INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

Similar documents
INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

ELECTRONIC MANUAL VOLTAGE CONTROL Model: MVC 300. Part Number:

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

ENGEN -100/ENGEN -200 ENGINE GENERATOR CONTROLLER

PM300E Voltage Regulator Instruction Manual

INSTRUCTION MANUAL FOR

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

EA07. Generator Automatic Voltage Regulator Operation Manual

UNIVERSAL VOLTAGE REGULATOR Manufactured in the USA by

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

XR500B Universal Voltage Regulator

MX431 Generator Automatic Voltage Regulator Operation Manual

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

CBS 212/CBS 212A CURRENT BOOST SYSTEM

PM500. Voltage Regulator User Manual. A Regal Brand. Scan here for other languages.

BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD.

EA16. Generator Automatic Voltage Regulator Operation Manual

MODEL 422 Submersible Pump Controller

Instruction Manual. Installation Operation Maintenance. KCR 760 Voltage Regulator

ESC2301. Universal Electronic Governor Controller Operation Manual

5001TCP SPEED CONTROLLER

5001TCP SPEED CONTROLLER

EG3000. Generator Electronic Governor Controller Operation Manual

ADDITIONAL INFORMATION. BE1-50/51B SELF POWERED TIME OVERCURRENT RELAY and RETROFIT KITS. FEATURES and APPLICATION Page 2

VoltPro VP4 Automatic Voltage Regulator

EG3002. Electronic Engine Governor Controller User Manual

ESD5500E Series Speed Control Unit

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

INSTALLING, OPERATING AND MAINTAINING THE MODEL D1028 COMPUTER INPUT BI-DIRECTIONAL GENERATOR FIELD REGULATOR INSTRUCTION MANUAL # S-225

A1P OPERATING MANUAL

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

EG1065X. Compatible with Barber Colman* Dyn1-1065X series * Use for reference purpose only and not a genuine Barber Colman product.

THE MODEL D1025 MKII BI-DIRECTIONAL GENERATOR FIELD REGULATOR INSTRUCTION MANUAL # S-276

EG1069X. Generator Electronic Governor Controller Operation Manual

ENGINE GOVERNING SYSTEMS

Specifications. Minimum Build Up Volts 3.5vac. Voltage Regulator

Power-Tronics, Inc. Electronic Voltage Regulators and Static Exciters P.O. Box , Kerrville, Texas 78029

AFM500X Automatic Flashing Module

EA06. Generator Automatic Voltage Regulator Operation Manual

TRAC-3 TENSION READOUT AND CONTROL

System 350 S350P Proportional Plus Integral Temperature Stage Module

Damper Actuator Installation

R & D SPECIALTIES ROTROL I USER'S MANUAL

RP-4000 Reserve Power Control

PowerOhm Installation Manual for BM R Series Braking Modules

INSTALLATION AND SET-UP MANUAL FOR THE NEW: AVR-07. A CONTROLPAK AVR Automatic Voltage Regulator for three-phase and single-phase alternators

INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS

PRODUCT SERIES: DPG-2100

ESD5550 / 5570 Series Speed Control Units

SE450 Static Exciter Module

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

Brake Pack SB50W. Standard AC Motors A-143. Standard AC Motors Intro duction. Brake Pack. AC Speed Control Motors Inverter.

CBC-300 Series & CBC-300C Series Dual Channel Adjust Clutch/Brake Controls

PRODUCT / TEST MANUAL 2C58K2 INSTANTANEOUS OVERCURRENT

Document: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger

SERIES 2335 SINGLE-PHASE ADJUSTABLE-SPEED DC MOTOR CONTROLLERS (1/6-2 HP)

XR500D-277V Special Voltage Regulator

UL/cUL FILE NUMBER E CE See last page of manual for CE Declaration of Conformity.

