ACTIVAL Electro-Mechanical Actuator for Control Ball Valve

Similar documents
ACTIVAL Electro-Mechanical Actuator for Control Ball Valve Model MY53X0AX000

ACTIVAL Electro-Mechanical Actuator for Control Ball Valve

Motorized Two-Way Ball Valve with Screwed-End Connection

ACTIVAL Two-way Ball Valve with Threaded-end Connection

ACTIVAL Motorized Three-Way Valve with Flanged-End Connection (JIS 10K / FC200)

ACTIVAL Motorized Two-Way Valve with Flanged-End Connection (Spring Return Type Actuator) (JIS 10K-FC200, -SCS13A)

ACTIVAL Motorized Two-way Valve with Flanged-end Connection (JIS 10K / FC200, SCS13A)

ACTIVAL Motorized Two-Way Valve with Flanged-End Connection <4-20 ma DC Input with 4-20 ma DC Feedback Output> (JIS 10K-FC200, -SCS13A)

Intelligent Component Series ACTIVAL Electro-Mechanical Actuator for Model VY530X Control Ball Valve Model MY5390A

Control Motor. Specifications/Instructions. Overview. Features IMPORTANT AB-6387

ACTIVAL Three-Way Ball Valve with Threaded-End Connection

ACTIVAL Motorized Two-Way Valve with Flanged-End Connection for High Differential Pressure Application (JIS 10K-FC200, -SCS13A)

ACTIVAL Motorized Three-Way Valve with Flanged-End Connection (JIS 10K / FC200)

Direct Coupled Damper Actuator Model MY6050A1001

Differential Pressure Transmitter

Direct Coupled Damper Actuator Model MY9050A1001

WARNING WARNING. ECM3000 Control Motor User's Manual CAUTION NOTICE SAFETY PRECAUTIONS

Pressure Transmitter

Intelligent Component Series ACTIVAL Motorized Two-Way Valve with Flanged-End Connection (PN16 / GG-20) (Spring Return Type Actuator)

Intelligent Component Series ACTIVAL Motorized Three-Way Valve with Flanged-End Connection (JIS 10K / FC200)

Intelligent Component Series ACTIVAL Motorized Two-Way Valve with Flanged-End Connection (JIS 10K / FC200, SCS13A)

Intelligent Component Series ACTIVAL Flow Measurement and Control Valve (JIS 10K / FC200)

Intelligent Component Series ACTIVAL Motorized Two-Way Valve with Flanged-End Connection (JIS 10K / FC200, SCS13A) (Spring Return Type Actuator)

Insertion Thermostat

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

ACTIVAL Flow Measurement and Control Valve Standalone Model (PN10 / GG-20)

Minimum 18 in-lb Torque

Power consumption In operation At rest For wire sizing. Functional data Torque Motor Spring return. Rated impulse voltage Control pollution degree 3

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

Versatile and Powerful

Minimum 27 in-lb Torque

MS Application. Features. Proportional Valve Actuator General Instructions

SAV Electronic Valve Actuator

SAX Electronic Valve Actuator

Flowrite 599 Series SAX Electronic Valve Actuator Non-spring Return, 24 Vac, 3-Position Control

Electromotoric Actuators

EX Series. Electric Actuators for Ball and Butterfly Valves

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz

Minimum 27 in-lb torque

P2050S-030, 1/2, Electronic Pressure Independent Valve Stainless Steel Ball and Stem, Female NPT Ends

Insertion Temperature/Humidity/ Dewpoint temperature Sensor HTY78X3/HY78X3/HTY78X6/HY78X6/HY79X3

Versatile and Powerful

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator

NV Direct Coupled Globe Valve Actuator

ZG-JSL, ZG-JSLA Jackshaft Retrofit Linkage For AF, NF, LF, NMX and AMX Series Actuators

Minimum 18 in-lb Torque. Applications. TF Series At A Glance. TF Series Spring Return Direct Coupled Actuator. For damper areas up to 4.

