX perimeter protection fence Oil collection tank MV and/or LV terminal cover box 3 Metal frame assembly 4 Transformer Substations
Outdoor compact: mb.m Technical details mb.m mb.m-4 mb.m-36 40,5 Rated Voltage Ur [kv] 4 36 / 40,5 Rated frequency fr [Hz] 50 Transformer Power [kva] 500 MV Switchgear Rated current cgmcosmos Ir [A] 400 / 630 - ga Ir [A] 630 - cgm.3 Ir [A] - 400 / 630 Short-time current Ik [ka / s] 6 / 0 / 5* (* cgmcosmos & cgm.3) Internal arc Class IAC AB [ka / s] 0 Width [mm] 997 Depth [mm] 96 Height [mm] 504 Weight (without transformer) [kg] 400-00 Configurations cgmcosmos-3l, cgmcosmos-lp, cgmcosmos-lv. cgm.3-3l, cgm.3-lp, cgm.3-lv. ga-3k, ga-kts, ga-klsf Optional: cgmcosmos-lp, cgmcosmos-4l, cgmcosmos-lv. cgm.3-lp, cgm.3-4l, cgm.3-lv. ga-4k, ga-kts, ga-klsf 4 Transformer Substations
Outdoor compact: mb.m References RES Countries with mb.m: Jordan 43 Transformer Substations
Thank you! more information: www.ormazabal.com and social networks Transformer Substation downloads: Brochures: CA-443 / 444 / 44 / 448 / 38 / 336 / 43 / 43 / 455 Manuals: IG-35 / 3 / 30 / 8 & others