INSTRUCTION MANUAL H WELDER INTERLOCK

Similar documents
ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

SOFT TOUCH FOR WELDERS

Application Engineering

OnCommand Troubleshooting Guide Hayward Industries

Contents. Section 3A: Consolidated Electronics... 3A-3. General Information... 3A-3

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

CBC-802 Plug-In Clutch/Brake Control with Solid State Switching

Flight Systems. Replacement for KASSEC DESCRIPTION

Application Engineering

ILISC515-A Shift Interlock (Manual Lift Door) Ford Transit

PowerMaster MODEL MBG. Installation Manual U L R UL 325 AND UL 991 LISTED MEDIUM DUTY BARRIER GATE OPERATOR TABLE OF CONTENTS

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

SOFT TOUCH FOR PNEUMATIC RIVETERS

CBC-802 Plug-In Clutch/Brake Control with Solid State Switching

On-Premise Pro Instruction Manual

Horizontal Circuit Switchers

SIDE ROLL SENSOR TROUBLESHOOTING GUIDE

Horizontal Circuit Switchers

Powercut Spare parts list. Edition Valid for serial no. 001-xxx-xxxx, 034-xxx-xxxx

Senior Swing Control Box. Table of Contents

CHIP. Reverse Osmosis System Controller Documentation

RENEWAL PARTS Supersedes: RP4 (1012) Form RP4 (813)

PD404-AN V analog control 4 Channel x 500 W Dimmer & Switch Packs ANALOG 0-10 V. Serial Number

Installation and Maintenancee Manual

INSTALLATION & OWNER'S MANUAL

Induction Power Supplies

ARC 1850 LIST OF FIGURES

PCS GEAR SELECT MODULE USER GUIDE v4.0

SOFT TOUCH for NON-UNITROL CONTROLS

PCNC 1100 Series 3 (32085) Column and Head Assembly

Setup and Configuration Guide Universal Switch Interface

Automatic concealed bollards 275 H600 and 275 H800 Control station

SOFT TOUCH for PNEUMATIC RIVETERS

Electronic Ballast EVG 2000-T

CV - 6SL INSTRUCTION MANUAL 6000W POWER SUPPLY

AeroVironment Universal Solar Pump Controllers

SE2000BX Static Exciter

Generator Start Control Module

INSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R

Installation and Operation Guide for PD5100 Automatic Transfer Switch

OPERATION/ MAINTENANCE MANUAL

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

DKG-509 AUTOMATIC MAINS FAILURE UNIT

19mm Thickness. Phone: Fax: Web:

HYPPOETL HYPPO DUALETL 12 VOLT DC Swing Gate Operator

AUTO-BLiP. User Manual Lotus INTELLIGENT DOWNSHIFTS. Version 1.0

SmartPak Welding Controller WK-MPS-16 Constant Current

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

AUTO-BLiP. User Manual Ford Mustang INTELLIGENT DOWNSHIFTS. Version 1.2

CDBR-B. Dynamic Braking Unit Instruction Manual. April 2009 Part Number: R1 Copyright 2009 Electromotive Systems

OPERATIONAL MANUAL EMBC-8025 INTELLIGENT BATTERY CHARGER. Version 1.5

Te 803 Electronic Controller. Service, Operation & Technical Information Manual

PowerOhm Installation Manual for BM R Series Braking Modules

Installation Instructions & Users Manual

ELECTRIC FENCE ENERGIZER SERVICE MANUAL MODEL 950 SERVICE MANUAL FOR OLLI 950 FENCE ENERGIZERS

LNII Series Motor and Drives

Documentation. RM-BV4 Micro DP. Filter control

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

12V DC MOTORISED OPENER FOR SWING GATES Section Table of Contents Page

ECONOMISER SERIES E2T USER MANUAL

J1 Plug Pin Identification

J1 Plug Pin Identification

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

Tekleen GB6 & GB7 USERS AUTOMATIC FILTERS, INC. MANUAL

ELECTRIC SCHEMATICS LS1 LS2. "1532ES / 1932ES" Service & Parts Manual - ANSI Specifications March 2008 Page 5-9 ART_2236 ART_2243