VA-715x Electric Valve Actuator

SECTION DC POWER SUPPLY/BATTERY CHARGER

Product Manual (Revision B) Original Instructions. EPG Electrically Powered Governor Models 501 and Installation and Operation Manual

M9216 Series Electric Spring Return Actuators

PowerOhm Installation Manual for BM R Series Braking Modules

Maintenance Manual 13 AMPERE POWER SUPPLY 19A704647P1-P3. Mobile Communications LBI-31801C

DIGITAL GENSET CONTROLLER

2301A Load Sharing & Speed Control with Dual Dynamics. Product Manual (Revision NEW, 1990) Original Instructions

Filtered PWM Speed Control for Permanent Magnet DC Motors

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

Graham. Vari Speed S1000 Instruction Manual. TRANSMISSIONS, Inc. Installation, Operation and Maintenance Manual

Product Instruction. Door Control Board: Board 1Ø4 for PM/SSC (R3)

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

TROUBLESHOOTING GENERATOR UNITS

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

XR500D Universal Voltage Regulator

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

ESD5100 Series Speed Control Unit PART NUMBER ESD5120 ESD (127)

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

The Z Series. SCR Power controllers for resistance heating applications. Zero-Fired SCR Power Controllers AMPS VAC

PowerOhm Installation Manual for LG ATV Series Braking Modules

BLDC SPEED CONTROL INSTRUCTION MANUAL Line voltage Brushless DC control

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

VoltPro VPBF8 Automatic Battery Flashing Module This Manual Covers Both VPBF8-12 and VPBF8-24 Models

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

POWER SUPPLY MODEL XP-800. TWO AC VARIABLE VOLTAGES; 0-120V and 7A, PLUS UP TO 10A. Instruction Manual. Elenco Electronics, Inc.

James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists

G76x Direct Spark Ignition Controls

Boston Gear Ratiotrol DC Motor Speed Control

CONTROL FEATURES AVAILABLE OPTIONS

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

Product Manual (Revision D, 5/2015) Original Instructions. 2301A Speed Control. Installation and Operation Manual

Model 930 Power Control System Instruction Manual

INSTRUCTION MANUAL MODEL PS VDC POWER SUPPLY

EDG6000 Electronic Digital Governor

F-Series. Circuit Breaker

Transcription:

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR Model: APR 125-5 Part Number: 9 1688 00 100 Publication Number: 9 1688 00 990 Revision H: 07/2001

CONTENTS SECTION 1 GENERAL INFORMATION...1-1 DESCRIPTION... 1-1 SPECIFICATIONS... 1-1 SECTION 2 FUNCTIONAL DESCRIPTION... 2-1 OVEREXCITATION SHUTDOWN... 2-1 ACCESSORY ITEMS... 2-1 Power Isolation Transformer... 2-1 Paralleling Module (APM 2000)... 2-1 Manual Voltage Control (MVC 300)... 2-1 Current Boost System (CBS 320)... 2-2 SECTION 3 INSTALLATION... 3-1 MOUNTING... 3-1 INTERCONNECTION... 3-2 SECTION 4 OPERATION... 4-1 GENERAL... 4-1 PRELIMINARY SET-UP... 4-1 OPERATION AT REDUCED SPEEDS... 4-1 SYSTEM START-UP... 4-1 OVEREXCITATION SHUTDOWN... 4-2 ADJUSTMENTS... 4-2 Field Flashing... 4-2 Frequency Roll-Off Adjustment... 4-2 Stability Adjustment... 4-3 Voltage Adjustment... 4-3 OPERATIONAL TEST... 4-3 SECTION 5 MAINTENANCE... 5-1 PREVENTIVE MAINTENANCE... 5-1 TROUBLESHOOTING... 5-1 SECTION 6 MANUAL CHANGE INFORMATION... 6-1 CHANGES... 6-1 Introduction iii

Warning To prevent personal injury or equipment damage, only qualified technicians/operators should install, operate, or service this device. Caution Meggers and high potential test equipment should be used with extreme care. Incorrect use of such equipment could damage components contained in the device.

