Common recommendations

Similar documents
IMPROVING MOTOR SYSTEM EFFICIENCY WITH HIGH EFFICIENCY BELT DRIVE SYSTEMS

Understanding NEMA Motor Nameplates

MOTOR SAMPLE PROBLEM #1 Low-Slip Drive Belts

ELECTRIC MOTORS, MOTOR MANAGEMENT, AND VARIABLE SPEED DRIVES SECTION M

3/29/2012 ELECTRIC MOTORS, MOTOR MANAGEMENT, AND VARIABLE SPEED DRIVES SECTION M WHY SO DIFFICULT? ELECTRIC MOTOR MANAGEMENT WHY BOTHER?

Introduction to Variable Speed Drives. Pekik Argo Dahono Electrical Energy Conversion Research Laboratory. Institute of Technology Bandung

Chapter 3.2: Electric Motors

Industrial Motors. But first..servos!

Machine Drive Electricity Use in the Industrial Sector

AC Adjustable Speed Drives (ASD s)

It s What s Inside that Counts

Efficient Variable Speed Pumping: A Low Cost Approach to Green Energy

Código de rotor bloqueado Rotor bloqueado, Letra de código. Rotor bloqueado, Letra de código

Energy Efficient Motors

Motor Efficiency, Selection and Management. A Guidebook for Industrial Efficiency Programs

Optimizing Drive Systems for Energy Savings

EMERGING TECHNOLOGIES IN MOTORS AND DRIVES

AR No. # - Install (Belt Type Here)

Power Quality Luis Vargas Research Engineer 9/18/2008

Steve Schouten. Donna Densmore

ECE1750, Spring Motor Drives and Other

Synchronous Generators I. EE 340 Spring 2011

R13 SET - 1. b) Describe different braking methods employed for electrical motors. [8M]

AAFAME Presentation. Shermco Industries Inc. Drives and Automation Application, Sales and Service Manager, Irving Texas.

Synchronous Generators I. Spring 2013

Working through the electric motor replacement maze

Designing a Mechanically Adjustable Speed Drive for AC Motor Applications to Eliminate Vibrations Without Additional Harmonics

Energy savings in drive applications

POWER FACTOR IMPROVEMENT CONCEPT FOR LARGE MOTORS

Hybrid Motor Technology to Achieve Efficiency Levels Beyond NEMA Premium

1.1 Block Diagram of Drive Components of Electric Drive & their functions. Power Processor / Modulator. Control. Unit

Variable Speed Pumping

Synchronous Motor Drives

Project Summary Fuzzy Logic Control of Electric Motors and Motor Drives: Feasibility Study

Variable Frequency Drives

How to: Test & Evaluate Motors in Your Application

Electric Motors. Presentation from the Energy Efficiency Guide for Industry in Asia

MOTOR SURVEY. Solutions for Industry

Realizing Energy Savings in Fan and Pump Systems using Variable Frequency Drives. Schaedler Yesco Expo 2012

Pump & Motor Efficiency

General Purpose Permanent Magnet Motor Drive without Speed and Position Sensor

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. MOTOR CLASSIFICATION. 2010, The McGraw-Hill Companies, Inc.

Building Bridges to Net Zero Adjustable Speed Motor and VFD Applications and Opportunities in Multifamily Buildings

Planning and Commissioning Guideline for NORD IE4 Motors with NORD Frequency Inverters

"Motors, Power, and Data Loggers Greg Jourdan-Wenatchee Valley College Tuesday, May 8, Sessions Session 1-8:30-9:25 a.m. Motors 101 Session

Pump & Motor Efficiency

Motor Basics AGSM 325 Motors vs Engines

% of Design Input Power (kw)

Motor Efficiency Improvements for Pumping Applications. Brent McManis, P.E. Industry Engineering Manager Baldor Electric: A Member of the ABB Group

REDUCING ENERGY CONSUMPTION IN WATER PUMPING STATIONS

Planning and Commissioning Guideline for NORD IE4 Synchronous Motors with NORD Frequency Inverters

Using Variable Speed

Permanent Magnet Motors for ESP Applications Updating the Track Record of Performance. Lorne Simmons VP Sales & Marketing

Technical Explanation for Inverters

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Jeff Fehr, Senior Application Engineer. ACH550 Flux Optimization White Paper

Table of Contents. Foreword...xiii. Chapter One Introduction, Objectives of the Guide...1

Energy Conservation By Energy Efficient Motor In Industry (Case Study Of Polyplast Industry)

Energy Savings by means of Energy Efficient Electric Motors

Energy Efficiency with Low Voltage Motors

Application Information

Best Practice High Eff iciency Motors

IT 318 SUPPLEMENTARY MATERIAL CHAPTER 4

University of New South Wales School of Electrical Engineering & Telecommunications ELEC ELECTRIC DRIVE SYSTEMS.

