Low voltage bushings for pad-mounted distribution transformers Technical information guide

Similar documents
LV Bushing Oil to Air Dry Insulation PTAB-SLV832

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB

Eaton s Cooper Power Systems

ABB Power T&D Company Inc. General Information: DT-100 DT-150 DV-100 DV-150. De-energized Switches TPL , July 1999, Page 1 of 4

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

High-voltage primary bushings installation instructions

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

Product Description: Objective and Certification: Test Samples and Test Cable:

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

Type VRLTC load tap changer

Effective March 2015 Supersedes S August 2012

Type NR oil switch installation and operation instructions

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Load Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA Technical Guide Nut Mount Weld Mount

Surge arrester POLIM-H.. ND

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

Dry Well Cannister Type CLT, OIL Immersed PTAP-AFH926. Technical Guide Load-break, Dead-break

Surge arrester POLIM-H..SD

A 1.2 kv class externally removable secondary bushing

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

IL Instruction Leaflet Page 1 November,2001. Type DTW De-energized Tap Changer Application, Installation & Selection Guide

Surge arrester POLIM-C.. HD

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

AG903-07E TDFN Current Sensor Evaluation Board

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

MEDIUM VOLTAGE PRODUCT. TJC 4 Indoor voltage transformers

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

Surge arrester POLIM-H..N

STAINLESS STEEL FORGED FITTINGS 3000lb 304/304L & 316/316L Forged Stainless Steel Fittings Product Specifications

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

Voltage limiting device HVL

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

LOW VOLTAGE WIND CONVERTERS. ABB wind turbine converters ACS880, 800 kw to 8 MW

Bushings for High Voltage AC Applications

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

Thermal Overload Relays

SACE Emax 2/ML Low-voltage air circuit breakers for naval applications

General information on handling and maintenance of SDC TM Solid Dielectric Capacitor Bushings

EMPAC Metal enclosed capacitor bank for wind applications

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Voltage limiting device HVL

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

Electronic overload relay EF65, EF96 and EF146

Electronic overload relays EF205 and EF370

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

NF31E-.. / NFZ31E-.. Contactor Relays AC / DC Operated - with Screw Terminals

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

INSTALLATION PRODUCTION TESTS

25 kv Apparatus Bushings

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

Product Brochure. Generator Circuit-Breaker HVR-EBCB For hydro or pump storage power plant

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Manufacturing Facility is ISO9001:2000. Welded Steel Pipe Conform to ASTM A53. Threads Conform to ASME B1.20.1

Thermal overload relay TF140DU and TF140DU-V1000

ABB cable glands SCG series Stainless Steel 316L, general purpose cable glands

2600T Series Pressure Transmitters Custom Linearization Table with ABB Asset Vision Basic

Thermal overload relay TF65 and TF96

Test report. Type VRLTC load tap changer VRLTC 1500A Type test summary report

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

Flush Mount AIN ALPHA Meters. General. Hardware Kit

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

Transformer bushings, type GOH. Technical guide

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance

MEDIUM VOLTAGE PRODUCT. KECA 80 C85 Current Sensor Instructions for installation, use and maintenance

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

ABB central inverters PVS to 2091 kva

LV Capacitors QCap-L series Capacitors for power factor correction

MEDIUM VOLTAGE PRODUCT. KECA 250 B1 Current Sensor Instructions for installation, use and maintenance

Modular Standardized Electrical and Control Solutions for Fast Track Projects

MEDIUM VOLTAGE PRODUCT. KECA 80 D85 Current Sensor Instructions for installation, use and maintenance

CERTIFIED TEST REPORT

AF / AF30Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF / AF16Z pole Contactors AC / DC Operated - with Screw Terminals

Effective November 2016 Supersedes September 1998 (S )

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Mini contactors B6, BC6 with 3 pole

A Member of the. Integrated Metering Technologies

Transcription:

Transformer components Low voltage bushings for pad-mounted distribution transformers Technical information guide ABB low voltage bushings terminate a transformer s internal low voltage leads at the tank wall and provide a standard threaded stud for connections to the external low voltage circuit. Description ABB low voltage bushings are molded from a high temperature, glass-reinforced nylon resin system (Dupont Zytel HTN ). The nylon body is molded around a copper stud. The copper stud is terminated at one end with a spade terminal which is used to make the internal transformer connections. The other end of the stud is threaded to accept various connectors which are used to connect to the external low voltage circuit. The bushings are available in two stud sizes: 0.625 inch diameter and 1.00 inch diameter. Ratings Conductor Diameter (inches) Voltage Rating (volts) BIL Rating (kv) Current Rating (amperes) 0.625 600 30 600 1.00 600 30 1400 Test proven quality and reliability The ABB low voltage bushings have passed a series of design tests which were designed to verify ratings, suitability for use on pad-mounted distribution transformers, and long term reliability. 1) Seal integrity test 2) Full wave impulse test 3) Low frequency voltage withstand test 4) Conductor stud torque test 5) Cantilever load test 6) Thermal cycle test 7) Temperature rise test In addition to the design testing, the following routine production tests are done on an audit basis: 1) Dimension check 2) Visual inspection 3) Leak test Interchangeable The ABB low voltage bushings have been designed to be dimensionally interchangeable with the majority of similar bushings available on the market. Included in these interchangeable dimensions are: the bolt circle for the integral mounting flange, the tank wall hole size, the conductor stud diameter, and the external thread size. Compact design The bushings have been designed to minimize the space required inside of the transformer. For both bushings, the dimension from the inside surface of the tank wall to the end of the stud has been reduced. This reduction may allow the transformer designer to reduce the volume of the transformer tank to save both oil and steel.

