TECHNICAL SPECIFICATIONS 40, 60, 80 kva (three phase input and output) GENERAL DATA Output Rated Power kva 40 60 80 Output Power Factor 0.8 Topology Technology Construction Parallel Configuration Redundant n+1 Capacity Upgrade Double Conversion AC-AC Efficiency On-Line, Double Conversion Second Generation, Tansformerless Parallelable Load sharing, Decentralized control High reliability, no limitation of paralleling Add your power as you grow (no limitation) 100%/75%/50%/25% Linear Load (cosф=0.8) % 96 / 96 / 95 / 92 100%/75%/50%/25% Linear Load (Resistive cosф=1) % 95 / 95 / 93.5 / 90 100%/75%/50%/25% Non-Linear Load (EN50091-1) % 93.5/93/91 /90 Eco-mode efficiency (load on by-pass) at 100% load % 98 Heat Dissipation With 100% Load (cos ф =0.8ind) w 1350 2000 2700 Heat Dissipation With 100% Load (Resistive cos ф =1) w 1700 2500 3400 Heat Dissipation With 100% Non-linear Load (EN50091-1) w 2300 3400 4500 Necessary Cooling Air (25-30 C) m 3 /h 510 770 1020 Audible Noise with 100% Load dba 56 58 70 Audible Noise with 75% Load dba 52 54 58 Ambient Temperature for UPS C 0-40 Ambient Temperature for Batteries (recommended) C 20-25 Storage Temperature C 5-50 Battery Storage Time at Ambient Temperature Max. 6 months Cooling Fan-assisted Relative Air-humidity Max. 95% at 20 C Standards EN 50091, part 1,2 and 3 Transportation Palette Provided with UPS Accessibility Front and rear for service and maintenance Positioning Input and Output Power Cabling Relay contacts RS 232 Interface Input Terminals Min. 60cm from rear From front and bottom For remote signalling and automatic computer shutdown For monitoring and integration in network management EMERGENCY OFF (Normally closed) GEN-ON (Normally open) BATTERY TEMPERATURE SENSOR /TD Page 1
RECTIFIER DATA Input Voltage BATTERY DATA INVERTER DATA BYPASS DATEN V 3X380/220V+N, 3x400V/230V+N, 3X415/240V+N Input Voltage Window V (%) 400V/230V (-25% and +15%) Other Input Voltages On request Input Frequency Hz 35-65 Input Power Factor 0.98 Input Current Form Inrush Current Sinewave : THDi =7% standard (THDi =5% with optional filter) Soft start Model kva 40 60 80 Input Power with charged battery and rated output power kva 34 50 64 Max. Input Power with battery charge and rated output power kva 48 74 96 Maximum Battery Charger Current (standard) Battery Charging Curve IU (DIN 41773) Temperature Controlled Battery Charger Battery Charger Ripple Battery Test Battery Type Variable Number of 12V Battery Blocks 15A Yes No ripples Automatic and periodic (adjustable) Lead-acid, Maintenance-free and NiCd 40-50 blocks Standardconfiguration 48 blocks Output Rated Power KVA 40 60 80 Output Rated Voltage V 3x380/220V, 3X400/230V, 3x415/240V Output Power Factor 0.8 Output Voltage Tolerance - Static % + /- 1 - Load Jump (0-100%, 100-0%) % + /- 4 - Distortion With Linear Load % + /- 1 - Distortion With Non-linear Load % + / - 3 (according to EN 50091-1) Recovery Time After Load Jump (0-100%, 100-0%) msec 20 Permissible Unbalanced Load % 100% (all 3 phases regulated independently) Output waveform sinewave Output Frequency Hz 50 or 60 Output Frequency Tolerance - Free-running, Quartz Oscillator % + /- 0.1 - Synchronized with mains (adjustable) % + /- 4 Overload Capability % 125 during 10min. and 150 during 1min. Crest - Factor 3: 1 Overload Capability 200% 5min, 1000% 10ms Transfertime Inverter - Bypass Bypass input voltag minimum Manuell Bypass 0 ms 190 V Yes /TD Page 2
POWER MANAGEMENT DISPLAY (PMD) The user-friendly PMD consists of three parts the MIMIC DIAGRAM, CONTROL KEYS and LCD that provides the necessary monitoring information about the UPS. MIMIC DIAGRAM The mimic diagram serves to give the general status of the UPS. The LED-indicators show the power flow status and in the event of mains failure or load transfer from inverter to bypass and vice-versa the corresponding LEDindicators will change colour from green (normal) to red (warning). The LED's LINE 1 (rectifier) and LINE 2 (bypass) indicate the availability of the mains power supply. The LED's INVERTER and BYPASS if green indicate which of the