INTRODUCTION This manual provides information concerning the operation and installation of APR 125-5, Voltage Regulator. To accomplish this, the following is provided. Specifications Functional Description Installation and Calibration Information Maintenance WARNING TO AVOID PERSONAL INJURY OR EQUIPMENT DAMAGE, ONLY QUALIFIED PERSONNEL SHOULD PERFORM THE PROCEDURES PRESENTED IN THIS MANUAL. Introduction i

First Printing: May 1985 Printed in USA 1993 2001, Basler Electric Co., Highland, IL 62249 July 2001 CONFIDENTIAL INFORMATION OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED FOR CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST, AND WITH THE MUTUAL UNDERSTANDING THAT IT WILL NOT BE USED IN ANY MANNER DETRIMENTAL TO THE INTEREST OF BASLER ELECTRIC COMPANY. It is not the intention of this manual to cover all details and variations in equipment, nor does this manual provide data for every possible contingency regarding installation or operation. The availability and design of all features and options are subject to modification without notice. Should further information be required, contact Basler Electric Company, Highland, Illinois. BASLER ELECTRIC ROUTE 143, BOX 269 HIGHLAND, IL 62249 USA http://www.basler.com, info@basler.com PHONE 618-654-2341 FAX 618-654-2351 ii Introduction

SECTION 1 GENERAL INFORMATION DESCRIPTION The Basler APR 125-5 Voltage Regulator is an encapsulated unit contained in a metal case. The regulator controls the dc exciter field power of medium-sized, 50 or 60 Hz brushless generators that have a 125 Vdc field to regulate the output voltage. Regulation is provided by sensing the generator output voltage, converting it to a dc signal and comparing the signal to a reference voltage signal. An error signal is developed and used to control the dc field power in order to maintain a constant generator output. SPECIFICATIONS See Table 1-1 for the electrical specifications and to Table 1-2 for the physical specifications of the APR 125-5. Table 1-1. Electrical Specifications Output Power (with a 240 Vac Input): Exciter Field Dc Resistance: Ac Input Power: Input Burden: Ac Sensing Voltage: 240 Vac: 480 Vac: Sensing Burden: Voltage Adjust Range: External Voltage Adjust Rheostat: 5 ADC @ 125 VDC (625 W) MAXIMUM CONTINUOUS. 8 Adc @ 200 Vdc (1600 W) forcing for one minute. 25 minimum to 100 maximum. 190 to 277 Vac, ±10%, single-phase, 50/60 Hz. 1000 VA maximum. 190/220 Vac at 50 Hz nominal; 208/240 Vac at 60 Hz nominal. 380/400/415 Vac at 50 Hz nominal; 416/450/480 Vac at 60 Hz nominal. 1 VA. 170 to 264 Vac or 340 to 528 Vac using the internal voltage adjust. The external voltage adjust provides a ±10% adjustment of the nominal value determined by the internal voltage adjust. A 5000, 2 W, locking-shaft potentiometer with a screwdriver slotted shaft is supplied with the regulator for remote mounting. Regulation Accuracy: ±0.25%. Voltage Drift: Response Time: <±1% voltage variation for a 50 C (90 F) change. <1.0 cycle. Frequency Compensation: See Figure 1-1. EMI Suppression: Voltage Build-up: Internal electromagnetic filter (EMI filter). Internal provisions for automatic voltage build-up from generator residual voltages as low as 6 Vac. Overexcitation Shutdown: See Section 2 Power Dissipation: 25 W maximum. General Information 1-1

Table 1-2. Physical Specifications UL Recognized/ CSA Certified Operating Temperature Storage Temperature Vibration Shock Weight UL Recognized per Standard 508, UL File No. E 97035. CSA Certified per Standard CAN/CSA-C22.2 No. 14-M91, CSA File No. LR 23131. -40 C (-40 F) to +70 C (+158 F). -65 C (-85 F) to +85 C (+185 F). Withstands: 1.2 G's at 5 to 26 Hz 0.036 inch double amplitude at 27 to 53Hz 5.0 G's at 53 to 1000 Hz. Withstands up to 15 G's in each of three mutually perpendicular axes. 5.1 lbs. (2.3 kg) net, 6.1 lbs. (2.85 kg) shipping. GENERATOR OUTPUT (% FROM NOMINAL) 120 100 80 60 40 20 0 0 "CORNER FREQUENCY" 50 Hz 60 Hz 10 20 30 40 50 60 FREQUENCY ( HZ) Figure 1-1. Typical APR 125-5 Frequency Compensation Curves 1-2 General Information

