ABB Power T&D Company Inc. General Information: DT-100 DT-150 DV-100 DV-150. De-energized Switches TPL , July 1999, Page 1 of 4

Similar documents
DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

Dry Well Cannister Type CLT, OIL Immersed PTAP-AFH926. Technical Guide Load-break, Dead-break

Load Break Switch Type LBOR-II, Oil Immersed PTAT-LIR975 IZUA Technical Guide Nut Mount Weld Mount

LV Bushing Oil to Air Dry Insulation PTAB-SLV832

Low voltage bushings for pad-mounted distribution transformers Technical information guide

High Voltage Bushing Wells for Pad Mounted Distribution Transformers Technical Guide

100 A externally operated one-, twoand three-phase tap-changer switch

Protective Link Expulsion Fuse Type Prolink, Oil Immersed, PTAP-APR925 IZUA Technical Guide 15 kv, 23 kv, & 35 kv

A 1.2 kv class externally removable secondary bushing

SERIES TAP-CHANGER

Eaton s Cooper Power Systems

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

CSP Circuit Breaker Three Phase

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

IL Instruction Leaflet Page 1 November,2001. Type DTW De-energized Tap Changer Application, Installation & Selection Guide

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

25 kv Apparatus Bushings

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

15 kv and 25 kv Thru-Bushings

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

Single pole connectors

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Easy assembly with standard tools. Fully insulated for direct mounting to steel panels

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

MATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****

VacClad-W type VCP-W 5 and 15 kv, 36-inch-wide switchgear components

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

ABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers

600 A 35 kv class deadbreak accessories, tools, and replacement parts

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

INSTALLATION PRODUCTION TESTS

8WH6 ipo Installation Terminals

Transformer components. De-energized tap changer, type DTW Technical information guide

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

600 A 15 kv class T-OP II deadbreak connector

600 A 25 kv class BT-TAP deadbreak connector

Westinghouse Electric Corporation Distribution Apparatus Division Bloomington, Indiana 47401

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

Kuhlman Electric Corporation Volt Instrument Transformers

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

Loadbreak Apparatus Connectors

PowerPact Circuit Breakers for Control Panel Disconnects Class 0611

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

www. ElectricalPartManuals. com INSTRUCTIONS NO LOAD TAP CHANGER TYPE WSB-4 INSTALLATION OPERATION MAINTENANCE

Distribution transformers Efficiency over life-cycle

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

25 kv class fused loadbreak elbow connector

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

Disconnect & ByPass Switches

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

On-Load Tap changer Type V

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper

Kuhlman Electric Corporation Volt Instrument Transformers

CERTIFIED TEST REPORT

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Technical Specification for Pole Mounted Capacitor Rack

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

600 A 35 kv class BT-TAP deadbreak connector

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

C. System Design and Performance Requirements

CAST RESIN DISTRIBUTION TRANSFORMERS 2016 EDITION

GROUP C. Apparatus Bushing.

H U B B ELL L ABOR ATORIES CAPABILITY GUIDE

15 kv Class Fused Loadbreak Elbow Connector with Interchangeable Fuse Capability

A Summary of Major Improvements to the ABB Recloser and Type R Breaker

Wind Power Solutions. Make Energy Renewable and Reliable!

Two-position sidewall (horizontal) and cover (vertical) mounted loadbreak switches

Power IT Liquid Filled Single Phase Padmounted Transformers kva

1ZSC AAV EN, REV. 4. Tap-changers for power transformers Product guide

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

D-73P disconnect and bypass switches

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV

Arktite Heavy Duty Circuit Breaking Plugs and Receptacles

Arktite Heavy Duty Circuit Breaking Plugs and Receptacles

100 / 110 DRYWELL FUSE SPECIFICATION

Arktite Heavy Duty Circuit Breaking Plugs and Receptacles

Transcription:

General Information: DT-100 DT-150 DV-100 DV-150 De-energized Switches TPL 44-816, July 1999, Page 1 of 4 Type DT-100 & DT - 150, Tap Changers; Type DV-100 & DV- 150, Dual Voltage Switches - General Information and Switch Ratings ABB Power T&D Company Inc.

General Description The ABB D series of tap changers and dual voltage switches are de-energized, rotary-type switches, suitable for use in distribution transformers, both pole and pad mounted. The switches are mounted through the tank wall and are operable from outside the transformer. They are available in single and multi-deck configurations with various types of coil lead connector styles so that they can be used in a wide variety of transformer applications. Ratings and performance features meet and often exceed the requirements of most transformer users. Tap Changer and Hardware Features and Advantages Multi-deck versatility The switches are available in various deck configurations for maximum versatility. Single and three phase applications are accommodated through the use of multiple interconnected decks. High BIL designs are available and may be ordered by contacting your ABB representative. Contact System The moving contact system for the DT-100 consists of a spring loaded, copper wiping contact while the remaining switch Contact Assembly DT-100 Shown DV-100 Shown configurations consist of a spring loaded, copper rolling contact. The rotor snaps into position between the adjacent stationary contacts as the external handle is turned. This contact/snap action is resistant to being placed in an open circuit position by providing a very positive feel to the operator when the switch is in position. The type DT-100 and DV-100 switches are rated for 100 A and the type DT-150 and DV-150 are rated for 150 A. The 100 A designs use a tin plated copper crimp type stationary contact. The 150 A designs, incorporate a variety of stationary contacts in order to provide maximum flexibility in making the internal transformer connections to the switch. The 150 A contacts are available with stud or bolt type connectors; all are tin plated copper. In all cases, the stationary contacts are of heavy duty construction and can be easily replaced in the event of a connection error without the need to remove the switch from the transformer. Hardware Kits (Sold Separately) The hardware kits available are illustrated on pages 11 and 14 of Dimension Sheets 44-888. Each kit includes a handle with mounting screw, a mounting nut, an indicator plate, a gasket, and a warning label.

