Connection and regulation kit for HVAC terminal units

Similar documents
CALEFFI. Pressure independent control valve (PICV) 145 series 01262/14 GB B 51

CALEFFI. Motorised temperature regulating unit for heating and air conditioning systems WYP UPM series 01254/17 GB

CALEFFI. Pre-assembled distribution manifolds for. heating and air-conditioning systems. 663 series 01065/18 GB. replaces dp 01065/06 GB.

CALEFFI. Composite manifolds specifically designed for radiant panel systems. 670 series 01126/18 GB. replaces dp 01126/11 GB.

CALEFFI. Direct supply unit for heating systems. 165 series 01237/17 GB. replaces dp 01237/15 GB. Function

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/14 GB

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/18 GB. replaces 01260/14 GB

CALEFFI. Modulating temperature regulating unit with distribution kit for primary circuit. 171 series 01153/15 GB. replaces 01153/07 GB

CALEFFI. Motorised ball valve for central heating systems. 638 series 01196/18 GB. replaces dp 01196/12 GB

ACCREDITED. brass EN CW617N brass EN CW614N brass EN CW614N, chrome plated PTFE PSU EPDM

CALEFFI. Mixing valves and actuators series 01169/17 GB. replaces dp 01169/09. Function

COMPONENTS FOR SOLAR THERMAL SYSTEMS

CALEFFI. Pre-assembled distribution manifold for radiant panel systems S1 series 01144/11 GB. Replaces 01144/07 GB.

CALEFFI. Manifolds in composite specifically designed for radiant panel systems. 670 series 01126/05 GB. Function

COMPONENTS FOR SOLAR THERMAL SYSTEMS

FLOW RATE STATIC BALANCING Valves for radiators

THERMOSETTER Recirculation thermal balancing valve

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Product range. Technical specifications. Characteristic components

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Important Product range Technical specifications

TA-6-way valve. NPT threads. Standard control valves 6-way valve for change-over systems

Pre-assembled distribution manifolds for radiant panel systems

CALEFFI. Ball shut-off valve fitted for integrated flow rate measuring sensor. 111 series 01234/13 GB. (kpa) (mm w.g.) G (m 3 /h)

Technote. Frese OPTIMA - Pressure independent control & balancing valve. Application. Features. Benefits.

SELF-CLEANING FILTER

CALEFFI. Pre-assembled distribution manifolds for radiant panel systems. series 663 & /05 NA. Function

CT3202.0_01 EN February 2018

ZONE CONTROLE / 2-WAY

LF24-SR US TF24-SR US TFX24 US LF24 US. B3 B Three-way Characterized Control Valve, Chrome Plated Brass Ball and Brass Stem

CALEFFI. Motorised ball zone valves with 3-contact control BY series 01131/18 GB. replaces 01131/11 GB

Open/close ball valves 2-port and changeover ball valves 3-port, PN40

Leakage rate. Valve body. U.S. Registered Trademark EN0B-0308GE51 R1002 Copyright 2002 Honeywell Inc. All rights reserved

V5832A/5833A,C SMALL LINEAR VALVES PN16 FOR MODULATING AND ON/OFF-CONTROL SPECIFICATIONS

CALEFFI. Hydraulic separator-manifold SEPCOLL. 559 series 01084/16 GB. replaces dp 01084/13 GB

Pressure Independent Control Valve

Direct/Factory Mounting Valve Set

Technote. Frese OPTIMA Compact DN10-DN50 - pressure independent balancing & control valve. Application. Features. Benefits.

Safety cap. Measuring probe. Seal. Operating principle. Advantages of balanced circuits. Balanced circuits have the following principal benefits:

3-port seat valves PN6 with flanged connection

VVP45 and VXP45 Series Two-port and Three-port Seat Valves ANSI Class 250 Short-stroke Valves

CONTROL EQUIPMENT STAZ-16, STBZ-16

Product Sheet Pre-Fabricated Flushing Bypass Assembly for Terminal Applications Mini-Flush 40

2-port and 3-port ball valves PN 40

3-Port Seat Valves with Flange, PN 6

3-Port Seat Valves with Flange, PN 10

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features.

V5822A / 5823A,C SMALL LINEAR VALVES PN16 FOR MODULATING AND ON/OFF-CONTROL SPECIFICATIONS GENERAL

ROTARY PRESSURE INDEPENDENT CONTROL VALVE TECHNICAL MANUAL

2-Port and 3-Port Zone Valves, PN16

1 DESCRIPTION 2 WORKING PRINCIPLE 2.1 REGULATION ST

Pressure independent balancing and control valve

HERZ-Connect 4 / Compact Connect 4 & Commissioning Centres

PCS. HVAC Products. Technical submission. Type of Product

R EGI S TERED. Function

VG6000. Globe Valves Series for Terminal Units. Product Bulletin

Pre-Fabricated Flushing Bypass Assembly for Plant Applications Hero Plant DN15-150

B2/B3 Series Characterized Control Valve, Non-Spring Return Actuator

VBGx-xx-xx Externally Threaded Control Ball Valves PN25 (DN40 TO DN50)

3-port seat valves PN10 with flanged connection

Product Sheet Pre-Fabricated Flushing Bypass Assembly for Plant Applications Hero Plant DN15-150

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Operating principle Application diagram. Regulator-actuator Wiring diagrams

