April 2004 / BULLETIN for Supermarket Systems DDR-20 OLDR-15

Similar documents
Condensed Catalog 410A January 2008

t EVAPORATOR PRESSURE REGULATING VALVES

Defrost Differential Pressure Regulating Valves Installation and Service Instructions

Hot gas bypass regulator type CPCE Liquid gas mixer type LG (accessory)

The System Features These Advantages: Designing the Low Pressure Oil Return System

611H Flo-Con Pressure Regulators & Valves

Pulse Width Modulation Valves. Models SPW-0 thru -7

April 2007 / BULLETIN Solenoid Valves. The right solenoid valve for any job.

Refrigeration Solenoid Valves & 3-Way Heat Reclaim Valves

Subcritical CO 2 Innovations

PRODUCT DATA HDF SERIES Solenoid Valve

Solenoid Valves. Installation and Servicing Instructions SD-15/ TYPES B6, B9, B10, B14, B19, B25 SERIES (Brass Connections) GENERAL

November 2015 / BULLETIN Solenoid Valves. Installation and Servicing Instructions ENGINEERING YOUR SUCCESS

(S)PORT - (S)PORT-II Evaporator Pressure Regulators

3-Way Valves. Installation and Servicing Instructions

Solenoid valve for R410A and R744 Types EVR 2 - EVR 6 and EVRH 10 - EVRH 40

Solenoid valves type EVR 2 40 NC / NO

MAKING MODERN LIVING POSSIBLE. Solenoid valves Type EVU for fluorinated refrigerants REFRIGERATION AND AIR CONDITIONING.

EVAPORATOR PRESSURE REGULATORS

Specifications, Applications, Service Instructions & Parts. Flanged and Weld-in 3/4" thru 4" Port (20 mm thru 100 mm) for Refrigerants

Thermostatic and Automatic Expansion Valves

Pilot operated main valves for regulating pressure and temperature, type PM

Danfoss Saginomiya 4 - Way Reversing Valves

Crankcase Pressure Regulating Valves

Electrical Control Valves Series EX4, EX5, EX6, EX7 & EX8

Solenoid valve. Solenoid Coil

Solenoid valve Types EVR 2 EVR 40 NC/NO

Reliable season change

Sporlan Gas Cooler/ Flash Gas Bypass Valves

EX4 / EX5 / EX6 / EX7 / EX8 Electrical Control Valves

Solenoid valves Type EVU for fluorinated refrigerants

Solenoid valves Type EVR 2 40 NC/ NO REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Electrical Control Valves

Low Profile Unit Coolers

SOLENOID VALVES SOLDER CONNECTIONS

Reliable season change

Solenoid valves. Solenoid valves, type PKVD Solenoid valves, type EVR NC / NO

Why and how to adjust a TXV / TEV

800SVRM-7 5/04 RATE-OF-FLOW CONTROL 800 SERIES CONTROL VALVES

ANSI/AHRI Standard 760 (I-P) 2014 Standard for Performance Rating of Solenoid Valves for Use with Volatile Refrigerants

Pilot controlled servo valves Type ICS - Solenoid Valves Pressure Regulating Valves. Technical leaflet MAKING MODERN LIVING POSSIBLE

Pilot Controlled Servo Valves ICS

Solenoid valves type EVRA 3 to 40 and EVRAT 10 to 20

Electrically Operated Expansion Valve Types AKV 10, AKV 15 and AKV 20

THERMOSTATIC EXPANSION VALVES

Pilot-operated servo valve Type ICS

Appendix A. Standard Symbols for Hydraulic Components

Solenoid valves Type EVU

Industrial Refrigeration Control Valves. Catalog C12

Product Guide for HFO / HFO Blends. R448A/R449A R450A/R513A R1234ze. R134a R407A/F R404A/507 R12/502

Pilot-operated servo valve Type ICS

Copeland Screw TM Compressors

Alco Controls. Components for the Refrigeration Industry. Product Selection Catalogue

Parker TEV Model Visual

PRESSURE REDUCING VALVE

PRESSURE REDUCING VALVE

BULLETIN Type A4AM. March 2002 Installation, Service and Parts Instruction. Refrigerating Specialties Division Fig.

MODULOAD CAPACITY CONTROL FOR 3D COMPRESSORS

Solenoid valves type EVSA 25 50

Pressure and temperature regulators, type PM, and pilot valves

(770) Turning Parts Changers Into TROUBLESHOOTERS!

