Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

Similar documents
A200 NEMA Contactors and Starters A200

Motor Control. Motor Control Electrical Aftermarket Products and Services Contents

Installation Sheet January, 2016 Supersedes February, 2013

Installation Sheet January, 2016 Supersedes June 2013

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

NEMA Contactors & Starters (Freedom)

Instructions for Replacing

3. Coils shall be of molded construction

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Multi-Pak Group Control

Bussmann series Quik-Spec Power Module Switch elevator disconnect

A. Submit manufacturer's literature and technical data before starting work.

Enclosures. See Section Typical Description

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

Horizontal Circuit Switchers

MAGNETIC MOTOR STARTERS

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

Contactors & Starters Index

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Industrial Control Transformers

Horizontal Circuit Switchers

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

SECTION MOTOR CONTROL

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

4.4. Definite Purpose Contactors and Starters A Starters A27, B27. NEMA Type 1 Enclosed Control

Instructions for Type W Three Phase, Standalone Overload Relays, Size 1 through 6

TA Ta VA CTRL-XFRMR

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

Two-way cable interlock kit for Magnum fixed circuit breakers

IEC Utilization Categories (Explanation)

OTEC Transfer switch open transition

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

TO COME. CEP7 Solid-State Overload Relay for Motor Control Centers and Enclosed Control

Application Description

SECTION PANELBOARDS

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

NEMA Full Voltage Power Devices. Section 1. Control Catalog 1-1

Two-way cable interlock kit for Magnum drawout circuit breakers

Transfer switch OTEC open or delayed transition

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

COM Overcurrent Relay

contactor may be required to interrupt up to 200% current. The N.O. contacts are equipped with permanent magnet blowouts to meet this requirement.

Ampgard medium voltage motor control renewal parts

J lh. NEMA AC Contactors for Motor Loads (Bulletin 500) and Non-motor Loads (Bulletin 500L) Sizes 0 through 4 (all series), Size 5 (series L)

AC Relays. Type IC5182. Ordering Information. Control Power Requirements. Contact Ratings (Amperes)

920 Remote Control Switches

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION MOTOR CONTROLLERS

IN2 Enclosed Switches and Circuit Breakers

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

RENEWAL PARTS AK-2-15 AK-2-25 AK-3-25 AKF-2-25 AK-2A-15 AK-2A-25 AK-3A-25 AKF-2A-25 AKU-2-25 AKU-3-25 AKU-2A-25 AKU-3A-25

Definite Purpose Contactors and Starters

Q and M-Frame Circuit Breaker Instruction Leaflet for Installation and Operation for Thermal Magnetic Trip Units

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories

VacClad-W type VCP-W 5 and 15 kv, 36-inch-wide switchgear components

Synergy EN product information

Installation Instructions for JDB, JD, HJD, JDC, JW HJW, JWC Circuit Breakers and Molded Case Switches

B CW POWER RELAY

Magnetic Overload Relays

TABLE I. AMPGARD EQUIPMENT RATINGS

Transfer switch OTEC and OTECSE open transition

Design Standard. Purpose: Design Standard:

Control Circuit Protection

AF series contactors (9 2650)

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

Size 3 and 4 Starter. Reversing Catalog Number as specified in table below. Catalog Number. Price U.S. $ W201K1CF W201K1CN W201K2CF W201K2CN

SIGNAL WORDS QUALIFIED PERSON

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Coil Data Nominal Current MA Nominal VA Sealed Single Pole Normally Open (SPNO) White Rodgers Q

CR193 Vacuum Limitamp* Contactors

Overload Relay Heater Tables

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

Coil Data Nominal Current MA Nominal VA Sealed. Coil Data Nominal Current MA Nominal VA Sealed. Single Pole Double Throw (SPDT)

SECTION MOTOR CONTROLLERS

Motor Protection. Presented By. Scott Peele PE

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GEF Renewal Pans. low Vohage Power Circuit Breakers. Type AKR-30S and AKRU-30S. www. ElectricalPartManuals. com

