NORTHERN HEAT PUMP INC. Specification Manual Ground Source Heat Pumps XTERRA SERIES FORCAIR RAVE/ RAHE 36 THRU 70 FORCAIR2 RTVE/ RTHE 30 THRU 60 AQUA2 RAWE/CDWE 36 THRU 140 SOURC3 RMVE/ RMHE 36 THRU 70 Rev 9 Mar-27-09
DESCRIPTIONS RESIDENTIAL MODEL # DESCRIPTION RA VE 502 - C 1 3 1 UNIT DESIGNATION R=RESIDENTIAL UNIT TYPE A=STANDARD M=MULTI D=DUAL COMPRESSOR S=SPECIAL W=HEAT ONLY T=TWO SPEED P=MINI UNIT STYLE W=HYDRONIC V=VERTICAL D=DOWNFLOW H=HORIZONTAL S=SPLIT REFRIGERANT TYPE E=R410A REFRIGERANT F=R22 REFRIGERANT NORMAL SIZE X 1000 BTU/H DESUPERHEATER OPTION 1=NONE 2=PARTIAL DESUPERHEATER 3=FULL TIME POWER SUPPLY 1=208/230V 1Ph 2=208/230V 3Ph 3=575V 3Ph 4=460/480V 3PH 5=220/240V 1PH 50HZ 6=380V 3PH 50HZ BLOWER TYPE 1=None 2=Standard PSC 3 Speed Blower 3=ECM Blower CONFIGURATION 1=LEFT SIDE RETURN (STD) 2=RIGHT SIDE RETURN 3=NONE HEAT EXCHANGER C=PER F=S.S. FLATPLATE H=CUPRO HYDRONIC LOOP N=CUPRO NICKEL SERIAL # DESCRIPTION XL 08 01 A 1000 A BILL OF MFG YEAR OF MFG MONTH OF MFG MFG LOCATION A=SOUTH RAILWAY PLANT SEQUENTIAL NUMBER FUTURE USE A=LINE NUMBER
DESCRIPTIONS COMMERCIAL MODEL # DESCRIPTION CD WE 114 2 - C 1 1 UNIT DESIGNATION C=COMMERCIAL UNIT TYPE A=STANDARD M=MULTI D=DUAL COMPRESSOR S=SPECIAL W=HEAT ONLY T=TWO SPEED P=MINI POWER SUPPLY 1=208/230V 1Ph 2=208/230V 3Ph 3=575V 3Ph 4=460/480V 3PH 5=220/240V 1PH 50HZ 6=380V 3PH 50HZ BLOWER TYPE 1=None 2=Standard PSC 3 Speed Blower 3=ECM Blower UNIT STYLE W=HYDRONIC V=VERTICAL D=DOWNFLOW H=HORIZONTAL S=SPLIT REFRIGERANT TYPE E=R410A REFRIGERANT F=R22 REFRIGERANT HEAT EXCHANGER C=PER F=S.S. FLATPLATE H=CUPRO HYDRONIC LOOP N=CUPRO NICKEL NORMAL SIZE X 1000 BTU/H DESUPERHEATER OPTION 1=NONE 2=PARTIAL DESUPERHEATER 3=FULL TIME SERIAL # DESCRIPTION XL 08 01 A 1000 A BILL OF MFG YEAR OF MFG MONTH OF MFG MFG LOCATION A=SOUTH RAILWAY PLANT SEQUENTIAL NUMBER FUTURE USE A=LINE NUMBER
Single Compressor Single Capacity RAVE 36 Data Sheet Electrical Specification Mechanical Specifications Compressor Blower Loop Pump Without pumps Refrigerant: R-410A Voltage Elect. Total Min. Max. Fuse/ Air Coil Symbol RLA LRA FLA HP FLA HP FLA Ampac Breaker Square Rows Tube Fins/ 208/230-1-60 1 20 112 4.3.5 2.2 1/3 24.3 29.3 40 Feet Deep O.D. Inch 575-3-60 3 5.7 34.1 4.3.5 - - 10 11.4 15 2.78 5 0.375 12 *HACR - type breaker per NEC Water Coil Type Working Press Canister 600 psig Blower Size Comp. Type 9x9 Scroll Blower Performance Net Weight Shipping Weight Static 305 355 0.10 0.20 0.25 0.30 0.35 0.40 0.50 Pressure CFM 1200 1100 1060 1020 975 950 885 ISO 13256-1 Performance Data Rated at 1100 CFM and 7.0 GPM Ground Water Ground Loop Capacity Capacity Capacity Capacity 35,300 19.9 34,700 4.3 46,600 13.3 31,100 3.0 Capacity Data All performance at 1100 CFM and 7.0 GPM Total Total Power Fluid Air Capacity Fluid Air Capacity Power Temp ( o input Temp. F) (BtuH) Temp. Temp (BtuH) input t (kw) (kw) Stage 1 Stage 1 25 32000 2.1 4.4 25 27900 1.8 22.7 30 33400 2.1 4.6 30 27100 1.8 21.8 40 34000 2.2 4.5 40 26900 1.8 21.0 50 37900 2.2 5.0 50 26200 1.8 20.2 60 60 o 41600 2.4 5.1 60 60 o 25300 2.0 17.6 70 46100 2.5 5.4 70 24800 2.2 14.3 80 47300 2.7 5.2 80 25900 2.4 12.6 90 48100 2.8 5.1 90 27000 2.7 9.2 25 31400 2.3 2.7 25 34400 1.9 21.3 30 32700 2.3 2.8 30 33500 1.9 20.5 40 33400 2.4 3.2 40 33200 2.0 19.8 50 37100 2.4 3.6 50 32300 2.0 19.0 60 68 o 40800 2.6 4.3 60 68 o 31200 2.2 16.6 70 45200 2.7 4.4 70 30600 2.3 13.4 80 46400 2.9 4.3 80 32000 2.6 11.9 90 47200 3.0 5.2 90 33300 2.9 8.7 25 29200 2.4 3.6 25 43600 2.1 27 30 30400 2.4 3.8 30 42400 2.1 26 40 31000 2.5 3.7 40 42000 2.2 25 50 34500 2.5 4.1 50 40900 2.2 24 60 80 o 37900 2.7 4.2 60 80 o 39500 2.4 21 70 42000 2.8 4.4 70 38700 2.6 17 80 43200 3.0 4.3 80 40500 2.9 15 90 43900 3.1 4.2 90 41200 3.2 11 NORTHERN HEAT PUMP 3-201 South Railway Ave. Winkler, Manitoba R6W 1J9, CANADA Northern Heat Pump Water Source Heat Pumps Phone (204) 325-9772 Fax (204) 325-4954
Single Compressor Single Capacity Data Sheet RAVE 50 Electrical Specification Compressor Blower Loop Pump Without Pumps Voltage Elect. Total Min. Max. Fuse/ Symbol RLA LRA FLA* HP* FLA HP FLA Ampac. Breaker 208/230-1-60 1 30 145 4.3.75 2.2 0.3 34.3 41.8 60 Blower Performance Static Pressure 0.10 0.20 0.25 0.30 0.35 0.40 0.50 CFM 1640 1550 1495 1440 1390 1360 1290 Mechanical Specifications Refrigerant: R-410A Air Coil Square Rows Tube Fins/ Feet Deep O.D. Inch 3.88 5 0.375 12 Water Coil Type Working Press Canister 600 psig Blower Size Comp. Type 10 x 10 Scroll Net WEIGHT Shipping Weight 320 340 ISO 13256-1 Performance Data Rated at 1550 CFM and 13.0GPM Ground Water Ground Loop Capacity Capacity Capacity Capacity 48,900 20.2 45,600 4.1 47,000 11.5 36,000 2.9 Capacity Data All performance rated at 1550 CFM and 10.0 GPM Total Total Power Fluid Air Capacity Fluid Air Capacity Power input Temp ( o Temp. F) (BtuH) Temp. Temp (BtuH) input (kw) (kw) Stage 