VPI45.. VPI45..Q. Combi valves, PN 25. Building Technologies. VPI45..Q with pressure test points ACVATIX

B2 Series Characterized Control Valve, Non-Spring Return Actuator

M4410C/L SMALL LINEAR THERMOELECTRIC ACTUATORS

VPI45..Q with pressure test points. Combi valves, PN 25

FO-BV Series. Fixed-orifice balancing and control valves. Technical Data Sheet. WattsIndustries.com

3-port seat valves PN16 with flanged connection

3-port seat valves, external thread, PN16

3-Port Seat Valves with Male Thread, PN 16

2-port and 3-port valves with T-bypass PN 16

Pressure independent balancing and control valve AB-QM DN

VE-S_15-32 Pressure Independent Balancing & Control Valves

Terminator PICV. Technical Manual

Components for central heating

Fan-coil valves Series

TRF.. series spring return rotary actuators for CCV

2-port shutoff valves and 3-port changeover ball valves, PN 40, with internally threaded connection

Innovation + Quality. Valves, controls + systems Balancing and Control Valves

2-port seat valves PN16 with flanged connection

TA-6-way valve. Standard control valves 6-way valve for change-over systems

VPI45..Q with pressure test points. Combi valves, PN 25

VP1000. Pressure Independent Control Valve. Product Bulletin

2-Port and 3-Port Zone Valves, PN 16 / 20

2-Port and 3-Port Zone Valves & Actuators, PN16

V5032. Kombi-2-plus Manual double regulating balancing valve. Product specification sheet

Balancing Valves. Venturi Commissioning Valve (FODRV) & (DRV) Cu x Cu Compression DN10-DN50. BOSS TM 901SC Venturi DRV DN

2-Port and 3-Port Zone Valves PN 16

3-port valves vxf42..

3-port seat valves PN16 with flanged connection

ACTIVAL Three-Way Ball Valve with Threaded-End Connection

Flow controller with integrated control valve (PN 16) AHQM return and flow mounting

CALEFFI. zone valves. Z series 01115/14 NA. Replaces 01115/11 NA. Function

2-way and 3-way globe valves

VG6000 Series Forged Brass Valves

VE-x Plug & Seat Valve Assemblies

CALEFFI. FLOWCAL Automatic flow balancing valve with polymer cartridge. 121 series 01141/11 NA. Function

Cocon QTZ Pressure independent control valve

CALEFFI. HydroMixer motorized temperature mixing unit. 167 series 01239/13 NA. Function

Pressure Independent Control Valve

Mounting and Operating Instructions EB 5894 EN. Electric control valves with jet pump. Flanged version of valve with jet pump

Combi valves PN 16 with flanged connections

Transcription:

Connection and regulation kit for HVC terminal units 149 series 01336/18 G FM 21654 003 Function The preassembled group for terminal units is compact and able to shutoff, adjust and filter the secondary circuit of the terminal unit. It also allows to perform maintenance and setting operations of the system. It allows the connection of fan coils, cold beams or ceiling conditioning systems with the main distribution network. Complete with insulation suitable for both heating and cooling. vailable with Venturi device for flow rate measurement Product range 149 series Connection and regulation kit for HVC terminal units size DN 15 (1/2 F x 3/4 M), DN (3/4 F x 1 M), DN 25 (1 F x 1 1/4 M) Reference documentation Tech. broch. 01142 Thermoelectric actuator with manual opening and position indicator 6563 series Tech. broch. 01198 Thermoelectric actuator. 6562 series. Thermoelectric actuator with low power consumption. 6564 series. Tech. broch. 01262 Pressure independent control valve (PICV) FLOWMTIC. 145 series. Technical specifications Materials ody: dezincification resistant alloy EN 12165 CW602N Strainer mesh: ISI 304 Shutoff valves knobs: P6G30 PICV Headwork: dezincification resistant alloy EN 12164 CW602N Control stem and piston: stainless steel EN 883 (ISI 303) Obturator seat: 0,02 0,4/0,08 0,8/0,12 1,2 m3/h: PTFE 0,18 1,8/0,30 3,00 m3/h: stainless steel EN 883 (ISI 303) Obturator: EPDM Pressure regulator membrane: EPDM Springs: stainless steel EN 2703 (ISI 302) Seals: EPDM Seals: nonasbestos fibre Preadjustment indicator: P6G30 Knob: P6 Performance Medium: water, glycol solutions Maximum percentage of glycol: % Max. working pressure: 25 bar Max. differential pressure with actuator code 1414 and 656. series thermoelectric actuators: 5 bar Working temperature range: 1 C mbient temperature range: 0 C Nominal Dp control range: 25 400 kpa Flow rate regulation range: 0,02 3,00 m3/h (see hydraulic characteristics) Max. flow rate, with 656. series thermoelectric actuator fitted, reduced by: 0,02 0,4/0,08 0,8/0,12 1,2 m3/h: % 0,18 1,8/0,30 3,00 m3/h: 25% Strainer mesh size: 800 µm Insulation Material: PPE Density: 30 Kg/m3 Thermal conductivity: 0,037 W/(m K) at C Reaction to fire (UL94): class HF Connections System side 1/2 F (DN 15) 3/4 F (DN ) 1 F (DN 25) Terminal unit side: 3/4 M (DN 15) 1 M (DN ) 1 1/4 M (DN 25)

