SafeGear TM Motor Control Center Arc resistant metal-clad construction

Similar documents
SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

T300MVi JK OEM POWER CELLS MEDIUM VOLTAGE VACUUM CONTACTOR. Reliability in motion. Reliability in motion

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

Medium Voltage Metal-Enclosed Switches

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

Descriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Medium Voltage Metal-Enclosed Switches

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

Air-insulated switchgear UniGear type ZS1

Advance 27 ANSI 27 kv switchgear

3TM Vacuum Contactors

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

SIMOVAC and SIMOVAC-AR. Medium-voltage controllers 2.3 kv kv. usa.siemens.com/simovac

Descriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

The safest, most reliable Switchgear in the market today

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Basics of Medium Voltage Motor Control Starter Power Components & Starter Types

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Spare Parts

A. Submit manufacturer's literature and technical data before starting work.

Low & Medium Voltage Vacuum Contactors

Type IMC Indoor current transformer

PIX-H Metal-clad switchgear up to 17.5kV

Vacuum Circuit Breaker VS1

CPG.0 Single busbar gas-insulated cubicles

33KV INDOOR SWITCHGEAR

OTEC Transfer switch open transition

Critical Power Switchboards. Selection and Application Guide

OVERVIEW DESCRIPTION AND CHARACTERISTICS APPARATUS AND TYPES AVAILABLE SWITCHGEAR CHARACTERISTICS INSTRUMENT TRANSFORMERS MEASUREMENT SENSORS

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV

Power/Vac OEM Express Switchgear

SWITCHGEAR DIVISION PRODUCT PROFILES

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

Typical Specification

with Vacuum Circuit Breaker HAF

C1000 Series Automatic Cap Bank

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

JOSLYN CLARK VACUUM CONTACTORS

EMPAC Metal enclosed capacitor bank for wind applications

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

W-SLC Medium Voltage fused contactor truck A safe, reliable and efficient motor starter

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak

SIEMENS-ALLIS. Medium Voltage. Metalclad Switchgear. www. ElectricalPartManuals. com

Horizontal Circuit Switchers

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

DRIESCHER Y WITTJOHANN, S.A. MEDIUM VOLTAGE SOLUTIONS

Transfer switch OTEC and OTECSE open transition

Transfer switch OTEC open or delayed transition

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Medium Voltage. ANSI C37.20 and NEMA SG-5

Electrical Switchgear Replacement Montgomery County Community College

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

CP Automatic capacitor bank

University of Houston Master Construction Specifications Insert Project Name

ZX2 Gas-insulated medium voltage switchgear

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

Contactor V-Contact VSC/P

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

Section 18. Medium Voltage Equipment. BuyLog Catalog 18-1

Padmount Solid Dielectric Switchgear Catalog

RBA Catalog Numbers and Information

Transcription:

SafeGear TM Motor Control Center Arc resistant metal-clad construction

Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor 4 Cubicle features 6 SafeGear MCC section view 7 General dimensions 7 1. Description Designed for the highest degree of safety and reliability, the arc-resistant metal-clad construction Motor Control Center, SafeGear MCC, provides the greatest case of use on the market. For optimal flexibility, the SafeGear MCC is designed to be used in combination with SafeGear Metal-Clad switchgear so a transition section is not required. SafeGear MCC is equipped with mechanical interlocks between the draw-out contactor truck and the front door to increase operation and maintenance safety. 2 SafeGear Motor Control Center Arc resistant metal-clad construction ABB