Power consumption Wire/transformer sizing. Motor. Spring return. Motor. Spring return. EMC Low voltage directive

FSAF24(-S) US, FSAF120(-S) US

ELECTRIC ACTUATOR. Unic Series ROTARY TYPE Unic Z, 05 Unic 10 Unic 20, 40 Unic 60, 100, 150, 200 OPERATION MANUAL. Koei Industry Co., Ltd.

Electromotoric actuators

Operation Manual. Document No.: KE KITZ EKSR Series Spring Return Type Electric Actuators. For KITZ Ball Valves

Hinged Safety Door Switch

LF Series At A Glance

Electrical data Nominal voltage AC V / DC V Nominal voltage frequency

Electric Top-Guided Single-Seated Control Valves

G6K. Surface Mounting Relay with the World s Smallest Mounting Area. Application Examples. Model Number Legend. Ordering Information

Electromotoric Actuators

D4DL. Guard Lock Safety-door Switch. Model Number Structure

GV-A Manufactured by Germany s Elster GmbH High-Performance Gas Solenoid Valve for Industrial Applications

Combi valves PN 16 with flanged connections

WARNING Warnings are indicated when mishandling this product might result in death or serious injury to the user.

OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

SERVO-TOP II ELECTRONIC ACTUATOR

LJASeries. Limit Switches with Positive Opening Mechanism

Infilex ZM Zone Manager Model WY5122

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Installation, Operation and Maintenance Manual

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

Actuators for air dampers and control valves of oil burners

EVS RP6020. Instruction Manual

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

RP Instruction Manual

Limit Switches with Positive Opening Mechanism

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

MIZCON Plus Cooling Tower Controller Model R7010W

Linear Valve Electric Actuator

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18)

INSTALLATION AND OPERATING INSTRUCTIONS OF THE INTERNATIONAL ISOBOX SERIES ISOLATION TRANSFORMERS.

ELECTRONIC CONTROL ACTUATOR

WaterMAG. Electromagnetic Flowmeter for Water Applications. Model MCB10A OVERVIEW APPLICATIONS FEATURES. No. SS2-MCB

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

HEAVY DUTY POWER RELAYS FEATURES

ELECTRONIC CONTROL ACTUATOR

Power Controller. (see note 1) 10 sec

MF /MS Series

MF-22xx3. Application. Features. Floating Valve Actuator General Instructions

VERTICAL TYPE LIMIT SWITCHES (INCLUDES LAMP TYPE)

HS6B Series Subminiature Interlock Switch

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

Switching DC Power Supply

MODEL: PSN3. Final Control Elements. STROKE 6: 0 to 60 mm (0 to 2.36 )

ML6420, ML7420 Non-Spring Return Electric Linear Valve Actuators

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

Solid State Relays G3RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. SSR and Socket Combinations

Technical Instructions. SQV Series Electromotive Valve Actuators. Document No

Electromotoric Actuators

Transcription:

ElectroMechanical Actuator for Control Ball Valve AB690 Specifications/Instructions Overview Model MY3_0A actuator is designed specifically for Models VY3_ twoway and VY3_3 threeway proportional control ball valves, which control the chilled/hot water in heating, ventilation and air conditioning (HVAC) applications. Model MY3_0A_000 has a reversible synchronous motor, which operates at a low voltage of V AC. Six kinds of control signals are available to operate the ball valves: Floating (3position) with nominal 3 Ω feedback potentiometer Nominal 3 Ω resistance input 0 ma DC input 0 V DC input 0 0 V DC input Floating (3position) These control signals provide proportional control in combination with an electric/electronic proportional controller or a DDC (direct digital control) controller. * DDC: Direct Digital Control Features Compact and lightweight: The can be installed in a limited space. Easy and simple mounting onto Models VY3_ and VY3_3 valves: The actuator can be mounted without tools, and no adjustment is required (onetouch leverlocking mechanism). IEC IP: Dustproof and splashproof enclosure enables to be installed in an AHU (air handling unit). Easy manual override: The actuator operation can be switched to manual from electric. It besides can be manually operated without tools. Highlyvisible position indicator: Valve position is easily recognized with the indicator/ manual lever. Energysaving: No power is consumed in fully open/closed position of the valve because of the limit switch mechanism. (Only for Model MY30A.) Builtin auxiliary switch (except Model MY370A) : The switch is adjustable between 080% position. 0 V DC output (for position feedback) available with 0 ma DC input type, 0 V DC input type, and 00 V DC input type. 90 stroke in 60 seconds (0 Hz) / 0 seconds (60 Hz) operating time. Model MY3_0A conforms to all the standards related to CE Marking. 0008 Azbil Corporation All Rights Reserved.

