Development of control unit for smart power supply system using battery energy storages and residential PV-PCSs

Similar documents
Construction of power supply system using electric vehicle for stable power delivery from PV generation

Functional PCS power supply system with EV battery storage for stable PV power delivery

Technology from the New Product SANUPS K for a Smart Grid Society

BIDIRECTIONAL DC-DC CONVERTER FOR INTEGRATION OF BATTERY ENERGY STORAGE SYSTEM WITH DC GRID

Development of Novel Connection Control Method for Small Scale Solar - Wind Hybrid Power Plant

Power Management with Solar PV in Grid-connected and Stand-alone Modes

Technology of Estimating Short Circuit Current and Ground Fault for Direct Current Distribution Systems

Development of Emergency Train Travel Function Provided by Stationary Energy Storage System

Design of Active and Reactive Power Control of Grid Tied Photovoltaics

Achieves a high-efficiency conversion of 94% despite being isolated type through digital control

Multi-Port DC-DC Converter for Grid Integration of Photo Voltaic Systems through Storage Systems with High Step-Up Ratio

Modeling and Analysis of Vehicle with Wind-solar Photovoltaic Hybrid Generating System Zhi-jun Guo 1, a, Xiang-yu Kang 1, b

Analysis and Design of Improved Isolated Bidirectional Fullbridge DC-DC Converter for Hybrid Electric Vehicle

Design and Control of Hybrid Power System for Stand-Alone Applications

International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. (An ISO 3297: 2007 Certified Organization)

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Design and Development of Bidirectional DC-DC Converter using coupled inductor with a battery SOC indication

Abstract- In order to increase energy independency and decrease harmful vehicle emissions, plug-in hybrid electric vehicles

A Novel Hybrid PV/Wind/Battery based Generation System for Grid Integration

HOMER OPTIMIZATION BASED SOLAR WIND HYBRID SYSTEM 1 Supriya A. Barge, 2 Prof. D.B. Pawar,

Available online at ScienceDirect. Energy Procedia 36 (2013 )

Mathematical Model of Electric Vehicle Power Consumption for Traveling and Air-Conditioning

A Novel Hybrid Smart Grid- PV-FC V2G Battery Charging Scheme

High Speed V-Series of Fast Discrete IGBTs

Development of the SANUPS P73K Power Conditioner with Peak Power Cut Function

GRID CONNECTED SOLAR WIND HYBRID POWER BASED ON IOT

Design and Simulation of Grid Connected PV System

A Novel DC-DC Converter Based Integration of Renewable Energy Sources for Residential Micro Grid Applications

Electric cars: Technology

Electric cars: Technology

All-SiC Module for Mega-Solar Power Conditioner

Intelligent Control Algorithm for Distributed Battery Energy Storage Systems

Microgrid with Solar Power and Fuel Cell Technology

Development of Higher-voltage Direct Current Power Feeding System for ICT Equipment

Figure 1 I-V characteristics of PV cells. Meenakshi Dixit, Dr. A. A. Shinde IJSRE Volume 3 Issue 12 December 2015 Page 4687

DC Microgrids and Distribution Systems for Residences

Increasing the Battery Life of the PMSG Wind Turbine by Improving Performance of the Hybrid Energy Storage System

Power Electronics Projects

Available online at ScienceDirect. Procedia Engineering 170 (2017 )

Next-generation Inverter Technology for Environmentally Conscious Vehicles

Increasing community demonstration smart-grid projects involving consumers

The evaluation of endurance running tests of the fuel cells and battery hybrid test railway train

APPLICATION OF BOOST INVERTER FOR GRID CONNECTED FUEL CELL BASED POWER GENERATION

A Novel GUI Modeled Fuzzy Logic Controller for a Solar Powered Energy Utilization Scheme

Control System for a Diesel Generator and UPS

A Study of Suitable Bi-Directional DC-DC Converter Topology Essential For Battery Charge Regulation In Photovoltaic Applications

Research on PV and battery control system with energy management technology in stand-alone DC micro grid