SECTION 2 FUNCTIONAL DESCRIPTION OVEREXCITATION SHUTDOWN See Figure 2-1. If the exciter field voltage exceeds 190 Vdc, the regulator automatically removes the field current after a time delay. The time delay is inversely proportional to the magnitude of the detected overvoltage condition. At approximately 280 Vdc, the field voltage is removed instantaneously. Overexcitation shutdown will not operate below 160 Vdc. Upon detection of overexcitation and the resulting field voltage shutdown, the regulator will not reset or return to an operational condition until the generator output drops to less than 6 Vac for ten (10) seconds minimum. TIME DELAY (SECONDS) 1000 800 600 500 400 300 200 100 80 60 40 30 20 10 160 180 200 220 240 260 FIELD VOLTS (dc) ZONE OF ZERO DELAY 280 Figure 2-1. Typical Inverse Time Delay Characteristic Curves ACCESSORY ITEMS Power Isolation Transformer A low voltage power isolation can be used to provide electrical isolation and to match voltages from the generator to the regulator. To obtain maximum regulator output power (exciter field resistance of 25 to 30$), select a power isolation transformer of 1.0 kva or greater. For field resistances of 30$ or more, the transformer may be derated (500 VA at 50$, 250 VA at 100$. Paralleling Module (APM 2000) To parallel two or more generators using droop or cross-current compensation, use this module and a current transformer with a 5 A nominal secondary such as the Basler CT series. Manual Voltage Control (MVC 300) This control offers back-up excitation for the regulator in critical applications. The regulated output of this electronic manual control improves the performance of a generator using traditional types of manual control. Functional Description 2-1

Current Boost System (CBS 320) Using the electronics built into the APR 125-5, and a current transformer to tap the generator's line current, the CBS 320 boosts the field current during short circuit or large motor starting. 2-2 Functional Description

SECTION 3 INSTALLATION MOUNTING The regulator may be mounted in any position. Refer to the outline drawing (Figures 3-1 and 3-2). The regulator may be mounted directly on the generator set using 1/4" hardware. Select the proper hardware to withstand any expected shipping/transportation and operating conditions. Figure 3-1. APR 125-5 Outline Drawing Figure 3-2. External Voltage Adjust Potentiometer, Basler P/N 06390 Installation 3-1

INTERCONNECTION See Figures 3-3 through 3-5 for interconnections. a. Connect the jumper from COM to either the 50 Hz or 60 Hz terminal depending upon the generator frequency. b. Remove the jumper and connect terminals CB- and CB+ to the CBS 320 inputs (if used). If the CBS 320 is not being used, leave the jumper in place. c. If an external voltage adjust control is being used, connect the potentiometer to terminals 6 and 7 as shown. If not, connect a jumper between terminals 6 and 7. d. Connect the exciter field to terminals F+ and F-. Be sure to observe polarity. e. Connect the input power to the generator stator to provide power to terminals 3 and 4-E3 within the voltage range of 190 to 277 Vac nominal. Fuse both leads. Install the optional shutdown switch, if desired. f. Connect the sensing input to either 240 (E1) or 480 (E1) and to terminal 4-E3 depending on voltage. The sensing should be connected "line-to-line".. 3-2 Installation