AB690 Safety Precautions Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual nearby for quick reference. Restrictions on Use This product was developed, designed, and manufactured for general air conditioning use. Do not use the product in a situation where human life may be at risk or for nuclear applications in radiation controlled areas. If you wish to use the product in a radiation controlled area, please contact Azbil Corporation. Particularly when the product is used in the following applications where safety is required, implementation of failsafe design, redundant design, regular maintenance, etc., should be considered in order to use the product safely and reliably. Safety devices for protecting the human body Start/stop control devices for transportation machines Aeronautical/aerospace machines For system design, application design, instructions for use, or product applications, please contact Azbil Corporation. Azbil Corporation bears no responsibility for any result, or lack of result, deriving from the customer s use of the product. Recommended Design Life It is recommended that this product be used within the recommended design life. The recommended design life is the period during which you can use the product safely and reliably based on the design specifications. If the product is used beyond this period, its failure ratio may increase due to timerelated deterioration of parts, etc. The recommended design life during which the product can operate reliably with the lowest failure ratio and least deterioration over time is estimated scientifically based on acceleration tests, endurance tests, etc., taking into consideration the operating environment, conditions, and frequency of use as basic parameters. The recommended design life of this product is 0 years. The recommended design life assumes that maintenance, such as replacement of the limited life parts, is carried out properly. Refer to the section on maintenance in this manual. Warnings and Cautions WARNING CAUTION Signs Alerts users that improper handling may cause death or serious injury. Alerts users that improper handling may cause minor injury or material loss. Notifies users that specific actions are prohibited to prevent possible danger. The symbol inside graphically indicates the prohibited action. (For example, the sign on the left means that disassembly is prohibited.) Instructs users to carry out a specific obligatory action to prevent possible danger. The symbol inside graphically indicates the actual action to be carried out. (For example, the sign on the left indicates general instructions.) CAUTION Provide a circuit protector (e.g., a fuse or circuit breaker) for the power source. Failure to do so may cause a short circuit leading to fire or device failure. Install, wire, and use this product under the conditions specified by this manual. Failure to do so may cause fire or device failure. Do not put a load or weight on this product. Doing so may damage the product. Installation and wiring of the actuator must be performed by personnel qualified to do instrumentation and electrical work. Mistakes in installation or wiring may cause fire or electric shock. Before wiring, setting, or maintenance, be sure to turn off the power to this product. Failure to do so may result in electric shock or device failure. After the actuator is installed, make sure that the lock lever is closed (locked). If the lever is not locked, the actuator may fall out, resulting in injury. All wiring must comply with applicable codes and ordinances. Otherwise there is a danger of fire.

AB690 CAUTION For wiring, strip the insulation from cables as specified in this manual. If the length of exposed wire is longer than specified, it may cause electric shock or short circuit between adjacent terminals. If it is too short, it may not make proper contact. After wiring, setting, or maintenance, be sure to reattach the cover. Failure to do so may result in electric shock. Do not touch the moving parts of this product. Doing so may cause injury. Model Numbers with Control Signals and Auxiliary Switch / 0 V DC Output (for position feedback) Model number MY30A000 Control signal Floating (3position) with nominal 3 Ω feedback potentiometer Builtin auxiliary switch / 0 V DC output signal One auxiliary switch UL/cUL (Note ) MY30A000 Nominal 3 Ω resistance input One auxiliary switch MY330A000 to 0 ma DC input (Note ) 0 V DC analog output signal MY330A000 to 0 ma DC input One auxiliary switch MY30A000 to 0 V DC input (Note ) 0 V DC analog output signal MY30A000 to 0 V DC input One auxiliary switch MY30A000 0 to 0 V DC input (Note ) 0 V DC analog output signal MY30A000 0 to 0 V DC input One auxiliary switch MY370A0000 Floating (3position) None Notes:. 0 V DC output is available only with 0 ma DC input (Model MY330A000), 0 V DC input (Model MY30A000), and 00 V DC input (Model MY30A000).. Depending on the model number, this product has acquired the following UL/cUL certification. UL60730/, CAN/CSA E60730: / :3 Rated impulse voltage : 330 V (Over Voltage Category I), Control pollution degree:, Type of action: Use the class power supply. Provide a circuit protector (8 A max.) such as a fuse or circuit breaker for the power source. Rain and snow must be avoided. zoptions Item Model number Specification Waterproof connector* 83036 0 Applicable wire Dia. 6 8 mm 03 Dia. 7 9 mm 0 Dia. 9 mm Outdoor cover 83696700 * Required to maintain IP. Note: IEC: International Electrotechnical Commission 3