Technical information Integral flange The mounting flange on the bushings is molded as an integral part of the bushing. This eliminates the need for a separate mounting flange and, in the case of a metal mounting flange, the associated electrical losses created by the induced current in the flange. Compression limited gasket designs The integral flange of the bushing has a molded-in gasket seat to ensure proper gasket location and compression during mounting. The gasket surfaces provide controlled compression and containment of the highly resilient Buna-N gasket. Conductor length Bushings are available with a standard or extended length thread design. Proven nylon body These ABB bushings are molded from a glass-reinforced, high temperature nylon resin (Dupont Zytel HTN). The Zytel HTN resin is a highly reliable thermoplastic that fulfills the required application needs for strength, temperature stability and low moisture absorption. The resin system retains its mechanical and electrical properties in the high temperature environment associated with pad-mounted distribution transformer applications. Certification To certify the product ratings, production samples of the bushings were tested. The tests were conducted in accordance with ANSI/IEEE standards where applicable. Design tests The design tests were divided into (3) three categories: 1) Dielectric tests (impulse test and 60 Hz withstand test) 2) Mechanical strength tests (leak test, stud interface strength test and cantilever test) 3) Environmental tests (thermal cycle test, oil compatibility test) Dielectric tests Impulse test The purpose of this test is to verify the impulse withstand of the bushing. Sample bushings were subjected to three positive and three negative full wave impulses. The voltage impulse used was the standard 1.2 x 50 µs wave having the crest value of the specified voltage. The withstand voltage level of the bushings are well above the BIL rating of 30 kv. Samples successfully passed 36 kv test levels. Samples also successfully passed chopped wave tests well above the rating of 36kV. Low frequency / 60 Hz withstand test The purpose of the low frequency withstand test is to verify the integrity of the insulation structure of the bushing at operating frequency. Bushing samples were tested at 12 kv for one minute and then allowed to rest for one minute. They were then retested for another minute. All samples passed this test. Mechanical strength tests Leak tests The purpose of the leak test is to ensure that, over the life of the bushing, no leak will develop between the copper stud and the nylon resin body. The bushings were tested using a helium leak detector. The sensitivity of the helium leak detector is 1 x 10-5 atm cc/sec. The bushings were attached to a leak test fixture which mates the bushing such that any leak will be detected if helium passes into the detector through the bushing. All bushings passed with no indication of leaks. Stud interface strength test The purpose of this test is to verify that no damage will result when terminals are connected or removed from the bushings. The bushings were mounted in a manner simulating a typical transformer installation, then a nut was threaded onto the copper stud and 50 foot-pounds of torque was applied. For the 0.625 inch diameter copper stud bushing, the stud will fail before the 50 foot-pound level is reached. For the 1.00 inch diameter copper stud bushing, the 50 foot-pound torque test was repeated 20 times. Finally, the bushings were leak tested to verify that the seal between the copper stud and the nylon resin body was not damaged. Both the 0.625 and 1.00 inch low voltage bushings successfully passed this test. Cantilever test This test demonstrates the ability of the bushing to withstand the stresses generated when attaching a lead to the conductor. With the bushings mounted in a manner to simulate its application on a transformer, an extension was threaded onto the bushing stud and a load applied until failure. The 0.625 inch bushing was mounted so that one of the mounting holes is at the 6 o clock position. Then a cantilever load was applied, resulting in the stud yielding before the bushing body failed. The 1.00 inch bushing withstood 280 foot-pounds when mounted with one of mounting holes in the 12 o clock position and withstood 375 foot-pounds when mounted with one of the mounting holes in the 6 o clock position. 2 Low voltage bushings for pad-mounted distribution transformers Technical information

Technical information Environmental test Thermal cycle test The purpose of the thermal cycle test is to verify the integrity of materials used in the bushing over the expected service life of the bushing. The previously leak tested bushings were subjected to 20 thermal cycles in air. Each thermal cycle consists of the following: 1) 1-hour transition to 140 C 2) 2-hour hold at 140 C 3) 1-hour transition to -40 C 4) 1-hour hold at -40 C Oil compatibility test The purpose of this test is to verify that the bushing does not have any damaging effects on the properties of the oil when the bushing is submerged in the transformer oil. The bushing passes the standard oil compatibility test. Technical information Low voltage bushings for pad-mounted distribution transformers 3

For more information please contact: ABB Inc. 1128 South Cavalier Drive Alamo, Tennessee 38001, USA Phone: +1 731 696 5561 Main: +1 800 955 8399 Fax: +1 731 696 5377 Email: alamo.customer_service@us.abb.com Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. The information, recommendations, description and safety notations in this document are based on our experience and judgment. This information should not be considered all inclusive or covering all contingencies. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. If further information is required, ABB Inc. should be consulted. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction in whole or in parts is forbidden without prior written consent from ABB Inc. 1ZUA2761-600 rev. 4 www.abb.com/electricalcomponents With regard to purchase orders, the agreed particulars shall prevail. In no event will ABB Inc. be responsible to the user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever including but not limited to use of equipment, plant or power system, cost of capital, profits or revenues, cost of replacement power, additional expenses in the use of existing power facilities, or claims against the user by its customers resulting from the use of the information, recommendations, description and safety notations contained herein. Copyright 2011 ABB. All rights reserved.