1 Stage 1 25 43500 2.6 4.9 25 36400 1.6 23.4 30 45400 2.8 4.7 30 35400 1.6 22.6 40 46300 3.0 4.5 40 35100 1.7 21.0 50 51600 3.2 4.7 50 34200 1.9 18.3 60 60 o 56600 3.3 5.0 60 60 o 33000 2.0 16.5 70 62700 3.4 5.4 70 32400 2.4 13.5 80 64400 3.4 5.5 80 33800 3.0 11.1 90 65500 3.6 5.3 90 35300 3.9 9.1 25 42700 4.2 3.0 25 44900 2.0 22.0 30 44500 4.1 3.2 30 43700 2.1 21.2 40 45500 3.4 3.9 40 43300 2.2 19.7 50 50500 3.4 4.3 50 42200 2.4 17.2 60 68 o 55500 3.6 4.5 60 68 o 40700 2.6 15.5 68 61500 3.9 4.6 68 40000 3.2 12.7 80 63200 3.8 4.9 80 41800 4.0 10.5 90 64200 3.9 4.8 90 43500 5.1 8.6 25 39700 2.9 4.0 25 56900 2.0 27.8 30 41400 3.1 3.9 30 55400 2.1 26.9 40 42200 3.3 3.7 40 54800 2.2 25.0 50 47000 3.6 3.9 50 53400 2.5 21.8 60 80 o 51600 3.7 4.1 60 80 o 51600 2.6 19.6 70 57200 3.8 4.4 70 50500 3.2 16.0 80 58800 3.8 4.5 80 52900 4.0 13.2 90 59800 4.0 4.4 90 53800 5.0 10.8 NORTHERN HEAT PUMP 3-201 South Railway Ave. Winkler, Manitoba R6W 1J9, CANADA Northern Heat Pump Water Source Heat Pumps Phone (204) 325-9772 Fax (204) 325-4954
Single Compressor Single Capacity RAVE 57 Data Sheet Electrical Specification Mechanical Specifications Compressor Blower Loop Pump Without Pumps Refrigerant: R-410A Voltage Elect. Total Min. Max. Fuse/ Air Coil Symbol RLA LRA FLA HP FLA HP FLA Ampac Breaker* Square Rows Tube Fins/ 208/230-1-60 1 33.6 158 5.0 0.75 2.2 1/6(x2) 38.6 47.0 70 Feet Deep O.D. Inch 575-3-60 3 8.6 54 2.2 0.75 - - 10.8 13.6 15 3.88 5 0.375 12 *HACR - type breaker per NEC Water Coil Type Working Press Canister 600 psig Blower Size Comp. Type 10 x 10 Scroll Blower Performance Net Weight Shipping Weight Static 340 365 0.10 0.20 0.25 0.30 0.35 0.40 0.50 Pressure CFM 1800 1700 1640 1580 1525 1490 1410 ISO 13256-1 Performance Data Rated at 1700 CFM and 14.0GPM Ground Water Ground Loop Capacity Capacity Capacity Capacity 53,600 20.4 51,300 4.2 62,400 11.6 44,700 3.2 Capacity Data All performance rated at 1700 CFM and 13.0 GPM 57000 i Total l i Total l Power Power Fluid Air Capacity Fluid Air Capacity Temp ( o input Temp. Temp ( o input F) (BtuH) Temp. F) (BtuH) (kw) (kw) Stage 1 Stage 1 25 49600 3.2 4.5 25 43300 1.8 23.9 30 51800 3.5 4.4 30 42100 1.8 23.0 40 52700 3.7 4.2 40 41700 2.0 21.4 50 58800 4.0 4.4 50 40700 2.2 18.7 60 60 o 64500 4.1 4.6 60 60 o 39300 2.3 16.8 70 71500 4.2 5.0 70 38500 2.8 13.7 80 73400 4.2 5.1 80 40200 3.5 11.4 90 74600 4.4 4.9 90 41900 4.5 9.3 25 48700 5.1 2.8 25 53400 2.4 22.5 30 50700 5.0 3.0 30 52000 2.4 21.7 40 51800 4.2 3.6 40 51500 2.6 20.1 50 57600 4.2 4.0 50 50100 2.9 17.6 60 68 o 63300 4.4 4.2 60 68 o 48400 3.1 15.8 68 70100 4.8 4.3 68 47500 3.7 12.9 80 72000 4.6 4.6 80 49700 4.6 10.7 90 73200 4.8 4.5 90 51700 5.9 8.7 25 45300 3.6 3.7 25 67700 2.4 28.4 30 47200 3.8 3.6 30 65700 2.4 27.4 40 48100 4.1 3.4 40 65200 2.6 25.5 50 53500 4.4 3.6 50 63500 2.9 22.2 60 80 o 58800 4.5 3.8 60 80 o 61300 3.1 20.0 70 65200 4.7 4.1 70 6010 3.7 16.4 80 67000 4.7 4.2 80 62800 4.6 13.5 90 68100 4.9 4.0 90 63900 5.8 11.1 NORTHERN HEAT PUMP 3-201 South Railway Ave. Winkler, Manitoba R6W 1J9, CANADA Northern Heat Pump Water Source Heat Pumps Phone (204) 325-9772 Fax (204) 325-4954
Single Compressor Single Capacity RAVE 70 Data Sheet Electrical Specification Mechanical Specifications Compressor Blower Loop Pump Without Pumps Refrigerant: R-410A Voltage Elect. Min Max. Fuse/ Air Coil Symbol RLA LRA FLA* HP* FLA HP FLA Circuit Breaker Square Rows Tube Fins/ 208/230-1-60 1 35.7 148 5.75 2.2 0.3 40.7 49.6 70 Feet Deep O.D. Inch 3.88 5 0.375 12 Water Coil Type Working Press Brazed Plate 600 psig Blower Performance Blower Size Comp. Type Static 10 x 10 Scroll 0.10 0.20 0.25 0.30 0.35 0.40 0.50 Pressure Net WEIGHT Shipping Weight CFM 2020 1900 1840 1770 1710 1670 1580 355 380 ISO 13256-1 Performance Data Rated at 1900 CFM and 15.0GPM Ground Water Ground Loop Capacity Capacity Capacity Capacity 73,300 20.6 63,900 4.1 72,400 10.0 57,400 3.0 Capacity Data All performance rated at 1900 CFM and 15.0 GPM Total Power Total Fluid Air Capacity y Fluid Air Power Capacity Temp. Temp ( o input F) (BtuH) Temp. Temp input (kw) (kw) (BtuH) Stage 1 25 60395 3.6 4.9 25 53200 2.2 24.1 30 62900 3.9 4.7 30 51600 2.2 23.3 40 64100 4.2 4.5 40 51300 2.4 21.6 50 71500 4.5 4.7 50 49900 2.6 18.9 60 60 o 78500 4.6 5.0 60 60 o 48200 2.8 17.0 70 87000 4.8 5.4 70 47300 3.4 13.9 80 89200 4.7 5.5 80 49300 4.3 11.5 90 90700 5.0 5.3 90 51500 5.5 9.4 25 59200 5.8 3.0 25 65600 2.9 22.7 30 61700 5.6 3.2 30 63800 2.9 21.9 40 63000 4.7 3.9 40 63300 3.1 20.3 50 70000 4.8 4.3 50 61500 3.5 17.8 60 68 o 77000 5.0 4.5 60 70 o 59500 3.7 16.0 70 85300 5.4 4.6 68 58300 4.5 13.1 80 87500 5.2 4.9 80 61000 5.6 10.8 90 89000 5.4 4.8 90 63500 7.2 8.8 25 55100 4.0 4.0 25 83100 2.9 28.7 30 57300 4.3 3.9 30 80800 2.9 27.7 40 58500 4.6 3.7 40 80000 3.1 25.7 50 65100 5.0 3.9 50 77900 3.5 22.5 60 80 o 71500 5.1 4.1 60 80 o 75300 3.7 20.2 70 79200 5.3 4.4 70 73700 4.5 16.5 80 81500 5.3 4.5 80 77200 5.6 13.7 90 82800 5.6 4.4 90 78300 7.0 11.2 NORTHERN HEAT PUMP 3-201 South Railway Ave. Winkler, Manitoba R6W 1J9, CANADA Northern Heat Pump Water Source Heat Pumps Phone (204) 325-9772 Fax (204) 325-4954
