INDUCTROL. Voltage Regulator CPO 97.09F. updated 03/09

Similar documents
A/C Generator Systems

Welcome VA School Bus Technicians From

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics

3 Phase Voltage Imbalance

Institute of Technology, Nirma University B. Tech. Sem. V: Electrical Engineering 2EE305: ELECTRICAL MACHINES II. Handout: AC Commutator Motors

ASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc.

1 Low-voltage Power-factor Correction capacitors KNK APPLICATION DESIGN

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:

Chapter 5 FOUNDATION. 2010, The McGraw-Hill Companies, Inc. 2010, The McGraw-Hill Companies, Inc.

INDEX Section Page Number Remarks

Código de rotor bloqueado Rotor bloqueado, Letra de código. Rotor bloqueado, Letra de código

CCE RR KARNATAKA SECONDARY EDUCATION EXAMINATION BOARD, MALLESWARAM, BANGALORE G È.G È.G È.. Æ fioê, d È 2017

Introduction to Variable Speed Drives. Pekik Argo Dahono Electrical Energy Conversion Research Laboratory. Institute of Technology Bandung

Most home and business appliances operate on single-phase AC power. For this reason, singlephase AC motors are in widespread use.

Understanding The HA2500's Horiz Driver Test

Handout Activity: HA773

Number 9 January SECTION 1 Dimming of T12 Fluorescent lamps 2. SECTION 2 Dimming of T8 Fluorescent lamps 4. SECTION 3 Do's and Don'ts 6

INSTITUTE OF AERONAUTICAL ENGINEERING Dundigal, Hyderabad

DO COMMERCIAL BUILDINGS HAVE POWER PROBLEMS? THE ANSWER IS - THEY CERTAINLY DO.

Joslyn Clark Controls, Inc. Simple, Safe, Retrofit Programs to Significantly Extend Life of Existing Circuit Breakers

Danyal Education (Contact: ) A commitment to teach and nurture. c) sketch a graph of voltage output against time for a simple a.c.

EE6351 ELECTRIC DRIVES AND CONTROL UNIT-1 INTRODUTION

PQC-STATCON. PPHVC-Power Quality Solutions. Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads

Variable Speed Pumping

Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors

Power Quality and Energy Management

Grounding Of Standby & Emergency Power Systems

MEANWELL DC/AC POWER INVERTERS

smartvar Dynamic VAR Compensator

Power Quality Luis Vargas Research Engineer 9/18/2008

Is Uncorrected Power Factor Costing You Money?

DISSECTIBLE TRANSFORMER - large

ABB n.v Power Quality in LV installations

MOTOR INSTALLATION. Knowledge of proper installation techniques is vital to the effective operation of a motor

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 CHARACTER OF SERVICE

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

ECE1750, Spring Motor Drives and Other

USER MANUAL MPS 1-5KW SERIES

CMD-4000 SERIES REV. A 4+ FUNCTION REMOTE CONTROL DOOR LATCH OPENER SYSTEM INTRODUCTION

AC MOTOR TYPES. DESCRIBE how torque is produced in a single-phase AC motor. EXPLAIN why an AC synchronous motor does not have starting torque.

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

MYRON ZUCKER CALMANUAL POWER FACTOR CORRECTION APPLICATION GUIDE INC.

Working Principle of Power Saver as per Manufacture:

50 Hz Mini/Micro Computer Regulator (MCR) Series Installation and Operation Manual

MODEL 2602A-12 3 STAGE AUTOMATIC BATTERY CHARGER OWNER S MANUAL SAVE THESE INSTRUCTIONS


Diesel generator set 6BT5.9 series engine

1.1 Block Diagram of Drive Components of Electric Drive & their functions. Power Processor / Modulator. Control. Unit

Save Thousands of Dollars Per Year!