Dual power flow Interface for EV, HEV, and PHEV Applications

DESIGN AND ANALYSIS OF CONVERTER FED BRUSHLESS DC (BLDC) MOTOR

Remarkable CO 2 Reduction of the Fixed Point Fishing Plug-in Hybrid Boat

Development of the Single Phase PV Inverter SANUPS P61A

K. Surendhirababu *, D. Karthikeyan *, K. Vijayakumar *, K. Selvakumar * and R. Palanisamy *

PVI1000 : Outdoor High-Efficiency Power Conditioners for Mega Solar Projects

1. RENEWABLE ENERGY I.SOLAR ENERGY PROJECT TITLES WE CAN ALSO IMPLEMENT YOUR OWN CONCEPT/IDEA

Power Flow Management and Control of Hybrid Wind / PV/ Fuel Cell and Battery Power System using Intelligent Control

Integration of Photovoltaic-Fuel Cell Scheme for Energy Supply in Remote Areas

Current State of the Renewable Energy in Kyushu Electric Power and Our Future Plan. Kyushu Electric Power Co. Inc. June 8, 2017

A Bidirectional Universal Dc/Dc Converter Topology for Electric Vehicle Applicationsand Photovoltaic Applications

Robust Control Technique for Grid-connected Power Conditioner

Decoupling and Control of Real and Reactive Power in Grid-Connected Photovoltaic Power System

International Journal of Advance Research in Engineering, Science & Technology

Photovoltaic Systems Engineering

Island Smart Grid Model in Hawaii Incorporating EVs

Design and Implementation of Non-Isolated Three- Port DC/DC Converter for Stand-Alone Renewable Power System Applications

LOW CARBON FOOTPRINT HYBRID BATTERY CHARGER FINAL PRESENTATION

Microgrid System for Isolated Islands

Application of one-axis sun tracking system. Colak I. and Demirtas M.

A STUDY ON A SUPPLY-DEMAND SIMULATION MODEL FOR THE STAND-ALONE HYBRID POWER SUPPLY CONSISTING OF FUEL CELL AND ENERGY CAPACITOR SYSTEMS

Dynamic Modelling of Hybrid System for Efficient Power Transfer under Different Condition

The Circuit and Control Technology in the Power Conditioner and Converter for Wind Turbine Systems

International Conference on Advances in Energy and Environmental Science (ICAEES 2015)

OPTIMAL OPERATION OF SMART HOUSE FOR REAL TIME ELECTRICITY MARKET. University of the Ryukyus, Okinawa, Japan

Power Conditioning of Microgrids and Co-Generation Systems

Design of Three Input Buck-Boost DC-DC Converter with Constant input voltage and Variable duty ratio using MATLAB/Simulink

Simulation Modeling and Control of Hybrid Ac/Dc Microgrid

Using Opal-RT Real-Time Simulation and HIL System in Power and Energy Systems Research

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY

The Master of IEEE Projects. LeMenizInfotech. 36, 100 Feet Road, Natesan Nagar, Near Indira Gandhi Statue, Pondicherry

ENERGY MANAGEMENT FOR HYBRID PV SYSTEM

Recent trends and Importance of Power Electronics: Dr. Siva Kumar K IIT Hyderabad

5 kw Multilevel DC-DC Converter for Hybrid Electric and Fuel Cell Automotive Applications

Small Scale-Wind Power Dispatchable Energy Source Modeling

Development and Analysis of Bidirectional Converter for Electric Vehicle Application

NET METER REQUEST FORM

The hierarchical three layer protection of photovoltaic generators in microgrid with co-ordinated droop control for hybrid energy storage system

Providing Energy Management of a Fuel Cell-Battery Hybrid Electric Vehicle Fatma Keskin Arabul, Ibrahim Senol, Ahmet Yigit Arabul, Ali Rifat Boynuegri

Hybrid Three-Port DC DC Converter for PV-FC Systems

DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID

Inverter with MPPT and Suppressed Leakage Current

Conclusions. Fall 2010

off-grid Solutions Security of supply Basics: Off-grid energy supply

Hybrid Solar Panel Fuel Cell Power Plant

Impact of Reflectors on Solar Energy Systems

Implementation of Bidirectional DC-DC converter for Power Management in Hybrid Energy Sources

A.Arun 1, M.Porkodi 2 1 PG student, 2 Associate Professor. Department of Electrical Engineering, Sona College of Technology, Salem, India

High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development Co., Ltd.