AB690 Specifications Power supply Applicable valves Item Power consumption Timing Control signals Analog output (only with 0 ma DC, and 0V DC inputs) Specification V AC ± %, 0/60 Hz Twoway control ball valves : Model VY3_A Threeway control ball valves : Model VY3_3A Model MY30A/MY370A : Max. VA Model MY30A/MY330A/MY30A/MY30A : Max. 7 VA 60 ± 6 sec. (0 Hz) / 0 ± 6 sec. (60 Hz) Floating (3position) with nominal 3 Ω feedback potentiometer Feedback potentiometer Total resistance: Nominal 3 Ω Max. applied voltage: V DC Nominal 3 Ω resistance input ma DC to 0 ma DC input (input impedance: 00 Ω) 0 V DC to 0 V DC input (input impedance: 0 kω or higher) V DC to 0 V DC input (input impedance: 0 kω or higher) Floating (3position) Range: V DC (0 %) to 0 V DC (00%) Max. load: 0 kω or higher (Max. ma) Environmental conditions Rated operating conditions Transport storage conditions Ambient temperature * 0 C to 0 C ( to F) 0 C to 70 C (Fluid temperature: 0 C to 00 C (3 to F) ) * Do not allow the fluid to freeze. Ambient humidity % RH to 9 % RH % RH to 9 % RH Vibration m/s 0 m/s Materials Case: Plastic (polycarbonate resin) (Color: Gray) Cover: Plastic (polycarbonate resin) (Color: Gray ) Yoke: Plastic (polyphenylene sulfide resin) (Color: Black) Auxiliary switch (except Model MY370A) Installation locations Installation orientation Valve position indication Manual override Wiring Enclosure rating Insulation Dielectric strength Position for shipment Weight One SPST Maximum applied voltage/current : 30 V AC, 00 ma Actuating position : variable within 0 % to 80 % Setting accuracy : ± 0 % Indoor (salt air, corrosive gas, flammable gas, and organic solvent must be avoided.) Outdoor ( Use the outdoor cover etc. to be ordered separately. Direct sunlight, salt air, corrosive gas, flammable gas, and organic solvent must be avoided.) Installable in any position ranging from upright to sideways. Indicator/manual lever shows the valve position by pointing at the value of the scale on the actuator bilateral sides. 0 (%) : fully closed for Model VY3_ / for Port B (BAB) of Model VY3_ 00 (%) : fully open for Model VY3_3 / for Port A (AAB) of Model VY3_3 Disconnect from the power suppy. Turn the indicator/manual lever while pressing the lever release button. Electrical connection: Quickfit screwless termial Conduit thread: G/ (ISO 7) Equivalent to IEC IP: Dustproof and splashproof Between terminal and case : 0 MΩ or higher at 00 V DC Between terminal and case: 00 V/min with ma or less leakage current 00 % (fully open) Auxiliary switch: 0 % 0. kg

AB690 Dimensions and Parts Identification 80 mm (3.") 68. mm (.67"). mm (.03") Cover Case 9 mm (3.8") Indicator/ manual lever Lever release button 68 mm (.68") mm (0.6") 00 mm (3.9") Yoke Lock lever Figuar. Dimensions and parts identification 80 mm (Min. 3.") 0 mm (Min..7") 300 mm (Min..8") 0 mm (Min..97") 0 mm (Min..7") 70 mm (Min..76") Figuar. Mounting dimensions with clearance