Technical specifications for actuator code 1414 Proportional linear actuator Electric supply: 24 V (ac/dc) Power consumption: 2,5 V (ac) 1,5 W (dc) Control signal: 0 V Protection class: IP 43 mbient temperature range: 0 C Supply cable length: 1,5 m Connection: M30 p.1,5 Specifications of 6562 series thermoelectric actuator Normally closed Electric supply: 230 V (ac) 24 V (ac) 24 V (dc) Starting current: 1 Running current: 230 V (ac) = 13 m 24 V (ac) 24 V (dc) = 140 m Running power consumption: 3 W uxiliary microswitch contact rating (code 656112/114): 0.8 (230 V) Protection class: IP 54 (in vertical position) Double insulation construction: CE mbient temperature range: 0 C Operating time: opening and closing from 1 s to 180 s Electric supply cable length: 80 cm Characteristic components Dimensions 1 2 3 4 4 4C 4 PN25 CR Group with Venturi device 1. ctuator (optional) 2. Pressure independent control valve (PICV) 3. Fill/drain cock (optional) 4. ypass kit composed of: 4. Threeway shutoff valve 4. Venturi device for flow rate measurement with connections H for pressure test ports (present only in 149.00 codes) H 4C. Threeway shutoff valve with integrated strainer DN 15 DN DN 25 DN 15 DN DN 25 C D E F G H I 9 191 9 191 0 Mass (kg) 2,4 2,5 3,0 300 83 1 1 300 80 137 300 94 154 146 300 80 137 300 9 154 146 300 80 137 0 0,02 0,04 0,06 0,08 0,1 0,12 0,14 0,16 0,18 0,2 0,25 0,3 0,35 0,4 0,6 0,7 0,8 0,9 1 1,1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 Flow rate range shortcut charts Group Group without without Venturi Venturi device device H 0 0,02 0,04 0,06 0,08 0,1 0,12 0,14 0,16 0,18 Group with Venturi device 0,2 0,25 0,3 0,35 0,4 0,6 0,7 0,8 0,9 1 1,1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 Group with Venturi device H H 0 0,02 0,04 0,06 0,08 0,1 0,12 0,14 0,16 0,18 0,2 0,25 0,3 0,35 0,4 0,6 0,7 0,8 0,9 1 1,1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 Group without Venturi device

Hydraulic characteristics of the group without Venturi device Code flow rate range 1494 H 0,02 0, m 3 /h 1494 0,08 0,40 m 3 /h 1494 0,08 0,80 m 3 /h 1495 H 0,02 0, m 3 /h 1495 0,08 0,40 m 3 /h 1495 0,08 0,80 m 3 /h 1495 0,12 1, m 3 /h 1496 0,18 1,80 m 3 /h 1496 0,3 3,00 m 3 /h DN 15 15 15 25 25 djustment position 1 2 3 4 5 6 7 8 9 0,02 0,04 0,06 0,08 0,1 0,12 0,14 0,16 0,18 0,2 25 25 25 25 25 25 25,5 25,5 26 26 * * * * * * * * * * 0,08 0,12 0,16 0,2 0,24 0,28 0,32 0,36 0,40 25 25,5 26 26 26,5 26,5 27 27 27 * * * * * * * * 0,08 0,16 0,24 0,32 0,40 0,48 6 0,64 0,72 0,8 25 25 25,5 26 26 27 27,5 28 28,5 29 * * * * 0,8 1 1,4 1,7 2,1 0,02 0,04 0,06 0,08 0,1 0,12 0,14 0,16 0,18 0,2 25 25 25 25 25 25 25,5 25,5 26 26 * * * * * * * * * * 0,08 0,12 0,16 0,2 0,24 0,28 0,32 0,36 0,40 25 25,5 26 26 26,5 26,5 27 27 27 * * * * * * * * * 0,08 0,16 0,24 0,32 0,40 0,48 6 0,64 0,72 0,8 25 25 25,5 26 26 27 27,5 28 28,5 29 * * * * * * 0,6 0,8 1 0,12 0,24 0,36 0,48 0,6 0,72 0,84 0,96 1,08 1,2 25 25 25,5 26 26 26,5 26,5 27 27,5 28 * * * * 0,8 1,1 1,4 1,8 2,2 0,18 0,36 4 0,72 0,9 1,08 1,26 1,44 1,62 1,8 35 35 35 35 35 28 25 25 25 25 * * * 0,6 0,9 1,3 1,7 2,3 2,8 3,5 0,3 0,6 0,9 1,2 1,5 1,8 2,1 2,4 2,7 3 35 35 35 35 35 35 35 35 35 35 * * * 1,6 2,4 3,5 4,8 6,3 7,9 9,8 (*) Values not indicated as Δp negligible (Δp bypass kit < kpa) ypass kit (without Venturi) Δp (mm w.g.),000 5,000 size Kv DN 15 DN DN 25 5,5 8,1 9,6 Δp (kpa) Minimum differential pressure required To choose the pump you need to add the minimum pressure difference required by the group to the fixed head losses of the most disadvantaged circuit. The minimum Δp of the connection group and adjustment is obtained: Δp min group = Δp bypass kit + Δp min PICV 2,000 1,000 where: Δp bypass kit = bypass kit head loss Δp min PICV = minimum PICV load loss 0 5 Dp min PICV 0 2 1 0,2 0,01 0,025 0,05 0,1 0,25 1 2,5 5 Dp bypass kit DN 15 DN DN 25 Kv kit bypass (m 3 /h) 5,5 8,1 9,6