REFRIGERATION STRAINERS

Pilot-operated servo valve Type ICS

Electric Expansion Valve Type AKVO 10

PRESSURE REDUCING CONTROL VALVE

Capacity regulators (hot gas bypass) PMC and CVC

Solenoid valves EVRA and EVRAT

Rack Oil regulation and System Oil Failures

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

Product Guide for HFO / HFO Blends. R448A/R449A R450A/R513A R1234ze. R134a R407A/F R404A/507 R12/502

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 13 Pumps and Accessory Equipment Revised

DIFFERENTIAL PRESSURE RELIEF REGULATOR TYPE A4AL Port Size 3/4"- 4" (20-100mm) For Ammonia, R-22, R134a, R404a, R507 and other common refrigerants.

Replacing the Internal Oil Filter Elements for HS85 and OS 85 Screw Compressors

2003 Explorer Sport/Sport-Trac Workshop Manual. 7. Disconnect the vacuum harness connector. Remove the nut.

HFK. Balanced Port Thermo Expansion Valve Kits. Save Inventory $ and Valuable Truck Stock Space

P SERIES INTENSIFIER PUMP

2003 Mustang Workshop Manual

Section Va: Valve Actuators

June 2015 / BULLETIN Catch-All. Liquid & Suction Line Filter-Driers FILTER-DRIERS. It s the CORE that counts!

Solenoid valves, type EVRA 3 40 and EVRAT REFRIGERATION AND AIR CONDITIONING. Technical leaflet

AE R5 February 1997 Reformatted November 2010

Electric Expansion Valves

Adjustable Differential Relay A1

Section 6.1. Implement Circuit - General System. General: TF Configuration TB Configurations Implement Control Valve:

Sporlan V-Series Ruby Seat Solenoid Valves

EMERSON CLIMATE TECHNOLOGIES-EX

Steel Suction Line Accumulators

Specifications, Applications, Service Instructions & Parts. HCK1, HCK1W PISTON-TYPE CHECK VALVE ¾" thru 6" (20 thru 150 mm)

Section 6.1. Implement Circuit - General System. General: Implement Control Valve:

Mustang Series PRESSURE REDUCING CONTROL VALVE. M115 (Globe) M1115 (Angle) Schematic. Standard Components. Options & Accessories.

Application Data CONTENTS. COMPRESSOR PHYSICAL DATA (Table 1) Table 1 Open-Drive Compressors

Multi Ejector Solution TM for R744 (CO 2 ) Product type - CTM 1 and CTM 2 Liquid Ejector

V46 Series Pressure-Actuated Water-Regulating Valves

Electric expansion valves Types AKVA 10, 15 & 20

WATER COOLED AIR CONDITIONING UNITS MODEL CVWSEK-060 WATER SIDE ECONOMIZER FOR CSV060B VERTICAL R-410A STYLE B R-410A

Eclipse 2000 Service Parts

SOLENOID VALVES FOR REFRIGERATING SYSTEMS

Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.

Corp L3 Revised CB17/CBH17 SERIES UNITS SPECIFICATIONS CB17-95V CBH17-95V

3-Way Valves. Installation and Servicing Instructions

Transcription:

April 2004 / BULLETIN 90-50 for Supermarket Systems DDR-20 OLDR-15

Page 2 / Bulletin 90-50 SPORLAN DEFROST DIFFERENTIAL PRESSURE REGULATING VALVES OFFER THESE BENEFITS: Able to maintain a differential pressure between the defrost header and the liquid header, allowing reverse flow during the defrost cycle. Combines a liquid differential valve and a solenoid valve into one component, thus reducing piping costs. Ability to adjust the differential setting from 5 to 50 psid. In many supermarket applications refrigerant gas from the discharge line, or from the top of the receiver, is used for defrost. This method of defrost diverts a portion of the hot gas or cool gas (from the top of the receiver) to the suction line, and back through the evaporator being defrosted. The gas condenses in the evaporator and flows in reverse, through a check valve, around the TEV and liquid line solenoid valve. Liquid refrigerant then flows to the liquid header where it is distributed to evaporators not in the defrost cycle. In order for reverse flow to occur, the pressure of the defrost header must be greater than the pressure of the liquid header. The difference in pressure is known as the defrost differential. Several methods are used to obtain the defrost differential. A common liquid line method is to install a differential check valve in parallel with a solenoid valve between the receiver and the liquid header. When the solenoid valve is closed during defrost, it allows the differential check valve to control the receiver at a greater pressure than the liquid header. Sporlan offers the (O)LDR-15, (O)LDR-20, XTM and XTO versions for this application. The (O)LDR, XTM or XTO valves combine the features of the liquid differential check valve and the solenoid valve into a single component. A discharge line method is to install a discharge differential pressure regulating valve in the discharge line before the condenser. In order for the reverse flow of hot gas to occur, the pressure of the discharge gas (defrost header) must be greater than the pressure of the receiver (liquid header). Sporlan offers the DDR-20 for this application. A solenoid feature allows the valve to control the differential when the coil is de-energized and to operate full open when the coil is energized. OPERATION (O)LDR, XTM AND XTO VALVE DESIGN & OPERATION The (O)LDR is designed to maintain a differential pressure between the receiver and the liquid header. A pilot differential valve controls the (O)LDR by varying the pressure on top of the main piston. These valves are available in two port sizes, the (O)LDR-15 (1") and the (O)LDR-20 (1-5/16"). Inlet pressure enters the pilot assembly through a passageway in the valve body on the (O)LDR-15, and through an external tube connected to the inlet fitting on the (O)LDR-20. The outlet on the pilot differential valve is connected to the outlet fitting with an external tube on both valves. Sporlan liquid line differential valves have a solenoid bypass feature that allows the valve to remain full open or modulate to maintain a differential. We supply two versions of liquid line differential valves: The OLDR is in the full open position when the coil is de-energized (Figure 3), and it is in the differential operation mode when the coil is energized (Figure 1). The OLDR uses the coil. Refer to Bulletin 30-10 for more information on Sporlan solenoid coils. The LDR is in the differential operation mode when the coil is de-energized (Figure 2), and it is in the full open position when the coil is energized (Figure 4). The LDR uses the coil. Refer to Bulletin 30-10 for more information on Sporlan solenoid coils. The XTM operates identically to the LDR-15 and the XTO operates identically to the LDR-20. The special feature of the XTM and XTO versions are the unique outlet fitting configurations. Different outlet fittings are indicated by a suffix -1, -4, or -5 (i.e. the XTM-1 has connections 1-3/8" ODF x 1-3/8" ODF 90 elbow). For piping considerations, if replacement is necessary, an exact replacement is best. The internal parts are interchangeable between the LDR-15 and the XTM, and between the LDR-20 and XTO. Refer to the Specification table on page 8 for further details, and Bulletin 90-51 for service and installation instructions. (O)LDR, XTM AND XTO DIFFERENTIAL OPERATION OLDR - Coil Energized LDR, XTM and XTO - Coil De-energized The plunger lifts off the pilot port, allowing inlet pressure to enter the chamber on top of the main piston. It then bleeds out through the pilot differential valve (See Figures 1 and 2). When the differential pressure across the valve is below the setting of the pilot differential valve, the pilot differential valve modulates closed. Closing the pilot differential valve allows pressure to build on top of the main piston. As this FOR USE ON REFRIGERATION and/or AIR CONDITIONING SYSTEMS ONLY Bulletin 90-50, April 2004, supersedes Bulletin 90-50, dated May 1999, and all prior publications. Copyright 2004 By Sporlan Company, Washington, MO 63090

Bulletin 90-50 / Page 3 Coil Energized OLDR-20 Differential Operation Coil De-Energized OLDR-20 Full Open Operation Coil Coil Pilot Port Pilot Differential Pilot Port Pilot Differential P2 Spring Strainer P2 Spring Strainer Figure 1 Figure 3 Coil De-energized LDR-20 & XTO Differential Operation Coil Energized LDR-20 & XTO Full Open Operation Coil Coil Pilot Port Pilot Differential Pilot Port Pilot Differential P2 Spring Strainer P2 Spring Strainer Figure 2 Figure 4 pressure () approaches the inlet pressure (), the force, combined with the force from the spring (P2), pushes the piston down, modulating the valve in the closing direction. As the differential pressure rises above the pilot differential valve setting, the pilot differential valve modulates open. This bleeds refrigerant from the chamber on top of the piston at a faster rate than refrigerant is entering, so the pressure () decreases. As this pressure () plus the pressure from the spring (P2) falls below the inlet pressure (), the inlet pressure pushes the piston up, modulating the valve open. The valve will open only as far as necessary to maintain the pilot differential valve setting. The pilot differential valve will then modulate the piston from partially open to partially closed to maintain the valve setting. (O)LDR, XTM AND XTO FULL OPEN OPERATION OLDR - Coil De-energized LDR, XTM and XTO - Coil Energized The plunger moves down to close the pilot port, stopping all flow to the chamber above the piston. The refrigerant remaining above the piston then bleeds to the valve outlet through an orifice (bleed hole) in the pilot differential valve piston. The pressure in the chamber () decreases so the inlet pressure () moves the piston up and the valve opens (See Figures 3 and 4). DDR-20 VALVE DESIGN AND OPERATION The DDR-20 is designed to create a differential pressure between its inlet (discharge) pressure and the receiver pressure. The pilot differential valve controls the DDR-20 by varying the pressure on top of the main piston. The pilot differential valve senses receiver