AB690 Installation CAUTION Install, wire, and use this product under the conditions specified by this manual. Failure to do so may cause fire or device failure. Do not put a load or weight on this product. Doing so may damage the product. zfactory preset position Actuator shaft: fully open Indicator/manual lever: completely turned clockwise. zprecautions for installation Observe the following cautions in order to avoid failure of this product. Do not strike or jar this product. Do not install this product near a steam coil etc. Hightemperature radiant heat may cause failure of the actuator. In addition, observe the following cautions. Install the product in a position allowing easy access for maintenance and inspection. If the product is installed in a ceiling, make a trapdoor for inspection within 08 mm (0 ) around the valve. zmounting position Install the product so that fluid flows in the direction pointed by the arrow on the body. It can be mounted in any position ranging from upright to sideways (90 tilted). Note: If the product is installed outdoors, place it in upright position. Indicator/ manual lever Figuar. Indicator/manual lever position for shipment zmanually opening/closing operation IMPORTANT Before opening or closing the valve manually, turn off the power. If the valve is manually opened or closed while the power ( V AC) is applied, the actuator may break down. Do not manually open or close the valve beyond the fully open or fully closed scale. () Turn off the power. () While pressing the lever release button, turn the indicator/manual lever. Note: No tool is required. Upright Sideways Indicator/ manual lever Lever release button Figuar 3. Correct mounting Actuator is below the valve. Figuar 6. Manually opening/closing operation Figuar. Incorrect mounting 6

AB690 zzmounting on valve (3) Check that the valve stem points to the fully open position. When the valve stem points to the 00 position, the round hole on the side of the valve stem faces to the tip on the joint surface of actuator. CAUTION Installation and wiring of the actuator must be performed by personnel qualified to do instrumentation and electrical work. Mistakes in installation or wiring may cause fire or electric shock. Round hole After the actuator is installed, make sure that the lock lever is closed (locked). If the lever is not locked, the actuator may fall out, resulting in injury. Tip Tip IMPORTANT () Mount the product on the valve (Model VY3 A00 ). Align the four holes on the valve with the tip on the actuator. Check the factory preset position of the actuator and valve. The actuator and valve can be assembled by 90 steps. When changing the mounting position of the actuator, set the valve position to 00 % (fully open) for the valve and actuator. If the valve and actuator are assembled in different valve positions, gears in the actuator will be damaged because the actuator will try to close or open the valve although the valve stops at the fully closed or fully open position. Actuator The indicator/manual lever should be at the 00 position. Indicator/ manual lever Valve The arrow on the stem should point to the 00 position. Align the round hole on the side of the valve stem with the tip on the joint surface of actuator. Actuator (Model MY3_0A_000) Lock lever Lever release button () While pressing the lever release button, turn the indicator/manual lever to the fully open position. Valve stem Valve (Model VY3 A00 ) Press the lever release button Note: Do not press the lever release button while operating. Keep the heat insulator away from the lever release button or the indicator/manual lever. () Turn the lock lever to all the way to the right end. () Turn the lock lever to the left end (marker). Released Marker 7