Single Compressor Dual Capacity RTVE 30 Data Sheet Electrical Specification Compressor Blower Loop Pump Without Pumps Voltage Elect. Total Min. Max. Fuse/ Symbol RLA LRA FLA* HP* FLA HP FLA Ampac. Breaker 208/230-1-60 1 19 82 4.3.75 2.2 1/3 23.3 28.1 40 Blower Performance Static 0.10 0.20 0.25 0.30 0.35 0.40 0.50 Pressure CFM 1020 980 898 865 832 796 775 ARI 13256-1 FULL LOAD Performance Data Rated at 1000 CFM and 7.0 GPM PART LOAD Performance Data Rated at 700 CFM and 7.0 GPM Mechanical Specifications Refrigerant: R-410A Air Coil Square Rows Tube Fins/ Feet Deep O.D. Inch 3.88 5 0.375 12 Type Water Coil Working Press Canister 600 psig Blower Size Comp. Type 10 x 10 Scroll Net WEIGHT Shipping Weight 305 355 GWHP 50F EWT 60F EWT. Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 28,230 31,400 22.9 15.45 21,880 31,200 3.9 3.9 GLHP 32F EWT 77F EWT. PART LOAD 41F 60F Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 26,700 34,100 23.0 15.5 16,800 24,000 3.3 3.2 Capacity Data All performance at 700 CFM 1st stage; 980 CFM 2nd stage and 7.0 GPM Fluid Air Capacity input Capacity input Fluid Air Capacity input Capacity input Temp. Temp ( o F) (BtuH) (kw) (BtuH) (kw) Temp. Temp (BtuH) (kw) Stage 1 (BtuH) (kw) Stage 2 Stage 1 Stage 1 Stage 2 Stage 2 Stage 1 Stage 1 Stage 2 Stage 2 25 17200 1.3 13 4.0 40 22700 1.7 17 3.9 39 25 28400 1.0 10 27.6 6 35800 1.9 19 20.9 9 30 19000 1.4 4.1 25300 1.9 4.0 30 28100 1.1 26.5 35600 2.0 19.8 40 22000 1.5 4.3 29400 2.1 4.2 40 27700 1.1 25.5 33900 2.0 18.8 50 26100 1.7 4.4 34400 2.4 4.3 50 24300 1.0 24.4 29800 2.4 13.9 60 60 o 29100 1.9 4.6 38400 2.5 4.5 60 60 o 21400 1.0 22.3 25500 2.2 12.7 70 33300 2.0 4.8 44000 2.8 4.7 70 20900 1.1 19.5 22400 1.8 13.4 80 34600 2.1 4.8 45600 2.9 4.7 80 18500 1.1 16.7 20800 1.7 13.4 90 35000 2.0 5.1 46200 2.7 4.9 90 18000 1.3 13.6 20200 1.9 12.0 25 16800 1.3 3.9 19900 1.5 3.8 25 35000 1.1 33.1 44200 2.0 19.7 30 18800 1.4 4.0 21300 1.6 3.9 30 34700 1.0 33.1 44000 2.1 18.7 40 21900 1.5 4.2 25000 1.8 4.0 40 34200 1.1 32.3 41800 2.1 17.7 50 25600 1.8 4.3 28100 2.0 4.1 50 29900 1.0 29.1 36800 2.5 13.1 70 70 60 28600 1.9 4.5 35700 2.4 4.3 60 26400 1.0 26.5 31500 2.4 11.9 70 32700 2.1 4.7 39300 2.6 4.5 70 25800 1.1 23.2 27700 2.0 12.6 80 33900 2.1 4.7 43600 2.8 4.5 80 22900 1.2 19.9 25600 1.8 12.6 90 34300 2.0 4.9 46400 2.8 4.8 90 22200 1.4 16.2 24900 2.0 11.3 25 15600 1.2 3.8 16800 1.3 3.7 25 44300 0.9 32.8 56000 2.2 24.9 30 17500 1.3 3.9 19800 1.5 3.8 30 43900 0.9 31.5 55700 2.4 23.6 40 20300 1.4 4.1 23300 1.7 4.0 40 43300 1.0 30.3 52900 2.4 22.4 50 23800 1.7 4.2 27100 1.9 4.1 50 37900 1.2 29.1 46600 2.8 16.6 60 80 o 26600 1.8 4.4 33200 2.3 4.3 60 80 o 33400 1.3 26.5 39800 2.6 15.1 70 30400 1.9 4.6 36600 2.4 4.5 70 32700 1.4 23.2 35000 2.2 16.0 80 31500 2.0 4.6 40500 2.7 4.5 80 29000 1.5 19.9 32500 2.0 15.9 90 31900 1.9 4.9 43100 2.7 4.7 90 28100 1.7 16.2 31500 2.2 14.3 NORTHERN HEAT PUMP 3-201 South Railway Ave. Winkler, Manitoba R6W 1J9, CANADA Northern Heat Pump Water Source Heat Pumps Phone (204) 325-9772 Fax (204) 325-4954
Single Compressor Dual Capacity Data Sheet RTVE 40 Electrical Specification Compressor Blower Loop Pump Without Pumps Voltage Elect. Total Min. Max. Fuse/ Symbol RLA LRA FLA* HP* FLA HP FLA Ampac. Breaker 208/230-1-60 1 24 96 4.3.75 2.2 1/3 34.3 34.3 50 Blower Performance Static 0.10 0.20 0.25 0.30 0.35 0.40 0.50 Pressure CFM 1250 1200 1100 1060 1020 975 950 ARI 13256-1 FULL LOAD Performance Data Rated at 1300 CFM and 9.0 GPM PART LOAD Performance Data Rated at 1100 CFM and 9.0 GPM Mechanical Specifications Refrigerant: R-410A Air Coil Square Rows Tube Fins/ Feet Deep O.D. Inch 3.88 5 0.375 12 Water Coil Type Working Press Canister 600 psig Blower Size Comp. Type 10 x 10 Scroll Net WEIGHT Shipping Weight 325 375 GWHP 50F EWT 60F EWT. Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 36,550 45,920 23.4 19.0 28,900 43,770 3.8 3.8 GLHP 32F EWT 77F EWT. PART LOAD 41F 60F Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 37,500 46,200 20.6 14.7 28,000 34,600 3.6 3.2 Capacity Data All performance at 750 CFM 1st stage; 1200 CFM 2nd stage and 9.0 GPM Fluid Air Capacity input Capacity input Fluid Air Capacity input Capacity input Temp. Temp ( o F) (BtuH) (kw) (BtuH) (kw) Temp. Temp (BtuH) (kw) Stage 1 (BtuH) (kw) Stage 2 Stage 1 Stage 1 Stage 2 Stage 2 Stage 1 Stage 1 Stage 2 Stage 2 25 20400 1.5 4.0 28100 2.1 3.9 25 22000 0.8 27.6 27400 1.4 20.9 30 24500 1.7 4.1 33200 2.4 4.0 30 22000 0.8 26.5 27100 1.5 19.8 40 30100 21 2.1 43 4.3 39000 27 2.7 42 4.2 40 21500 08 0.8 25.55 26400 15 1.5 18.88 50 35200 