Hydraulic characteristics of the group with Venturi device Code Flow rate range 149400 H 0,02 0, m 3 /h 149400 H 0, 0, m 3 /h 149400 0, 0,40 m 3 /h 149400 0,40 0,80 m 3 /h 1490 H 0,02 0, m 3 /h 1490 H 0, 0, m 3 /h 1490 0, 0,40 m 3 /h 1490 0,40 0,80 m 3 /h 1490 0,80 1, m 3 /h 149600 1, 1,80 m 3 /h 149600 1,8 3,00 m 3 /h DN 15 15 15 15 25 25 Kv Venturi (m 3 /h) 0,25 0, 1, 2,35 0,25 0, 1, 2,35 5,00 5,00 9,60 djustment position 1 2 3 4 5 6 7 8 9 0,02 25 0,02 25 0,04 0,06 0,08 0,1 25 25 25 25 1,8 4 7,1 11,1 0,1 0,12 0,14 0,16 0,18 0,2 25 25 25,5 25,5 26 26 2,8 4 5,4 7,1 9 11,1 0,2 0,24 0,28 0,32 0,36 0,40 26 26,5 26,5 27 27 27 2,4 3,4 4,6 6,1 7,7 9,5 0,4 0,48 6 0,64 0,72 0,8 26 27 27,5 28 28,5 29 1,9 2,7 3,7 4,9 6,2 7,6 0,04 0,06 0,08 0,1 25 25 25 25 1,8 4 7,1 11,1 0, 0,12 0,14 0,16 0,18 0,2 25 25 25,5 25,5 26 26 2,8 4 5,4 7,1 9 11,1 0,2 0,24 0,28 0,32 0,36 0,40 26 26,5 26,5 27 27 27 2,4 3,4 4,6 6,1 7,7 9,5 0,4 0,48 6 0,64 0,72 0,8 26 27 27,5 28 28,5 29 1,9 2,7 3,7 4,9 6,2 7,6 0,84 0,96 1,08 1,2 26,5 27 27,5 28 2,3 2,9 3,7 4,6 1,26 1,44 1,62 1,8 25 25 25 25 5,1 6,6 8,4,3 1,8 2,1 2,4 2,7 3 35 35 35 35 35 3,5 4,8 6,3 7,9 9,8 ypass kit (with Venturi) Δp (mm w.g.) size Kv H 0,3 H 0,6 1,3 2,9 5,6 9,6 Δp (kpa) Venturi Δp (mm w.g.) size Kv H 0,25 H 1,1 2,35 5 9,6 Δp (kpa),000,000 5,000 5,000 2,000 2,000 1,000 1,000 0 5 0 5 0 2 0 2 1 1 0,2 0,01 0,025 0,05 0,1 0,25 1 2,5 5 0,2 0,01 0,025 0,05 0,1 0,25 1 2,5 5 Kv kit bypass (m 3 /h) H H 0,3 0,6 1,3 2,9 5,6 9,6 H H Kv Venturi (m 3 /h) 0,25 1,1 2,35 5,0 9,6

Operating principle The group layout is shown in the diagram below: TERMINL UNIT SYSTEM 1. ctuator (optional) 2. Pressure independent control valve (PICV) 3. Fill/drain cock (optional) 4. Venturi device with connections for pressure test ports (present only in 149.00 codes) 5. Threeway shutoff valve 6. ypass 7. Shutoff valve with integrated strainer The group allows to: adjust and maintain the flow rate of the terminal unit constant as the differential pressure conditions of the main circuit changes due to the pressure independent control valve PICV (2); isolate the terminal unit through the threeway shutoff valves (57); bypass the flow through the threeway shutoff valves (57) and the integrated bypass (6); filter the inlet water to the terminal unit through the strainer located inside the shutoff valve (7); measure the flow rate passing through the terminal unit using the device with Venturi effect and the pressure test ports (4) with which the connection of the measuring instrument is easy (present only in codes 149.00); clean the circuit and drain the water through the drain cock (optional) (3) Construction details Compact body The group is designed specifically for small dimensions, compact and easy to install to facilitate the terminal unit connection to the main circuit. Individual components assembled in site Threeway ball valve The shutoff valves have been designed at threeway to minimize the dimensions and connections of the kit. The internal ball is designed to open the straight path () (for normal operation), the bypass path () (for passage through the bypass) or to completely close the passage and isolate the circuit of the terminal unit (C). UNIT OPEN hydraulic connections Laborious installation and with high risk of hydraulic leakage UNIT YPSS C Preassembled group 4 hydraulic connections Integrated bypass The group is complete with bypass, which is an indispensable element for each terminal circuit. The bypass allows to: perform the flushing, washing and cleaning operations of the main circuit tubes without fluid passage through the terminal unit; perform the shutoff and maintenance operations of the terminal unit. Ease of installation and low risk of hydraulic leakage