30 top tips to tackle HVAC challenges No.03 - Permanent magnet motors

AC Motors vs DC Motors. DC Motors. DC Motor Classification ... Prof. Dr. M. Zahurul Haq

Doubly fed electric machine

Characteristics Analysis of Novel Outer Rotor Fan-type PMSM for Increasing Power Density

Welcome to basics of drives training module, looking at process control and various control methods. To view the presenter notes as text, please

A Practical Primer On Motor Drives (Part 11): AC And DC Motor Types

Sensible flow saves Variable Speed Drives (VSDs) saving energy in the industrial sector

Motor Systems Technology Developments

Variable Speed Drives Controlling Centrifugal Pumps Energy Savings

AR No. # Low Pressure Irrigation

QUESTION BANK SPECIAL ELECTRICAL MACHINES

Energy Independence & Securities Act Frequently Asked Questions

Improving Rotary Screw Compressor Performance using Variable Speed Drives. John Cosner, JCI/Frick

COMPANY INTRO. PowerCore Engineering

Technical Guide No. 7. Dimensioning of a Drive system

Chapter 3.1: Electrical System

Electrical Machines -II

Energy Saving Solutions Using Variable Frequency Drives

Whitepaper Dunkermotoren GmbH

ENERGY CONSERVATION IN AUTOMATIC FLUID FLOW CONTROL USING VARIABLE FREQUENCY DRIVE

Modern Design for Variable Speed Motor-Generators:

STUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM

Motors & Drives Rebate Application

Premium Efficiency Motor Rebate Program (Retrofit Applications) Efficiency Requirements Page

Variable Speed Drives in Electrical Energy Management. Course Content

Motors and Variable Speed Drives for Pumps and Fans. Reid Hart, PE

Long-Term Costs and Savings of Properly Rewound Motors

30% and Higher Energy Savings with EC Motors. BUILDINGSNY.COM Javits Center, NY March 21-22, 2017

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011

CHAPTER 1 INTRODUCTION

Permanent Magnet Synchronous Motor. High Efficiency Industrial Motors

Fall 1997 EE361: MIDTERM EXAM 2. This exam is open book and closed notes. Be sure to show all work clearly.

Small step, big impact: Energy efficiency and dynamic performance

G PULLAIAH COLLEGE OF ENGINEERING & TECHNOLOGY DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

J. Kueck, P. Otaduy, J. Hsu, Oak Ridge National Laboratory

SMC -50 Technology and Control Advances

Transcription:

Motor Overview Why are motors important? What is a motor? Optimizing the motor component power factor efficiency and losses motor/load relationships standards Common recommendations Review of CD-ROM

Industrial Electricity Use Lighting/Other 8% Motor-Driven Systems 69% Process Heating 11% Electrolytics 12% Source: DOE presentation, March 1999: Introduction to Motor Systems Management

Industrial motor energy use by application Total 2.3 Quadrillion Btu/yr material handling 12% material processing 23% pumps 24% other 4% refrigeration 7% compressed air 16% fans 14% Source: United States Industrial Electric Motor Systems Market Opportunities Assessment, Office of Industrial Technologies, Office of Energy Efficiency and Renewable energy, US DOE, December 1998, Table 1-16, page 43

Motor size profile compared to energy use Total population 12.4 million units Total Energy Use: 2.3 Quadrillion Btu/yr < 5 hp 59% 250+ 45% 7.5-20 hp 26% 25-50 hp 9% 125-200 14% 60-100 13% 25-50 13% 7.5-20 10% < 5 5% >250hp 1% 125-200 hp 2% 80-100hp 3% Source: OIT pg. 40

What is a motor? Source: Energy-Efficient Motor Systems: A Handbook on Technology, Programs, and Policy Opportunities, 1991, American Council for and Energy-Efficient Economy.