2.3 4.4 45400 3.1 4.3 50 21000 0.9 24.4 25600 2.0 13.9 60 60 o 39300 2.5 4.6 55600 3.7 4.5 60 60 o 20300 0.9 22.3 24300 2.1 12.7 70 46700 2.9 4.8 61200 3.9 4.7 70 19600 1.0 19.5 24100 2.0 13.4 80 50000 3.1 4.8 67800 4.3 4.7 80 19000 1.1 16.7 25800 2.1 13.4 90 54600 3.1 5.1 72200 4.3 4.9 90 17400 1.3 13.6 27000 2.5 12.0 25 20000 1.5 3.9 27500 2.1 3.8 25 27100 0.8 32.9 33800 1.5 19.7 30 24000 1.8 4.0 32500 2.5 3.9 30 27000 0.8 33.0 33500 1.6 18.7 40 29500 2.1 4.2 38200 2.8 4.0 40 26500 0.8 32.1 32600 1.7 17.7 50 34500 2.4 4.3 44500 3.2 4.1 50 25900 0.9 28.9 31600 2.2 13.1 60 70 38500 2.5 4.5 54500 3.7 4.3 60 70 25000 1.0 26.3 30000 2.3 11.9 68 45800 2.9 4.7 60000 3.9 4.5 68 24200 1.1 23.0 29700 2.1 12.6 80 49000 3.1 4.7 66500 4.3 4.5 80 23400 1.2 19.7 31900 2.3 12.6 90 53500 3.2 4.9 70800 4.3 4.8 90 21500 1.3 16.1 33300 2.7 11.3 25 18600 1.4 3.8 25600 2.0 3.7 25 34400 0.9 32.8 42800 1.7 24.9 30 22300 1.7 3.9 30200 2.3 3.8 30 34200 0.9 31.5 42400 1.8 23.6 40 27400 1.9 4.1 35500 2.6 4.0 40 33600 1.0 30.3 41300 1.8 22.4 50 32100 2.2 4.2 41400 3.0 4.1 50 32800 1.2 29.1 40000 2.4 16.6 60 80 o 35800 2.4 4.4 50700 3.5 4.3 60 80 o 31700 1.2 26.5 38000 2.5 15.1 70 42600 2.7 4.6 55800 3.7 4.5 70 30600 1.3 23.2 37600 2.4 16.0 80 45600 2.9 4.6 61800 4.1 4.5 80 29700 1.5 19.9 40400 2.5 15.9 90 49800 3.0 4.9 65800 4.1 4.7 90 27200 1.7 16.2 42200 3.0 14.3 NORTHERN HEAT PUMP 3-201 South Railway Ave. Winkler, Manitoba R6W 1J9, CANADA Northern Heat Pump Water Source Heat Pumps Phone (204) 325-9772 Fax (204) 325-4954
Single Compressor Dual Capacity Data Sheet RTVE 51 Electrical Specification Compressor (x2) Blower Loop Pump Without Pumps Voltage Elect. Min. Symbol RLA LRA FLA* HP* FLA HP Ampac. Max. Fuse/ Breaker 208/230-1-60 1 26 118 4.3.75 2.2 0.3 36.8 50 Blower Performance Static 0.10 0.20 0.25 0.30 0.35 0.40 0.50 Pressure CFM 1600 1550 1400 1370 1320 1260 1225 ARI 13256-1 FULL LOAD Performance Data Rated at 1500 CFM and 11.0 GPM PART LOAD Performance Data Rated at 1100CFM and 11.0 GPM Mechanical Specifications Refrigerant: R-410A Air Coil Square Rows Tube Fins/ Feet Deep O.D. Inch 5 0.375 12 Type Net WEIGHT 340 Water Coil Working Press Canister 600 psig Blower Size Comp. Type 10 x 10 Scroll Shipping Weight 360 GWHP 50F EWT 60F EWT. Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 48,000 58,600 23.0 18.0 37,400 51,200 4.0 4.3 GLHP 32F EWT 77F EWT. PART LOAD 41F 60F Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 39,200 50,400 16.5 12.0 31,300 46,600 3.3 2.9 Capacity Data All performance at 1150 CFM 1st stage; 1600 CFM 2nd stage and 11.0 GPM Fluid Air Capacity input Air Capacity input Capacity input Capacity input Fluid Temp. Temp (BtuH) (kw) (BtuH) (kw) Temp. Temp (BtuH) (kw) Stage 1 (BtuH) (kw) Stage 2 Stage 1 Stage 1 Stage 2 Stage 2 Stage 1 Stage 1 Stage 2 Stage 2 25 25600 1.9 4.0 36400 2.8 3.8 25 27500 1.0 27.4 34200 1.8 20.8 30 28800 2.1 4.1 39800 3.0 3.9 30 27400 1.0 26.3 33900 1.9 19.7 40 32300 2.2 4.3 44900 3.2 4.1 40 26800 1.1 25.3 33000 1.9 18.7 50 33200 2.2 4.4 46800 3.3 4.2 50 26200 1.1 24.3 32000 2.6 13.8 60 60 o 37200 2.4 4.6 52100 3.5 4.4 60 60 o 25300 1.1 22.1 30400 2.7 12.6 70 41900 2.6 4.8 57000 3.6 4.6 70 24500 1.3 19.3 30100 2.5 13.3 80 48500 3.0 4.8 65900 4.2 4.6 80 23700 1.4 16.5 32300 2.7 13.2 90 50500 2.9 5.1 68700 4.2 4.8 90 21800 1.6 13.4 33700 3.1 11.8 25 25100 1.9 3.9 35600 2.8 3.7 25 33900 1.1 31.9 42200 1.9 19.6 30 28300 2.1 4.0 39000 3.0 3.8 30 33800 1.0 32.8 41900 2.0 18.5 40 31700 2.2 4.2 44000 3.3 3.9 40 33100 1.0 32.1 40800 2.1 17.6 50 32600 2.2 4.3 45900 3.4 4.0 50 32400 1.1 28.9 39500 2.7 13.0 60 70 36500 2.4 4.5 51000 3.6 4.2 60 70 31300 1.2 26.3 37500 2.9 11.8 70 41100 2.6 4.7 55800 3.7 4.4 70 30200 1.3 23.0 37200 2.7 12.5 80 47500 3.0 4.7 64600 4.4 4.3 80 29300 1.5 19.7 39900 2.9 12.5 90 49500 2.9 4.9 67300 4.2 4.7 90 26900 1.7 16.0 41600 3.4 11.1 25 23300 1.8 3.8 33100 2.7 3.6 25 43000 0.9 32.6 53500 2.2 24.8 30 26300 2.0 3.9 36300 2.9 3.7 30 42800 0.9 31.3 53000 2.3 23.5 40 29500 2.1 4.1 41000 3.1 3.9 40 42000 1.0 30.1 51600 2.3 22.3 50 30300 2.1 4.2 42700 3.1 4.0 50 41000 1.2 28.9 50000 3.0 16.5 60 80 o 33900 2.2 4.4 47500 3.3 4.2 60 80 o 39600 1.5 26.3 47500 3.2 15.0 70 38200 2.4 4.6 51900 3.5 4.4 70 38300 1.7 23.0 47000 3.0 15.9 80 44200 2.8 4.6 60100 4.0 4.4 80 37100 1.9 19.7 50500 3.2 15.8 90 46000 2.8 4.9 62600 4.0 4.6 90 34000 2.1 16.0 52700 3.7 14.1 NORTHERN HEAT PUMP 3-201 South Railway Ave. Winkler, Manitoba R6W 1J9, CANADA Northern Heat Pump Water Source Heat Pumps Phone (204) 325-9772 Fax (204) 325-4954