AB690 Wiring CAUTION Provide a circuit protector (e.g., a fuse or circuit breaker) for the power source. Failure to do so may cause a short circuit leading to fi re or device failure. Install, wire, and use this product under the conditions specifi ed by this manual. Failure to do so may cause fire or device failure. Installation and wiring of the actuator must be performed by personnel qualified to do instrumentation and electrical work. Mistakes in installation or wiring may cause fi re or electric shock. Before wiring, be sure to turn off the power to this product. Failure to do so may result in electric shock or device failure. All wiring must comply with applicable codes and ordinances. Otherwise there is a danger of fi re. For wiring, strip the insulation from cables as specifi ed in this manual. If the length of exposed wire is longer than specified, it may cause electric shock or short circuit between adjacent terminals. If it is too short, it may not make proper contact. Connecting cable Connect the cable as instructed below. Refer to Terminal Diagram. () Open the cover. () Pass the cable through the conduit hole. () While pressing the button, connect the wires. () Pass the cable through the conduit. (3) Strip 8 mm (0.3 0.3 ) from the wire sheath. Strip the wires. 8 mm (0.3"0.3") IMPORTANT This product is designed for V AC power supply voltage. Do not apply power supply voltage other than V AC. For the 0 V DC input type, 0 0 V DC input type, and 0 ma input type, check the polarity of the power supply and 0 V DC feedback signal, and then correctly wire the product. Incorrect wiring may result in PCB (print circuit board) burnout. How to maintain IP (dustproof, splashproof) In order to maintain IP performance, use the waterproof connector when the product is used in high humidity environment or outdoor. Close the cover fi rmly. Use the waterproof connector (option) and apply a waterproofi ng treatment for the conduit holes. () While pressing the button on the terminal block, insert the lead wires for connection. () Lightly pull each lead wire to check that it does not come out. CAUTION After wiring, be sure to reattach the terminal cover. Failure to do so may result in electric shock. 8

AB690 Auxiliary Switch Settings CAUTION Do not put a load or weight on this product. Doing so may damage the product. Before beginning setup work, be sure to turn off the power to this product. Failure to do so may result in electric shock or device failure. (3) Set the position where the auxiliary switch is turned ON. The position can be set from 0 % to 80 %. Model MY30A000 has one builtin auxiliary switch connected to the terminals 7 and 8. Models MY30A000, MY330A000, MY30A000, and MY30A000 have one builtin auxiliary switch connected to the terminals 6 and 7. When the is in open operation from 0 % position, the auxiliary switch is turned on (the terminals 7 and 8 or 6 and 7 are electrically connected) at the preset position. Terminals 7 and 8 for Model MY30A. Terminals 6 and 7 for Models MY30A, MY330A, MY30A, and MY30A. OFF 0 0 Preset switching position Setting range 80 Auxiliary switch ON position 00 () In the electric operation mode, set the valve position to the fully closed position. (Example for setting 0 %) () While pressing the lever release button, manually move the indicator/manual lever to the position set by step (3). Check that the connection between "blue gray" becomes conducted. Press the lever release button () While pressing the lever release button, manually move the indicator/manual lever to the fully open position. Check that the auxiliary switch is being conducted. Press the lever release button () Turn off the power on the product and open the cover. (6) Close the cover. CAUTION After settings, be sure to reattach the cover. Failure to do so may result in electric shock. 9

AB690 Terminals Connection zmodel MY30A000 (Nominal 3 Ω feedback potentiometer, with auxiliary switch) CLOSE (0) OPEN (00) 3 6 7 8 30 V AC, 00 ma zmodel MY30A000 (Nominal 3 Ω resistance input, with auxiliary switch) 3 6 7 30 V AC, 00 ma T T W B R V AC power zmodel MY330A000 ( 0 ma DC input, with auxiliary switch) 3 6 7 30 V AC, 00 ma T T Vacant V AC power 0 ma DC zmodel MY330A000 ( 0 ma DC input, with 0 V DC output) 0 V DC output 3 6 7 T T Vacant V AC power 0 ma DC Figuar 7. Wiring terminal diagrams 0

AB690 zmodel MY30A000 / MY30A000 ( 0 V DC / 0 0 V DC input, with auxiliary switch) 3 6 7 T T Vacant 30 V DC, 00 ma V AC power 00 V DC / 0 V DC zmodel MY30A000 / MY30A000 ( 0 V DC / 0 0 V DC input, with 0 V DC output) 0 V DC output 3 6 7 T T Vacant V AC power 00 V DC / 0 V DC zmodel MY370A0000 (Floating (3position), with auxiliary switch) 3 6 7 8 Vacant Figuar 8. Wiring terminal diagrams

AB690 Wiring Examples zmodel MY30A000: Floating (3position) with nominal 3 Ω feedback potentiometer CLOSE (0) OPEN (00) V AC 3 CLOSE (0) OPEN (00) 6 7 8 Model MY30A000 zmodel MY30A000: Nominal 3 Ω resistance input CLOSE (0) OPEN (00) W B R CLOSE (0) W 3 B OPEN (00) R 6 7 Model MY30A000 T V AC T Model AT7J zmodel MY30A000: 0 0 V DC input with auxiliary switch T V AC T (Voltage output) 6 7 Model MY30A000 Note: Terminals and are connected inside the actuator.