Types of Electric Motors AC induction/asynchronous Single-phase Three-phase AC synchronous DC motors

Induction Motors and Power Factor Active component responsible for torque and useful work Reactive component creates the rotating magnetic field Active part is small at no load and at its max at full load, while reactive is almost constant Ratio of active to total current is called power factor (PF)

Induction Motors and Power Factor At no load, active component is equal to motor inefficiencies At full load PF is typically between 70-95% Utilities penalize for PF lower than 85-95% AC synchronous motors can generate reactive power

Induction Motors and Power Factor Source: Energy-Efficient Motor Systems: A Handbook on Technology, Programs, and Policy Opportunities, 1991, American Council for and Energy-Efficient Economy.

Electrical Power In Losses Motor efficiency and losses 80-95% Shaft Power Out 5-20%

Motor losses and load relationship Source: Energy-Efficient Motor Systems: A Handbook on Technology, Programs, and Policy Opportunities, 1991, American Council for and Energy-Efficient Economy.

Motor efficiency standards NEMA (National Electrical Manufacturer s Association) defines energy efficient motors EPACT 92 (Energy Policy Act of 1992)

Motor h and costs Source: Energy-Efficient Motor Systems: A Handbook on Technology, Programs, and Policy Opportunities, 1991, American Council for and Energy-Efficient Economy.

Motor Recommendations 1. Replace motors with energy-efficient motors NEW HI-EFF MOTOR MOTOR REWIND 3. Use energy-efficient belts 2. Install variable speed drive control 4. Optimize motor size with load

Motor Recommendations Measure Avg. Savings ($/yr) Simple Payback (yr) % Implemented E2 Motors 1,287 1.9 72 VSD Controls 12,451 2.4 34 E2 Belts 2,541 0.6 63 Optimize Size 3,943 1.7 45

Energy Efficient (E2) Motors NEW HIGH EFFIENCY MOTOR MOTOR REWIND

E2 Motors - Background About 20-40% less losses than standard motors Increase in efficiency of 1-10% Larger motors yield smaller efficiency increases Motormaster Program available at www.oit.doe.gov/bestpractices/software_databases/software.shtml

E2 Motors - Background Horsepower Rating (hp) Estimated Existing Efficiency Proposed Efficiency Cost Premium ($ per motor) 1 75 84.6 49 1.5 78.1 85.8 58 2 80.2 86.2 37 3 81.8 88.8 101 5 84.4 89.78 125 7.5 86.1 91.3 157 10 86.7 91.7 134 15 87.7 92.6 134 20 89.6 93 123 25 89.8 93.6 229 30 90.2 93.8 273 40 90.4 94.4 409 50 91.5 94.4 420 60 91.5 95 579 75 91.9 95.3 605 100 92.1 95.4 1044 125 91.6 95.3 1417 150 92.7 95.5 1327 200 93.3 95.7 1801 250 93.8 95.8 2053 300 94.1 96.1 1402 350 94.3 96 1096 400 94 95.9 792 500 93.8 96.6 833

E2 Motors - Background E2 motors may not always be beneficial Less slip can help or hurt energy conservation Not usually suited for variable torque loads because they require hp µ rpm 3 Increasing speed by 1% corresponds to a 3% increase in hp

To Rewind or Not to Rewind? What is motor rewinding? Commonly done with large motors Why is it done? Are there any drawbacks? When should it be considered?

Rewinding Source: Energy-Efficient Motor Systems: A Handbook on Technology, Programs, and Policy Opportunities, 1991, American Council for and Energy-Efficient Economy.

E2 Motors Anticipated Savings Ê 1 1 ˆ EC = HP N C 1 LF UF H Á - ç C ç Ë P Ê 1 1 ˆ DR = HP N C LF CF Á - 1 Ë ç ç C P

E2 Motors Anticipated Savings EC annual energy conservation, kwh/yr HP horsepower of motor considered, hp N number of motors of a given size, no units C1 conversion constant, 0.746 kw/hp LF load factor, fraction of rated load at which motor normally operates UF usage factor, fraction of operating time when motor actually runs, no units H annual operating time of equipment driven by motor, h/yr _ C estimated efficiency of existing motor _ P estimated efficiency of proposed motor DR demand reduction, kw/mo CF coincidence factor, probability that the equipment contributes to the facility peak demand, per month

E2 Motors Load Factor Load Factor - Fraction of rated load at which motor NORMALLY operates. Estimating Load Factor Kilowatt Ratio Method Amperage Method Slip Method

E2 Motors-Kilowatt Ratio Method Load Factor = P i P ir = È V I PF Í Î 1000 È hp Í Î h 0.7457 P i = Measured 3f power in kw P ir = Input power at full-rated load in kw V = RMS voltage, line-to-line of 3 f I = RMS current, mean of 3 f PF = Power factor as a decimal hp = Nameplate rated horsepower h fl = Efficiency at full-rated load fl 3

