Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Similar documents
Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

EMPAC Metal enclosed capacitor bank for wind applications

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Product brochure. Gas-insulated switchgear ELK-04 C, 145 kv Modular and reliable

Descriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Product brochure. Gas-insulated switchgear ELK-04 C, 145 kv Modular and reliable

ABB central inverters PVS to 2091 kva

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

ZX-Family Gas-insulated medium voltage switchgear

OHB Outdoor sulphur Hexafluoride circuit-breaker

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

Solid Dielectric, Three Phase Reclosers CATALOG VS11

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com

Power IT MV Live Tank Vacuum Circuit Breaker. Model OVB-SDB

Product brochure. Gas-insulated switchgear ELK-4, 800 kv Pioneering technology for extra-high voltage applications

Type SDV7 distribution circuit breaker family

Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

Power IT MV Live Tank Vacuum Circuit Breaker Model VBF

Product Brochure. Generator Circuit-Breaker HVR-EBCB For hydro or pump storage power plant

SDV7. Outdoor distribution circuit breaker family 15.5 kv to 38.0 kv. usa.siemens.com/sdv7

Power Voltage Transformers for Air Insulated Substations

B kv Gas-insulated Substations

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Air-insulated switchgear UniGear type ZS1

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

Brochure. Modular Systems wind portfolio Power Collection and Grid Connection products

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

Low Voltage Systems MNS and MNS is PowerCenter

US Panorama. New SACE Emax 2 UL 1066 From Circuit Breaker to Power Manager

Outdoor live tank SF 6. circuit breaker Type OHB for 24/36/40.5 kv applications

Product Brochure. Gas-insulated Switchgear ELK-14 The modular system for GIS, 245 kv

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Product Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

MEDIUM VOLTAGE PRODUCT. TJC 4 Indoor voltage transformers

Cobra-S. Catalog Cobra-S

ZX2 Gas-insulated medium voltage switchgear

Mini Contactors Applications and Segments

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

PQstorI One stop solution for energy storage and power quality

Mini contactors B6, BC6 with 3 pole

Descriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

Type SDV7 distribution circuit breaker family Answers for energy.

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

Solid Dielectric, Single Phase Recloser

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

CP Automatic capacitor bank

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

Solid Dielectric, Single Phase Reclosers

Modular Capacitor Systems Reactive Compen. sation. Copyright 2002 ABB. All rights reserved.

Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance

Publication No.: PSG

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

Product Group Brochure. PS Range Capacitor Vacuum Switches

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Independent Testing Laboratory for High Voltage Equipment

B kv T&D GAS INSULATED SWITCHGEAR

3AP1 DTC for 145 and 245 kv

Low voltage bushings for pad-mounted distribution transformers Technical information guide

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

Gas Insulated Metal-clad Switchgear, HMGS!

Overview Gas Insulated Switchgear Modular and flexible, kV. ABB Group April 17, 2009 Slide 1

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

Transmission Switching

Marine generators Proven generators for reliable power on board

GE Electrical Distribution. Gerapid High Speed DC Circuit Breakers. On the move. imagination at work

Medium voltage vacuum circuit breaker. E-VAC series

Surge arrester POLIM-H..SD

Raising the bar. UHV switchgear and components

Contactor V-Contact VSC/P

More power for railway lines Maximum efficiency with proven system behavior

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

CPG.0 Single busbar gas-insulated cubicles

Low voltage capacitors CLMD Improving power factor and enhancing power quality of your network

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

Powering business worldwide

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

SACE Emax 2/ML Low-voltage air circuit breakers for naval applications

Voltage limiting device HVL

Short form catalogue Motor protection and control Manual motor starters

Voltage limiting device HVL

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

Live Tank Circuit Breakers Buyer s Guide

Transcription:

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility and industry customers to improve their performance while lowering environmental impact. A complete range of high voltage circuit breakers ABB offers the widest range of high voltage circuit breakers on the market. Our portfolio of dead tank circuit breakers ranges from 72.5 kv to 800 kv. The ABB Group of companies operates in approximately 100 countries and employs around 145,000 people. ABB has a long history of developing innovative technologies to address the changing demands of power systems. As these systems continue to evolve, switching solutions must be designed to meet present-day applications as well as anticipate the future state of the grid. 2 145PM40-C Dead Tank Circuit Breaker