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

Bolted contact switches. Pringle switches

I.L. 29C121A WARNING 1. INTRODUCTION. Maximum Freq. Maximum Dielectric Voltage Current Withstand (V) (A) Voltage (V)

28.1. NEMA Contactors and Starters. Contents. Contactors Non-Reversing and Reversing. Freedom Series. Product Description

Wiring Diagrams DIAGRAM INDEX

Certi cation Record INDUSTRIAL CONTROL EQUIPMENT Motor Controllers Magnetic

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits

3.1. NEMA Manual Starters. Contents Description Types B230, B330, Switches... MS Series, Single-Phase Starters...

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

Transcription:

Instruction Leaflet IL0330300E Supersedes I.L. 7055C, Pages 8, Dated June 998 Instructions for A00, A0, A50 size 6, two- or three-pole non-reversing or reversing motor controllers Contents Description Page The controller............................ Installation............................... Type B overload relay...................... 3 Type A overload relay...................... 3 Overload relay heaters..................... 3 Type GCO current transformers.............. 4 Coverage................................ 4 Control relay............................. 4 Auxiliary contacts type J................... 6 Line and load terminals..................... 6 Mechanical interlocks...................... 6 Maintenance............................. 6 Magnet suspension........................ 7 Contact overtravel and replacement........... 7 Contact forces............................ 7 Arc box................................. 7 Kickout springs........................... 7 Operating coil............................ 8 AC/DC coils.............................. 8 The controller An A00, A0, or A50 motor controller, when wired as shown in the appropriate connection diagram, will operate as a full-voltage starter and will give protection against overload. However, it will not protect against short-circuit currents when wired and provided with overload relay () heaters as listed in heater selection tables or when used with any means of inherent protection activated by motor temperature. This industrial type-controller is designed to be installed, operated, and maintained by adequately trained workmen. These instructions do not cover all details, variations, or combinations of the equipment, its storage, delivery, installation, checkout, safe operation, or maintenance. Care must be exercised to comply with local, state, and national regulations, as well as safety practices, for this class of equipment. This motor controller is suitable for use on a circuit capable of delivering not more than the current (rms symmetrical amperes) shown in Table in circuits rated not more than the voltage shown.

Instruction Leaflet IL0330300E Instructions for A00, A0, A50 size 6, two- or three-pole Table. Short-circuit ratings Short-Circuit Protective Device (SCPD) Maximum size SCPD Circuit breaker Interrupting rating Short-circuit withstand rating Current Class R fuse 600A 65,000A 00,000A Class L fuse 800A 65,000A 00,000A Magnetic only type CB Thermal magnetic circuit breaker 600A,000A 30,000A 600A 5,000A 30,000A 35,000A 8,000A 4,000A 5,000A 30,000A 4,000A Voltage 600V 480V 600V 480V 600V 480V 600V 480V 480V Disconnect means Westinghouse catalog no. prefix MCS (high mag. trip) MCS (high mag. trip) LA HLB, HLC LA, LB, LC HLB, HLC Thermal/magnetic type CB + CL 600A 00,000A 00,000A 600V NB+TRI-PAC Instantaneous adjustable trip. Circuit breaker. Inverse-time circuit breaker. Inverse-time circuit breaker with current-limiting attachment. Table. Controller ratings NEMA Three-phase horsepower at 60 Hz Amperes size 00V 30V 460/575V Open Enclosed 6 50 00 400 600 540 0.38 (9.7) Wide 4 Mtg. Slots.75 (69.9) E 3.06 (77.7).75 (69.9) Two-pole controllers have the same current ratings as three-pole devices but are not suitable for controlling three-phase motors. Reset Rod.00 (79.4) Installation Mount the motor controller on a vertical surface with the line terminals above the load terminals. Once installed, the assembly should be checked to ensure proper operation of the basic contactor mechanism and accessory devices before power is applied. The following list and the MAINTENANCE instructions should be used as a guide: A. The crossbar and springs must operate freely. B. Auxiliary contacts and mechanical interlocks must be properly installed and adjusted. C. The proper operating coil must be installed and properly connected. D. The crossbar must be in position. The contactor will not operate if the crossbar is rotated forward, out of position. E. The arc box must be in place. The contactor must never be operated in a power circuit unless the arc box is securely bolted in place. F. The main contacts must have overtravel and spring force and move freely. 0.7 (6.9) 8.44 (4.4) 9.5 (4.3) 6.50 (65.) 9.5 (35.0) 4.8 (.) Figure. A00 dimension drawing (in inches) 3.50 (596.9)