two are supplying power to the critical load. When the LED-indicator BATTERY is lit it means that the battery due to mains failure is supplying the load. The LED-indicator ALARM is a visual indication of any internal or external alarm condition. At the same time the audible alarm will be activated. PUSHBUTTONS The pushbuttons serve to manage the UPS by performing commands. The 2xON/OFF pushbuttons serve to startup or shutdown the UPS if pressed simultaneously. The pushbuttons UP and DOWN allow working through the PMD-menu. The RESET pushbutton serves to cancel the audible alarm in the event of a disturbance. If the alarm condition was oniy transient the LED-indicator ALARM would also extinguish otherwise it will remain on (red). DISPLAY The 2 x 20 character LCD simplifies the communication with the UPS. The menu driven LCD enables the access to the EVENT REGISTER, or to monitor the input and output U, I, f, P, Autonomy Time and other Measurement's, to perform commands like start-up and shut-down of INVERTER or load transfer from INVERTER to BYPASS and vice-versa and finally it serves for the DIAGNOSIS (SERVICE MODE) for adjustments and testing (for more details see the USER MANUAL of PX60). ON/ OFF ON/ OFF Power Management Display (PMD) OPTIONALS Extended Battery Autonomies Remote Signalling Panel (RSP) Temperature-depending Battery Charger Parallel Configuration LanChute Software SNMP - Card/Adapter Input or Output Isolation Transformer In matching battery frames BX50ms/c and BX50ms/u For UPS-Status indication Batteries are charged depending on temperature An unlimited number of units may be paralleled for redundancy or capacity upgrade For automatic shut-down and monitoring For network management and remote monitoring For special voltages or for galvanic isolation Input -filter For input THDi< 5% /TD Page 3
MECHANICAL CHARACTERISTICS PX60 M 40-80kVA MODEL kva 40 60 80 Dimensions (WxHxD) mm 580 x 1400 x 750 580 x 1800 x 750 Protection Degree IP 20 Ventilation Fan assisted Colour RAL 9002 Foot Print m 2 0.435 /TD Page 4
PX60 Midi 80kVA (Depth 750mm) РХ60 Midi 40 and 60kVA (Depth 750mm) Battery Cabinet BX50ms/u Battery Cabinet BX50ms/c 1800 1400 Powerbox Тур Description Battery Partlist Size (WxHxD) Weight Power/Backup in mm in Kg 40 KVA /40/0 40 KVA, 0 Min /40/0 580x1400x750 170,0 /40/9 40 KVA, 9 Min 40 x 24 Ah /40/0 + BX50ms/c/a (580+580)x1400x750 680,0 /40/22 40 KVA, 22 Min 2 x 40 x 24 Ah /40/0 + BX50ms/c/b (580+580)x1400x750 1040,0 /40/38 40 KVA, 38 Min 3x40x24 Ah /40/0 + BX50ms/u/c 580x1400x750+ 1440,0 580*1800*750 60 KVA /60/0 60 KVA, 0 Min /60/0 580x1400x750 190,0 /60/6 60 KVA, 6 Min 40x24 Ah /60/0 + BX50ms/c/a (580+580)x1400x750 700,0 /60/13 60 KVA, 13 Min 2 x 40 x 24 Ah /60/0 + BX50ms/c/b (580+580)x1400x750 1060,0 /60/23 60 KVA, 23 Min 3 x 40 x 24 Ah /60/0 + BX50ms/u/c 580x1400x750 + 1460,0 580*1800*750 80 KVA /80/0 80 KVA, 0 Min /80/0 580x1800x750 220,0 /80/9 80 KVA, 9 Min 2 x 40 x 24 Ah /80/0 + BX50ms/u/b 580+580x1800x750 1130,0 /80/15 80 KVA, 15 Min 3x40x24 Ah /80/0 + BX50ms/u/c 580+580x1800x750 1490,0 /80/23 80 KVA, 23 Min 4 x 40 x 24 Ah /80/0 + 2*BX50ms/u/b 580+580x1800x750 2040,0 /TD Page 5
Block Diaqram STANDARD VERSION (SINGLE INPUT FEED) VERSION ON REQUEST (DUAL INPUT FEED) MAINS (3X380V/220V, 3x400/230V,3x415/240V Fuse В Cable В Fuse С Cable С MAINS (3X380V/220V, 3x400/230V,3x415/240V Slim Frame Mainten. Bypass Slim Frame Mainten. Bypass Cable D Cable D Load Cable Sections and Fuse Ratings recommended by European standards. Alternatively, local standards to be respected STANDARD VERSION (SINGLE FEED INPUT) Load VERSION ON REQUEST (DUAL FEED INPUT) Power (kva) Fuse A (Agl/CB) Cable A Cable D Power (kva) Fuse В (Agl/CB) Cable В Fuse С Cable С Cable D 40 3 x 80 5 x 25 5 x 25 40 3x80 5 x 25 3 x 80 5 x 25 5 x 25 60 3 x 100 5 x 35 5 x 35 60 3 x 100 5 x 35 3 x 100 5 x 35 5 x 35 80 3 x 125 5 x 50 5 x 50 80 3 x125 5 x 50 3 x 125 5 x 50 5 x 50 The UPS's may be paralleled for power capacity upgrade or redundancy, horizontally without any limitation of the number of paralleled UPS's. UPS 1 UPS 2 UPS n /TD Page 6