Three types of operating handles are available: A hook stick operable handle (which is lockable), a 300 series stainless steel pointer type handle, and a low profile pointer type handle. The hook stick handle and the low profile pointer handle are molded from a glass reinforced, high strength resin. External Hardware DV-100 Shown with Pointer Handle The external indicator plate is a molded black plate with white letter position indication and operating information. It is available with a variety of imprints to designate positions and/or ratings. See the ordering information section of this document for more details. Corrosion and Weather Resistance All external parts of the switches are designed to withstand the aging effects of sunlight and corrosive environments. Almost all external parts are nonmetallic and are molded from high strength, weather-resistant, UV grade glass reinforced resins. Any metal external parts are 300 series stainless steel. Sealing System The sealing system features a double O-ring rotary shaft seal and a positively retained static tank seal; all elastomeric seals are fabricated from high temperature Nitrile elastomer. The double O-ring rotary shaft seal provides a mechanically balanced shaft-seal assembly which prevents overstressing of the O-ring due to shaft longitudinal and flexural movement which can occur if only one O-ring is used. The use of two O-rings also provides a redundant seal for the critical shaft General Assembly and Seals seal application. In addition to the double O-rings, the switch contains mechanical stops to prevent the spring loaded moving contact from applying an asymmetrical force on the rotor seals. The molded-in gasket seat provides full retention of the static tank seal, ensures accurate placement for this seal, and provides protection from over compression or displacement by virtue of the positive compression stops built into the retention system. Interchangeability While there may be some competitive designs which are not dimensionally interchangeable, the ABB tap changer and dual voltage switch product line has been designed to fit into the same tank hole as many of the competitive products. Production Tests In addition to the design testing, the following routine testing is done on a sample of each day s production to insure ongoing compliance to requirements. 1. Dimension check to verify all critical dimensions. 2. Leak test to verify the shaft seal integrity. 3. Mechanical operation test to verify mechanical integrity.

Order Information Tap Changers and Dual Voltage Switches (Mounting Hardware Kits Sold Separately) Ampere Terminal Type & Connection Size Terminal Angle Terminal Style # 1 Deck TC 150 kv BIL 2 Deck TC 150 kv BIL 3 Deck TC 150 kv BIL 1 Deck DV 125 kv BIL 2 Deck DV 125 kv BIL 3 Deck DV 125 kv BIL 100 Crimp-# 12-10 AWG 0 9820A44H01 1C11075G02 1 609C227G09 609C178G12 609C176G05 609C177G09 609C181G12 100 Crimp-# 12-10 AWG 0 9820A44H02 1C11075G01 1 609C227G18 609C178G05 609C176G09 609C177G05 609C181G05 100 Crimp-# 12-10 AWG 45 9820A44H04 1C11075G03 1 609C227G15 609C178G15 609C176G15 609C177G15 609C181G15 100 Crimp-# 12-10 AWG 90 9820A44H03 1C11075G04 1 609C227G16 609C178G16 609C176G16 609C177G16 609C181G16 150 Hole-0.25 (6.3mm) 45 1B11081H04 609C175G12 609C227G12 609C178G09 609C176G12 609C177G12 609C181G08 150 Hole-0.25 (6.3mm) 90 1B11081H02 609C175G07 609C227G11 609C178G14 609C176G11 609C177G11 609C181G11 150 Stud-0.25-20 Thread 45 1B11082G04 609C175G13 609C227G13 609C178G13 609C176G13 609C177G13 609C181G13 150 Stud-0.25-20 Thread 90 1B11082G02 609C175G08 609C227G14 609C178G11 609C176G08 609C177G08 609C181G09 1 Refer to DS 44-888 Page 13 for dimensions of single phase de-energized tap changer. Design Tests The ABB tap changers and dual voltage switches passed a series of tests which were designed to verify their suitability for use in oil filled distribution transformers and their long term reliability. The tests are listed below: Full Wave Impulse Test Low Frequency Voltage Withstand Test Corona and RIV Test Mounting Flange Strength Test Mechanical Life Test Safe Transit Test Cantilever Load Test Shaft Torque Test Side Thrust Test Contact Temperature Rise Test Thermal Runaway Test Thermal Cycle Withstand Test Coil Oven Bake Test Short Circuit Tests Helium Leak Test Pressure-Powdered Chalk Test ABB Power T&D Company Inc. Components Division 1128 Highway 412 S. Alamo, TN 38001-3813 U.S.A. TPL 44-816 July 1999 Page 4 of 4