Compact design with enhanced reliability ABB is proud to offer the Type 145PM40-C SF 6 Dead Tank Circuit Breaker, based on well-established interrupter and operating mechanism platforms. Standards The 145PM40-C Dead Tank Circuit Breaker is tested for high transient recovery voltage (TRV) performance and is certified for class C2 capacitive switching and class M2 mechanical endurance. ANSI/IEEE C37.09 ANSI/IEEE C37.04 ANSI/IEEE C37.06 ANSI/IEEE C37.06.1 IEC 62271-1 IEC 62271-100 Certifications ISO 9001 ISO 14001 OHSAS 18001 Applications The 145PM40-C was designed for: overhead transmission lines transformer applications capacitive switching applications Type PM circuit breaker family With just under 50,000 breakers delivered to date, spanning voltages up to 800 kv, the ABB type PM dead tank circuit breakers remain the most purchased brand in the industry. This is due to their low cost of ownership and strong performance, backed by industry-leading service and support. Benefits of ABB s advanced technology Common platform The design shares common features and existing technology with other ABB switchgear platforms, ensuring established and time-tested reliability. The 145PM40-C offers the most commonly purchased features as standard or available options. High performance and long life for all applications The 145PM40-C dead tank circuit breaker is certified for Class C2 capacitive switching and Class M2 mechanical endurance (10,000 operations). Our high performance, dual-motion self-blast interrupter achieves full ratings up to 145 kv, 40 ka. The breaker is designed for a design life of a minimum of thirty (30) years under normal operating environments. Environmental awareness The type PM uses SF 6 as the insulating medium. ABB has invested a great deal to reduce SF 6 leaks through design, manufacturing techniques and innovative monitoring technologies. The 145PM40-C also utilizes 20% less SF 6 than other state-of-the-art designs. Ease of installation and maintenance The type 145PM40-C is shipped completely assembled and filled with positive SF 6 pressure, allowing for the quickest installation time in the industry. Only standard tools are required for installation, inspection and normal maintenance and repair tasks. MSD mechanism The MSD mechanism incorporates proven design principles from ABB s earlier spring operating mechanisms, including stable, reliable, low power operating latches and cam disc operation for closing operation control. The MSD torsion spring operating mechanism is designed with a minimum of components, ensuring a high degree of total reliability and minimal need for maintenance. An important innovation of the MSD design is the use of the torsion springs for opening and closing energy storage. This allows for a very compact design, with both closing and opening springs contained within the operating mechanism. 145PM40-C Dead Tank Circuit Breaker 3

Features Tanks Single-piece tanks are ultrasonically cleaned. Each tank is ASME pressure vessel tested and certified, and receives a UM stamp. Control cubicle ABB prides itself on offering generously sized control cubicles at workable heights to vastly improve access to the equipment over its lifetime. Insulating medium The Type 145PM40-C uses SF 6 as the insulating medium. ABB has invested in monitoring technology, manufacturing techniques, and innovative designs to reduce SF 6 gas leaks. Single-piece interrupter Our single-piece high-performance modular interrupters employ state-of-the-art technology that minimizes line-ground insulation components. Bushings ABB offers a variety of bushing options, including silicone and porcelain insulators, to meet customer application needs and environmental conditions. ABB utilizes tapered designs, where feasible, to reduce the SF 6 volume and therefore installed inventory in our customer s fleet. Bushing current transformers ABB utilizes slipover bushing current transformer (BCT) designs for our dead tank product line which allow for cost effective, efficient and safe removal or exchange without removing the bushings. MSD1 mechanism The closing springs in the MSD1 mechanism generate the required driving force to close the circuit breaker and charge the opening spring. Immediately after each closing operation, a motor drives the spring charging gear to automatically charge the closing springs. After recharging the closing springs, the circuit breaker is capable of a rapid reclosing with a dead time interval of 0.3 s (i.e. O - 0.3 s - CO stored energy). 4 145PM40-C Dead Tank Circuit Breaker

Technical data Rated per ANSI and IEC standards Maximum continuous voltage kv 145 Operating frequency Hz 50 / 60 Interrupting time 3 cycles (50 ms) Impulse withstand voltage 2 µ-sec chopped wave kv Peak 838 Full wave lightning impulse (BIL) kv Peak 650 Power frequency withstand voltage 60 Hz 1 minute dry withstand kv 310 60 Hz 1 minute wet withstand kv 275 Continuous current A 2000, 3000, 3150 (2) Close and latch current ka 104 Short circuit breaking current ka 40 Minimum operating gas pressure @ 20 C psig / MPa, abs 72 / 0.60 Normal operating gas pressure @ 20 C psig / MPa, abs 87 / 0.70 Permissible ambient temperature C -40 to +55 (1) Interrupter enclosure dead tank Configuration 3 pole units on single frame Design outdoor Expected lifetime yrs 30 Dimensions (H x W x L) ft / mm 14.8 x 11.6 x 8.2 / 4330 x 3540 x 2500 Weight, SF 6 gas lbs / kg 46 / 21 Operating mechanism Type spring-spring, type MSD1 Quantity per breaker 1 Energy storage torsion spring Standard operating duty O-0.3s-CO-15s-CO Seismic rating 0.5g value per IEEE 693 Charging source universal motor Available voltages 48 VDC 110-125 VAC or VDC 220-250 VAC or VDC Power 900 W Charging motor Operating current 16 A @ 48 V 12 A @ 110 V 6 A @ 220 V Peak starting current 125 A @ 48 V 50 A @ 110 V 25 A @ 220 V Max recharge time 15 seconds Available voltages 48 VDC 110-125 VDC 220-250 VDC 10 A @ 48 V 2.1 A @ 110 V Trip Trip and close coils 4.4 A @ 110 V Current 2.0 A @ 220 V 10 A @ 48 V Close 2.1 A @ 110 V 4.4 A @ 110 V 2.0 A @ 220 V Above are not necessarily limiting values; further information available upon request. Notes (1) Requires tank heaters on applications with ambient temperatures less than -30º C (2) Limited continuous current ratings at greater than +40 C 145PM40-C Dead Tank Circuit Breaker 5