Figure 3-3. 208/240 Vac Interconnection Diagram Installation 3-3

Figure 3-4. 410/450/480 Vac Interconnection Diagram 3-4 Installation

Figure 3-5. Isolation Transformer Interconnection Diagram Installation 3-5

SECTION 4 OPERATION GENERAL The below procedures provide instructions for setting up, starting, operating, and adjusting the APR 125-5 Voltage Regulator. Symptoms of problems occurring during start-up that result from incorrect regulator adjustment and certain generator system problems that resemble faulty regulation, are included together with possible solutions. PRELIMINARY SET-UP To prevent damage to the regulator, complete the following steps before proceeding with system start-up: a. Verify that the voltage regulator specifications conform with the generator system requirements. b. Ensure that the regulator has been installed and connected in accordance with Section 3. OPERATION AT REDUCED SPEEDS During periods of prime mover idling, use the shutdown switch to remove power from the regulator. SYSTEM START-UP See Table 4-1 for system start-up. Table 4-1. System Start-Up Procedure Symptom Remedy 1. Perform the preliminary setup. 2. Start prime mover and bring up to rated speed. 3. Slowly adjust VOLT adjustment or external voltage adjust rheostat until voltage reaches nominal. 4. Apply and remove load to check stability. 5. Check regulation under normal operating conditions. N/A a. Voltage does not buildup b. Voltage builds up and then decays a. Voltage does not build up to rated value b. Voltage high and uncontrollable Generator response too slow or is hunting (oscillating). Poor regulation. a. Flash field b. Troubleshoot Troubleshoot N/A a. Check generator output for shorted or excessive load b. Troubleshoot Troubleshoot a. Check generator output for shorted or excessive load. b. Troubleshoot. a. Check that prime mover is up to speed. b. Check that voltmeter is connected at the same point as the regulator sensing. c. Use an average sensing voltmeter (not an RMS sensing). d. Troubleshoot. Operation 4-1

Procedure Symptom Remedy 6. Reduce generator frequency to approximately 5 Hz below nominal. Generator output should decrease from this point. Generator output voltage does not decrease at desired frequency. a. Check that all wiring is in accordance with Section 3. b. Adjust FREQ control. OVEREXCITATION SHUTDOWN The overexcitation shutdown is included to remove the regulator output power if the exciter field voltage exceeds 190 Vdc. After regulator output power is shutdown, the regulator can be reset by decreasing the input voltage to less than 6 Vac for a minimum of 10 seconds. This may be accomplished by stopping the prime mover or by interrupting the regulator input with the shutdown switch. ADJUSTMENTS Field Flashing When the regulator is operated with the generator for the first time, the polarity of the residual magnetism may not be correct or of sufficient magnitude. If the residual voltage at terminals 3 and 4-E3 is greater than 6 Vac, replace the regulator. If generator residual voltage is less than 6 Vac at terminals 3 and 4-E3, shut down the prime mover and proceed with the following steps: Caution Do not flash the field with the generator in motion. The regulator may be damaged. 1. With the prime mover at rest, apply a dc source (ungrounded), of not more than 48 Vdc, to terminals F+ (positive) and F- (negative) in series with a limiting resistor. Use one (1) ohm of resistance for each volt from the dc power source with a power rating of least one (1) watt per ohm. EXAMPLE: If using a 24 Vdc source, use a 24 ohm, 24 watt resistor. 2. Allow the field to be flashed for approximately ten seconds before removing the dc source. 3. If voltage build-up does not occur after performing steps (1) and (2), verify the polarity of the dc source used in steps (1) and (2) and re-perform. Frequency Roll-Off Adjustment The APR 125-5 underfrequency adjust is factor preset to cause an average 2 V drop in the generator's line input voltage to the regulator when the frequency is between 55 and 55.6 Hz (for 60 Hz applications). For 50 Hz applications, the frequency "roll-off" is factory preset to between 45.75 and 47.75 Hz. To reset the frequency roll-off, proceed as follows: 1. Adjust the prime mover RPM to the desired frequency compensation (corner frequency roll-off) point. 2. Adjust the front panel FREQ control until the output voltage starts to drop off. 3. Bring the prime mover up to rated speed. The output voltage should return to normal. 4-2 Operation