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

PEC 5068 BDFB 1-10 Loads, 500A Max/Load -48V, 2000A Max Load/Bay

Generator Start Control Module

Linear Actuator Swing Gate Operator Installation Manual Model # LA405-24

PowerOhm Installation Manual for BM R Series Braking Modules

Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2

PEC 827E. 120 VAC AC Distribution Shelf. Critical Power Product Manual

OpenEVSE. Testing Basic and Advanced

Noran Tel. Fuse Panel Technical Practice N NCY 4/4TPA & 6/6 GMT NEBS Level 3 Certified

Wiring Installation Instructions for : Pressure. Wiring Installation Instructions for : Temperature. 2 1/16 Spek Pro Professional Racing Gauge

POWERLINE 2000 Energy Management System TM

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

ELECTRO-MECH SCOREBOARD CO.

Hitachi America, Ltd.

Heated Bakery Merchandiser Series. Series: WBC Operation Manual

INSTRUCTION MANUAL TURNTABLE MODEL EM-4709

Series 905-IV16(E) CAN/CANopen Input Modules Installation and Operating Manual

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

OPERATING INSTRUCTIONS

AUTO-BLiP. User Manual Chevrolet Corvette. Version 1.2

Generator Start Control Module

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

Yaskawa Electric America Unit Troubleshooting Manual Section One: Introduction & Checks Without Power GPD 506/P5 and GPD 515/G5 (0.

FLOAT BATTERY CHARGER

Product Guide: Series III Pump Control Board Set (RoHS)

1.0 Features and Description

GLM SERIES CONTROL Users Manual Rev:

Electronically Commutated Motors

Manual, HAPS-Hydraulic Auxiliary Power Supply

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

3200NT Timer Service Manual

GSC400 Series. Automatic Gen-Set Controller Manual. Revision 2.5

SINUS K 13. ACCESSORIES Braking resistors APPLICATION TABLES 78/160 INSTALLATION INSTRUCTIONS

PT Series Phase Converters OPERATION & INSTALLATION MANUAL

Transcription:

INSTRUCTION MANUAL 700200H WELDER INTERLOCK MICROPROCESSOR BASED Welder Interlock Control Wiring Diagram 420721 NEMA 1 Cabinet ENTRON Controls, LLC. 1402 S. Batesville Road Greer, South Carolina 29650 (864) 416-0190 FAX: (864) 416-0195 www.entroncontrols.com ENTRON Controls, LLC. 700200H Page 1

THIS PAGE IS INTENTIONALLY BLANK Page 2 700200H ENTRON Controls, LLC.

ENTRON Controls, LLC. MICROPROCESSOR BASED WELDER INTERLOCK CONTROL INSTALLATION AND OPERATION MANUAL FOR: WELDER INTERLOCK CAUTION READ THIS MANUAL COMPLETELY BEFORE ATTEMPTING TO INSTALL OR OPERATE THIS CONTROL ENTRON Controls, LLC., reserves the right to alter the contents of this manual without previous notice. ENTRON Controls, LLC. Greer, South Carolina 29650 ENTRON Controls, LLC. 700200H Page 3

