Centro América Application of EMI Diagnostics to Diesel Generators

Similar documents
LEAP - Life Expectancy Analysis Program For Electrical Rotating Machines. Marcio Gennari ABB Brazil Automation Products Machines Service Osasco

Primary Heat Transport (PHT) Motor Rotor Retaining Ring Failure

Unit 32 Three-Phase Alternators

Generator. Jason S DiSanto. 6B Users Conference San Antonio, TX June 19-22, 2017

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

Vibration studies and on-site balancing of GT-1 assembly

Double earth fault in a PSP during back to back launching sequence

Preparing the Site. Information About the Site Requirements CHAPTER

MCE TM Product Information 5 kv Electric Motor Analyzer

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Customer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment

34 th Hands-On Relay School

REAP CARE ROTATING ELECTRICAL ASSET PROGNOSTIC CARE

Hydro Plant Risk Assessment Guide

ASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc.

Electric Motor Controls BOMA Pre-Quiz

Time Delay Technique for Pinpointing PD Noise on Combined Cycle Systems Troy Coleman, Plant Technical Services

Combustion Turbine Outages For 2008

Substation inspection guidelines Mark B. Goff, P.E.

VEIKI-VNL Electric Large Laboratories Ltd. H-1158-Budapest, Vasgolyó utca 2-4. HUNGARY

Based on the findings, a preventive maintenance strategy can be prepared for the equipment in order to increase reliability and reduce costs.

PAC TRAINING PUMP MOTORS

Excitation system is of Static Silicon Excitation System, including excitation transformer, thyristors, and AVR.

team master medium voltage solid state starters

Unified requirements for systems with voltages above 1 kv up to 15 kv

Condition Monitoring of Electrical Machines ABB MACHsense Solution

Inspection Testing Repair

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

Chapter 6 Generator-Voltage System

HYDRO - 200CX HZ

Comprehensive Technical Training

Independent Testing Laboratory for High Voltage Equipment

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Products & Services EQ Series AC Drives. TEAMMaster WOUND ROTOR MOTORS WORLD SERIES SYNCHRONOUS MOTORS. EXPLOSION PROOF (Division 1, Zone 1)

PROBLEMS WITH NEWER GENERATORS

Artesis MCM Case Studies. March 2011

INDUCTION MOTOR. There is no physical electrical connection to the secondary winding, its current is induced

Hybrid Motor Technology to Achieve Efficiency Levels Beyond NEMA Premium

AFM500X Automatic Flashing Module

AIR COOLED RECTIFIER SPECIFICATION S-50-A

Large Air Cooled Generator Failure

Abbeon Cal, Inc. Model BD-50E HIGH FREQUENCY GENERATOR OPERATING MANUAL

High Voltage Technology & Testing

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

CENTER BREAK GROUP OPERATED AIR BREAK SWITCHES RATED 15.5kV THROUGH 170kV EFFECTIVE DATE: 10/25/16 REV B

BHARAT ALUMINIUM COMPANY LTD. SPECIFICATIONS FOR SYNCHRONOUS GENERATOR GENERAL Make : Jinan Power Equipment Factory Type : WX2

XQ-5200 Solar T60 Gas Turbine-Generator 5,200 ekw Iso Conditions 13.8 kv

Modifiable TITAN Horizontal Motors Accessories and Modifications

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

CP-250E-60/72-208/240-MC4 Microinverter with Modular Trunk Cable

Annex A-4 DIESEL UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES BALANCE OF PLANT GENERATOR DIESEL ENGINE

Generator Termination Bus-bar Arrangement - Design requirements: Utility Perspective

STANDARD FOR AN ELECTRICAL PREVENTIVE MAINTENANCE (EPM) PROGRAM

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC

SE2000BX Static Exciter

Wind Power Services. One Standard for Safety, Quality & Repairs Across North America INTEGRATED POWER SERVICES

Contents INTRODUCTION... 2 CHECK YOU HAVE RECEIVED... 4 WHAT YOU WILL NEED...4 TECHNICAL CHARACTERISTICS...5 WIRING DIAGRAMES...6 CABLES...

Grounding Of Standby & Emergency Power Systems

Variable Frequency Drive Basics

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

SINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options

Wind Power Services. One Standard for Safety, Quality & Repairs Across North America INTEGRATED POWER SERVICES

Page 1. Design meeting 18/03/2008. By Mohamed KOUJILI

V. Design, Application, Maintenance & Operation Technical Requirements

15 kv and 25 kv Thru-Bushings

Development of Large-capacity Indirect Hydrogen-cooled Turbine Generator and Latest Technologies Applied to After Sales Service

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

Science Part B Chapter 4- Electrical Energy. Lesson 1-

Solution Overview. Asset Condition Monitoring. Extend operational life and reduce downtime

Generators for the age of variable power generation

CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

HYDRO Instruction Manual for Model. Hydraulic Generator. Setting the Standard in Mobile Power

Photographs of large cities, such as Seattle, Washington, are visible reminders of how much people rely on electrical energy.