E2 Motors-Amperage Method I Load Factor = I V r V r I = RMS current, mean of 3 f I r = Nameplate rated current V = RMS voltage, mean line-to-line of 3 f Vr = Nameplate rated voltage

E2 Motors-Amperage Method

E2 Motors Slip Method The speed of the rotating magnetic field is known as the synchronous speed. frequency of the applied voltage (Hz) 60 S s = number of pole pairs Thus, a three-phase induction motor with 4 poles (2 pole pairs) at 60 Hz has a synchronous speed of 1800 rpm.

E2 Motors Slip Method The difference between the synchronous and actual speeds is called the motor slip.

E2 Motors Slip Method Load Factor = S s S s - S - S m r S s = Synchronous speed in rpm S m = Measured speed in rpm S r = Nameplate full-load speed

E2 Motors Incremental Savings = Annual where EML f motor replacement fraction 1 EML = Estimated Motor Life ( ª 12 yrs) = th IS n = Incremental Savings in n year = n x f x S

E2 Motors Sample Problem Motor Driven Equipment Number of Motors Horsepower (hp) Load Factor Coincidence Factor Usage Factor Operating Time (h/yr) Hydrostatic test pump 1 250 0.75 0.2 0.5 500 Oven fan 1 40 0.9 0.9 0.9 4420 Should either of these motors be replaced with high efficiency motors or should they simply be rewound? If replacement is recommended, what are the associated energy, demand, and cost savings? What is the payback period? Use the table of data extracted from the Motormaster program to help you decide. Given: Unit Electric Cost = $0.05/kWh Demand Cost = $10.00/kW

Adjustable Speed Drive (ASD) Control P2/E2 Site Assessment Grant Program Training

ASD - Background Provides the ability to precisely match motor output to process requirements. Power varies as the cube of speed Most effective for applications with varying loads. Common applications: fans, compressors, pumps P2/E2 Site Assessment Grant Program Training

ASD - Potential Benefits Improved product quality Improved process throughput Improved process control Energy savings Reduced maintenance

Common Problems with VFDs VFDs create dirty power (odd-power harmonics) which can upset sensitive equipment Early bearing failure Doesn t save energy when motor is at full load Low speeds can cause cogging

Flow Control Methods Use of outlet dampers and throttle valves Change head pressure to control flow rate Control motor speed

Flow Control without ASD Motor runs at constant speed Flow rate controlled by valve

Power Source Flow Control without ASD Signal Control Valve Controlled Flow Pump Motor

Flow Control with ASD Motor speed varies Flow rate controlled by motor speed Energy is saved

Power Source ASD Flow Control with ASD Signal Controlled Flow Pump Motor

Types of ASDs Mechanical Hydraulic clutches Adjustable belts and pulleys Electrical (Variable Frequency Drives) Pulse Width Modulated (PWM) Voltage Source Inverter (VSI) Current Source Inverter (CSI) Brushless DC Drive (BDCD) Switched Reluctance Drive (SR) Flux Vector Drive (FV)

Pulse Width Modulated (PWM) Uses complex computer software Motor frequency produced with sinusoidally varying pulses of voltage Advantages High power factor Can control several motors at once Smooth speed control, even at low speeds, which eliminates cogging Responds very quickly to speed changes Suitable for almost all applications

PWM Disadvantages Over voltage may lead to failure for motors under 50 hp Decrease cable length between motor and ASD Noisy operation Early bearing failure Use shaft grinding brush instead of graphite grease

Voltage Source Inverter (VSI) Use simple electronic circuit Advantages Able to control several motors at once Very high speed drives available Disadvantages Speed control close to zero unavailable Low frequency results in cogging Power factor proportional to speed No regenerative braking

Current Source Inverter (CSI) Mostly replaced with PWM Advantages Capable of regenerative braking Disadvantages Difficulty controlling more than one motor Poor performance below 50% of rated load

Brushless DC Drive (BDCD) Uses permanent magnets on rotor as poles Advantages Motor shaft speed and position controlled very accurately Able to quickly reaccelerate to high speeds Disadvantages Limited to motors with permanent magnets

Switched Reluctance Drive (SR) Configured specifically for switched reluctance motors Advantages Wide speed range Dynamic response Disadvantages Expensive Cogging occurs close to zero speed