Single Compressor Dual Capacity Data Sheet RTVE 60 Electrical Specification Compressor (x2) Blower Loop Pump Voltage Elect. Symbol RLA LRA FLA* HP* FLA HP 208/230-1-60 1 32.1 148 5.75 2.2 0.3 Blower Performance Static 0.10 0.20 0.25 0.30 0.35 0.40 0.50 Pressure CFM 1760 1700 1540 1500 1450 1386 1350 ARI 13256-1 FULL LOAD Performance Data Rated at 1950 CFM and 13.0 GPM PART LOAD Performance Data Rated at 1350 CFM and 13.0 GPM GWHP 50F EWT 60F EWT. Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 54,700 67,200 21.1 16.7 59,600 67,900 3.6 4.2 GLHP 32F EWT 77F EWT. PART LOAD 41F 60F CO Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 Stage 1 Stage 2 26,800 60,300 17.7 9.3 38,600 52,200 3.4 3.3 Without Pumps Min. Ampac. Max. Fuse/ Breaker 45.1 70 Mechanical Specifications Refrigerant: R-410A Air Coil Square Rows Tube Fins/ Feet Deep O.D. Inch 3.88 5 0.375 12 Water Coil Type Working Press Canister 600 psig Blower Size Comp. Type 10 x 10 Scroll Net WEIGHT Shipping Weight 355 380 Capacity Data All performance at 1350 CFM 1st stage; 1900 CFM 2nd stage and 13.0 GPM Fluid Air Capacity input Capacity input Fluid Air Capacity Input Capacity input Temp. Temp ( o F) (BtuH) (kw) (BtuH) (kw) Temp. Temp (BtuH) (kw) stage 1 (BtuH) (kw) Stage 2 Stage 1 Stage 1 Stage 2 Stage 2 Stage 1 Stage 1 Stage 2 Stage 2 25 30770 2.3 4.0 43600 3.3 3.9 25 27500 1.0 27.4 34200 1.8 20.8 30 34600 2.5 4.1 47700 3.5 4.0 30 27400 1.0 26.3 33900 1.9 19.7 40 38800 2.6 4.3 53900 3.8 4.2 40 26800 1.1 25.3 33000 1.9 18.7 50 39800 2.7 4.4 56200 3.9 4.3 50 26200 1.1 24.3 32000 2.6 13.8 60 60 o 44600 2.8 4.6 62500 4.1 4.5 60 60 o 25300 1.1 22.1 30400 2.7 12.6 70 50300 3.1 4.8 68400 4.3 4.7 70 24500 1.3 19.3 30100 2.5 13.3 80 58100 3.5 4.8 79100 5.0 4.7 80 23700 1.4 16.5 32300 2.7 13.2 90 60600 3.5 5.1 82400 4.9 4.9 90 26100 1.9 13.4 40500 3.8 11.8 25 30100 2.3 3.9 42800 3.3 3.8 25 33900 1.1 31.9 42200 1.9 19.6 30 33900 2.5 4.0 46800 3.6 3.9 30 33800 1.0 32.8 41900 2.0 18.5 40 38000 2.7 4.2 52900 3.8 4.0 40 33100 1.0 32.1 40800 2.1 17.6 50 39000 2.7 4.3 55100 3.9 4.1 50 32400 1.1 28.9 39500 2.7 13.0 60 70 43700 2.9 4.5 61200 4.1 4.3 60 70 31300 1.2 26.3 37500 2.9 11.8 68 49300 3.1 4.7 67000 4.3 4.5 70 30200 1.3 23.0 37200 2.7 12.5 80 57000 3.6 4.7 77500 5.0 4.5 80 29300 1.5 19.7 39900 2.9 12.5 90 59400 3.5 4.9 80800 4.9 4.8 90 32200 2.0 16.0 50000 4.0 11.1 25 28000 2.1 3.8 39800 3.1 3.7 25 43000 0.9 32.6 53500 2.2 24.8 30 31500 2.3 3.9 43500 3.3 3.8 30 42800 0.9 31.3 53000 2.3 23.5 40 35400 2.5 4.1 49200 3.6 4.0 40 42000 1.0 30.1 51600 2.3 22.3 50 36300 2.5 4.2 51200 3.7 4.1 50 41000 1.2 28.9 50000 3.0 16.5 60 80 o 40700 2.7 4.4 56900 3.9 4.3 60 80 o 39600 1.5 26.3 47500 3.2 15.0 70 45800 2.9 4.6 62300 4.1 4.5 70 38300 1.7 23.0 47000 3.0 15.9 80 53000 3.4 4.6 72100 4.7 4.5 80 37100 1.9 19.7 50500 3.2 15.8 90 55200 3.3 4.9 75100 4.6 4.7 90 40800 2.6 16.0 63200 4.5 14.1 NORTHERN HEAT PUMP 3-201 South Railway Ave. Winkler, Manitoba R6W 1J9, CANADA Northern Heat Pump Water Source Heat Pumps Phone (204) 325-9772 Fax (204) 325-4954
Water to water heat pumps. XTERRA SERIES Stainless steel cabinet Insulated to reduce condensation Compressor is high efficiency scroll Safety devices to prevent compressor damage AQUA2 R410A RAWE 36 8 gpm loop 5 gpm hyd. 8 gpm loop 5 gpm hyd. LOOP HYD CAP LOOP HYD HR EWT LWT MBTU/hr KW EWT LWT MBTU/hr KW 70.0 25.7 1.7 4.4 35.0 31.5 1.6 19.7 85.0 25.6 1.8 4.2 40.0 33.4 1.6 20.8 25 100.0 25.5 2.1 3.6 50 45.0 35.3 1.6 21.8 110.0 25.4 2.3 3.3 50.0 36.6 1.6 22.3 115.0 25.3 2.5 3.0 55.0 37.9 1.7 22.7 120.0 25.2 3.1 2.4 35.0 32.1 1.9 17.1 70.0 28.3 1.6 5.1 40.0 34.1 1.9 18.2 85.0 27.6 1.4 4.7 60 45.0 36.2 1.9 19.3 30 100.0 27.3 2.0 4.0 50.0 37.7 1.9 19.8 110.0 27.1 2.2 3.6 55.0 39.1 1.9 20.3 115.0 27.0 2.4 3.3 35.0 32.8 2.3 14.4 120.0 26.6 3.0 2.6 40.0 34.9 2.2 15.6 70.0 31.0 1.6 5.7 70 45.0 37.1 2.2 16.8 85.0 29.5 1.7 5.2 50.0 38.7 2.2 17.3 35 100.0 29.1 2.0 4.4 55.0 40.4 2.3 17.8 110.0 28.7 2.1 4.0 Data subject to change without notice 115.0 28.7 2.3 3.6 120.0 27.9 2.8 2.9 70.0 32.9 1.5 6.4 85.0 31.4 1.6 5.6 40 100.0 31.0 1.9 4.7 110.0 30.5 2.1 4.3 115.0 30.5 2.3 3.9 120.0 29.7 2.8 3.2 70.0 36.8 1.5 7.0 85.0 37.7 1.8 6.1 50 100.0 37.1 2.1 5.1 110.0 36.5 2.3 4.7 115.0 35.9 2.5 4.2 120.0 34.8 3.0 3.4 Rated outside the scope of ARI AQUA2 R410A RAWE 50 11 gpm loop 8 gpm hyd. 11 gpm loop 8 gpm hyd. LOOP HYD CAP LOOP HYD CAP EWT LWT MBTU/hr KW EWT LWT MBTU/hr KW 70.0 38.7 2.6 4.4 35.0 39.6 2.1 19.3 85.0 38.8 2.9 3.9 40.0 42.3 2.1 20.4 25 100.0 38.7 3.4 3.3 50 45.0 44.9 2.1 21.5 110.0 38.5 4.0 2.9 50.0 46.8 2.1 21.9 115.0 38.4 4.2 2.7 55.0 48.6 2.2 22.3 120.0 37.9 4.6 2.4 35.0 39.3 2.4 16.7 70.0 40.8 2.3 5.1 40.0 42.3 2.4 17.9 85.0 40.7 2.7 4.4 60 45.0 45.2 2.4 19.0 30 100.0 40.6 3.2 3.7 50.0 47.2 2.4 19.5 110.0 40.4 3.8 3.2 55.0 49.3 2.5 19.9 115.0 40.3 3.9 3.0 35.0 39.1 2.8 14.1 120.0 39.8 4.5 2.6 40.0 42.3 2.8 15.3 70.0 47.0 2.5 5.6 70 45.0 45.4 2.8 16.5 85.0 44.9 2.7 4.9 50.0 47.7 2.8 17.0 35 100.0 44.3 3.2 4.1 55.0 50.0 2.9 17.5 110.0 44.0 3.5 3.7 Data subject to change without notice 115.0 43.7 3.8 3.4 120.0 42.3 4.4 2.9 70.0 50.0 2.4 6.2 85.0 47.7 2.6 5.4 40 100.0 47.1 3.1 4.5 110.0 46.8 3.4 4.1 115.0 46.4 3.7 3.7 120.0 45.0 4.3 3.1 70.0 56.4 2.4 6.8 85.0 57.3 2.8 5.9 50 100.0 56.4 3.4 4.9 110.0 55.5 3.7 4.5 115.0 54.6 4.0 4.0 120.0 53.0 4.7 3.3 Rated outside the scope of ARI