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

Standard for an Electrical Preventive Maintenance (EPM) Program

Hydro Plant Risk Assessment Guide

CALTRAP INSTALLATION AND OPERATIONS MANUAL

APPENDIX B SPECIFICATION FOR GENERATOR OVERHAUL EMD MODEL AR10 D18... B-1

SafeGear TM Motor Control Center Arc resistant metal-clad construction

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Location of Noise Sources in Fluid Power Machines

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

An Investigation into a new method to repair motor cores and improve Efficiency

SPH3U UNIVERSITY PHYSICS

Doubly fed electric machine

700 Series Troubleshooting Guide for C711/C712 Alternators

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting

Global VPI Insulated Indirectly Hydrogen-Cooled Turbine Generator for Single-Shaft Type Combined Cycle Power Generation Facilities

Motor Basics AGSM 325 Motors vs Engines

VAN DE GRAAFF GENERATORS - 400kV

C802/C802D/C802TD/C820 Alternators Troubleshooting Guide

N1387 Series Troubleshooting Guide for N Alternators

NXPLUS C Single busbar. Maintenance-free for lifetime

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

TC Series Cooling Systems

Design specifications

Transcription:

Application of EMI Diagnostics to Diesel Generators CATEGORIAS *Experiencias con características de lotes de combustibles * Control de eficiencia de motores * Aliados clave para operadores de motores * Mejores prácticas en equipos auxiliares * Seguridad y Medio Ambiente * Reporte de incidentes en equipos y soluciones implantadas

EMI Diagnostics of Air Cooled Generators Doble Engineering Company 2

Richard Ladroga Jose Vallejo Doble Global Power Services Doble Engineering Company 3

Condition Based Maintenance Goals are: Prevent in service failures Focus maintenance on equipment as needed when deterioration is indicated Identify where maintenance is not needed Not over maintain and waste resources Doble Engineering Company 4

Numerous types of on-line diagnostic methods are applied such as Infrared & Vibration. Two on line technologies PDA (partial discharge analysis) & EMI (electromagnetic interference) can be used to evaluate the condition of generator insulation. Doble Engineering Company 5

Partial discharge analysis, PDA, is a time domain technique that measures and classifies electrical impulses resulting from insulation defects. Doble Engineering Company 6

PDA was developed in Canada in the 1960 s to detect stator deterioration in large high voltage hydro generators. Very few Diesel generators have been tested. Doble Engineering Company 7

There is no test standard for the various PDA test instruments. Test results depend on the device used and the year constructed. Direct comparison of data from different generators is difficult if not impossible. Doble Engineering Company 8

PDA looks at electrical discharges associated with mica based stator insulation systems. Signals from other sources or defects are usually discarded as noise. Data trending of several tests is necessary. Doble Engineering Company 9

The second method to evaluate generators is EMI Diagnostics Doble Engineering Company 10

EMI Electromagnetic Interference The precise frequency domain measurement and identification of RF energy that results from electrical activity at defects. Doble Engineering Company 11

EMI will detect insulation deterioration and conductor defects Both electrical and mechanical problems can be identified. Doble Engineering Company 12

High voltage discharges (partial discharges) and low voltage arcing generate light, chemical changes (ozone), audible noise (sound), heat and radio noise (EMI). Doble Engineering Company 13

EMI analysis has been used for 70 years to locate defects in power lines that resulted in radio and television interference. Application to power plant equipment started in 1980. EMI data collection follows the international standard CISPR 16. Doble Engineering Company 14

EMI data is collected from the temporary installation of a single split core radio frequency current transformer (RFCT) around a power conduit, on a safety ground or around a neutral lead. There are no hot connections required to any energized conductor and no interference with operation for data collection. This one test location permits a global survey of the entire generator system. Doble Engineering Company 15

Unlike PDA, EMI Diagnostics is a system as well as machine diagnostic technique. More system component defects are detected than generator stator problems. This includes many types of mechanical abnormalities. Doble Engineering Company 16

EMI data is processed by instruments that comply with CISPR 16 standards. Doble Engineering Company 17

Data is collected from one split core RFCT (radio frequency current transformer) Doble Engineering Company 18

The RFCT used has a 12 cm window. The frequency range is 0.05 to 100 MHz. Doble Engineering Company 19