TABLE OF CONTENTS 1.0 GENERAL DESCRIPTION... 5 2.0 INSTALLATION... 7 2.1 INSTALLATION DIAGRAMS... 7 2.2 WIRING AND CABINET DIAGRAMS... 8 2.3 WELDER INTERLOCK INTERCONNECTION (CASCADING)... 9 2.4 USING WELDER INTERLOCKS IN 3-PHASE SYSTEMS... 10 3.0 GENERAL OPERATING REQUIREMENTS... 11 3.1 OPERATING VOLTAGE... 11 3.2 FUSING AND SAFE OPERATION... 12 4.0 I/O RELAYS SPECIFICATIONS... 13 5.0 OPERATION... 14 6.0 PRIORITY... 15 7.0 APPLICATIONS AND PROGRAMMING EXAMPLES... 16 7.1 WELDER INTERLOCK USED WITH EN1701 CONTROLS... 16 7.2 WELDER INTERLOCK USED WITH EN1721 CONTROLS... 18 8.0 WARRANTY AND SERVICE... 20 FIGURES FIGURE 1-1. 2-4 WELDER INTERLOCK... 5 FIGURE 1-2. 2-8 WELDER INTERLOCK... 5 FIGURE 1-3. 2-8 CONTROL BOARD... 6 FIGURE 1-4. RELAY RACK BOARD PB8 FOR PCB2 410254... 6 FIGURE 1-5. RELAY RACK BOARD PB16 FOR PCB2 410255... 6 FIGURE 2-1. CONNECTION OF WELDER INTERLOCK BOARD TO RELAY RACK BOARD... 7 FIGURE 2-2. DETAILED BOARD AND HARNESS LAYOUT... 7 FIGURE 2-3. WELDER INTERLOCK WIRING DIAGRAM... 8 FIGURE 2-4. WELDER INTERLOCK CABINET DIMENSIONS... 9 FIGURE 2-5. INTERCONNECTION OF MULTIPLE WELDER INTERLOCKS... 9 FIGURE 2-6. INTERCONNECTION OF WELDER INTERLOCKS IN A 3-PHASE SYSTEM... 10 FIGURE 3-1. TS1 CONNECTIONS AND VOLTAGE SELECTION JUMPERS SETTINGS... 11 FIGURE 3-2. DANGER, WARNING AND NOTICE LABELS... 12 FIGURE 6-1. PRIORITY SWITCH SW2... 15 FIGURE 7-1. EN1701 AND WELDER INTERLOCK CONNECTIONS... 16 FIGURE 7-2. EN1721 AND WELDER INTERLOCK CONNECTIONS... 18 TABLES TABLE 3-1. VOLTAGE SELECTION JUMPERS SETTINGS... 11 TABLE 4-1. I/O RELAYS OPTIONS WITH FACTORY P/Ns... 13 TABLE 4-2. I/O RELAYS... 13 Page 4 700200H ENTRON Controls, LLC.

1.0 GENERAL DESCRIPTION The Welder Interlock is designed for applications with more than one NEMA S2H welding control (with valve output and interlocking pressure switch) connected on the same power line. The main purpose is to allow only one welder to weld at a time, when more than one welder is initiated on the same power bus that cannot support the demands of more than one control. As of June 2007, EN1000 and EN1001 Controls with PROM firmware version 619016-002BB and higher have a special P.O..O. 20 added for use with welder interlock. P.O..O. 20 removes delays associated with SQUEEZE and HOLD times (see Instruction Manual 700120, Section 5.4.7). Use of this PROCESS OUTPUT significantly decreases wait times for interlocked welders. As of August 2003, priority operation has been revised. A new microprocessor based Control Board A/N 410358 has been designed to replace the previous TTL board A/N 410256. Besides the base version of the A/N 410358 board, which is made for 2 to 8 welders, other variations are possible for controlling up to a total of 24 welders, using only one Welder Interlock Control Board in one cabinet. Two or more Welder Interlock Controls can be interconnected or cascaded, as described in Section 2.3. The Welder Interlock consists of a Control Board, a Relay Rack Board, a Control Transformer and harnesses. Figure 1-1 is the 2-4 Welder Interlock and Figure 1-2 is the 2-8 Welder Interlock. Figure 1-1. 2-4 Welder Interlock Figure 1-2. 2-8 Welder Interlock ENTRON Controls, LLC. 700200H Page 5