Power Quality Solutions POWER QUALITY SOLUTIONS: ACTIVE HARMONIC FILTERS

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

2014 ELECTRICAL TECHNOLOGY

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality

CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS

10. Starting Method for Induction Motors

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

Power Protection Discrete Automation & Motion South Africa

Photographs of large cities, such as Seattle, Washington, are visible reminders of how much people rely on electrical energy.

Electrical Machines II. Week 5-6: Induction Motor Construction, theory of operation, rotating magnetic field and equivalent circuit

EEE3441 Electrical Machines Department of Electrical Engineering. Lecture. Introduction to Electrical Machines

WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 RULE NO. 2

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

powerdriveinverters.com Owner s Guide Please Save for Future Reference 300 Watt DC to AC Power Inverter

Ihr autorisierter Distributor: Neumüller Elektronik GmbH Motor Protectors

ADF. Restoring the perfect wave

Diesel generator set QSB7 series engine

One Solution for Ideal Power Quality

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

National 4 Physics - Electricity and Energy Summary Notes

Drive Fundamentals. Motor Control Bootcamp May 15-18, Copyright 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC CO900H

Diesel generator set QSK50 series engine

Page 1. Design meeting 18/03/2008. By Mohamed KOUJILI

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

smart mounting smart tools Mounting Tools Dismounting Tools Induction Heaters

Solutions for Power Quality and Productivity

Steve Schouten. Donna Densmore

PCS AC POWER LINE CONDITIONERS. PCS H SERIES - THREE PHASE - 6 to 500 kva H - THREE PHASE SERVO ELECTRONIC DESIGN. AC - THREE PHASE - 6 TO 500 kva

ROTATING MAGNETIC FIELD

ENERGY EFFICIENT MOTORS AND POWER SAVING Dr. K. Brahmanandam E.E.E Department, M.V.S.R.E.C, Hyderabad, India

Fuses still the best form of overload protection

Diesel generator set QSK23 series engine

USER MANUAL. Copyright 2006, PowerStation, LLC All rights reserved MODEL: PS5000M

RODIX, INC. FC-40-PLC Plus Series Control Troubleshooting Guide for Circuit Board P/Ns and

INDUCTION MOTOR. There is no physical electrical connection to the secondary winding, its current is induced

Ultra Series. Vertical Pump Motors HP. Durability, Reliability and Efficiency at the Heart of Industrial Operations

MEBS Utilities services Department of Electrical & Electronic Engineering University of Hong Kong

PRO-WAVE INVERTER 12 VOLT, 150W PURE SINE WAVE

CHAPTER 6 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION GENERATOR

MYERS 3MW VERTICAL DISCHARGE WASTEWATER PUMPS. Sewage, high-capacity sump, effluent

Variable Frequency Drives

Is Your Wiring System Safe and Energy Efficient?

PROCESS ELECTRONICS CORPORATION

Hydraulic Drive Technology for Woodworking Machinery

Installation and Operation Guide. Tundra HD 2500 Power Inverter. for the. Webasto BlueCool Truck System

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS)

Chapter 5: DC Motors. 9/18/2003 Electromechanical Dynamics 1

Electrical Theory. Generator Theory. PJM State & Member Training Dept. PJM /22/2018

INTERACTIVE SCIENCE 2A

Unit AE01K Knowledge of Locating and Correcting Simple Electrical Faults in the Automotive Workplace

Transcription:

INDUCTROL Voltage Regulator CPO 97.09F updated 03/09

Are voltage ups & downs costing you money? GE INDUCTROL voltage regulators can eliminate irregularities VOLTAGE ups and downs may be costing you thousands of dollars. Fluctuating voltage is the constant enemy of electrical and electronic equipment. It can reduce operating efficiency, increase maintenance costs, damage expensive electronics and cost you plenty in the process. All electrical equipment is designed to operate at a specific voltage. Unfortunately, input voltage does not always remain constant. While you can operate most electrical equipment over a wide range of input voltage, you do so at the sacrifice of life, economy or optimum performance - or all three. Modern electrical equipment is much more sensitive to voltage variations than electrical equipment of the past, and therefore more vulnerable to damage. GE INDUCTROL voltage regulators supply a constant voltage tailored to your equipment. They actually sense inadequate or excessive voltage and quickly make uninterrupted corrections automatically. No need to calculate impedance between source bus and the INDUCTROL- the INDUCTROL maintains the voltage to the load. The Inside Story INDUCTROL voltage regulators are designed to perform either of two basic functions on electric circuits (or a combination of both): Maintain an output voltage or current at± 1% despite variations in the supply voltage or the connected load. Provide a widely adjustable output voltage or current from an essentially constant supply. The design is simple and reliable. Essentially, the INDUCTROL voltage regulator is a variable ratio auto-transformer consisting of laminated steel rotor and stator. The construction is similar to that of an electric motor except that the rotor rotates only 180 mechanical and electrical degrees. The rotor contains the exciting (or shunt) winding and the stator has the regulating or series winding. In operation, the automatic control circuit monitors the output voltage, senses any need for voltage correction and actuates a reversible electric motor which drives the regulator rotor. As the position of the rotor winding changes, the flux linkages between windings change to increase or decrease the magnitude of the voltage induced in the series winding, thus adding to or subtracting from the supply voltage and producing a precisely controlled output voltage. The voltage correction is obtained solely by transformer action by varying the degree of mutual coupling between the shunt and series windings of the regulator. There are no sliding contacts or brushes. You get outstanding performance Trouble Fee operation - because there are no brushes or sliding contacts, very little maintenance is required. Fast, accurate response - with automatic control the INDUCTROL starts correction in 2 cycles and completes within one second for the usual 2% change in line voltage. Unlike step voltage regulators, the dynamic voltage regulation on the INDUCTROL maintains the voltage within± 1% of the pre-selected value at all times. No wave form distortion - unlike impedance changing regulators, no harmful wave distortion is induced. Problems with sensitive electronic equipment are therefore eliminated. Rugged constmction- the INDUCTROL voltage regulator can take up to 100% overload for one hour with ±10% units rated through 225 circuit kva. It has a short circuit capability of 15 times rated current for 2 seconds. High power fi:~ctor- since it is a variable transformer, the INDUCTROL voltage regulator has almost no effect on the system power factor. This results in a substantial cost reduction. Efficient pe1for111ance- INDUCTROL voltage regulators are highly efficient. Typical efficiencies exceed 99% at full load and are maintained at relatively high values even at reduced loads. INDUCTROL voltage regulators pay for themselves No matter what the application, variations in voltage can cause considerable loss of time and money. By reducing unnecessary downtime and costs, GE INDUCTROL regulators can actually pay for themselves. What's more, alternative methods for solving poor voltage problems are usually more expensive than INDUC TROL regulators. Contact your local GE Sales Engineer. He or she will welcome the opportunity to review your problem and help you solve it.