Where the RFCT is placed depends on the generator under investigation. A safe low voltage or grounded location is selected for data collection. Doble Engineering Company 20

Typical RFCT temporary placement at the generator stator neutral. Doble Engineering Company 21

A power conduit is the best location to collect data from small generators. Doble Engineering Company 22

Several radio frequency detectors are available to use. The Peak (PK) detector is very fast and measures the maximum amplitude of a discharge. The RMS detector is very slow and measures the power of the discharge. Doble Engineering Company 23

The QP or Quasi Peak Detector is the one specified in the CISPR 16 standard to measure EMI. When this international standard is followed all EMI data collected can be directly compared. Doble Engineering Company 24

EMI Diagnostics measures and identifies the radio frequency signals resulting from high voltage PD and low voltage arcing with a QP detector. Doble Engineering Company 25

Doble Engineering Company 26

The resulting radio frequency spectrum, or EMI Signature is unique for each physical location and type of defect present within that electrical system. Doble Engineering Company 27

Different frequencies in the EMI Signature describe different problems. Doble Engineering Company 28

With EMI Diagnostics No interference with operations Totally non-invasive technique No applied signal Completely passive measurements Doble Engineering Company 29

Maintenance recommendations can be given with the first test. Trending numerous tests is not necessary to analyze data. Doble Engineering Company 30

Over 7,000 tests conducted since 1980 More than 500 different machine designs 25 hp - 1,400 MW Fossil, hydro, geothermal, nuclear Over 65 types of system defects and conditions have been identified Doble Engineering Company 31

EMI Diagnostics is applicable to all Power Systems 25, 50, 60 Hz Best results 2,300 Volts ac and higher Some success with 250 & 600 V dc power systems Doble Engineering Company 32

Preliminary analysis is conducted as data is collected Doble Engineering Company 33

Generators EMI Diagnostics Evaluates Generator: rotor & stator, insulation and conductors Exciter: all types Voltage regulator Bearings, shaft grounding and seals And other mechanical systems Doble Engineering Company 34

Evaluation of the main generator condition is very important. No maintenance is indicated for this generator. Doble Engineering Company 35

Data is displayed in a log-log format to better show large and small quantities. Doble Engineering Company 36

These examples of determining the condition of generators discusses small high speed hydro generators. These machines are built the same as Diesel generators and develop the same problems. Doble Engineering Company 37

Hydro Plant in Bolivia Doble Engineering Company 38

High Speed Hydro Generators are a similar design as used for diesel driven generators. Doble Engineering Company 39

EMI Signature with slip ring arcing and minor endwinding contamination. Doble Engineering Company 40

A hand held EMI Sniffer is used to further locate each location of the EMI, slip rings, bearing stator, or power cables. Doble Engineering Company 41

Minor dust had collected on endwindings. Doble Engineering Company 42

Indications of shaft currents through a bearing. Doble Engineering Company 43

A major advantage of EMI Diagnostics is the ability to compare the signatures of identical generators. This way the conditions can be ranked and the serious deterioration maintained first. Doble Engineering Company 44

Both generators have minor endwinding corona. Minor maintenance was recommended. Doble Engineering Company 45

This is the corona bleaching that was present after 25 years of service. Doble Engineering Company 46

Unit 3 has more contamination than Unit 4. Doble Engineering Company 47

Unit 3 had more contamination than Unit 4. Doble Engineering Company 48

EMI Diagnostics permits this ranking of contamination to better plan maintenance. The generators that need cleaning can be scheduled first. Cleaning of other stators can be postponed. Doble Engineering Company 49

The generators with no problems can continue to operate without unnecessary down time. Doble Engineering Company 50

Testing of emergency generators is one area where there is usually very little activity. Doble Engineering Company 51

Typical large emergency generator Doble Engineering Company 52

Diesel generator shafts are ungrounded. Most low frequency EMI is from the exciter. Emergency Diesel Generator Div 2 vs Div 1 10000 Microvolts (Quasi-Peak) 1000 100 10 1 Div 2 Diesel Gen. 11-10-04 Exciter noise Div 1 Diesel Gen. 09-08-04 Noise spike Random noise 0.1 0.01 0.1 1 10 Frequency (MHz) Doble Engineering Company 53

If there were stator deterioration it would be seen at frequencies above 1 MHz as with the following two generators. Doble Engineering Company 54

Unit 1 has stator serious deterioration. Doble Engineering Company 55

Both generators have stator problems. A stator rewind for Unit 1 was recommended. The Unit 2 generator had already failed. Doble Engineering Company 56