2. SafeGear MCC applications Suitable for most applications Utilities and power plants Substations Power generation stations Transformer stations Switching stations Main and auxiliary switchgear Infrastructure Shops Hospitals Educational Waste water treatment Industry Pulp and paper Cement Textiles Chemicals Food Automotive Oil and gas facilities Metallurgy Rolling mills Mines Transportation Airports Ports 3. Electrical features Electrical features SafeGear MCC Enclosure Type Type 1 Gasketed* Arc resistance accessibility type Type 2B Rated voltage (kv) Up to 7.2 Insulation level / Power Frequency / Lighting impulse BIL (kv) 7.2 / 20 / 60 Rated frequency (Hz) 60 Rated main bus current (A) 1200, 2000 or 3000 Rated contactor current (A) 400 * Also known in Mexico as NEMA 1A 4. Standards The SafeGear MCC and main apparatus contained in it comply with the following standards: UL 347, 5th edition UL 50/50E IEEE C37.20. 2 IEEE Guide C37.20.7 CSA C22.2 No. 253-09 CSA 22.2 No. 14 NMX-J-564/106-ANCE NRF-146 NRF-048 Medium-Voltage AC contactors, controller and control centers Enclosure for Electrical Equipment Standard for Metal-clad switchgear Guide for test metal-enclosed switchgear for internal arcing faults Medium-voltage ac contactors, controllers, and control centers Industrial Control Equipment Asociación de Normalización y Certificación, A.C Tableros de Distribución en Media Tensión Diseño de instalaciones eléctricas SafeGear Motor Control Center Arc resistant metal-clad construction ABB 3

5. Standard service conditions The rated SafeGear MCC features are guaranteed under the following conditions: Minimum ambient temperature: 5 C Maximum ambient temperature: + 40 C Maximum 24 hour ambient relative humidity: 95% non-condensing The normal operational altitude is up to 1000m above sea level. For higher altitude applications, please contact your ABB sales representative Non-corrosive and non-contaminated atmosphere Transition section is not required for connections with ABB s SafeGear Metal-Clad switchgear of similar rating 6. HCV vacuum contactor Description HCV -5HA coil drive unit The medium voltage V-Contact HCV contactors are suitable for alternating current operation and are normally used to control customer s requirements for a high number of hourly operations. The basic contactors consist of: Molded polyester resin monoblock containing the vacuum interrupters Bistable electromagnet drive Multi-voltage feeder Auxiliary contacts Mechanical status indicator (open/closed). Reduced maintenance: Vacuum bottle contacts have long life with virtually no maintenance required. Environment resistant: Ideal for use in high dust areas. Switching arc is contained within the vacuum bottle, shielding the main contacts. Electronic control drive unit: All contactors include electronic control of the operating coil which offers a wide control voltage of 115/120 or 230/240V ac 50/60Hz (120/125 or 240/250V dc), anti-chopping feature and reduced power consumption. Designed for safety: High voltage and low voltage parts are totally separated by an insulated barrier (non-flammable molded frame). Coil Drive Unit Vacuum Interrupter Auxiliary Contacts Vacuum contactors are rated to perform switching operations before the unit requires maintenance, typically 2.5 millions. Since vacuum contactors are not designed for interrupting currents higher than a few kiloamperes, a fuse in series is required to protect the distribution system against faults. A contactor requires a holding current in the solenoid coil to keep it in the closed position. Although the holding current is often quite small, customers are sometimes concerned that the contactor will open during a brief control power outage. Some designs incorporate mechanical latches to keep the contactors in a closed position. However, these latches do not perform all the functions of conventional circuit breakers. A latched vacuum contactor is not a circuit breaker in terms of functionality or in terms of its rating. However, properly utilized it can provide long service and trouble-free operation. Armature Armature 4 SafeGear Motor Control Center Arc resistant metal-clad construction ABB

Electrical Characteristics of HCV Description HCV-5HA Rated Voltage 7200 Volts Rated Current 400 Amps 7000A RMS Symmetrical @5000V Max. Interrupting Capacity 4500A RMS Symmetrical @7200V Max. Permissible Switching Frequency 1200/Hour Mechanical Life 2,500,000 Operations Electrical Life 250,000 Operations Closing Time 75-100 ms Opening Time* 20-30 ms Arcing Time 10 ms or less Pick-Up Voltage AC or DC 85% Rated (Hot) - 70% Rated (Cold) Drop-Out Voltage AC or DC 50% Rated (Hot) - 40% Rated (cold) Rated Control Voltage AC 115/120 or 230/240 V 50/60 Hz Rated Control Voltage DC 120/125 or 240/250 V Coil Circuit Inrush 670 VA AC (700 W DC) Coil Circuit Holding 85 VA AC (85 W DC) Auxiliary Contact Arrangement 3 N.O. - 3 N.C. Auxiliary Contact Rating 10 A, 600 V (NEMA Class A600) Description Permissible Switching Frequency Mechanical Life Tripping Voltage Tripping Current HCV-5HAL (Latched Type Only) 300/Hour 250,000 Operations 40-60% Rating DC 4.8 A DC Max *DC switching, opening terminals 3 & 4. Fuse technology Time-current characteristic curve of a power fuse There are two kinds of power fuses: standard (general purpose) and current limiting fuses. Ratings of standard fuses depend on (1) the normal continuous current and (2) the time it takes for the fuses to respond to the different magnitudes of overcurrent. Fusable links, the principle elements of every fuse, can have different lengths and thickness and can be made of different metals or alloys. The interrupting medium of a fuse also influences its operating characteristics. This characteristic of the standard fuse is an inversely proportional time-overcurrent curve, as shown schematically in the figure. Time in log scale Current in log scale Inrush current of an induction motor Normal Full load current Range of fuse operation Operating range of device protected by the fuse Proper selection of a fuse for an induction motor is very important. An improperly selected fuse can permanently damage the motor and other equipment in the system. Both starting inrush and normal load currents have to be considered. SafeGear Motor Control Center Arc resistant metal-clad construction ABB 5