Simulation Analysis of Closed Loop Dual Inductor Current-Fed Push-Pull Converter by using Soft Switching

EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION

J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy***

SOLAR PHOTOVOLTAIC ARRAY FED WATER PUMP RIVEN BY BRUSHLESS DC MOTOR USING KY CONVERTER

Transcription:

International Journal of Smart Grid and Clean Energy Development of control unit for smart power supply system using battery energy storages and residential PV-PCSs Kiyotaka Fuji a,b*, Takahisa Kawagoe b, Kenta Tanoue b, Atsushi Shiota b, Yasunori Mitani b, Thongchart Kerdphol b, Yaser Qudaih b a Department of Biological Functions and Engineering Graduate School of Life Science and Systems Engineering, Kyushu Institute of Technology, Kitakyushu 808-0196, Japan b Department of Electrical and Electronic Engineering, Kyushu Institute of Technology, Kitakyushu 804-8550, Japan Abstract This research deals with the Non-Isolated Bidirectional Dc-Dc Converter (NBDC) control unit development for a smart power supply system using personal residential Photovoltaic-Power Conditioning Subsystem (PV-PCS), the results of circuits evaluation, and isolated PV-PCS operation connected battery storage (Electric vehicle storage etc.). The smart power supply system using the existing residential PCS with battery storage has an advantage that it can suppress the energy change during normal operation and can also construct the isolated power supply in an emergency case of power system cut-off. In PV power generation, PV power fluctuations caused by weather changes make the difficulty to obtain stable power output. Further, it can be expected that this adversely affects to the power system. By using this smart system control with an isolated power supply function, this battery storage can be provided the power for critical loads during the utility outage. In this paper, the comparison of voltage control mode in terms of battery voltage range is considered for the smart system operation. In particular, IGBT power semiconductor gate drive circuit of light insulation and current-voltage detection circuit with used photo-coupler of light insulation are newly developed for the smart power supply system operation. Moreover, the isolated power supplies effectiveness, the smart circuit development, and the experiment results of the PV-PCS interconnection isolated power system for stable supply with the existing residential PV-PCS of Japan are investigated, analyzed and discussed. Keywords: Non-Isolated bidirectional dc-dc converter, battery storage, photovoltaic power generation, power conditioning subsystem, light insulation photo-coupler, electric vehicle 1. Introduction Economic activity and energy consuming activities are inextricably linked. Thus, energy consumption is absolutely imperative in order to grow a certain economic. Currently, a primary energy is depended on a large part of fossil fuel resource. Thus, carbon dioxide (CO 2 ) that is emitted by combustion of the fossil fuel increases with the energy consumption has been increased. For this reason, the whole world is working towards to a low carbon society for reducing CO 2 emissions as much as possible. By the influence of East Japan earthquake of March 2011 and a feed-in tariff for renewable energy of enforcement in July 2012, the introduction of photovoltaic power generation has been activated based on Japanese government s plan. On the other hand, it is attracting the attention to commercialize Electric Vehicles (EVs) in the automotive industry as activities toward a low-carbon society [1]-[6]. Photovoltaic (PV) power generation has a characteristic that the power output fluctuates severely depending on the weather conditions. Therefore, if a large amount PV generated power to the grid has been introduced, there is a risk of adverse effect on the stable power supply and power quality. Moreover, when the power system had been cut off by the disaster, it makes the difficulties to obtain stable power from * Manuscript received April 15, 2015; revised August 12, 2015. Corresponding author: Kiyotaka Fuji; Tel.: +81-90-5743-3431; E-mail address: fuji19690708@gmail.com. doi: 10.12720/sgce.4.3.159-168