Water to water heat pumps. XTERRA SERIES Stainless steel cabinet Insulated to reduce condensation Compressor si high efficiency scroll Safety devices to prevent compressor damage AQUA2 R410A RAWE 57 13 gpm loop 9 gpm hyd. 13 gpm loop 9 gpm hyd. LOOP HYD CAP LOOP HYD HR EWT LWT MBTU/hr KW EWT LWT MBTU/hr KW 70.0 48.7 3.2 4.4 35.0 55.0 3.1 18.0 85.0 47.3 3.3 4.2 40.0 58.2 3.1 19.0 25 100.0 47.0 3.8 3.6 50 45.0 61.4 3.1 20.0 110.0 46.9 4.4 3.1 50.0 63.7 3.1 20.4 115.0 46.8 4.6 3.0 55.0 66.0 3.2 20.8 120.0 46.3 5.2 2.6 35.0 55.7 3.6 15.6 70.0 52.6 3.0 5.1 40.0 58.9 3.5 16.7 85.0 51.8 3.2 4.7 60 45.0 62.2 3.5 17.7 30 100.0 51.2 3.8 4.0 50.0 64.9 3.6 18.1 110.0 51.0 4.5 3.3 55.0 67.7 3.6 18.6 115.0 50.7 4.5 3.3 35.0 56.5 4.3 13.2 120.0 50.5 5.7 2.6 40.0 59.7 4.2 14.3 70.0 56.5 3.0 5.6 70 45.0 62.9 4.1 15.4 85.0 56.2 3.2 5.2 50.0 66.1 4.2 15.9 35 100.0 55.7 3.8 4.4 55.0 69.3 4.3 16.3 110.0 55.2 4.1 4.0 Data subject to change without notice 115.0 54.7 4.5 3.6 120.0 53.7 5.2 3.1 70.0 65.0 3.0 6.3 85.0 65.1 3.4 5.6 40 100.0 64.4 4.0 4.7 110.0 63.5 4.3 4.3 115.0 62.6 4.7 3.9 120.0 60.7 5.4 3.3 70.0 68.0 2.9 6.8 85.0 69.3 3.3 6.1 50 100.0 68.4 3.9 5.1 110.0 67.4 4.2 4.7 115.0 66.3 4.6 4.2 120.0 64.4 5.4 3.5 Rated outside the scope of ARI AQUA2 R410A RAWE 70 15 gpm loop 12 gpm hyd. 15 gpm loop 12 gpm hyd. LOOP HYD CAP LOOP HYD HR EWT LWT MBTU/hr KW EWT LWT MBTU/hr KW 70.0 54.7 3.6 4.4 35.0 55.0 3.3 16.6 85.0 54.3 4.1 3.9 40.0 58.2 3.3 17.6 25 100.0 54.0 4.7 3.4 50 45.0 61.5 3.3 18.5 110.0 53.8 5.5 2.9 50.0 63.8 3.4 18.9 115.0 53.6 5.6 2.8 55.0 66.0 3.4 19.2 120.0 53.2 6.5 2.4 35.0 56.3 3.9 14.4 70.0 59.6 3.4 5.1 40.0 59.6 3.9 15.2 85.0 59.5 4.0 4.4 60 45.0 62.8 3.9 16.1 30 100.0 58.8 4.6 3.8 50.0 65.6 3.9 16.6 110.0 58.4 5.4 3.2 55.0 68.4 4.0 17.2 115.0 58.2 5.5 3.1 35.0 57.7 4.7 12.2 120.0 57.7 6.5 2.6 40.0 60.9 4.7 12.9 70.0 64.5 3.4 5.6 70 45.0 64.2 4.7 13.7 85.0 64.7 3.9 4.9 50.0 67.4 4.7 14.4 35 100.0 63.9 4.5 4.1 55.0 70.7 4.7 15.1 110.0 63.3 3.9 3.8 Data subject to change without notice 115.0 62.8 5.4 3.4 120.0 61.6 6.3 2.9 70.0 74.8 3.5 6.2 85.0 75.0 4.1 5.4 40 100.0 73.9 4.8 4.5 110.0 72.9 5.2 4.1 115.0 71.8 5.7 3.7 120.0 69.8 6.7 3.1 70.0 78.9 3.4 6.8 85.0 79.9 4.0 5.9 50 100.0 78.5 4.7 4.9 110.0 77.3 5.1 4.5 115.0 76.1 5.6 4.0 120.0 73.9 6.6 3.3 Rated outside the scope of ARI
Water to water heat pumps. XTERRA SERIES Stainless steel cabinet Insulated to reduce condensation Compressors are high efficiency scroll Safety devices to prevent compressor damage AQUA2 R410A CDWE72 16 gpm loop 10 gpm hyd. 16 gpm loop 10 gpm hyd. LOOP HYD CAP LOOP HYD HR EWT LWT MBTU/hr KW EWT LWT MBTU/hr KW 70.0 51.4 3.4 4.4 35.0 63.0 3.2 19.7 85.0 51.2 3.6 4.2 40.0 66.8 3.2 20.8 25 100.0 51.0 4.2 3.6 50 45.0 70.6 3.2 21.8 110.0 50.8 4.6 3.3 50.0 73.2 3.2 22.3 115.0 50.6 5.0 3.0 55.0 75.8 3.4 22.7 120.0 50.4 6.2 2.4 35.0 64.2 3.8 17.1 70.0 56.6 3.2 5.1 40.0 68.2 3.8 18.2 85.0 55.2 2.8 4.7 60 45.0 72.4 3.8 19.3 30 100.0 54.6 4.0 4.0 50.0 75.4 3.8 19.8 110.0 54.2 4.4 3.6 55.0 78.2 3.8 20.3 115.0 54.0 4.8 3.3 35.0 65.6 4.6 14.4 120.0 53.2 6.0 2.6 40.0 69.8 4.4 15.6 70.0 62.0 3.2 5.7 70 45.0 74.2 4.4 16.8 85.0 59.0 3.4 5.2 50.0 77.4 4.4 17.3 35 100.0 58.2 4.0 4.4 55.0 80.8 4.6 17.8 110.0 57.4 4.2 4.0 Data subject to change without notice 115.0 57.4 4.6 3.6 120.0 55.8 5.6 2.9 70.0 65.8 3.0 6.4 85.0 62.8 3.2 5.6 40 100.0 62.0 3.8 4.7 110.0 61.0 4.2 4.3 115.0 61.0 4.6 3.9 120.0 59.4 5.6 3.2 70.0 73.6 3.0 7.0 85.0 75.4 3.6 6.1 50 100.0 74.2 4.2 5.1 110.0 73.0 4.6 4.7 115.0 71.8 5.0 4.2 120.0 00 69.6 6 6.0 60 3.4 Rated outside the scope of ARI AQUA2 R410A CDWE100 22 gpm loop 16 gpm hyd. 22 gpm loop 16 gpm hyd. LOOP HYD CAP LOOP HYD CAP EWT LWT MBTU/hr KW EWT LWT MBTU/hr KW 70.0 77.4 5.2 4.4 35.0 79.2 4.2 19.3 85.0 77.6 5.8 3.9 40.0 84.6 4.2 20.4 25 100.0 77.4 6.8 3.3 50 45.0 89.8 4.2 21.5 110.0 77.0 8.0 2.9 50.0 93.6 4.2 21.9 115.0 76.8 8.4 2.7 55.0 97.2 4.4 22.3 120.0 75.8 9.2 2.4 35.0 78.6 4.8 16.7 70.0 81.6 4.6 5.1 40.0 84.6 4.8 17.9 85.0 81.4 5.4 4.4 60 45.0 90.4 4.8 19.0 30 100.0 81.2 6.4 3.7 50.0 94.4 4.8 19.5 110.0 80.8 7.6 3.2 55.0 98.6 5.0 19.9 115.0 80.6 7.8 3.0 35.0 78.2 5.6 14.1 120.0 79.6 9.0 2.6 40.0 84.6 5.6 15.3 70.0 94.0 5.0 5.6 70 45.0 90.8 5.6 16.5 85.0 89.8 5.4 4.9 50.0 95.4 5.6 17.0 35 100.0 88.6 6.4 4.1 55.0 100.0 5.8 17.5 110.0 88.0 7.0 3.7 Data subject to change without notice 115.0 87.4 7.6 3.4 120.0 84.6 8.8 2.9 70.0 100.0 4.8 6.2 85.0 95.4 5.2 5.4 40 100.0 94.2 6.2 4.5 110.0 93.6 6.8 4.1 115.0 92.8 7.4 3.7 120.0 90.0 8.6 3.1 70.0 112.8 4.8 6.8 85.0 114.6 5.6 5.9 50 100.0 112.8 6.8 4.9 110.0 111.0 7.4 4.5 115.0 109.2 8.0 4.0 120.0 106.0 9.4 3.3 Rated outside the scope of ARI