How to spot a voltage fluctuation and what to do about it You can't see fluctuating voltage, but you can easily recognize the results. Look for these danger signals- they are a dead giveaway to voltage irregularity: Lighting Problem: Dim lights or fast lamp burn-out; fluorescent lamps slow to start; high pressure sodium and mercury lights go out. Cause: Under-voltage cuts light output, reduces lamp efficiency. Over-voltage sharply cuts lamp life, increases power costs, lamp replacement costs soar, ballasts or transformers may be damaged. Solution: GE INDUCTROL regulator maintains voltage to within ±1% of pre-selected output. Computers Problem: Incorrect information, lost data resulting in downtime to restore inputs. PC boards and other electrical components burn out due to high voltage. Cause: Fluctuating voltage. Solution: GE INDUCTROL voltage regulator maintains constant output voltage without generating radio interference. Medical Equipment Problem: X-ray, MRI, CAT Scan, and other diagnostic monitoring equipment malfunctions or behaves erratically. Problem cannot be traced to failure of the equipment. Cause: Fluctuating voltage hits and runs, often leaving no visible evidence. Technicians may waste hours looking for the cause within the equipment. Solution: GE INDUCTROL voltage regulator prevents costly downtime during critical or emergency situations by supplying correct voltage under varying loads and source voltage. Communication Equipment Problem: Power output of the transmitter decreases when voltage decreases, causing poor reception. Also, costly printed circuit boards burn out due to excessive voltage. Cause: Variations in input voltages result in corresponding variations in output power levels. Solution: GE INDUCTROL voltage regulators can provide either a substantially constant output from a variable supply or a variable output from a relatively constant supply. Long Feeder Runs Problem: Expensive over-bussing or over-cabling is required to compensate for voltage drop on low-voltage distribution feeders. Cause: Expensive voltage drop on long feeders. Solution: Combine INDUCTROL regulators with load-rated conductors to save money. Electrical Seam Welding and Plating Problem: High rejection rate on welded products due to inadequate heat during welding. Cause: Variations in voltage. Solution: GE INDUCTROL voltage regulator maintains voltage levels necessary to provide sufficient heat. Motors Problem: Insulation breaks down when reduced starting torque results from inadequate voltage. Cause: Under-voltage causes overheating; over-voltage decreases power factor. Solution: GE INDUCTROL voltage regulator increases motor life and reduces maintenance. Resistance Heating & Infrared Ovens Problem: High rejection rate results from either too much heat (which causes blistering) or too little heat (which causes sticky surfaces). Cause: Varying in-plant load demands. Solution: GE INDUCTROL regulator permits production of correct amounts of heat under varying loads. These are only a few of the most common applications forge INDUCTROL voltage regulators; the list is practically endless. Wherever there is electrically-operated equipment, voltage ups and downs can cause problems. Here are some of the other types of equipment that GE regulators can help operate more effectively: Electronic Appliances carrier telephone equipment d-e power supplies electronic precipitators ground-support equipment power supplies radar equipment radio transmitters sonar spectrographs television transmitters medical equipment Commercial Applications blueprinting film processing office machinery photoengraving power distribution in buildings air renewal and A/C systems refrigerating chambers Industrial Applications anodizing and plating automotive parts battery-plate forming capacitor charging carton sealing equipment cement manufacturing corona detection electric hoist manufacturing and testing electrochemical processes glass products high-voltage power supplies induction heaters in-plant power distribution machine-tool control materials-handling equipment metalworking machinery motor testing pumps fans compressor manufacturing printing-press devices radiant heaters switchboard panel and control manufacturing test equipment textile processes vacuum equipment welding wire enameling wood products

INDUCTROL voltage regulators pay for themselves - No matter what the application, variations in voltage can cause considerable loss of time and money. By reducing unnecessary downtime and costs, GE INDUCTROL regulators can actually pay for themselves. What's more, alternative methods for solving poor voltage problems are usually more expensive than INDUCTROL regulators. Contact your local GE Sales representative today. He or she will welcome the opportunity to review your problem and help you solve it. 1223 FAIRGROVE CHURCH ROAD CONOVER, NORTH CAROLINA 28613 Telephone Fax Toll Free (US only) (828) 466-7824 (828) 466-5441 (800) 500-0662