160 International Journal of Smart Grid and Clean Energy, vol. 4, no. 3, July 2015 photovoltaic power generation in homes and facilities. In addition, because of nuclear power plants shut down, there is also a condition that power supply capacity has been tight depending on a season. However, in each home and each facility, if the power independence state can easily achieve from the power system, it is possible to adjust the flexible operation of "peak load reduction of the power system" or "power supply continuation of emergency power outage". Nevertheless, if the an electric vehicle can be used as a movable storage battery, power secure in power failure and fluctuation control and peak load reduction is expected by using the combination of the widely spread photovoltaic power generation to every household and facilities [7]-[9]. In this study, the system for coordinating the existing photovoltaic power generation systems and electric vehicle storage battery is proposed. Power supply system of the grid-connected system and independence system with a fluctuation suppression, peak load reduction and new functions of the power ensure in the power failure is constructed. Therefore, the development of Bidirectional dc-dc converter control circuit and control system is the main purpose as the coordinated control equipment of the photovoltaic power generation system and electric vehicle. Bidirectional Dc-Dc Converters (BDC) has recently received a lot of attention due to the increasing need of systems with the capability of bidirectional energy transfer between two dc buses. Apart from traditional application in dc motor drives, the new applications of BDC have focused and included energy storages in renewable energy systems, fuel cell energy systems, Hybrid Electric Vehicles (HEV) and Uninterruptible Power Supplies (UPS). The fluctuated nature of most renewable energy resources, like wind and solar, makes them unsuitable for standalone operation as the sole source of power. A common solution to overcome this problem is to use an energy storage device besides the renewable energy resource in order to compensate these fluctuations and maintain a smooth and continuous power flow to the loads. As the most common and economical energy storage devices in medium-power range are batteries and super-capacitors, a dc-dc converter is always required energy exchange between storage device and the rest of system. Such a converter must have the bidirectional power flow capability with flexible control in all operating modes. For example, in HEV applications, BDCs are required to link different dc voltage buses and transfer energy between them. Besides, a BDC is used to exchange energy between main batteries (200-300V) and the drive motor with 500V dc link. High efficiency, lightweight, compact size and high reliability are some important requirements for the BDC used in such an application. Another, in a line-interactive UPS, the UPS output terminals are connected to the grid and therefore energy can be fed back to the inverter dc bus and charge the batteries via a BDC during normal mode. In backup mode, the battery needs the inverter dc bus again via BDC but this converter must be reversed power flow direction. Therefore, based on the above advantage, a smart power supply system using the Non-Isolated Bidirectional Dc-Dc Converter (NBDC) is developed [10]-[14]. This paper deals with the grid interconnection independence power supply system construction and its smart circuit study. Then, the developments and evaluations of the most important IGBT semiconductor device gate-drive circuit and voltage-current detecting circuit of the control system are described in the circuit that makes up the system. Moreover, the comparison of voltage control mode in battery voltage range is considered for this smart system operating. In addition, the isolated power supplies effectiveness, the smart circuit developments and the experiment results of the PV-PCS interconnection isolated power system for stable supply with the existing residential Photovoltaic-Power Conditioning Subsystem (PV- PCS) of Japan are investigated and discussed. This paper can be divided into six parts. The first part discusses a brief introduction of the control unit development of smart residential PV-PCS power supply system connected battery storage using BDC. The second part describes about the outline of smart power supply system. The third part discusses the residential PV-PCS stable power supply delivery system configuration about non-isolated BDC (NBDC) fundamental control. The fourth part discusses about the residential PV-PCS power supply system development with self-supported power supply function. The fifth part discusses about the PV-PCS power supply system operation experiment with battery storage in isolated mode. Lastly, the sixth part summarizes the conclusion.