Page 4 / Bulletin 90-50 pressure through a field installed pilot line connecting the pilot differential valve to the receiver. Inlet pressure enters the pilot assembly through an external tube. This inlet pressure bleeds through a fixed restrictor to the top of the main valve piston. Pressure on top of the main piston is bled off through the pilot differential valve. A solenoid bypass feature is incorporated in the valve so that the valve will modulate fully open when there is no need to create a differential. Energizing the solenoid coil opens the valve fully. The DDR-20 uses the coil. Refer to Bulletin 30-10 for more information on Sporlan solenoid coils. DDR-20 DIFFERENTIAL OPERATION Coil De-energized The kick-off spring forces the pin and plunger down, closing Port A and opening Port B. Discharge gas enters the chamber on top of the piston through Port B, and is bled out through the pilot differential valve, to the receiver (See Figure 5). When the differential pressure between the discharge line and the receiver is below the setting of the pilot differential valve, the pilot differential valve modulates closed. Closing the valve allows pressure to build on top of the main piston. As this pressure () approaches the inlet pressure (), the force, combined with the force from the spring (P2), pushes the piston down, modulating the valve closed. As the differential pressure rises above the pilot differential valve setting, the pilot differential valve modulates open. The open pilot differential valve bleeds refrigerant from the chamber on top of the piston at a faster rate than refrigerant is entering, therefore the pressure decreases. As this pressure () plus the pressure from the spring (P2) falls below the inlet pressure (), the inlet pressure pushes the piston up, modulating the valve open. The valve opens only as far as necessary to maintain the pilot differential valve setting. The pilot differential valve then modulates the piston from partially open to partially closed to maintain the valve setting. DDR-20 FULL OPEN OPERATION Coil Energized Energizing the solenoid pulls the pin and plunger up, opening Port A. The discharge gas entering the pilot assembly then forces the small ball up to close Port B (See Figure 6). When Port B is closed, discharge gas can no longer enter the chamber on top of the main piston. The pilot differential valve closes, and refrigerant from the top of the piston bleeds to the suction line through Port A and Fitting C. This decreases pressure in the chamber (), so the inlet pressure () moves the piston up and the valve opens. APPLICATION Defrost Differential Pressure Regulating s are used on supermarket systems to allow reverse flow of refrigerant gas through the suction line and evaporator during a defrost. The valves accomplish this by maintaining the defrost header at a greater pressure than the liquid header. Correct application depends Figure 5 Coil De-Energized Differential Operation Figure 6 Coil Energized Full Open Operation Top View Fitting "C" to Suction To Receiver Fitting C Fitting "C" to Suction To Receiver 200 Mesh Strainer 200 Mesh Strainer P2 (Spring) P2 (Spring) Port A Port B Port A Port B