1.0 GENERAL DESCRIPTION (cont.) The Welder Interlock 2-8 Control Board (A/N 410358) is shown in Figure 1-3. In addition to other components on the board, there are two relays which are used for welder interlock cascading: DC Input relay (white), and DC Output relay (red). Connector J1 is used to connect the Control Board to the Relay Rack Board. Connector J3 (P3) or J3A is used to connect the Control Board to the power supply (Control Trans-former) and to provide access to three terminals on TS1. With PROM firmware version 619041-001 ORIG, rotary switch SW2 is used to enable and select priority. In addition, as of October 2013, with PROM firmware version 619041-001A and higher, rotary switch is also used to set the Welder Interlock Board to Master Board working mode or Slave Board working mode (see Section 5.0 and Section 6.0). Figure 1-3. Welder Interlock 2-8 Control Board Board PCB2 A/N 410254 2-4 Welder Interlock, with I/O relays is shown in Figure 1-4. Figure 1-4. Relay Rack Board PB8 for PCB2 410254 Board PCB2 A/N 410255 2-8 (or 5-8) Welder Interlock, with I/O relays is shown in Figure 1-5. Figure 1-5. Relay Rack Board PB16 for PCB2 410255 Page 6 700200H ENTRON Controls, LLC.

2.0 INSTALLATION 2.1 INSTALLATION DIAGRAMS The block diagram for the Control Board connection to the Relay Rack Boards (2-4 or 2-8 Welder Interlock) is shown in Figure 2-1. For detailed information about wiring, refer to Wiring Diagram 420721 (Figure 2-3) for 2-8 Welder Interlock. Figure 2-1. Connection of Welder Interlock Board to Relay Rack Board Input relays: Terminals on PCB2-TS2 marked SV1-x and SV2-x denote connections to solenoid valve output terminals located in the welding controls being interlocked. Output relays: Terminals on PCB2-TS2 marked PS1-x and PS2-x denote connections to pressure switch terminals located in the welding controls being interlocked. The PS2 connections are normally connected to TS1-GND. Figure 2-2 shows the detailed board and harness layout inside the cabinet of a 2-4 Welder Interlock. Figure 2-2. Detailed board and harness layout ENTRON Controls, LLC. 700200H Page 7

2.2 WIRING & CABINET DIAGRAMS Figure 2-3. Welder Interlock Wiring Diagram Page 8 700200H ENTRON Controls, LLC.

2.2 WIRING & CABINET DIAGRAMS (cont.) Figure 2-4. Welder Interlock Cabinet dimensions 2.3 WELDER INTERLOCK INTERCONNECTION (CASCADING) When more than 8 (or more than 24) controls are to be interlocked, additional Welder Interlocks can be interconnected as shown in Figure 2-5. Connect TS1-OUT of the first Welder Interlock to TS1-IN on the second. Connect TS1-OUT on the second unit to TS1-IN of the next unit, etc. Connect TS1- OUT of the last unit to TS1-IN of the first one. Connect TS1-COM of all controls in parallel. Detailed Welder Interlock operation is described in Section 5.0. Figure 2-5. Interconnection of multiple Welder Interlocks ENTRON Controls, LLC. 700200H Page 9

2.4 USING WELDER INTERLOCKS IN 3-PHASE SYSTEMS When more controls are to be interlocked in 3-phase systems, the configuration can be used as shown in Figure 2-6. Three groups of the welding controls are connected to L1-L2, L2-L3, and L3-L1, respectively. It is not necessary for three Welder Interlocks to be interconnected, as described in previous section, although it is possible (contact factory for details). L1-L2 L2-L3 L3-L1 Figure 2-6. Interconnection of Welder Interlocks in a 3-phase system 3.0 GENERAL OPERATING REQUIREMENTS 3.1 OPERATING VOLTAGE The Welder Interlock can operate at 120, 240, 380, 480, and 575 VAC. When a 380 or 575 VAC main is desired, please consult the factory. When control is converted from one line voltage to another, only rearranging jumpers on TS1 is required, shown in Figure 3-1 and Table 3-1. WARNING THIS CONTROL IS A MULTI-VOLTAGE UNIT WHICH CAN BE CHANGED FROM ONE VOLTAGE TO ANOTHER BY RE-ARRANGING JUMPERS ON TERMINAL STRIP TS1 INSIDE THE UNIT. IF CONTROL IS USED WITH A VOLTAGE OTHER THAN THE ONE FOR WHICH IT IS WIRED, SERIOUS DAMAGE CAN RESULT. Incoming line voltages on L1-L2 are independent of voltages existing at PCB2-TS2. Page 10 700200H ENTRON Controls, LLC.