Stability Adjustment An oscilloscope or other voltage recording device should be used if a stability setting is desired that will provide the fastest possible voltage response with good generator stability. 1. Rotation of the front panel STAB control in the clockwise (CW) direction will slow response time. 2. Rotation of the front panel STAB control in the counter-clockwise (CCW) direction will speed response time. If rotated too far CCW, the generator voltage may oscillate (hunt). 3. Rotate the front panel STAB control CCW until the system starts oscillating and then rotate CW just past the point where oscillation occurred. Voltage Adjustment 1. Installation of a jumper across terminals 6 and 7 allows the internal (front panel) VOLT adjustment to vary the generator nominal voltage over the range shown in Table 1-1. 2. The 5000 ohm external potentiometer (supplied with the regulator) may be connected in place of the jumper and will allow for a ±10% adjustment of the voltage range. The nominal value of this range is set by the front panel VOLT control. 3. If a range less than or greater than that provided by the 5000 ohm potentiometer is desired, a 2 Watt potentiometer of any value from 1000 ohms to 10000 ohms may be substituted. OPERATIONAL TEST To operationally test any APR 125-5, refer to Figure 4-1 and perform the following steps in the order given: a. Connect the voltage regulator as shown by Figure 4-1 and apply 240 Vac as shown. b. Adjust the front panel VOLT control fully counter-clockwise (CCW). RESULT: Observe that the lamp does not light. c. Adjust the front panel VOLT control fully clockwise (CW). RESULT: Observe that the lamp is now lit. d. Adjust the front panel VOLT control until the lamp just goes out. Regulator operation is satisfactory if the above results are obtained. Stability, however, must be tested with the generator and regulator operating. Operation 4-3

Figure 4-1. Operational Test Set-Up 4-4 Operation

SECTION 5 MAINTENANCE PREVENTIVE MAINTENANCE A periodic inspection should be made of the voltage regulator to ensure that it is clean and free from accumulations of dust and moisture. Be sure that all terminal connections are clean and tight. TROUBLESHOOTING In case of failure/defective operation of the unit, the following table (Table 5-1) is provided to aid in the determination of the cause and the possible solution. Table 5-1. Troubleshooting Symptom Possible Cause Remedy Voltage does not build up a. No voltage or incorrect voltage to power input at terminals 3 and 4 E3 b. Overexcitation circuit is shutting off regulator a. Flash field b. Verify wiring c. Check fuses d. Check shutdown switch e. Replace regulator Shutdown prime mover then restart (Watch for high voltage) Voltage builds up and then decays a. Open external voltage adjust rheostat or no connection between terminals 6 and 7 Replace external voltage adjust rheostat or the jumper across terminals 6 and 7 b. Defective regulator Replace regulator Voltage does not build up to rated value a. Terminals CB+ and CBare not jumpered Install jumper across terminals CB+ and CBb. Wrong sensing tap selected c. Internal or external voltage adjustments are improperly set Check sensing tap Adjust front panel VOLT control and/or external voltage adjust rheostat d. Faulty regulator Replace regulator Voltage high and uncontrollable a. No sensing input Verify wiring b. Wrong sensing tap Check sensing tap c. Faulty regulator Replace regulator Generator response too slow or is hunting (oscillating)this point. a. Improper front panel STAB adjustment Re-adjust front panel STAB adjustment b. Faulty regulator Replace regulator Maintenance 5-1

Symptom Possible Cause Remedy Poor regulation a. Field resistance not matched to regulator capability or regulator output rating too low for generator requirements b. Incorrect jumper selection for 50 Hz or 60 Hz operation c. Low prime mover speed Verify specifications Check for improper frequency jumper installation Verify prime mover speed 5-2 Maintenance

SECTION 6 MANUAL CHANGE INFORMATION CHANGES Substantive changes in this manual to date are summarized in Table 6-1. Table 6-1. Summary of Changes Revision Summary of Changes ECA/ECO. Date H Revised the manual to current manual style and added UL recognition and CSA Certification. Corrected new Figure number 3-5 to show 240 V connection from transformer. 14085 07/10/01 Manual Change Information 6-1