Kiyotaka Fuji et al.: Development of control unit for smart power supply system using battery energy storages and 161 2. Outline of Smart Power Supply System Using Battery Storage and Residential PV-PCS As PV power generation greatly depends on weather conditions, the output has bad influences to the power system. On the other hand, it is known that the surplus power is generated at the light load time of the power system. This causes the increasing of voltage problem in the power distribution network [15], [16]. Recently, the power supply capacity in Japan is tight because of the cease of operations of nuclear power plants. If households can use the power independently from the power system, these loads can be detached voluntarily from the power system at the event of power shortage. Therefore, there is a flexible operation of reducing the load in the power system and uninterrupted power supply to the load during power outage [7], [9]. Effectiveness of smart power supply system using residential PV-PCS and battery storage with the grid-connected and self-sustainable power supply (isolated power supply function of residential PCS) is described as follows. 2.1. Grid-connected model or isolated model When households could use the power independently from the power system in case of power shortage, the power system load is reduced. When PV output fluctuation could be suppressed by the charging and discharging control of battery storage, the fluctuation can absorbs and stable power can supply to their load or the power system from a consumer side. When the reverse power flow of renewable energy is increased the distribution line voltage, battery storage system can avoid the distribution line voltage issue and can suppress PV output fluctuation. 2.2. Emergency model It is difficult to get the stable power from only PV system because the output of PV fluctuates with the amount of solar radiation. However, the proposed power system can supply the stable power to households and refuges by combining the proposed system with EV and lead battery. Fig. 1. Fundamental PV-PCS smart power supply system structure with self-supported power outlet. 3. Smart Power Supply System Configuration Using Battery Storage and Residential PV-PCS 3.1. PV-PCS smart power supply system structure with self-supported power outlet In Fig. 1, it is shown smart power supply system configured with the existing residential Photovoltaic (PV) and Power Conditioning Subsystem (PCS). The commercial PV-PCS system in Japan is a product compliant to the power system interconnection guidelines with the reversing power flow function. Also, the existing residential PV-PCS is able to be grid interconnection to the power supply system constantly, and the proposed smart power supply system has a function of the isolated power supply on the power

162 International Journal of Smart Grid and Clean Energy, vol. 4, no. 3, July 2015 system cut-off. On the other hand, PV-PCS equipment can operate the solar energy power conversion, and it also has the advantage of non-polluting and noise less. However, it has the disadvantage of PV power fluctuation by weather changing. To suppress the PV power fluctuation, it is effective that use the construction of the PV power fluctuation suppressing control with connected the non-isolated bidirectional converter (NBDC) and lead battery or EV large-capacity battery to PV-PCS constant dc voltage bus, but in the existing residential PV-PCS is not installed the this connecting terminal. The proposed structure shown in Fig. 1 which has the important characteristics that it can be the output of the isolated power supply of the single phase 100Vac 1500W with using the PCS self-supported power outlet in the power system cut-off. 3.2. Non-isolated bidirectional dc-dc converter (NBDC) topology Fig. 2 shows the non-isolated bidirectional dc-dc converter (NBDC) topology including bidirectional converter structure and the theoretical operating waveform. NBDC structure shows in Fig. 2 which is standard buck-boost converter. V PV is the dc voltage of high voltage side (HV), and V batt is the dc voltage of low voltage side (LV). i is the discharge dc current which flows from V batt to V PV. Where T=1/f sw is the switching period and D is the NBDC control duty-cycle. Fig. 2 depicts the theoretical operating waveform of buck-boost converter with S1 and S2 of IGBT semiconductor module. Table 1 is shown the system operating mode in DC voltage regulation. PV array uses in this research which is installed at laboratory building of Kyushu Institute of Technology (Kyutech). There are sixteen cells in this array in which one cell has a maximum voltage of 23.6V and minimum current of 7.36A. Eight cells are arranged in series and there are two columns in parallel. The PV array capacity under study is 2.88kW. This capacity will be assumed as the residential use. As a dc voltage investigation result of Table.1, there are various types in the major EV (PHV) and lead battery of Japan. With regard to the EV battery voltage, 72V of COMS battery voltage is the smallest while the 360V of LEAF battery voltage is the largest. Therefore, a circuit configuration which is able to be connected in these dc battery voltage ranges has to be considered by each regulation modes of Table 1. i i L t + V PV ー S1 V batt D = V PV S2 + V batt ー S2:on S2:on S1:on S1:on DT (1-D)T Mode (1-D)T DT change S1:on V batt V PV Fig. 2. NBDC topology: NBDC structure, theoretical operating waveform. Table 1. System operating mode in DC voltage regulation V PV V batt Vpv PV-PCS voltage range in Kyutech Vbatt 60 [v] 188 [v] Lead 12 [v] Battery 24 [v] Vpv > Vbatt COMS 72 [v] Vpv < Vbatt Vpv > Vbatt PRIUS 207[v] i-miev 330[v] Vpv < Vbatt LEAF 360[v]