3.1 OPERATING VOLTAGE (cont.) Figure 3-1. TS1 Connections and Voltage Selection Jumpers settings Table 3-1. Voltage Selection Jumpers settings Voltage [VAC] 120 240 380 480 575 Jumper #3 Jumper #3 Jumper #3 Jumper #3 Jumper #3 TS1-L2 to TS1-L2 to TS1-L2 to TS1-L2 to TS1-L2 to TS1-CTH3 TS1-CTH3 TS1-CTH1 TS1-CTH1 TS1-CTH1 Jumper #4 Jumper #4 Jumper #4 Jumper #4 Jumper #4 Jumpers TS1-14 to TS1-14 to TS1-14 to TS1-14 to TS1-14 to TS1-CTHA TS1-CTH4 TS1-CTHA TS1-CTH4 TS1-CTH4 Add Jumper #2 Add Jumper #1 Add Jumper #1 Add 2KS, 10W instead of Jumper #1 NOTICE For 575 VAC voltage operation, add 2k Ohm, 10W resistor (A/N 600048) between TS1-CTH3 and TS1-CTH2, instead of Jumper #1. NOTICE Unless specified at the time of order, control is shipped with 120 VAC jumper settings. 3.2 FUSING AND SAFE OPERATION CONTROL FUSE This fuse, a 1/4 A, is used to protect the control circuits. The fuse holder is located within the cabinet, upper left section. CAUTION INSTALL PROPERLY SIZED FUSES IN SERVICE DISCONNECT SWITCH. CHECK WELDING MACHINE MANUFACTURER S RECOMMENDATIONS. DANGER VOLTAGES PRESENT IN THIS CONTROL CAN CAUSE SEVERE OR FATAL INJURY. DO NOT SERVICE ANY COMPONENT WITH POWER ON. USE ONLY THE FUSE TYPE SPECIFIED TO MAINTAIN SAFE OPERATION. ENTRON Controls, LLC. 700200H Page 11

3.2 FUSING AND SAFE OPERATION (cont.) Observe the hazard labels affixed to the control to maintain safe operation. Some of them are shown in Figure 3-2. Figure 3-2. Danger, Warning and Notice labels Page 12 700200H ENTRON Controls, LLC.

4.0 I/O RELAYS SPECIFICATIONS The Welder Interlock Control is shipped with Option K relays installed, unless otherwise specified. See Table 4-1 and Table 4-2 for ENTRON Part Numbers and more information about available relays. Table 4-1. I/O Relays Options with factory P/Ns CRI CRO OPTION VALVE INPUT VOLTAGE P/N COLOR PS OUTPUT VOLTAGE P/N COLOR A 90-140 VAC 314028 Yellow 3-60 VDC 314025 Red B 90-140 VAC 314028 Yellow 24-280 VAC 314024 Black C 180-280 VAC 314027 Yellow 3-60 VDC 314025 Red D 180-280 VAC 314027 Yellow 24-280 VAC 314024 Black E 12-32 VAC / 4-32 VDC 314026 White 3-60 VDC 314025 Red F 12-32 VAC / 4-32 VDC 314026 White 24-280 VAC 314024 Black G 12-32 VAC / 4-32 VDC 314026 White 3-200 VDC 314032 Red H 90-140 VAC 314028 Yellow 3-200 VDC 314032 Red J 180-280 VAC 314027 Yellow 3-200 VDC 314032 Red K 90-140 VAC 314028 Yellow 0-120 VDC, 0.5A 314052 Red L 180-280 VAC 314027 Yellow 0-120 VDC, 0.5A 314052 Red M 12-32 VAC / 4-32 VDC 314026 White 0-120 VDC, 0.5A 314052 Red Table 4-2. I/O Relays INPUT - DC / AC INPUT - AC OUTPUT - DC OUTPUT - AC 314026 314027/314028 314025/314032/314052 314024 WHITE YELLOW RED BLACK Contact factory for other available options and versions of Welder Interlock Control Board A/N 410358 and Relay Rack Boards for up to 24 welders per single Interlock Board in one cabinet without cascading. See Section 2.3 for more information about cascading Interlocks. ENTRON Controls, LLC. 700200H Page 13