Bulletin 90-50 / Page 5 on several factors. Either of the two types of defrost differential pressure regulating valves (liquid line or discharge line) can be applied on supermarket systems. However, the two types cannot be applied on the same system. LOCATION AND PIPING The (O)LDR, XTM and XTO valves are located between the receiver and the liquid header (See Figure 8). The DDR-20 is located in the discharge line before the condenser (See Figure 7). The two types of defrost differential valves (liquid line and discharge line) cannot be applied on the same system. Sporlan recommends consulting recognized piping references for assistance in piping procedures. Sporlan is not responsible for system design, any damage arising from faulty system design, or for misapplication of its products. If these valves are applied in any manner other than as described in this bulletin or other Sporlan literature, the Sporlan warranty is void. IMPORTANT: There are two pilot lines from the DDR- 20 that must be installed in the field for the valve to operate properly. The 1/4 SAE fitting on the pilot dif- ferential valve must be connected to the receiver. The second 1/4 SAE fitting, located below the solenoid coil (Fitting C), must be connected to the suction line. The pilot line to suction is not a constant high to low side bleed. It only bleeds the small amount of refrigerant from the top of the valve s main piston to open the valve when the solenoid coil is energized. Once the valve is open, and at all other times, there is no high to low side bleed. When the valve is modulating, the bleed through the pilot differential valve is to the receiver. ADJUSTMENT RANGE AND PRESSURE SETTINGS All defrost differential valves are set by turning the adjusting stem located under the cap on the pilot differential valve. The adjustment range is 5 to 50 psig. The (O)LDR, XTM and XTO have a factory setting of 18 psid, and the DDR-20 has a factory setting of 30 psid. Turning the stem clockwise increases the setting, counterclockwise decreases the setting. Adjustments must be made with the valve in its differential mode and no refrigerated cases in defrost, so that the head pressure is normal. Complete instructions on setting the valves are given in Bulletin 90-51. Figure 7 Typical Piping Diagram with DDR-20 Discharge Differential Regulator DDR-20 Discharge Differential Regulator 8D, 12D, 16D, Heat Reclaim Normal Condenser ORI Head Pressure Control OCV, Oil Check OR-1-1/2 Oil Reservoir Check Reclaim Condenser Type ORD-4 Discharge Bypass Receiver Pressurization Suction Filter Oil Filter PIPING KEY Oil Level Control Oil Separator Suction Discharge Liquid Oil Suction Header Defrost Header Restrictor of some type may be required Suction Throttling or Solenoid Stop for Defrost 2-Way Solenoid Defrost CDS-9 Step Motor Evaporator Control 2-Way Solenoid Defrost Reclaim Condenser Pump-out Solenoid (normally open) Evaporator Evaporator Catch-All Distributor TEV Check TEV Check See All Liquid Line Solenoid Check Liquid Header Liquid Line Solenoid with Check Feature (CE Series) Receiver

Page 6 / Bulletin 90-50 Figure 8 Typical Piping Diagram with (O)LDR-20 Liquid Differential Regulator 8D, 12D, 16D, Heat Reclaim Normal Condenser ORI Head Pressure Control OCV, Oil Check OR-1-1/2 Oil Reservoir Check Reclaim Condenser Type ORD-4 Discharge Bypass Receiver Pressurization Suction Filter Oil Filter PIPING KEY Oil Level Control Oil Separator Suction Discharge Liquid Oil Suction Header Defrost Header Restrictor of some type may be required Suction Throttling or Solenoid Stop for Defrost 2-Way Solenoid Defrost CDS-9 Step Motor Evaporator Control 2-Way Solenoid Defrost Reclaim Condenser Pump-out Solenoid (normally open) Evaporator Evaporator Catch-All Distributor TEV Check TEV Check See All Liquid Line Solenoid (O)LDR Liquid Differential Regulator Check Liquid Header Liquid Line Solenoid with Check Feature (CE Series) Receiver SELECTION Selection involves five basic system criteria: 1. Refrigerant 2. The type of Defrost Differential (Liquid Differential Pressure Regulating or Discharge Differential Pressure Regulating ) 3. Allowable design pressure drop across the valve 4. Liquid temperature 5. Common suction temperature A normally open OLDR version or an LDR version (differential mode when the coil is de-energized) must be determined if a liquid differential pressure regulating valve is desired. Example: Select a Liquid Defrost Differential Pressure Regulating for a 40 ton R-22 supermarket system with a liquid temperature of 90 F and a common suction temperature of 0 F. From the capacity table on page 7, the (O)LDR-15 has a capacity of 46.9 tons at a 2 psi pressure drop. The correction factor for 90 F liquid is 1.06, and the correction factor for 0 F suction is 0.91. Therefore 46.9 tons multiplied by 1.06 and 0.91 is equal to 45.2 tons. The OLDR-15-5/50 is the appropriate selection. Example: Select a Discharge Differential Pressure Regulating for a 20 ton R-404A supermarket system with a liquid temperature of 60 F and a common suction of -20 F. From the capacity table on page 7, the DDR-20 has a capacity of 18.7 tons at a 2 psi pressure drop. The correction factor for 60 F liquid is 1.43 and the correction factor for -20 F suction is 0.85. Therefore 18.7 tons multiplied by 1.43 and 0.85 is equal to 22.7 tons. The DDR-20-5/50 is the appropriate selection.