Kiyotaka Fuji et al.: Development of control unit for smart power supply system using battery energy storages and 163 Solar Array MPPT boost converter PCS DC-AC Inverter L O A D Power Grid output Isolated operation Battery Non-isolated Bidirectional DC-DC Converter Main Circuit Ipv In/Out current In/Out voltage Vpv Isolated drive CT-insulated current / Optically-insulated voltage detecting circuit Optically-insulated gate drive circuit Idet Vac Iac Vdet Pulse signal DSP controller Regulating Calculation PWM pattern output Fig. 3. Control block diagram using the residential PV-PCS with self-supported power supply function. Fig. 4. Development of smart gate drive circuit: Gate drive circuit board, schematic diagram. 4. Control Unit Development for Smart Power Supply System 4.1. Control system and circuit board development From Fig. 3, it demonstrates the control block diagram using the residential PV-PCS with selfsupported power supply function. Based on Fig. 3, the developed system is constructed with PV, PCS, NBDC including Insulation power supply, Battery, Optically-insulated gate drive circuit for IGBT semiconductor module, and CT-insulated current/optically-insulated voltage detecting circuit. DSP controller operates the duty regulation using the detected current/voltage in unit's primary/secondary side, and it outputs the PWM pattern according to the developed control algorithm as pulse signal. For

164 International Journal of Smart Grid and Clean Energy, vol. 4, no. 3, July 2015 Optically-insulated gate drive, HCPL3120 photo-coupler gate drive IC is used. In Fig. 4, it shows its Gate drive circuit board and schematic diagram. For Optically-insulated voltage detection, HCPL7800 photocoupler insulation AMP is used. From Fig. 5, it displays its Voltage-Current (VI) detecting circuit board and Voltage detecting schematic diagram. Their circuits were able to design 10cm x 20cm small size boards as shown in Fig. 4 and Fig. 5. Fig. 5. Development of smart detecting circuit: VI circuit board, voltage detecting schematic diagram. 4.2. Evaluation of the insulation voltage detecting circuit In the photo-coupler insulation IC (HCPL7800) of the optically-insulated voltage detecting circuit, for their evaluation, the equations of voltage transforming gain and voltage detection error are shown as the following; G IN is High voltage transforming gain [180/(240k+180)]. G HCPL7800 is IC transforming gain and its value is 8. G Vdet is the AMP IC designed gain on low voltage [15k/(1.5k+7.5k)]. Therefore, G Vout gain of the approximate 100 is calculated by the equation (1). To evaluate the developed board, it is necessary to calculate the error of the equation (2) with used the measurement. Table 2 and Fig. 6 are shown the evaluation result of isolated voltage detecting circuit. The results of table 2 were shown that the error is within 1%. However, the input voltage detection of more than 100V was the error <1% from Fig. 6. So, the error of less than 100V was in a range of 1% and <10%. Where, V IN is the input DC high voltage, V det is the detected DC voltage of the converter circuit in low voltage. Since the insulating current is detected by the all elements CT, isolated circuit is unnecessary. Addition, two step filter circuit for removing the detected white noise is configured to the current detection circuit. The voltage detecting circuit is a circuit important element in this study. The voltage detecting circuit is performed by a controllable low voltage from the high voltage. In order to avoid complication of the circuits, HCPL7800 device of the optically-insulated voltage converter is applied. Thus, without constituting a complicated the multistage AMP circuits, it can be advantageously insulated from the high voltage part. However, because of a detection accuracy error in each device, the accuracy evaluation is required after the configuration of the circuit. For example, when there is the detection error 5% in 300V for dc input voltage, 15Vdc steady-