Flux Vector Drive (FV) Best available control Uses same basic control as PWM Advantages Allows maximum torque performance Calculates exact direction and magnitude of motor flux Disadvantages Very expensive should only be used if superior control is needed

ASD Efficiency Efficiency with which ASDs convert constant-frequency power into adjustablefrequency power decreases with speed Uses 4-6% more of the full-load nameplate horsepower while running at full-load Cogging may occur

ASD Efficiency Variable Speed Drive Rating (hp) Percent of Full Operating Speed 25% 50% 75% 100% 1 9.4% 44.2% 70.5% 82.5% 5 29.6% 74.7% 88.3% 92.4% 10 35.3% 79.0% 90.3% 93.5% 25 35.6% 79.4% 90.6% 93.8% 50 43.3% 83.5% 92.1% 94.4% 100 54.8% 89.1% 95.0% 96.6% 250 61.2% 91.3% 96.1% 97.3%

ASD Efficiency 100% 80% 60% 40% 20% 0% ASD Efficiency 25 50 75 100 % of Full Operating Speed 1 hp 10 hp 100 hp

Fraction of Flow Rate Rated Load % % 100 104 95 89 90 76 85 64 80 54 75 44 70 36 65 29 60 24 55 18 50 14 45 11 40 9 35 6 30 4 25 3 20 2 Flow Rate % 0 10 20 30 40 50 60 70 80 90 100 0 20 Fraction of Rated Load % 40 60 80 100 ASD Power Draw 100 hp motor

Screening Methodology High annual operating hours Variable load characteristics Moderate to high horsepower rating

Percent Operating Hours 25 20 15 10 5 0 Load Duty Cycle Example of an Excellent VFD Candidate 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Percent Rated Flow

Percent Operating Hours 25 20 15 10 5 0 Load Duty Cycle Example of a Poor VFD Candidate 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Percent Rated Flow

Anticipated Savings EC = CEU - PEU ECS = EC x unit electric cost EC annual energy conservation, kwh/yr CEU current energy usage, kwh/yr PEU proposed energy usage, kwh/yr ECS energy cost savings, $/yr

Anticipated Savings CEU HP C 1 UF LF H = ç M HP horsepower of motor considered, hp C1 conversion constant, 0.746 kw/hp UF usage factor, no units LF load factor, no units H annual operating time of equipment driven by motor, h/yr _ M efficiency of the driving motor, no units

Anticipated Savings PEU HP C 1 UF i FRL ç Â ( H ) = i M Hi annual operating time at corresponding flow rate, h/yr FRL i fraction of the rated load at which motor will operate for corresponding operating time, no units

Anticipated Savings FRL i = Ê Q Á Ë Q ç pi ci ASD ˆ 3 Qpi proposed flow rate percentage, no units Qci one-speed flow rate percentage, 100% _ ASD adjustable speed drive efficiency, no units

Sample Problem A plastics plant uses a fan with a 100 hp motor that currently runs at constant speed. The air flow rate could be manipulated with an adjustable speed drive. The required air flow and parameters are shown below: Fraction of Flow Required (%) Operating Hours at Flow (h/yr) 100 500 75 3,000 50 2,000 25 500 LF - 1.0 UF - 1.0 Motor efficiency - 94.0% Operating hours - 6,000 h/yr Unit electric cost - $0.05/kWh What is the energy conservation and cost savings realized by installing an ASD?

ASDMaster Developed by the Electric Power Research Institution (EPRI) Adjustable Speed Drive Demonstration Office (ASDO) and Bonneville Power Administration Automated Windows based software package Total System Approach

ASDMaster Instruction on basic ASD operation Determines economic benefits Helps select the appropriate ASD for the application and environment Locates ASD manufacturers

Step 1 Screening Initial Data: Size of motor (hp) Type of equipment Operating Hours Variability of load on motor Feedback: High probability of energy savings Low probability of energy savings Inconclusive

Step 2 Data Collection Load Duty Cycle Determined from historical operating data Equipment Curve Obtained from equipment manufacturer Describes capability of machinery as pressure rise at various flow rates System Curve Quadratic function describes how system pressure changes with flow rate Input 2 points: Design point (static pressure) which is usually shown on equipment curve and any other point

Step 3 Calculations (Performed by ASDMaster) 1. Affinity Point 2. Shaft Speed 3. Fluid Power 4. Shaft Power 5. Motor Power 6. ASD Power 7. Annual Energy Consumption