5.0 OPERATION Full operation of the Welder Interlock Control Board may be summarized as follows: 1. The Welder Interlock will cyclically scan all relay inputs until an input relay (on PCB2 Board, terminals SV1-SV2) is found energized. The Welder Interlock will activate the associated output relay (on PCB2 Board, terminals PS1-GND) and it will stop cyclic scanning. 2. After that relay input is de-energized, the Welder Interlock will deactivate the output relay and continue to cyclically scan the next inputs until another input activation is detected. 3. At the end of each scan loop (24 steps), the Welder Interlock sends an output pulse (18 VDC) from CRO on the Control Board to TS1-OUT. The Welder Interlock pauses and waits until a pulse (18 VDC) is received at relay CRI on the Control Board, via TS1-IN. The scan of all relay inputs (maximum 24 per Welder Interlock) will then resume. See Section 6.0 for more information about priority. For PROM firmware version 619041-001A and higher: As of October 2013, in order for cascading interlock to work more reliably, Master Board working mode and Slave Board working mode have been introduced with PROM firmware version 619041-001A and higher. If multiple Interlock Boards are cascading connected together as a loop system, one Interlock Board must be set to Master Board working mode and other Interlock Boards must be set to Slave Board working mode. When Interlock Board is set to Master Board working mode, for every processing cycle, board will scan its input ports, process all the welding request(s) and pass the priority signal out to the Slave Interlock Board(s). Once the Master Interlock Board receives a return priority signal back from Slave Interlock Board(s), a new processing cycle will start. When Interlock Board is set to Slave Board working mode, for every processing cycle, board will wait for the priority signal from its Master Interlock Board. Once priority signal is received, the Slave Interlock Board will scan its input ports, process all the welding request(s) and pass the priority signal out to next Slave Interlock Board or Master Interlock Board. Once the priority signal has been passed out, the Slave Interlock Board will wait for a new priority input signal to start a new processing cycle. The Master/Slave Board working modes are set through rotary switch SW2 (see Section 6.0). NOTICE 1. If only one Interlock Board is used in entire Interlock system, that board must be set to Master Board working mode. 2. If multiple Interlock Boards are used and cascading connected in entire Interlock system, one of the boards must be set to Master Board working mode and the other Interlock Board(s) must be set to Slave Board working mode. 3. If multiple Interlock Boards are used and cascading connected in entire Interlock system, all the boards should use the same PROM firmware version. Page 14 700200H ENTRON Controls, LLC.

6.0 PRIORITY As of August 2003, priority operation has been revised. With PROM firmware version 619041-001 ORIG, using rotary switch SW2 (see Figure 6-1), priority may be enabled and selected: set SW2 to 0 to disable priority if priority is not required; set SW2 to any number from 1 to 8 to enable priority and select corresponding welder #1 to #8, respectively, as the welder with highest priority. Figure 6-1. Priority switch SW2 set SW2 to 9 to enable priority on welder #9 only on Welder Interlock Control Boards for more than 8 welders. As of October 2013, with PROM firmware version 619041-001A and higher, using rotary switch SW2, the Master/Slave Board working mode and priority may be enabled and selected: set SW2 to 0 to set Interlock Board to Master Board working mode and disable priority. set SW2 to any number from 1 to 4 to set Interlock Board to Master Board working mode, enable priority and select corresponding welder #1 to #4, respectively, as the welder with highest priority. set SW2 to any number from 5 to 8 to set Interlock Board to Slave Board working mode, enable priority and select corresponding welder #5 to #8, respectively, as the welder with highest priority. set SW2 to 9 to set Interlock Board to Slave Board working mode and disable priority. If priority is enabled, the control always checks the corresponding welder input and it will activate its output each time after any other welder is done with its welding sequence. In the case where multiple and/or all welder inputs are presented at the same time, the priority control will be first and then other initiated controls will be allowed to weld, beginning with the lowest order welder. NOTICE Priority switch is set to 0 (factory default setting) when Welder Interlock is shipped. Following is an example of how priority operation works with eight welders: Priority switch SW2 is set to 5 to enable and set priority for welder #5 over any other welder initiated. All other welder relay inputs are active. After power-up, the control will activate relay output for welder #5, since priority for that welder is set. After welder #5 is done, the control will activate the output of welder #1, and when this one is done, it will activate welder #5 again (only if its input is active again). After #5 is done, the control will activate welder #2 and again after this one is done, it will go back to #5, and sequence will continue in this order: 5-1 5-2 5-3 5-4 5-6 5-7 5-8. ENTRON Controls, LLC. 700200H Page 15