This plant had suffered several generator connection failures Doble Engineering Company 57

Crimp connections should never be used on large machines. Doble Engineering Company 58

No loose connections were detected. No generator maintenance was needed. Doble Engineering Company 59

The OEM had recommended all 5 generators be opened and the rotors removed. Since no deterioration was indicated it was recommended this activity could be postponed with minimum risk. Doble Engineering Company 60

An EMI Diagnostic also provides information on the condition of the GSU and AUX transformers. Switchyard defects are often detected. Doble Engineering Company 61

At this location arcing was detected when testing the GSU transformer. Doble Engineering Company 62

The 138 kv yard was searched for the source of the arcing EMI. Doble Engineering Company 63

A problem was located at both ends of the 138 kv power cables. Doble Engineering Company 64

The 138 kv cable grounds were loose and arcing. Doble Engineering Company 65

Switchgear problems have also be detected. At this location in Oklahoma a strong EMI source was detected in the 6.9 kv switchgear room. Doble Engineering Company 66

A switchgear defect location can be determined without opening the cubicles. Doble Engineering Company 67

The highest EMI activity was at the top of the third cabinet. HF Amplitude Signal Strength 10 9 8 7 6 5 4 3 2 1 0 HF 1 2 3 4 5 6 7 8 Breaker Location Doble Engineering Company 68

A potential transformer in cubical 3 was found to have a loose high voltage connection to the 6.9kV bus. It was repaired during the next short outage. Doble Engineering Company 69

With most equipment 80% no maintenance 15 % some level of concern 5 % need attention soon Doble Engineering Company 70

Identification of that 80% is very important for the allocation of resources to the 5% that do need attention. Doble Engineering Company 71

Summary EMI Diagnostics can provide information for condition based maintenance of systems with detectable deterioration. Data is collected without effecting operations. No design changes are necessary. Inherently safe technology. Doble Engineering Company 72

Air Cooled Generator Conditions Detected with EMI Diagnostics Doble Engineering Company 73

1. Slot discharges due to side packing deterioration 2. Slot discharged resulting from stator bar coating deterioration 3. Loose endwindings (broken ties) 4. Loose stator bars (loose wedging) 5. Loose phase rings (circuit rings) 6. Verify maintenance corrected all winding defects 7. Foreign metal objects on endwindings 8. Shaft oil seal rub 9. Arcing shaft grounding brush 10. Shaft currents through bearings 11. Contamination on windings (dirt, water & oil) cleaning recommended Doble Engineering Company 74

12. No contamination present (no maintenance necessary) 13. Arcing exciter commutator or main field slip-rings 14. Defective exciter diodes present 15. Loose brushless exciter components 16 Loose static exciter power circuits 17. Open exciter diode fuses 18. Defective voltage regulator components and / or control settings 19. Loose breaker parts 20. Foreign object on rotor 21. Loose surge capacitor connections Doble Engineering Company 75

Additional Defects Found, Motors Dirty stator windings Loose windings in slots and end-arms Broken rotor bars Synchronous motor field ground Rotor not set on magnetic center Frame had loose foundation (soft foot) Wiped bearings Defective outboard bearing insulation (or insulation shorted) Bearing oil seal rub Exciter drive shaft weather seal rub Coupling mis-alignment with driven gear box, pump, fan Defective or missing coupling insulation Circulating currents in driven pumps, coal mills, gearboxes, fans Magnetized gear box shafts / gears Doble Engineering Company 76

Motors Loose crimp / bolted line connections Coupling mis-alignment with driven gear box, pump, fan Defective or missing coupling insulation Circulating currents in driven pumps, coal mills, gearboxes, fans Magnetized gear box shafts / gears Loose neutral connections Loose surge / power factor capacitor connections Abrasive erosion of stator windings Defective motor lead insulation Detect wet power cables Detect 13 kv cable stress cone deterioration Verify correct maintenance was or was not performed Doble Engineering Company 77

Loose & broken support insulators Bus & Sub Station Conditions Identified Contaminated insulators (dirt, cement dust, water) Loose and corroded generator iso-bus hardware Stray circulating currents outside iso-bus enclosures Defective iso-bus enclosure insulation Foreign metal objects inside bus enclosure Defective bus potential transformer connections Open PT high voltage fuses * Loose AUX transformer connections Loose GSU transformer shield ground *Defective surge capacitor connections Loose disconnect switch components, Defective lightning arrestor Loose safety ground on unused 230 kv line Verify correct maintenance was / was not performed Verify no bus, transformer maintenance was necessary Doble Engineering Company 78

Are there any questions? Thank you for listening to the presentation Doble Engineering Company 79