Instructions for A00, A0, A50 size 6, two- or three-pole Instruction Leaflet IL0330300E Type B overload relay A00 motor controllers are usually equipped with a Type B blocktype ambient compensated overload relay (with gray reset rod). The controller can also be supplied with a Type B non-ambient compensated relay (with red reset rod). The relay is a bimetal actuated type with a normally closed control circuit contact. An optional isolated normally open control circuit contact is available for field mounting. When the overload relay trips, a yellow dot will appear flush with the molded surface below the reset rod. Resetting the relay returns this indicator to its normal concealed position. Type A overload relay An A00 motor controller can be equipped with a Type A nonambient compensated overload relay (unmarked and with red reset rod) or with a Type A temperature compensated overload relay (marked ambient compensated and with gray reset rod). Each relay is a bimetal actuated type with trip indicator, trip adjustment covering ±5% of rating and a normally closed control contact. The relay may be operated in either hand or automatic reset mode. Reset operation is determined by the position of the plate on the load side of the overload base. Position the reset plate away from the panel to set the hand position. Loosen the locking screw, move the reset plate toward the panelboard and retighten the screw to set the auto position. Automatic reset should not be used with two-wire control circuits where automatic starting of the motor may be hazardous. Overload relay heaters Overload relay () heaters are not included with the motor controller and must be ordered separately per the heater selection table and the information listed below. When installing heaters, be sure that connecting surfaces are clean and heaters are attached securely to the relay in the proper location with the screw provided. Install with the serpentine heating element facing away from the reset rod. The trip rating of a heater in a 40 C ambient is 5% of the minimum full load current shown in Table 3. When tested at 600% of its trip rating, the relay will trip in 0 seconds or less. Heaters should be selected on the basis of the actual full load current and service factor as shown on the motor nameplate or in the motor manufacturer s published literature. When the service factor of the motor is.5 to.5, select heaters from the heater application table. If the service factor of the motor is.0, or there is no service factor shown, or a maximum of 5% protection is desired, select one size smaller heater than indicated. When motor and overload relay are in different ambients, and when using noncompensated overload relays, select heaters from the table using adjusted motor currents as follows: decrease rated motor current % for each C motor ambient exceeds controller ambient; increase rated motor current % for each C controller ambient falls below motor ambient. WARNING TO PROVIDE CONTINUED PROTECTION AGAINST FIRE AND SHOCK HAZARD, THE COMPLETE OVERLOAD RELAY MUST BE REPLACED IF BURNOUT OF A CURRENT ELEMENT OCCURS. SEE TABLE 4. Type B block overload relay Type A block overload relay Table 3. Overload relay control circuit contact ratings Normally closed Normally open Vac Make Break Make Break Type A 4 0 0A A 5A 0.5A 0 600 400 VA 40 VA 600 VA 60 VA Type B 4 0 30A 3A 30A 3A 0 600 3600 VA 360 VA 3600 VA 360 VA 3