Ordering Information for automatic INDUCTROL Voltage Regulators Standard Design, Single-Phase, Dry-Type, TYPE AIRS (60 Hertz) 10% Raise and Lower Circuit Approx. Dimensions in Inches Approx. Wt. in Lb. KVA Amps Cat. No. Height Width Depth Net Ship 120 VOLTS, 2-WIRE (Connection Sketch 1) 8.5 71 3106500A+ 21 25 28 15 125 31D6501A+ 21 25 28 25 208 3106502A 21 25 28 50 416 3106503A 21 25 28 75 625 3106504A 21 25 28 100 832 3106505A 53 25 28 530 580 150 1250 3106506A 53 25 28 670 720 225 1875 31D6507A 53 25 28 240 VOLTS, 2-WIRE (Connection Sketch 1) 8.5 35.5 31D6510A+ 21 25 28 15 62.5 31D6511A+ 21 25 28 25 104 31D6512A 21 25 28 50 208 31D6513A 21 25 28 75 312 31D6514A 21 25 28 100 416 31D6515A 48 25 28 530 580 150 625 31D6516A 48 25 28 670 720 225 937 31D6517A 53 25 28 120/240 VOLTS, 3-WIRE (Connection Sketch 2) 8.5 35.5 3106520A+ 21 25 28 15 62.5 31D6521A+ 21 25 28 25 104 3106522A 21 25 28 50 208 3106523A 21 25 28 75 312 3106524A 21 25 28 100 416 3106525A 48 25 28 550 600 150 625 3106526A 48 25 28 690 740 225 937 31D6527A 53 25 28 480 VOLTS, 2-WIRE (Connection Sketch 1) 8.5 17.7 3106530A+ 21 25 28 15 31.2 31D6531A+ 21 25 28 25 52 3106532A 21 25 28 50 104 3106533A 21 25 28 75 156 3106534A 21 25 28 100 208 3106535A 48 25 28 550 600 150 312 3106536A 48 25 28 690 740 225 468 31D6537A 48 25 28 + This unit can operate at either 50 or 60 Hertz.

Standard Design, Single-Phase, Dry-Type, TYPE AIRS (60 Hertz) 20 /o Raise and Lower Circuit Approx. Dimensions in Inches KVA Amps Cat. No. Height Width Depth 120 VOLTS, 2-WIRE (Connection Sketch 1) 4.25 35.5 31D6600A+ 21 25 28 7.50 62.5 31D6601A+ 21 25 28 12.5 104 31D6602A 21 25 28 25.0 208 31D6603A 21 25 28 37.5 312 31D6604A 21 25 28 50.0 416 31D6605A 48 25 28 75.0 625 31D6606A 48 25 28 112.5 937 31D6607A 53 25 28 240 VOLTS, 2-WIRE (Connection Sketch 1) 4.25 17.7 31D6610A 21 25 28 7.50 31.2 31D6611A 21 25 28 12.5 52 31D6612A 21 25 28 25.0 104 31D6613A 21 25 28 37.5 156 31D6614A 21 25 28 50.0 208 31D6615A 48 25 28 75.0 312 31D6616A 48 25 28 112.5 468 31D6617A 48 25 28 480 VOLTS, 2-WIRE (Connection Sketch 1) 4.25 8.9 31D6630A+ 21 25 28 7.50 15.6 31D6631A+ 21 25 28 12.5 26 31D6632A 21 25 28 25.0 52 31D6633A 21 25 28 37.5 78 31D6634A 21 25 28 50.0 104 31D6635A 48 25 28 75.0 156 31D6636A 48 25 28 112.5 234 31D6637A 48 25 28 + Th1s un1t can operate at e1ther 50 or 60 Hertz. Approx. Wt. in Lb. Net Ship 530 580 670 720 550 580 690 720 530 580 670 720 S2 L2 Connection Sketch 1 Connection Sketch 2