Kiyotaka Fuji et al.: Development of control unit for smart power supply system using battery energy storages and 165 state error voltage is generated in the voltage regulation. G Vout G G 7800 G (1) IN HCPL Vdet VVdet [ v] error [%] Vin [ v] Vin[ v] 100 (2) GVout Table 2. Evaluation of isolated voltage detecting circuit Ch1 Ch2 Ch3 Ch4 Vin [v] 300.07 200.04 100.02 300.07 200.00 100.06 300.02 200.03 100.02 300.05 200.02 100.05 Vdet [v] 2.9818 1.9890 0.9949 2.9816 1.9907 0.9997 3.0213 2.0180 1.0132 3.0115 2.0109 1.0096 Error [%] 0.63 0.57 0.53 0.64 0.47 0.09-0.70-0.88-1.30-0.37-0.53-0.91 Fig. 6. Measurement result of isolated voltage detecting circuit. Conv Initial condition Emergency Switch Grid connected mode Isolated mode Emergency mode T PPV>PL F PVFS Charge power decision Discharge power decision EV battery power control PVFS Control mode Constant Voltage- Current Charge Control Constant Current Discharge Control Plimit >Pbatt F End T Fig. 7. Smart power supply system using self-supported power outlet: experiment unit, isolated control mode 5. Experiment of Smart Power Supply System in an Isolated Control Mode 5.1. Isolated power supply experiment unit and control mode In Fig. 7, it is shown the experiment unit and isolated control mode of smart power supply system

166 International Journal of Smart Grid and Clean Energy, vol. 4, no. 3, July 2015 using self-supported power outlet. Based on Fig. 7, it is used PCS unit of the manufacturing Mitsubishi Electric Corporation. Moreover, the unit control algorithm of isolated power supply mode is shown in Fig. 7 for the experiment. It has 2 modes of Battery discharging mode and PV charging mode on the isolated power supply system using NBDC. 5.2. Battery discharging and PV charging control experiment using NBDC Based on Fig. 8, it depicts the isolated power supply discharging experiment results in PCS-NBDC with 72V battery. Additionally, it shows the experiment structure of the 72V battery discharging operation with used the PCS and NBDC. Pconvpv is NBDC output power. Pconvev is 72V battery output power (NBDC input power). Ppcsin is PCS input power. Ppcsout is PCS output power (for Load power). Where, in Fig. 8, Iconvpv is NBDC output current, Iconvev is 72V battery output current (NBDC input current), Vconvpv is NBDC output voltage, and Vconvev is 72V battery output voltage (NBDC input voltage). Fig. 8 shows the experiment result of power factor 100% for loads. Loads are 80, 170, 260, and 320W respectively. In Fig. 9, it shows the isolated power supply charging experiment results of PV-NBDC with 72V battery. In fact, Fig. 9 demonstrates the experiment structure of the 72V battery charging operation with used PCS and NBDC. Pconvpv, Pconvev, Iconvpv, Iconvev, Vconvpv, Vconvev are the same as Fig. 8. In Fig. 9 shows the result of battery charging (Buck operation On/Off) experiment, where solar array open voltage is 236V and its maximum power voltage is approximately 188V and its maximum power current is approximately 15A. If PV generates maximum power, PV output voltage 188V is maintaining when battery changing current is less than maximum power current 15A. Therefore, it can be seen from Fig. 9 that the charging power to Battery is approximately 1000 W. Solar Array Isolated operation mode MPPT boost converter PCS DC-AC Inverter L O A D 80W Load 170W Load I convpv V convpv Non-isolated Bidirectional DC-DC Converter I convev V convev Battery Fig. 8. Isolated power supply discharging experiment of PCS-NBDC with 72V battery: experiment structure, power results. 260W Load 320W Load Solar Array Isolated operation mode PCS MPPT boost DC-AC converter Inverter L O A D I convpv V convpv Non-isolated Bidirectional DC-DC Converter I convev V convev Battery Fig. 9. Isolated power supply charging experiment of PV-NBDC with 72V battery: experiment structure, power results.