Dimensions and specifications 139.64 (3547) SHIPPING AND INSTALLED WIDTH 69.13 (1756) PHASE SPACING 55.86 (1419) METAL TO METAL 168.19 (4272) INSTALLED HEIGHT 106.77 (2712) MIN DISTANCE TO UNDERGROUND PARTS MIN BUSHING HEIGHT 147.36 (3743) HEIGHT TO LIVE 51.54 PARTS (1309) HEIGHT TO BOTTOM OF CONTROL CABINET 44.25 (1124) HEIGHT OF EXTENSION LEGS 158.35 (4022) TOP OF TERMINAL PAD 95.70 (2431) SHIPPING AND INSTALLED LENGTH 61.37 (1559) PHASE SPACING 49.61 (1260) METAL TO METAL Physical data Height - installed Width - installed Length - installed Footprint of frame Phase spacing Minimum height to ungrounded parts Shipping weight Typical installed weight with porcelain bushings and maximum BCT s 168.19 in (4272 mm) 139.64 in (3547 mm) 95.70 in (2431 mm) 60.23 in x 46.14 in (1530 mm x 1172 mm) 69.13 in (1756 mm) 106.77 in (2712 mm) 5860 lbs (2658 kg) 6070 lbs (2753 kg) 92.91 (2360) q OF BREAKER 6 145PM40-C Dead Tank Circuit Breaker

/ Protection and control interfaces Typical electrical drawings (+) 21 (+) 1 5A 52X1 52X1 23-1 9A 52Y1 5B 120 / 240 VAC 42-1 42-1 88-1 CABINET HEATER 75 W CABINET HEATER 75 W 125 / 250 VDC 11A 52A 52A 125 / 250 VDC 52B 52Y1 52Y1 52B 52B 52Y1 52X1 52CC-1 52TC1 63 (LOW GAS) 63 (LOW SPRING) (-) 22 (-) 2 AC schematic 42-1 Motor contactor 88-1 Motor 23-1 Non-adjustable thermostat Notes: 1) Secondary trip is same as primary Primary DC trip 9A 11A Remote trip pole 1 52A Auxiliary switch contact 52TC1 Trip coil DC close - pole 1 52X1 X relay, closing 52Y1 Y relay, anti pump 52B Auxiliary switch contact 5A 5B Remote close and reclose 52CC-1 Close coil 63 Permissive contact / alarm contact Typical controls features Accessory Dual trip coils 125 VDC AC / DC transfer Mini-monitor EB-27 CT terminal blocks Cabinet light - door activated 20 A GFI (cabinet exterior) Non-insulated wire terminals Fused knife switches Open/close push buttons Undervoltage relays Local remote switch Screw down device nameplates Popular CT options Accuracy ANSI Ratio Relaying Metering IEC 600:5 MR C-400 / C-800 0.3B-0.5 5P10@15VA 1200:5 MR C-400 / C-800 0.3B-1.0 CLASS 0.5@30VA 2000:5 MR C-400 / C-800 0.3B-1.0 10P20@50VA 3000:5 MR C-400 / C-800 0.3B-1.8 CLASS 0.5@30VA 4000:5 MR C-400 / C-800 0.3B-2.0 CLASS 0.2@15VA 145PM40-C Dead Tank Circuit Breaker 7

Shipping and installation With the exception of the high voltage terminals and extension legs, the type 145PM40-C ships fully assembled with positive gas pressure. For domestic deliveries, all components are transported to the customer on a single-drop, air ride trailer. Weight of gas at shipping pressure is provided with test report. Installation and commissioning The compact design is ideal for new or existing substation layouts for voltages up to 145 kv. The breaker fits within most existing footprints and can be used to quickly address the need for greater protection for minimal cost. Those familiar with the PM line of breakers can typically install and commission the breaker within 2 days given a prepared foundation. ABB offers supervision, installation, commissioning, and maintenance service on all ABB breakers. Representative installation of a 145 kv PM breaker in the United States. 8 145PM40-C Dead Tank Circuit Breaker

Notes 145PM40-C Dead Tank Circuit Breaker 9

Contact us ABB Inc. High Voltage Products - Dead Tank Breakers 100 Distribution Circle Mount Pleasant, Pennsylvania 15666, USA Phone: +1 (724) 696-1500 Fax: +1 (724) 696-1502 www.abb.us/highvoltage Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction in whole or in parts is forbidden without ABB s prior written consent. Copyright 2016 ABB. All rights reserved. Document Number: 2GNM110151 / April 2016