AB690 zmodel MY30A000: 0 0 V DC input with 0 V DC output V AC T T (Voltage output) 6 7 Position indicator Model MY30A000 Note: Terminals, and 7 are not connected inside the actuator. zmodel MY30A000: 0 V DC input with auxiliary switch (Voltage output) V AC T T 6 7 Model MY30A000 Note: Terminals and are connected inside the actuator. zmodel MY30A000: 0 V DC input with 0 V DC output V AC T T (Voltage output) 6 7 Position indicator Model MY30A000 Note: Terminals, and 7 are connected inside the actuator. zmodel MY330A000: 0 ma DC input with auxiliary switch (Current output) V AC T T 6 7 Model MY330A000 Note: Terminals and are connected inside the actuator. 3

AB690 zmodel MY330A000: 0 ma DC input with 0 V DC output T T V AC (Current output) 6 7 Position indicator Model MY330A000 Note: Terminals, and 7 are connected inside the actuator. zmodel MY370A0000: Floating (3position) CLOSE OPEN V AC 3 Model MY370A0000

AB690 Advanced Wiring Examples z 0 V DC input / 0 0 V DC input (an input signal used in common) (Voltage output) T T Model MY30A/MY30A T T V AC V AC Model MY30A/MY30A Note:. Terminals and are connected inside the actuator.. Two as shown in the figure above must be the sametype (same model number).terminals, and 7 are connected inside the actuator. z 0 V DC input / 0 0 V DC input (power supply used in common) (Voltage output) V AC T T Model MY30A/MY30A T T (Voltage output) Model MY30A/MY30A Note:. All actuators must be in phase when using common transformer supply. Connect one transformer terminal to T on each actuator. Connect the other transformer terminal to T on each actuator.. Do not connect the actuator power supply terminals in parallel. 3. If you do not connect the lead wire properly, actuator and wiring might get damaged.. Terminals and are connected inside the actuator.. Two as shown in the figure above must be the sametype (same model number). z 0 V DC input / 0 0 V DC input (both input signal and power supply used in common) T T V AC (Voltage output) Model MY30A/MY30A T T Model MY30A/MY30A Note:. All actuators must be in phase when using common transformer supply. Connect one transformer terminal to T on each actuator. Connect the other transformer terminal to T on each actuator.. Do not connect the actuator power supply terminals in parallel. Do not connect the actuator signal input terminals in parallel. 3. If you do not connect the lead wire properly, actuator and wiring might get damaged.. Terminals and are connected inside the actuator.. Two as shown in the figure above must be the sametype (same model number).

AB690 z 0 V DC input / 0 0 V DC input (system common wiring) Ground line ( ) is used as a common line (for analog signal () transmission). Actuator thus has to have mutual ground as the connected controller. V AC 39 0 (Voltage output) T T T Model MY30A/MY30A T Model MY30A/MY30A Note:. to be connected needs to be applicable to system common wiring.. Wiring length between the actuator terminal and 0 V branch connection point of the transformer secondary side must be: 0 m or shorter for JIS* IV electric wire with. mm² cross section (or equivalent) m or shorter for conducting wire with 0.7 mm² cross section * JIS: Japanese Industrial Standards 3. Terminals and are connected inside the actuator.. Two as shown in the figure above must be the sametype (same model number). Nominal 3 Ω resistance input (wiring for minimum position setting) Besides a proportional controller, the minimum opening range can be set from 0 % to approximately 0 % by adding 3 Ω manual potentiometer. 3 Ω manual potentiometer (Model Q06, etc.) R B W CLOSE(0) OPEN(00) W B R W B R 3 T T (Model TY900_Z etc.) Model MY30A Note: When abnormal circumstances (wire disconnection inside the actuator, input signal error, the end of feedback potentiometer life cycle etc.) occur, the valve cannot maintain the minimum opening. This also may result in a secondary damage. Avoid the applications having any possibility of causing a secondary damage. 6