Bulletin 90-50 / Page 7 CAPACITIES - TONS OF REFRIGERATION REFRIGERANT 22 134a 404A/507 PRESSURE DROP ACROSS VALVE - psi. 5 1 2 3 4 5. 5 1 2 3 4 5. 5 1 2 3 4 5 TYPES LDR-15, OLDR-15 & XTM 33. 2 46. 9 57. 6 66. 5 74. 3 31. 0 43. 9 53. 8 61. 2 69. 5 22. 0 31. 1 38. 1 44. 0 49. 2 TYPES LDR-20, OLDR-20 & XTO 73. 4 104 127 147 164 68. 7 97. 1 119 136 154 48. 6 68. 7 84. 2 97. 3 109 TYPE DDR-20 10.3 14. 6 20. 6 25. 1 29. 0 32. 3 8.57 12. 1 17. 0 20. 8 24. 0 26. 6 9.35 13. 2 18. 7 22. 8 26. 3 29. 3 Capacities are based on 40 F evaporator temperature, 100 F condenser temperature, 25 F superheated return gas, discharge gas temperature 50 F above isentropic compression. For capacities at other liquid or evaporator temperatures use multipliers in table below: REFRIGERANT LIQUID TEMPERATURE F REFRIGERANT LIQUID TEMPERATURE CORRECTION FACTORS 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 22 1.56 1.51 1.45 1.40 1.34 1.29 1.23 1.17 1.12 1.06 1.00 0.94 0.88 0.82 0.76 134 1.70 1.56 1.49 1.42 1.36 1.29 1.21 1.14 1.07 1.00 0.93 0.85 0.78 0.71 404A 2.04 1.94 1.84 1.74 1.64 1.54 1.43 1.33 1.22 1.11 1.00 0.89 0.77 0.65 0.53 EVAPORATOR TEMPERATURE CORRECTION FACTORS EVAPORATOR TEMPERATURE F 40 30 20 10 0 10 20 30 40 Multiplier 0.80 0.83 0.85 0.88 0.91 0.93 0.95 0.98 1.00 DESIGNATION / ORDERING INSTRUCTIONS Select from the capacity table above. When ordering be sure to give complete valve designation including voltage and cycles. OLDR O LDR 15 5/50 1-3/8 ODF 120/50-60 Normally Open DDR Liquid Differential Regulator Size Adjustment Range - psi Connections - Inches Electrical Specifications DDR 20 5/50 1-5/8 ODF 120/50-60 Discharge Differential Regulator Size Adjustment Range - psi Connections - Inches Electrical Specifications

Page 8 / Bulletin 90-50 VALVE TYPE PORT SIZE Inches * Add 1 pound for solenoid coil. The XTM-1, XTM-5, XTO-1 and XTO-4 are Underwriters Laboratories Listed under Guide No. YIOZ, File No. MH4576. Maximum Rated Pressure of 400 psig. MOPD of 300 psig. OLDR-15 DIFFERENTIAL SETPOINT RANGE SPECIFICATIONS CONNECTIONS - Inches INLET x OUTLET DIMENSIONS - Inches COIL A B C D Net WEIGHT - lbs* Shipping OLDR-15 1-1/8 ODF x 1-1/8 ODF 10.06 5.00 2.62 4 5 1 or LDR-15 1-3/8 ODF x 1-3/8 ODF 10.06 5.56 2.62 4 5 OLDR-20 1-5/8 ODF x 1-5/8 ODF 11.06 1.77 5.56 3.34 9 10. 5 1-5/16 or LDR-20 2-1/8 ODF x 2-1/8 ODF 11.06 1.77 6.12 3.34 9 10. 5 XTM-1 5/50 psi 1-3/8 ODF x 1-3/8 ODF, 90 Elbow 9.22 5.56 2.62 4 5 1 XTM-5 1-1/8 ODF x 1-3/8 ODF, 90 Elbow 9.22 5.56 2.62 4 5 XTO-1 1-5/8 ODF x 1-5/8 ODF, 90 Elbow 10.38 1.77 6.12 3.34 9 10. 5 1-5/16 XTO-4 2-1/8 ODF x 2-1/8 ODF 11.06 1.77 6.12 3.34 9 10. 5 DDR-20 1-5/16 1-5/8 ODF x 1-5/8 ODF See drawing below 9. 5 10. 5 C XTM C B A D NOTE: (O)LDR-15 size valves do not have the tube from inlet fitting to pilot assembly. Inlet pressure enters the pilot assembly through a passageway in the valve body. DDR-20 3.19 A 2.06 D B 8.56 4.50 1.80 4.44 5.93 5.87 5.53 5.53 PRINTED IN U.S. OF A. 25-404