ASDMaster Information Best Practices Website: http://www.oit.doe.gov/bestpractices /software_tools.shtml ASD link includes: Order form Overview and demonstrations Software available for $150

Energy Efficient (E2) Belts

E2 Belts - Background Standard V-Belts Efficiency of 90-96% Losses from flexing and slippage Cogged V-Belts 1-3% more efficient Lower flexing losses Synchronous Belts Efficiency of 98-99% No slippage Most expensive Not suitable for all applications

E2 Belts Anticipated Savings EC = Á Ë Ê N x HP x C ç 1 x LF ˆ x UF x H x FS Ê N HP C 1 LF ˆ DR = Á CF FS Ë ç ECS = EC x (effective energy rate) DS = DR x C 5 x (effective demand rate)

E2 Belts Anticipated Savings EC annual energy conservation, kwh/yr HP horsepower of motor considered, hp N number of motors of a given size, no units C 1 conversion constant, 0.746 kw/hp LF load factor UF usage factor H annual operating time of equipment driven by motor, h/yr FS fractional energy savings _ efficiency of the driving motor

E2 Belts Anticipated Savings DR demand reduction, kw/mo CF coincidence factor ECS energy cost savings, $/yr DS demand savings, $/yr C 5 number of months per year equipment contributes to the peak demand, generally this constant is 12 months/yr

E2 Belts Sample Problem A manufacturer of canned fruit is interested in reducing energy usage on its 50-1 hp exhaust fans by retrofitting with cogged V-belts. The plant manager stated that these fans run continuously throughout the year at full load. What will be the electric conservation, demand reduction, and total cost savings realized by using cogged V-belts on all of the motors? Given: Motor Efficiency = 80% Unit Electric Cost = $0.05/kWh Demand Cost = $10.00/kW

Optimize Motor Size

Motor Size - Background Motors commonly oversized to allow for growth and safety Motor efficiency and PF drops sharply after about 40% At low loads larger motors still maintain better h and PF Focus on oversized motors with high operating hours Know the typical and maximum load characteristics

Motor Size - Background Source: Energy-Efficient Motor Systems: A Handbook on Technology, Programs, and Policy Opportunities, 1991, American Council for and Energy-Efficient Economy.

Motor Size - Background Source: Energy-Efficient Motor Systems: A Handbook on Technology, Programs, and Policy Opportunities, 1991, American Council for and Energy-Efficient Economy.

Motor Size Anticipated Savings EC = CEU - PEU CEU PEU = = HP HP c p N LF c C 1 H UF ç c N LF p C 1 H UF ç p Ê HP c LF c HP p LF p ˆ DR = Á - C 1 Ë ç c ç p N CF

Motor Size Anticipated Savings EC annual energy conservation, kwh/yr CEU current energy usage, kwh/yr PEU proposed energy usage, kwh/yr HP C horsepower of current motor, hp HP P horsepower of proposed motor, hp LF C fraction of rated load at which current motor normally operates LF P fraction of rated load at which proposed motor will operate N number of motors of a given size, no units

Motor Size Anticipated Savings C 1 conversion constant, 0.746 kw/hp UF usage factor H annual operating time of equipment driven by motor, h/yr _ C estimated efficiency of existing motor _ P estimated efficiency of proposed motor DR demand reduction, kw/mo CF coincidence factor

Motor Size Sample Problem During an assessment, two 100 hp vacuum pump motors were metered throughout the day. It was determined that the North side vacuum pump was continuously loaded at 80 hp. The metering of the South side vacuum pump showed that it never needed more than 40 hp and that the average load was 35 hp. Both pumps run continuously throughout the year. What do you suggest they do and what are the associated savings? Given: Efficiency of 100 hp motor @ 35% rated load = 85% Unit electric usage cost = $0.05/kWh Unit demand cost = $10.00/kW Horsepower Rating (hp) Efficiency at 75% rated load 1 75 1.5 78.1 2 80.2 3 81.8 5 84.4 7.5 86.1 10 86.7 15 87.7 20 89.6 25 89.8 30 90.2 40 90.4 50 91.5 60 91.5 75 91.9 100 92.1

Motor Resources OIT BestPractices Program: Motors - www.oit.doe.gov/bestpractices/motors/ Baldor Motor and Drives - www.baldor.com Energy-Efficient Motor Systems: A Handbook on Technology, Programs, and Policy Opportunities, 1991, American Council for an Energy-Efficient Economy