Integrated strainer The components of a heating and air conditioning system are exposed to degradation caused by the impurities contained in the system's circuit. If the impurities in the thermal medium are not removed, they can impair operation of the units or components, such as boilers, heat exchangers, or terminal appliances in the circuits, especially in the system commissioning stage. The cartridge filter contained inside the group mechanically blocks the impurities contained in the thermal medium (before arriving to the terminal unit) and retains them by mechanical selection through a specific mesh wire filtering strainer. Flow rate meter (in the predisposed versions) The group contains a flow rate metering device based on Venturi effect. The possibility of measuring the flow rate in a simple way facilitates the system setting and setup operations. The metering device contains a diaphragm that, by restricting the crosssection of the channel, speeds up the medium and generates increased Dp (as measured) at the ends in order to guarantee precise flow rate metering. Each differential pressure value (measured at the ends of the diaphragm through the quickfit pressure test ports) has a corresponding accurate flow rate value, known the diaphragm Kv value. integrated PICV The group is equipped with a pressure independent control valve (PICV) capable of adjusting and maintaining the constant the flow rate even when the differential pressure conditions of the system changes. The flow rate is adjusted: manually on the automatic flow rate regulator, to restrict the maximum value. The adjustment is made turning the locking nut and positioning it on the relative adjustment number: this causes the passage section opening/closing () automatically by the control valve in combination with a proportional (0 V) or ON/OFF actuator, in accordance with the thermal load requirements of the section of the circuit to be controlled. The actuator adjusts the flow rate from the maximum value to the minimum value acting on the vertical displacement of the control stem (). Use with actuators The group is fitted to function with a proportional linear actuator (code 1414). When controlled by a regulator, the valve can modulate the flow rate in accordance with the system thermal load. s an alternative to a proportional linear actuator, the valve can also be controlled with an ON/OFF type thermoelectric actuator 656 series, for simpler temperature control logic. In order to use the kit with actuator in a heating system, it is necessary to remove the insulation part (precut) that covers the actuator, to avoid overheating. Pressure test ports The pressure independent control valve is supplied with upstream and downstream connections for fastplug pressure test ports (Caleffi code 000), to be fitted in the connections with the system cold and not in pressure. Installation versatility The group, without actuator, can be installed in any position. With an actuator fitted the valve can be installed in any position except upside down. During the operation it is possible to measure the Dp of the valve (using the differential pressure measuring station Caleffi code 130005/6) and check if the valve is working at the correct Dp range.

SIZE Design data system size is set up to serve 80 fan coils divided into 8 secondary circuits, as shown in the image below. In each secondary branch (see box) the system must serve 3 types of fan coil. The following design data are adopted: Type Ga = 4 l/h Ha = kpa Type Gb = 6 l/h Hb = 13 kpa Type C Gc = 900 l/h Hc = 17 kpa where: G = design flow rate H = fan coil design load loss Type C G C = 900 l/h H C = 17 kpa Type G = 6 l/h H = 13 kpa Type G = 6 l/h H = 13 kpa Type G = 4 l/h H = kpa Type G = 4 l/h H = kpa Type C G C = 900 l/h H C = 17 kpa Type G = 6 l/h H = 13 kpa Type G = 6 l/h H = 13 kpa Type G = 4 l/h H = kpa Type G = 4 l/h H = kpa Group with Venturi device Group size selection Each fan coil is served by a group of which it is necessary to choose: 1 the body size 2 the flow rate range and the related flow rate presetting. 1) Group without Venturi device If the choice is directed to a group without a Venturi device, proceed as follows: 1. The choice of the size is made according to the required flow H rates and, if possible, with diameters equal to those of the H connections to the batteries of the fan coils. 2. When, as in this case, the pressure independent control valves also 0 0,02 work 0,04 as 0,06 modulating 0,08 0,1valves, 0,12 0,14 it is 0,16 preferable 0,18 0,2to 0,25 use the 0,3 highest 0,35 possible preadjustment positions. For example, it is preferable to use adjustment positions of the locking nut from to 4 to make the adjustment more stable. For this reason, for type and the flow rate range is chosen, available in sizes DN 15 or DN. For type C, the next size is chosen, available exclusively in DN. The following sizes can be chosen: Type and flow rate range size DN Type C flow rate range size DN Type Type Type C Maximum flow rate Minimum flow rate 0,4 0,6 0,7 0,8 0,9 1 1,1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 Group without Venturi device H 0 0,02 0,04 0,06 0,08 0,1 0,12 0,14 0,16 0,18 0,2 0,25 0,3 0,35 0,4 0,6 0,7 0,8 0,9 1 1,1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 Type Type Type C