7.0 APPLICATIONS AND PROGRAMMING EXAMPLES 7.1 WELDER INTERLOCK USED WITH EN1701 CONTROLS The following application shows how to use the Welder Interlock with multiple EN1701 Controls (see Instruction Manual 700203 for control details). The Relay Rack should use Option E shown on Wiring Diagram 420721 or Section 4.0. The input relays should be white IDC5 relays (P/N 314026). The output relays should be red ODC5 relays (P/N 314025). Refer to Wiring Diagram 420721 for Welder Interlock connection and operation details. For this example, connections should be made as shown in Figure 7-1. Subsequent controls should be connected as Control 1, but on next available pair of relays. { {{ To Control 4 To Control 3 To Control 2 P3 OUTPUTS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 WAV / Q01 Q02 WAV2 HAV / Q03 Q04 COUNTER / Q05 STEPPER / Q06 PRE-WARN / Q07 Q08 Q09 Q10 Q11 Q12 EOS / Q13 FAULT / Q14 NOT READY / Q15 CONTACTOR / Q16 0V (to P1 pin 6) P2 INPUTS 1 2 START1 / I01 3 START2 / I02 4 START3 / I03 5 START4 / I04 6 P1 / I05 7 P2 / I06 8 P4 / I07 9 P8 / I08 10 P16 / I09 11 P32 / I10 12 13 14 15 16 17 24V (to P1 pin 2) RESET STEPPER / I11 RESET COUNTER / I12 RETRACT1 / I13 RESET FAULT / I14 2nd STAGE / I15 PROGRAM LOCKOUT / I16 CONTROL 1 Figure 7-1. EN1701 and Welder Interlock connections Page 16 700200H ENTRON Controls, LLC.

7.1 WELDER INTERLOCK USED WITH EN1701 CONTROLS (cont.) Programming can be done using either RPP1 or ENLINK. Program weld parameters as desired on all welders. In Output Map, map Output Q12 to EVENT. <<< OUTPUT MAP >>> Q01: WAV1 Q02: MOTOR Q03: HAV1 Q04: Reserved Q05: COUNTER1 Q06: STEPPER1 Q07: PRE-WARN1 Q08: Reserved Q09: Reserved Q10: Reserved Q11: Reserved Q12: EVENT! Visible window In Events menu, program an EVENT as follows: <<< EVENTS PROG 0 >>> Ev1: 12=On @SQZ+N Ev2: 12=Off @HLD+0 Ev3:?=Off @PSQ+0 Ev4:?=Off @PSQ+0! Visible window Value of N is the programmed SQUEEZE time minus one. ENTRON Controls, LLC. 700200H Page 17