Ampere rated fuses Application Voltage Type of fuses Rated Amps Motor Protection 5.5 Bolt - In 70, 100, 130, 170, 200, 230, 315, 390 Transformer Protection 7.2 Bolt - In 10, 15, 20, 25, 30, 40, 50, 65, 80, 100, 125, 150, 175, 200, 250, 300, 350 Motor Protection 5.5 Bolt - In 70, 100, 130, 150, 170, 200, 230, 390 7. Cubicle features Shutters Contactor truck assembly Single phase protection Exhaust plenum Main bus and supports Contactor truck assembly Main bus and supports The vacuum contactor and power fuses are mounted on a fully withdrawable rackable truck. This truck assembly eliminates the need of an isolation switch, therefore reducing the number of moving parts and simplifying the handling, maintenance and safety. Single phase protection A blown fuse trip system can actuate a limit switch that will trip the contactor and energize an indicating lamp located on the instrument compartment cell door. The available main bus ratings are 1200, 2000 and 3000A. Bus supports and insulation materials are flame-retardant, track-resistant and non-hygroscopic. Bus bars are made of cooper and have fully round edges. Bus insulation is heat-shrinkable tubing as standard (solid epoxy coating available as an option). Connection joints, as well as bus bars, are silver-plated (tin plated as an option). Shutters A metallic shutter blocks access to primary contacts when the contactor is in the Disconnected/Test position or withdrawn from the SafeGear MCC. The motion of the withdrawable contactor opens and closes the shutter automatically. Exhaust plenum In the event of an internal arc, the exhaust plenum will safely vent the gases outside the building. Power fuses Current limiting power fuses are installed with the withdrawble contactor and are suitable for use with motor, capacitor or transformer applications. Power fuses for motor protection (type R) will be equipped with bolted type connection. Optional power fuses for feeder or transformer protection (type E) equipped with bolted type connection are also available. 6 SafeGear Motor Control Center Arc resistant metal-clad construction ABB

8. SafeGear MCC section view 4 5 3 6 2 1 7 6 1. Lower contactor compartment 2. Low voltage compartment 3. Vent chamber 4. Upper contactor compartment or PT compartment 5. Plenum 6. Power cables compartment 7. Bus compartment 9. General dimensions 40.375 1025.5 95.000 2413 38.000 965.2 19.000 482.6 21.000 533.4 1.494 37.9 30.000 762 1.494 37.9 65.000 1651 1.578 40.1 67.723 1720.2 in[mm] SafeGear Motor Control Center Arc resistant metal-clad construction ABB 7

Contact us Your sales contact: www.abb.com/contacts More product information: www.abb.com/productguide www.abb.com The information contained in this document is for general information purposes only. While ABB strives to keep the information up to date and correct, it makes no representations or warranties of any kind, express or implied, about the completeness, accuracy, reliability, suitability or availability with respect to the information, products, services, or related graphics contained in the document for any purpose. Any reliance placed on such information is therefore strictly at your own risk. ABB reserves the right to discontinue any product or service at any time. 1YERSC 140011A00-REV 0 - SafeGear MCC 2.5 Copyright 2014 ABB. All rights reserved. Copyright 2014 ABB. All rights reserved