2) Group with Venturi device If the choice is directed towards a group with Venturi device, it is sufficient to identify the correct flow rate range. Group with Venturi device The following sizes can be chosen: Type and flow rate range size DN Type C flow rate range size DN H H 0 0,02 0,04 0,06 0,08 0,1 0,12 0,14 0,16 0,18 0,2 0,25 0,3 0,35 0,4 0,6 0,7 0,8 0,9 1 1,1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 Type Type Type C Group without Venturi device Determination of the Dp requested at the detachments towards the terminals Their value is determined with the formula: Dp detachment = Dp pipes + Dp min group + Dp fan coil where: Dp pipes = pdc main linefan coil connection sections H Dp min group (for the sake of simplicity we assume 2 kpa) = minimum Dp of connection and adjustment group Dp fan coil Type = kpa 0 0,02 0,04 0,06 Type 0,08 0,1 = 0,12 13 0,14 kpa0,16 0,18 0,2 0,25 0,3 0,35 Type C = 17 kpa Dp pipes Dp min group Dp fan coil Dp etachment 1) Group without Venturi device The load loss of the group is obtained from the corresponding table known the flow rate and the size of the 149 series groups chosen: Dp min group = Dp bypass kit + Dp min PICV Type Ga = 4 l/h flow rate range size DN Dp min PICV = 27 kpa Dp bypass kit 0 kpa Type Gb = 6 l/h flow rate range size DN Dp min PICV = 28 kpa Dp bypass kit = 0,6 kpa Type C Gc = 900 l/h flow rate range size DN Dp min PICV = 27 kpa Dp bypass kit = 1,4 kpa ased on these values the Dp min group are: Type Dp min group = 27 + 0 = 27 kpa Type Dp min group = 28 + 0,6 = 28,6 kpa Type C Dp min group = 27 + 1,4 = 28,4 kpa The pressure losses at the detachments are: Type Dp detachment = 2 + 27 + = 39 kpa Type Dp detachment = 2 + 28,6 + 13 = 43,6 kpa Type C Dp detachment = 2 + 28,4 + 17 = 47,4 kpa 2) Group with Venturi device The load loss of the group is obtained from the corresponding table known the flow rate and the size of the 149 series groups chosen: Dp min group = Dp bypass kit + Dp min PICV Type Ga = 4 l/h flow rate range size DN Dp min PICV = 27 kpa Dp bypass kit = 2,7 kpa 0,4 0,6 0,7 0,8 0,9 1 1,1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3 Type Gb = 6 l/h flow rate range size DN Dp min PICV = 28 kpa Dp bypass kit = 4,9 kpa Type Type Type C Type C Gc = 900 l/h flow rate range size DN Dp min PICV = 27 kpa Dp bypass kit = 2,9 kpa ased on these values the DP min group are: Type Dp min group = 27 + 2,7 = 29,7 kpa Type Dp min group = 28 + 4,9 = 32,9 kpa Type C Dp min group = 27 + 2,9 = 29,9 kpa The pressure losses at the detachments are: Type Dp detachment = 2 + 29.7 + = 41.7 kpa Type Dp detachment = 2 + 32,9 + 13 = 47,9 kpa Type C Dp detachment = 2 + 29,9 + 17 = 48,9 kpa Determination of system flow rate and head Considering that the group stabilizes the flow rate on all the branches and makes it independent from the various actions, the flow rates that cross the network are exactly the design ones. Once the flow rates in the various sections have been determined, the load losses of the pipes are calculated with the usual formulas.

INSTLLTION Connect the connection and adjustment group to the main pipe and then to the terminal unit using flexible pipes. racketing The unit is fitted for bracketing with threaded bar. The insulation can be closed with cable ties housed in the appropriate spaces. Use in heating system In order to use the kit with actuator in a heating system, it is necessary to remove the insulation part (precut) that covers the actuator, to avoid overheating. STRTING UP Using different positions of the threeway ball valves (hereinafter referred to as valve and valve ), different operation configurations can be obtained. Fig. 2 UNIT OPEN UNIT OPEN UNIT YPSS UNIT OPEN UNIT YPSS UNIT OPEN 1) Wash in bypass. Clean the main circuit, by simple washing or specific products, with the exception of the single terminal unit. Place both lever and lever on "UNIT YPSS". Fig. 2 Fig. 1 UNIT YPSS UNIT YPSS UNIT YPSS 3) Strainer cleaning To clean the strainer position both levers on. 2) Terminal unit washing Position both levers on UNIT OPEN, close the PICV using the knob and open the optional drain cock: in this way it is possible to flush the terminal unit using water coming from the main circuit without passing through the PICV (Fig. 2). Fig. 3 In cases where it is necessary, it is possible to wash the terminal unit even with the configuration shown in fig.2. In this case, set lever to "UNIT YPSS" and lever to "".

Unscrew the strainer holder cartridge by means of a key, paying attention to drain the water contained in the bypass. Maximum flow rate adjustment djust the maximum flow rate operating on the PICV adjustment nut. See section "Maximum flow rate adjustment". Remove the strainer holder cartridge and clean the strainer under running water. Check the PICV setting measuring the flow rate passing through the terminal unit using the Venturi device. See section "Flow rate measurement". Install the actuator and carry out the electric connections. 4) Filling Place lever on "" and lever on "UNIT OPEN", open the PICV using the appropriate knob. Close the drain cock (optional) as soon as the air is completely eliminated. dditional use configurations Terminal unit back wash In cases where it is required it is possible to back wash the terminal unit. Place lever on "" and lever on "UNIT YPSS" and wash unloading through the open flexible pipe. This configuration can be performed with the PICV actuator installed. Fig. 4 Fig. 6 UNIT OPEN UNIT YPSS 5) Normal operation Normal operation involves positioning both valves on "OPEN". Water passes through the strainer before entering in the terminal unit, protecting the unit against any residues and impurities present in the main circuit water. Isolate the line It is possible to exclude the terminal unit and thus isolate the secondary circuit. This configuration is generally used to perform maintenance on the terminal unit. Fig. 5 UNIT OPEN Fig. 7 UNIT OPEN