Standard Design, Three-Phase, Dry-type TYPE AIRT (60 Hertz) 10 % Raise and Lower Cooling Circuit AA =Self Cat. No. Approx. Dimensions in Inches kva Amps FA= Forced Height Width Depth 208Y/120 VOLTS, 4-WIRE (Connection Sketch 3) 10 27.8 AA 31D6550A+ 21 25 28 15 41.6 AA 31D6551A+ 21 25 28 20 55.6 AA 31D6552A 21 25 28 40 111 AA 31D6553A 21 25 28 60 167 AA 31D6554A 21 25 28 75 208 AA 31D6555A 48 25 28 150 416 AA 31D6556A 48 25 28 225 624 AA 3156557A 48 25 28 300 832 FA 31 D6801A 58 23 45 500 1387 FA 31D6802A 70 29 53 240 VOLTS, 3-WIRE (Connection Sketch 4) 10 24 AA 31D6700A+ 21 25 28 15 36 AA 31 D6701A+ 21 25 28 20 48 AA 31D6562A 21 25 28 40 96 AA 31D6563A 21 25 28 60 144 AA 31D6564A 21 25 28 75 180 AA 31D6540A 48 25 28 150 360 AA 31D6541A 48 25 28 225 540 AA 31D6542A 48 25 28 300 720 FA 31D6841A 58 23 45 500 1200 FA 31D6842A 70 29 53 480Y/277, 4-WIRE (Connection Sketch 3) 10 12 AA 31D6570A+ 21 25 28 15 18 AA 31D6571A 21 25 28 20 24 AA 31D6572A 21 25 28 40 48 AA 31D6573A 21 25 28 60 72 AA 31D6574A 21 25 28 75 90 AA 31D6575A 48 25 28 150 180 AA 31D6576A 48 25 28 225 270 AA 31D6577A 48 25 28 300 360 FA 31D6821A 58 23 45 500 600 FA 31D6822A 58 23 45 750 900 FA 31D6823A 58 23 45 1000 1200 FA 31D6824A 70 29 53 + Th1s un1t can operate at e1ther 50 or 60 Hertz. Approx. Wt. in Lb. Net Ship 520 570 740 790 520 620 740 840 950 1050 520 570 740 810 1165 1265 1420 1520 L3 3 >>------.~ S3 3 L3 > Connection Diagram 3 Connection Diagram 4

Standard Design, Three-Phase, Dry-type TYPE AIRT (60 Hertz) 20 % Raise and Lower Cooling Circuit AA =Self Cat. No. Approx. Dimensions in Inches kva Amps FA= Forced Height Width Depth 208Y/120 VOLTS, 4-WIRE (Connection Sketch 3) 5 13.9 AA 3106650A+ 21 25 28 7.5 20.8 AA 31D6651A+ 21 25 28 10 27.8 AA 3106652A 21 25 28 20 55.6 AA 3106653A 21 25 28 30 83.4 AA 3106654A 21 25 28 37.5 104 AA 3106655A 48 25 28 75 208 AA 3106656A 48 25 28 112.5 312 AA 31D6657A 48 25 28 150 416 FA 31D6811A 59 23 45 250 693 FA 31D6812A 59 23 45 375 1040 FA 31D6813A 70 29 53 500 1387 FA 31D6814A 70 29 53 240 VOLTS, 3-WIRE (Connection Sketch 4) 5 12 AA 3106706A+ 21 25 28 7.5 18 AA 31D6707A+ 21 25 28 10 24 AA 3106708A 21 25 28 20 48 AA 31D6709A 21 25 28 30 72 AA 31D6710A 21 25 28 37.5 90 AA 31D6711A 48 25 28 75 180 AA 31D6712A 48 25 28 112.5 270 AA 31D6713A 48 25 28 150 360 FA 31D6851A 58 23 45 250 600 FA 3106852A 58 23 45 375 900 FA 3106853A 58 23 45 500 1200 FA 3106854A 70 29 53 480Y/277, 4-WIRE (Connection Sketch 3) 5 6 AA 3106670A+ 21 25 28 7.5 9 AA 31D6671A+ 21 25 28 10 12 AA 3106672A 21 25 28 20 24 AA 31 D6673A 21 25 28 30 36 AA 3106674A 21 25 28 37.5 45 AA 31D6675A 48 25 28 75 90 AA 3106676A 48 25 28 112.5 135 AA 3106677A 48 25 28 150 180 FA 31D6831A 58 23 45 250 300 FA 3106832A 58 23 45 375 450 FA 3106833A 58 23 45 500 600 FA 3106834A 70 29 53 750 900 FA 3106835A 70 29 53 + This umt can operate at either 50 or 60 Hertz. Approx. Wt. in Lb. Net Ship 520 570 740 790 1165 1265 2050 2150 520 620 740 840 950 1050 1165 1265 1420 1520 520 570 740 810 1165 1265 1420 1520 2200 2300