AB690 Nominal 3 Ω resistance input (using relay and interlock) CLOSE (0) OPEN (00) W B R XO XC W B R 3 T T Switch when fully open Switch when fully closed (Model TY900_Z etc.) Model MY30A XO XC Note:. When XO is open, the actuator is in 00% open position (fully open). When XC is open, the actuator is in 0% open position (fully closed). When both are open, the actuator is in 0% open position (fully closed).. Connect between R and R directly. 3. Use relay with: 0 V, ma or lower min. contact load and 0 V, 0 ma or higher max. contact load. Nominal 3 Ω resistance input (summer / winter changeover) CLOSE (0) W OPEN (00) B R for summer (Model TY900_Z, etc.) CLOSE (0) W B X W 3 X B R Model MY30A T T ON: summer OFF: winter OPEN (00) R for winter (Model TY900_Z, etc.) X Note:. Connect between R and R directly.. Use relay with: 0 V, ma or lower min. contact load and 0 V, 0 ma or higher max. contact load. 7

AB690 Inspection and Maintenance Do not put a load or weight on this product. Doing so may damage the product. CAUTION Before wiring, setting, or maintenance, be sure to turn off the power to this product. Failure to do so may result in electric shock or device failure. After wiring, setting, or maintenance, be sure to reattach the cover. Failure to do so may result in electric shock. Do not touch the moving parts of this product. Doing so may cause injury. zinspection Inspect the according to Table. Manually open/close the at least once a month if it is left, being mounted on the valve, in inactive state for a long period. zmaintenance Visually inspect the fluid leakage of the assembled valve and the (actuator) operations every six months. If any of the problems described in Table are found, take corresponding actions shown in the table. Table. Inspection items and details Inspection item Inspection interval Inspection detail Visual inspection Semiannual Actuator damages. Fluid leaks from the valve gland and the valve connecting part. Loosened lock lever of the mounted onto the valve. Operating status Semiannual Valve unstable open/close operation. Abnormal noise and vibration. Routine inspection Any time Valve unstable open/close operation. Abnormal noise and vibration. Valve hunting Table. Troubleshooting (If your problem is not solved by the corresponding action, please contact Azbil Corporation near you.) Problem Part to check Action Valve does not operate smoothly / valve stops halfway /valve does not operate at all. Auxiliary switch does not operate at all. Fluid leaks when the fully closes the valve. Valve hunting occurs. mounting position vibrates or produces abnormal noise. produces abnormal noise when being in operation. Conditions of the power applied and of the input signal applied. Wiring condition / disconnected wires. Jammed foreign substance (may block the valve open/close operation). Condition of the auxiliary switch (cam switch) dial. Wiring condition / disconnected wires. incorrect mounting onto the valve. Secondary pressure condition and differential pressure condition. Unstable control. Lock lever status. Yoke damages. Check the power supply and the controller connected to the valve. Check the wiring. Remove the jammed foreign substances by manual operation. Adjust the dial setting. Check the wiring. Remount the actuator onto the valve referring to Installation on P... Adjust the inlet and outlet pressure. Correct the control parameter setting of controller. Lock (close) the lock lever. Consult with Azbil Corporation s sales/ service personnel. Consult with Azbil Corporation s sales/ service personnel. 8

AB690 Disposal Dispose of this product as industrial waste in accordance with your local regulations. Do not reuse all or any part of the product. 9

AB690 This product complies with the following harmonised standards of the Electromagnetic Compatibility Directive (EMCD) and the Restriction of the use of certain Hazardous Substances in Electrical and Electronic Equipment Directive (RoHSD). EMCD: EN 60006 EN 0 Class A, Group RoHSD: EN 08 is a trademark or registered trademark of Azbil Corporation in Japan or in other countries. Building Systems Company Kawana, Fujisawa, Kanagawa 8 JAPAN http://www.azbil.com/ Specifications are subject to change without notice. 0 AB690 Rev. 8.0 Mar. 08