FLOW RTE DJUSTMENT Maximum flow rate adjustment Unscrew the protective cap by hand to gain access to the maximum flow rate adjustment nut (), which can be turned with a hexagonal key. The locking nut is fixed to a position graduated scale, divided into steps corresponding to 1/ of the maximum available flow rate, which is also shown on the scale (11). Turn the locking nut to the numerical position corresponding to the required flow rate (design flow rate), referring to the Flow rate adjustment table. The notch (12) on the valve body is the physical positioning reference. Turning the locking nut (), which determines the number associated with the djustment position, results in opening/closing of the bore cross section in the external obturator (13). Hence, each bore cross section set on the locking nut corresponds to a specific Gmaxx value. 13 djustment position Gmax x 8 6 Gmax Gmax 8 Gmax 6 11 1 Gmax 1 12 25 kpa 30 kpa 400 kpa Δp minimum Δp (kpa) utomatic flow rate adjustment with actuator and external regulator fter adjusting the maximum flow rate, it is possible fit the actuator (0 V) code 1414 to the valve. Under the control of an external regulator the actuator can change the flow rate from the maximum value set (E.g.: Gmax 8 ) up to the minimum value, depending on the thermal load to be controlled always maintaining the automatic balancing of the systems. The actuator acts on the vertical displacement of control stem (4). This results in additional opening/closing, on the maximum bore cross section, by the internal obturator. For example, if the maximum flow rate has been set to position 8, the flow rate can be adjusted automatically by the actuator from Gmax 8 to completely closed (zero flow rate). 4 Flow rate adjustment curve The valve adjustment curve is of the linear type. n increase or decrease in the valve opening cross section corresponds to a directly proportional increase or decrease of the device's hydraulic coefficient Kv. The motor is factory configured with linear adjustment. It is possible to obtain an equalpercentage adjustment (see diagram below) setting the actuator (code 1414) for this operation by means of the dedicated switch inside it. (see specific instruction sheet). In this way the control signal is managed to obtain an equal percentage adjustment. % Kv Num. Linear adjustment 90 80 70 60 40 30 0 0 1 2 3 4 5 6 7 8 9 (V) 0 30 40 60 70 80 90 % stroke Gmax 8 75% Gmax 8 % Gmax 8 p (kpa) % Kv Num. Equal percentage adjustment 90 80 70 60 40 30 0 0 1 2 3 4 5 6 7 8 9 (V) 0 30 40 60 70 80 90 % stroke

FLOW RTE MESUREMENT Connect a differential pressure measuring station to the Venturi device pressure test ports on the group. Reading the Dp on the measuring device, to obtain the flow rate G you can refer to the characteristic Venturi diagram of the size being used. Or, analytically, you can calculate the flow rate by applying the equation: G = Kv Venturi x Dp Venturi (1.1) Example of flow rate measurement Reading a Dp Venturi of 4,5 kpa (red line) on a valve, using the characteristic Venturi chart of the valve in question, in the xaxis there is a flow rate equal to m3/h (blue line). Instead, to proceed analytically using the ratio (1.1), la measurement of a Dp Venturi equal to 4,5 kpa (bearing in mind that the Kv Venturi of the valve is equal to 2,35) leads to the calculation of a flow rate G = 2,35 x 0,045 = m3/h (1.1) H H Kv Venturi (m 3 /h) 0,25 1,1 2,35 5,0 9,6 Δp (mm w.g.) size Kv H 0,25 H 1,1 2,35 5 9,6 Δp (kpa),000 5,000 2,000 1,000 Dp (size) 0 5 Δp (mm w.g.) size Kv H 0,25 H 1,1 2,35 5 9,6 Δp (kpa) 0 2 1,000 5,000 2,000 0,2 0,01 0,025 0,05 0,1 0,25 1 2,5 5 1,000 0 0 5 2 1 Example of correction for liquid with different density Liquid density ρ = 1,1 Kg/dm3 Measured head loss Dp Venturi = 4,5 kpa Reference head loss Dp = 4,5 / 1,1 = 4,1 kpa With this value you use the Venturi diagram for the dimension used or the formula (1.1) and obtain the corresponding flow rate G equal to 0,47 m3/h. 0,2 0,01 0,025 0,05 0,1 0,25 1 2,5 5 Dp measurement Connecting the measuring instrument to the low pressure connection of the Venturi device and to the high pressure connection of the PICV it is possible to measure the working Dp of the terminal unit circuit. DT measurement Connecting the measuring instrument by means of appropriate probes (optional) to any low pressure test port connection of the Venturi device and to one of the PICVs it is possible to measure the working DT of the terminal unit circuit.

bedroom PPLICTION DIGRMS bedroom Installation in false ceiling for fancoil service false ceiling in the entrance bedroom false ceiling in the entrance bedroom false ceiling in the entrance bathroom false ceiling in the entrance bathroom bathroom bathroom Installation for cold beams service