Water to water heat pumps. XTERRA SERIES Stainless steel cabinet Insulated to reduce condensation Compressors are high efficiency scroll Safety devices to prevent compressor damage AQUA2 R410A CDWE 114 26 gpm loop 18 gpm hyd. 26 gpm loop 18 gpm hyd. LOOP HYD CAP LOOP HYD HR EWT LWT MBTU/hr KW EWT LWT MBTU/hr KW 70.0 96.4 6.4 4.4 35.0 110.0 6.1 18.0 85.0 93.6 6.5 4.2 40.0 116.4 6.1 19.0 25 100.0 93.1 7.6 3.6 50 45.0 122.9 6.1 20.0 110.0 92.9 8.6 3.1 50.0 127.4 6.2 20.4 115.0 92.7 9.1 3.0 55.0 132.0 6.3 20.8 120.0 91.7 10.3 2.6 35.0 111.4 7.1 15.6 70.0 104.2 6.0 5.1 40.0 117.9 7.1 16.7 85.0 102.5 6.4 4.7 60 45.0 124.3 7.0 17.7 30 100.0 101.4 7.5 4.0 50.0 129.8 7.2 18.1 110.0 100.9 9.0 3.3 55.0 135.3 7.3 18.6 115.0 100.4 8.9 3.3 35.0 112.9 8.6 13.2 120.0 100.0 11.3 2.6 40.0 119.3 8.3 14.3 70.0 111.9 5.9 5.6 70 45.0 125.8 8.2 15.4 85.0 111.3 6.3 5.2 50.0 132.2 8.3 15.9 35 100.0 110.3 7.4 4.4 55.0 138.6 8.5 16.3 110.0 109.3 8.1 4.0 Data subject to change without notice 115.0 108.3 8.8 3.6 120.0 106.2 10.2 3.1 70.0 129.0 6.0 6.3 85.0 128.9 6.7 5.6 40 100.0 127.6 7.9 4.7 110.0 125.8 8.5 4.3 115.0 124.0 9.3 3.9 120.0 120.1 10.8 3.3 70.0 134.6 5.8 6.8 85.0 137.3 6.6 6.1 50 100.0 135.5 7.8 5.1 110.0 133.4 8.4 4.7 115.0 131.3 9.2 4.2 120.0 127.4 10.7 3.5 Rated outside the scope of ARI AQUA2 R410A CDWE 140 30 gpm loop 24 gpm hyd. 30 gpm loop 24 gpm hyd. LOOP HYD CAP LOOP HYD HR EWT LWT MBTU/hr KW EWT LWT MBTU/hr KW 70.0 109.4 7.3 4.4 35.0 110.0 6.6 16.6 85.0 108.6 8.2 3.9 40.0 116.4 6.6 17.6 25 100.0 108.0 9.4 3.4 50 45.0 123.0 6.6 18.5 110.0 107.7 11.0 2.9 50.0 127.6 6.8 18.9 115.0 107.3 11.2 2.8 55.0 132.0 6.8 19.2 120.0 106.3 13.0 2.4 35.0 112.6 7.8 14.4 70.0 119.2 6.9 5.1 40.0 119.2 7.8 15.2 85.0 119.0 7.9 4.4 60 45.0 125.6 7.8 16.1 30 100.0 117.7 9.2 3.8 50.0 131.2 7.8 16.6 110.0 116.7 10.8 3.2 55.0 136.8 8.0 17.2 115.0 116.4 11.0 3.1 35.0 115.4 9.4 12.2 120.0 115.4 13.0 2.6 40.0 121.8 9.4 12.9 70.0 129.0 6.8 5.6 70 45.0 128.4 9.4 13.7 85.0 129.3 7.7 4.9 50.0 134.8 9.4 14.4 35 100.0 127.8 9.1 4.1 55.0 141.4 9.4 15.1 110.0 126.7 9.9 3.8 Data subject to change without notice 115.0 125.5 10.8 3.4 120.0 123.1 12.7 2.9 70.0 149.5 7.1 6.2 85.0 149.9 8.1 5.4 40 100.0 147.7 9.6 4.5 110.0 145.8 10.4 4.1 115.0 143.6 11.4 3.7 120.0 139.5 13.3 3.1 70.0 157.8 6.8 6.8 85.0 159.8 7.9 5.9 50 100.0 157.1 9.4 4.9 110.0 154.7 10.2 4.5 115.0 152.2 11.2 4.0 120.0 147.8 13.1 3.3 Rated outside the scope of ARI
Northern Heat Pump Electrical Data 410A Xterra Series, FORCAIR (V,H) & FORCAIR2 Without Pumps Voltage Compressor Fan Total Min. Max. Fuse Model (60 Hz) RLA LRA FLA FLA Ampac. Ckt Bkr. 16 208/230-1 10.0 48.0 2.0 12.0 14.5 20 22 208/230-1 15.0 61.0 2.0 17.0 20.8 30 23 208/230-1 15.0 61.0 2.0 17.0 20.8 30 24 208/230-1 14.3 64.0 2.0 16.3 19.9 30 30(2 stage) 208/230-1 19.0 82.0 4.3 23.3 28.1 40 30(2 stage) 208-3 13.5 88.0 4.3 17.8 21.2 30 31 208/230-1 18.6 79.0 4.3 22.9 27.6 40 36 208/230-1 20.7 105.0 4.3 24.3 29.3 40 575-3 5.7 34.0 4.3 10.0 11.4 15 40(2 stage) 208/230-1 24.0 96.0 4.3 28.3 34.3 50 44 208/230-1 25.7 134.0 4.3 30.0 36.4 50 50 208/230-1 30.0 145.0 4.3 34.3 41.8 60 575-3 6.8 40.0 4.3 10.1 12.8 15 51(2 stage) 208/230-1 29.4 134.0 4.3 33.7 41.1 50 57 208/230-1 33.6 158.0 5.0 38.6 47.0 70 575-3 8.6 54.0 5.0 13.6 15.8 15 60(2 stage) 208/230-1 32.1 148.0 5.0 37.1 45.1 70 70 208/230-1 35.7 148.0 5.0 40.7 49.6 70 Xterra Series AQUA2 & AQUA3 Without Pumps Voltage Compressor Pump/s Total Min. Max. Fuse Model (60 Hz) RLA LRA FLA FLA Ampac. Ckt Bkr. 24 208/230-1 14.3 64.0 2.2 16.5 20.1 30 36 208/230-1 20.7 105.0 2.2 22.9 28.1 40 575-3 5.7 34.0 2.2 7.9 9.3 15 50 208/230-1 30.0 145.0 2.2 32.2 39.7 60 575-3 6.8 40.0 2.2 10.1 10.7 15 57 208/230-1 33.6 158.0 4.4 38.0 46.4 70 575-3 8.5 54.0 4.4 12.9 15.0 15 70 208/230-1 35.7 148.0 4.4 40.1 49.0 70 Dual 72 208/230-1 20.7 105.0 4.3 24.3 29.3 40 208/230-3 15.0 88.0 4.3 19.3 23.1 30 575-3 5.7 34.0 4.3 10.0 11.4 15 Dual 100 208/230-1 30.0 145.0 4.3 34.3 41.8 60 208/230-3 19.6 123.0 4.3 23.9 28.8 40 575-3 6.8 40.0 4.3 11.1 12.8 15 Dual 114 208/230-1 33.6 158.0 5.0 38.6 47.0 70 208/230-3 22.9 155.0 5.0 27.9 33.6 50 575-3 8.5 54.0 5.0 13.5 15.6 15 Dual 140 208/230-1 35.7 148.0 5.0 40.7 49.6 70 208/230-3 25.0 149.0 5.0 30.0 36.3 50 575-3 8.6 54.0 5.0 13.6 15.8 15 Xterra Series SOURC3 1/3 HP Without Pumps Voltage Compressor Pump Fan Total Min. Max. Fuse Model (60 Hz) RLA LRA FLA FLA FLA Ampac. Ckt Bkr. 36 208/230-1 20.0 112.0 2.2 4.3 24.3 29.3 40 575-3 5.7 34.1 2.2 4.3 38.4 46.9 15 50 208/230-1 30.0 145.0 2.2 4.3 34.3 41.8 60 575-3 6.8 40.0 2.2 4.3 11.1 10.7 15 57 208/230-1 33.6 172.0 4.4 5.0 38.6 47.0 70 575-3 8.6 54.0 4.4 5.0 59.0 15.2 15 70 208/230-1 35.7 148.0 4.4 5.0 40.7 49.6 70 Due to continuing product improvements data may change without notice. CIRCUIT BREAKER OPTIONS - 15, 20, 30, 40, 50, 60, 70, 90, 100