7.2 WELDER INTERLOCK USED WITH EN1721 CONTROLS The following application shows how to use the Welder Interlock with multiple EN1721 Controls (see Instruction Manual 700211 for control details). The Relay Rack should use Option E shown on Wiring Diagram 420721 or Section 4.0. The input relays should be white IDC5 relays (P/N 314026). The output relays should be red ODC5 relays (P/N 314025). Refer to Wiring Diagram 420721 for Welder Interlock connection and operation details. For this example, connections should be made as shown in Figure 7-2. Subsequent controls should be connected as Control 1, but on next available pair of relays. { {{ To Control 4 To Control 3 To Control 2 P4 INPUTS 10 9 8 7 6 5 4 3 2 1 0V EXT INPUT 08 INPUT 07 INPUT 06 INPUT 05 INPUT 04 INPUT 03 INPUT 02 INPUT 01 +24V P2 OUTPUTS 4 7 5 + OUTPUT 09 6 8 + OUTPUT 10 9 10 + OUTPUT 11 11 12 + OUTPUT 12 13 (VOUT ) 14 VOUT + LINK WAV CONTROL 1 Figure 7-2. EN1721 and Welder Interlock connections Page 18 700200H ENTRON Controls, LLC.

7.2 WELDER INTERLOCK USED WITH EN1721 CONTROLS (cont.) Programming can be done using either RPP1 or ENLINK. Program weld parameters as desired on all welders. In Output Map, map Output Q12 to EVENT. <<< OUTPUT MAP >>> Q01: PRE-WARN Q02: STEPPER1 Q03: Reserved Q04: COUNTER1 Q05: CONTACTOR Q06: NOT READY Q07: FAULT Q08: EOS Q09: WAV1 Q10: MOTOR Q11: HAV1 Q12: EVENT! Visible window In Events menu, program an EVENT as follows: <<< EVENTS PROG 0 >>> Ev1: 12=On @SQZ+N Ev2: 12=Off @HLD+0 Ev3:?=Off @PSQ+0 Ev4:?=Off @PSQ+0! Visible window Value of N is the programmed SQUEEZE time minus one. ENTRON Controls, LLC. 700200H Page 19

8.0 ENTRON LIMITED WARRANTY AND FACTORY SERVICE ENTRON Controls, LLC., warrants that all ENTRON control panels, EXCEPT Mid-frequency Inverter controls, silicon controlled rectifiers (SCRs), insulated gate bipolar transistors (IGBTs), SCR and IGBT assemblies, circuit breakers, and electro-mechanical contactors, are free of manufacturing defects for a period of TWO YEARS from the date of original purchase and, in the event of a manufacturing defect, ENTRON will repair or replace, at its discretion, the defective part without any cost for parts or labor. All silicon controlled rectifiers, SCR and IGBT assemblies, circuit breakers and electro-mechanical contactors in ENTRON control panels are covered by a limited warranty from the original manufacturer. If these parts fail because of a manufacturing defect, they will not be repaired or replaced by ENTRON, but will be returned by ENTRON to the original manufacturer in accordance with said manufacturer s warranty. ENTRON Controls, LLC., warrants that all Mid-frequency Inverter controls are free of manufacturing defects for a period of ONE YEAR from the date of original purchase and, in the event of a manufacturing defect, ENTRON will repair or replace, at its discretion, the defective part without any cost for parts or labor. To obtain repairs or replacement parts under this warranty, the defective part must be returned, prepaid, to ENTRON Controls, LLC., 1402 S. Batesville Road, Greer, SC 29650. Please send your repair to the attention of Service with a description of the problem you are experiencing, contact person and phone number. EXCLUSIONS: This warranty does not cover damage by accident or misuse, unauthorized repair or modification to any control assembly by the customer. IMPORTANT NOTE: The warranty period is considered from the date of shipment and is tracked by a serial number code. USE OF OUT OF WARRANTY REPAIR SERVICE: To obtain service for any printed circuit board assembly or welding control after the warranty period, send the assembly or control, prepaid, to ENTRON Controls, LLC., and ENTRON will repair the printed circuit board assembly or control and return it to you without further warranty. Additional service charges will be invoiced at time of shipment. Your ENTRON Controls, LLC., Original Equipment Manufacturers (OEMs), Dealers and Distributors are your first response contact to secure technical assistance on control or welding problems. Should they be unable to assist you, please contact your ENTRON sales representative or the factory directly. Contact the factory at 864-416-0190. Page 20 700200H ENTRON Controls, LLC.