CCESSORI Code Voltage 1414 24 V 145 Proportional linear actuator for 145 series control valve. Electric supply: 24 V (ac/dc). Control signal: 0 V. mbient temperature range: 0 C. Protection class: IP 43. Connection: M 30 p.1,5 Supply cable length: 1.5 m. 130 Electronic flow rate and differential pressure measuring station. Supplied with shutoff valves and connection fittings. May be used for Dp measurements and setting of balancing valves. luetooth transmission between Dp measuring station and remote control unit. Versions with remote control unit with ndroid application for Smartphone and Tablet. Measurement range: 0 0 kpa. Static P max : 0 kpa. Electric supply from battery. 6562 Thermoelectric actuator. With opening position indicator. Quickcoupling installation, with clip adapter. With auxiliary microswitch. Electric supply: 230 V (ac) or 24 V (ac)/(dc). uxiliary microswitch contact rating: 0,8 (230 V). Running power consumption: 3 W. Starting current: 1. mbient temperature range: 0 C. Protection class: IP 54. Electric supply cable: 80 cm. Code 130006 with remote control unit, with ndroid app 130005 without remote control unit, with ndroid app Transmission via luetooth to the terminal with ndroid app (code 130006) Code Voltage 656212 230 V 656214 224 V 6562 230 V 6564 224 V without auxiliary microswitch without auxiliary microswitch Drain cock Transmission via luetooth to the terminal with ndroid app (code 130006) Code F0000680 F0000681 F0000682 3/4 M x quick connection 3/4 F 1 M x quick connection 1 F 11/4 M x quick connection 11/4 F 000 Couple of quickfit pressure/temperature ports. rass body. EPDM seals. Maximum working pressure: 30 bar. Working temperature range: 5 130 C. Connections: 1/4 M. Code 000

SPECIFICTION SUMMRY 149 series Connection and regulation kit for HVC terminal units in heating and cooling systems. Complete with: pressure independent control valve, threeway shutoff valves, integrated bypass, Venturi device with pressure test ports (only for dedicated versions), filtering cartridge and preformed shell insulation made of PPE. Sizes DN 15, DN and DN 25. Main connections on system side 1/2 F (from 1/2 to 1 ); terminal unit side 3/4 M (from 3/4 to 11/4 ). Connections centre distance: 80 mm. Pressure test port connections 1/4 F (ISO 2281) with cap (only for dedicated versions). Connection for code 1414 and 656 series thermoelectric actuators. M30 p.1,5. Flow rate adjustment range of the group with Venturi device: 0,02 0, m3/h (code 149..0 H); 0, 0, m3/h (code 149..0 H); 0, 0,40 m3/h (code 149..0 ); 0,40 0,80 m3/h (code 149..0 ); 0,80 1, m3/h (code 149..0 ); 1, 1,80 m3/h (code 149..0 ); 1,80 3,00 m3/h (code 149..0 ). Flow rate adjustment range of the group without Venturi device: 0,02 0, m3/h (code 149..0 H); 0,08 0,40 m3/h (code 149..0 ); 0,08 0,80 m3/h (code 149..0 ); 0,12 1, m3/h (code 149..0 ); 0,18 1,80 m3/h (code 149..0 ); 0,3 3,00 m3/h (code 149..0 ). Maximum flow rate, with 656. series thermoelectric actuator fitted, reduced by % (25% for code 149... 149...). Linear or equipotential flow rate adjustment characteristic, which can be set up by actuator depending on the characteristics of the terminal unit. Maximum working pressure 25 bar. Maximum differential pressure with actuator code 1414 (and 656. series) installed: 5 bar. Nominal operation Δp range 25 400 kpa. Working temperature range 1 C. mbient temperature range 0 C. Strainer mesh size 800 µm. Medium: water and glycol solutions; maximum percentage of glycol %. Dezincification resistant alloy body and adjustment headwork; stainless steel strainer mesh; EPDM diaphragm, obturator and seals. Code 1414 Proportional linear actuator for 145 series control valve. Proportional linear actuator. Electric supply 24 V (ac/dc). Power consumption 2,5 V (ac), 1,5 W (dc). Control signal 0 V. Protection class IP 43. mbient temperature range 0 C. Connection M30 p. 1,5. Electric supply cable length 1,5 m 6562 series Thermoelectric actuator, with position indicator. Normally closed, with auxiliary microswitch (code 656212/4). Selfextinguishing polycarbonate protective shell. Colour white RL 90 (code 6562/4), grey RL 9002 (code 656212/4). Electric supply 230 V (ac); 24 V (ac); 24 V (dc). Starting current 1. Running current 13 m 230 V (ac); 140 m 24 V (ac) 24 V (dc). Running power consumption 3 W. uxiliary microswitch contact rating (code 656212/4) 0,8 (230 V) Protection class IP 54. Made with double insulation. Medium working temperature range: 5 75 C. mbient temperature: operation 0 C EN 60721 33 Cl. 3K3, max. humidity 85%, transportation 70 C EN 6072132 Cl. 2K2, max. humidity 95%, storage 5 C EN 6072131 Cl. 1K2, max. humidity 95%. Opening/closing time from 1 to 180 s. Supply cable length 80 cm. To ENEC and SEV standard. Code 000 Couple of quickfit pressure/temperature ports rass body. EPDM seals. Working temperature range: 5 130 C. Max. working pressure: 30 bar. Code 130005 Electronic flow rate and differential pressure meter with no remote control unit, with ndroid app. Supplied with shutoff valves and connection fittings. Differential pressure 0 0 kpa. Static pressure: < 0 kpa. System temperature: 30 1 C. Code 130006 Electronic flow rate and differential pressure measuring station with remote control unit and with luetooth transmission. Supplied with shutoff valves and connection fittings. Differential pressure 0 0 kpa. Static pressure: < 0 kpa. System temperature: 30 1 C.

We reserve the right to make changes and improvements to the products and related data in this publication, at any time and without prior notice. Caleffi S.p.. S.R. 229 n. 25 280 Fontaneto d gogna (NO) Italy Tel. +39 0322 8491 Fax +39 0322 863723 info@caleffi.com www.caleffi.com Copyright 18 Caleffi