Fan Performance Data Xterra Series, FORCAIR (VH), Hydronic & SOURC 3 UNIT FAN EXTERNAL STATIC PRESSURE-IN WG Airflow Correction Factors SIZE SPEED 0.10 0.15 0.20 0.25 Nominal CFM Low 1000 960 930 885 BTU/hr BTU/hr RA**36 Medium* 1135 1095 1060 1005 80% 0.96 0.92 High 1205 1145 1105 1105 85% 0.97 0.95 Low 1300 1250 1215 1175 90% 0.98 0.97 RA**50 Medium 1480 1425 1390 1350 95% 0.99 0.99 High* 1660 1600 1550 1495 100% 1.00 1.00 Low 1790 1740 1090 1640 105% 1.01 1.01 RA**57 Medium* 2110 2075 2040 2000 110% 1.02 1.02 High 2300 2260 2215 2140 Low 1790 1740 1090 1640 Air Temperature Correction Factors RA**70 Medium 2110 2075 2040 2000 High* 2300 2260 2215 2140 Air Temp BTU/hr BTU/hr PSC Motor *Denotes factory setting 65F DB 0.67 1.02 70F DB 0.79 1 75F DB/63F WB 0.9 0.97 80F DB/67F WB 1 0.93 Loop Side Fow rate Correction Factors Nominal GPM BTU/hr BTU/hr Hydronic side flow ratecorrection Factors 70% 0.98 0.94 Nominal GPM 80% 0.99 0.96 BTU/hr BTU/hr 90% 0.99 0.98 100% 1 1 100% 1 1 120% 1.03 1.01 110% 1.01 1.02 140% 1.06 1.02 120% 1.02 1.04 Data and specifications may change without notice Northern Heat Pump Water Source Heat Pumps
Note: Cupro Nickel coil have higher pressure drops. Pressure Drop Pressure Drop Heat Exchanger 30, 36, 40 Heat Exchanger 70-2x3 GPM Pd Pd GPM Pd Pd ft psi ft psi 4 3.9 1.7 8 3.9 1.7 5 5.4 2.4 10 5.4 2.4 6 6.9 3.0 12 6.9 3.0 7 11.1 4.8 14 11.1 4.8 8 12.9 5.6 16 12.9 5.6 9 15.0 6.5 18 15.0 6.5 10 22.0 9.5 20 22.0 9.5 11 27.1 11.7 22 27.1 11.7 Pressure Drop Pressure Drop Heat Exchanger 48, 50, 51 Heat Exchanger 100-2x4 GPM Pd Pd GPM Pd Pd ft psi ft psi 6 6.9 3.0 12 6.9 3.0 7 11.1 4.8 14 11.1 4.8 8 12.9 5.6 16 12.9 5.6 9 15.0 6.5 18 15.0 6.5 10 22.0 9.5 20 22.0 9.5 11 27.1 11.7 22 27.1 11.7 12 33.5 14.5 24 33.5 14.5 13 39.3 17.0 26 39.3 17.0 Pressure Drop Pressure Drop Heat Exchanger 57, 60, 61 Heat Exchanger 114-2x5 GPM Pd Pd GPM Pd Pd ft psi ft psi 7 11.1 4.8 14 11.1 4.8 8 12.9 5.6 16 12.9 5.6 9 15.0 6.5 18 15.0 6.5 10 21.9 9.5 20 21.9 9.5 11 27.7 12.0 22 27.7 12.0 12 33.5 14.5 24 33.5 14.5 13 39.3 17.0 26 39.3 17.0 14 43.0 18.6 28 43.0 18.6 Pressure Drop Pressure Drop Heat Exchanger 68, 70 Heat Exchanger 140-2x6 GPM Pd Pd GPM Pd Pd ft psi ft psi 8 16.0 6.9 16 16.0 6.9 9 18.0 7.8 18 18.0 7.8 10 22.0 9.5 20 22.0 9.5 11 29.7 12.8 22 29.7 12.8 12 36.4 15.7 24 36.4 15.7 13 45.0 19.4 26 45.0 19.4 14 50.0 21.6 28 50.0 21.6 15 55.0 23.8 30 55.0 23.8 Data and specifications may change without notice
Model CFM Supply Supply Air Duct Size Min. or Equiv. (includes allowance for 1" internal insulation) Return Air Flange Size Blower Opening Maximum KW Electric Duct Heater RAVE36 1100 12" x 22"; 14" x 18"; 16" x 16" 19 1/8" x 22 1/8" 10 1/4" x 13 1/4" 15 RAVE50 1550 14" x 28"; 16" x 22"; 17" x 20" 19 1/8" x 22 1/8" 10 1/4" x 13 1/4" 20 RAVE57 1700 14" x 30"; 17" x 22"; 18" x 21" 20 1/2" x 29" 10 1/4" x 13 1/4" 25 RAVE70 1900 14" x 32"; 18" x 24"; 20" x 22" 20 1/2" x 29" 10 1/4" x 13 1/4" 25 RT_E30 1050 12" x 22"; 14" x 18"; 16" x 16" 19 1/8" x 22 1/8" 10 1/4" x 13 1/4" 15 RT_E40 1200 12" x 22"; 14" x 20"; 16" x 18" 19 1/8" x 22 1/8" 10 1/4" x 13 1/4" 20 RT_E51 1600 14" x 28"; 16" x 22"; 18" x 20" 20 1/2" x 29" 10 1/4" x 13 1/4" 25 RT_E60 2000 18" x 24"; 20" x 22" 20 1/2" x 29" 10 1/4" x 13 1/4" 25 RMVE30 1050 12" x 22"; 14" x 18"; 16" x 16" 19 1/8" x 22 1/8" 10 1/4" x 13 1/4" 15 RMVE36 1100 12" x 22"; 14" x 18"; 16" x 16" 19 1/8" x 22 1/8" 10 1/4" x 13 1/4" 15 RMVE50 1550 14" x 28"; 16" x 22"; 17" x 20" 19 1/8" x 22 1/8" 10 1/4" x 13 1/4" 20 RMVE57 1700 14" x 30"; 17" x 22"; 18" x 21" 20 1/2" x 29" 10 1/4" x 13 1/4" 25 RMVE70 1900 14" x 32"; 18" x 24"; 20" x 22" 20 1/2" x 29" 10 1/4" x 13 1/4" 25
Acceptable Branch Duct Sizes Acceptable Main or Trunk Duct Sizes CFM Round Rectanglar Round Rectanglar 50 4" 4 x 4 75 5" 4 x 5; 4 x 6 100 6" 4 x 8; 4 x 6 150 7" 4x10;5x8;6x6 x x 6 200 8" 5 x 10; 6 x 8; 4 x 14; 7 x 7 250 9" 6 x 10; 8 x 8; 4 x 16 300 10" 6 x 14; 8 x 10; 7 x 12 350 10" 6 x 20; 6 x 16; 9 x 10 400 12" 6 x 18; 10 x 10; 9 x 12 10" 4 x 20; 7 x 10; 6 x 12; 8 x 9 450 12" 6 x 20; 8 x 14; 9 x 12; 10 x 11 10" 5 x 20; 6 x 16; 9 x 10; 8 x 12 500 10" 10 x 10; 6 x 18; 8 x 12; 7 x 14 600 12" 6 x 20; 7 x 18; 8 x 16; 10 x 12 800 12" 18 x 18; 9 x 15; 10 x 14; 12 x 12 1000 14" 10 x 18; 12 x 14; 8 x 24 1200 16" 10 x 20; 12 x 18; 14 x 15 1400 16" 10 x 25; 12 x 20; 14 x 18; 15 x 16 1600 18" 10 x 30; 15 x 18; 14 x 20 1800 20" 10 x 35; 15 x 20; 16 x 19; 12 x 30; 14 x 25 2000 20" 10 x 40; 12 x 30; 15 x 25; 18 x 20 2200 22" 10 x 45; 15 x 28; 18 x 22; 20 x 20 Tables calculated for 0.05 to 0.10 inches of water friction per 100' of duct. At these duct design conditions, along with the pressure drop through the filter, the total design external static pressure is 0.20 inches of water. Normal airflow at 0.20 inches of water should then be used for these calculations. No allowances have been made for internal duct insulation for the listed sizes.