Instruction Leaflet IL0330300E Instructions for A00, A0, A50 size 6, two- or three-pole Table 4. Replacement overload relay Overload relay Catalog number Type B Non-ambient compensated BN3A Ambient compensated BA3A Type A Non-ambient compensated AN3A Ambient compensated AA3A Coverage The combination of Type GCO 600/5 ratio current transformers, Type A or B thermal overload relay, Type AR control relay and A0 Size 6 contactor is intended to provide motor overload protection for motors with full load amperes (FLA) from 36 to 600A, 600V. The overload relay () must be installed in a vertical position as shown in Table 6 with the reset rod at the bottom. The Type GCO transformer secondary wires (white and black) are then connected to the terminals with the white wire connected to the upper terminal. Wire pairs (one black, the other white) must be connected to the terminals of the same pole. Table 5. Heater selection A or B overload relay Motor full load current in amperes for use with three heaters only Open starter Enclosed starter Heater Compensated or non-compensated Compensated Size 6 (with 600/5 current transformers) Non-compensated 36 59 36 59 9 39 FH4 60 83 60 83 40 63 FH5 84 30 84 30 64 87 FH6 3 340 3 340 88 36 FH7 34 374 34 374 37 347 FH8 375 4 375 4 348 38 FH9 4 448 4 448 38 47 FH30 449 489 449 489 48 455 FH3 490 57 490 57 456 494 FH3 58 585 58 540 495 540 FH33 586 600 FH34 Type GCO current transformers Catalog (code) number The Type GCO current transformers were specifically designed to mount on the A00 Size 6 controller and operate the Types A or B thermal overload relays. The 600/5 ratio Type GCO transformers have a single turn primary winding provided by the controller load connection straps. The secondary wires one white, the other black are color coded for polarity identification. These Type GCO current transformers are not to be used to power additional auxiliary devices and should never be energized with the secondary leads open circuited, because the open circuit overvoltage can damage the transformer. Table 6. AR relay data Contact ratings (A600) Continuous Max. current Max. VA Volts current Make Break Make Break 0 0 60 6 700 70 40 0 30 3 700 70 480 0 5.5 700 70 600 0. 700 70 Note: Coil Power AC: 96 VA Open, 4 VA Closed, 4.5 Watts Closed. Control relay To eliminate the need for a large capacity control transformer or heavy duty pushbuttons, the Size 6 A00 family of controllers includes an interposing control relay with each contactor (symbol CR in Figure and symbols FX and RX in Figure 3). The Type AR relay furnished is a two pole device, each pole rated 0A continuously, up to 600V. The contacts of the AR relay control power to the contactor coil and the AR relay coil, in turn, is operated by the external control scheme. Figures and 3 show the contactor coils operating at the same voltage as the control relay coils. An optional method of wiring is to take contactor coil power from L and L via the relay contacts, and operate the remainder of the control circuit at some reduced voltage obtained from a control transformer or a separate source. 4

Instructions for A00, A0, A50 size 6, two- or three-pole Instruction Leaflet IL0330300E Starter To Line L L L3 (FV) To Line L3 L L M 3CT CT CT T3 T T To Load 3 To Separate Control Supply X 0 OA OC BO DO Scheme No. Stop Start M 3 A B C D X 0 Ma A M B C D Scheme No. 3 X Pushbutton Station T T T3 To Load To Separate Control OA OC OA OC Scheme No. Scheme No. BO DO BO DO Extra Interlocks Mb M M May Be N.O. or N.C. Universal Intlk. N.O. & N.C. Must Use Same Polarity 3 Start Stop Coil rating Control voltage Connect to Scheme number 0/0V 0 0 0/40V 0 40 440/480V 440 480 550/600V 550 600 A & B C & D A & B C & D A & B C & D A & B C & D Figure. Non-reversing control circuit To AC Supply L3 L Separate Control When Used L3 L L Fuse Used) F R Remove When Separate Control is Used I T3 To Motor FX RX FX RX R F F ] R Stop Rev For 3 FX I For 4 6 Figure 3. Reversing control circuit 5 RX AR control relay 5

Instruction Leaflet IL0330300E Instructions for A00, A0, A50 size 6, two- or three-pole Table 7. AR relay operating coils Vac Hertz Part number 60 76C663G06 4 60 76C663G07 48 60 76C663G08 0/0 60/50 76C663G0 08 60 76C663G0 40/0 60/50 76C663G03 480/440 60/50 76C663G04 600/550 60/50 76C663G05 Auxiliary contacts type J Each Size 6 controller will accommodate a total of two auxiliary contact units, providing a total of four auxiliary circuits. The contact unit is retained in a metal bracket by spring clips and operated by a metal operator mounted on the crossbar. Additional auxiliary contact units are available with various contact arrangements as listed in Table 8. The metal bracket, mounting hardware, and operating arm can be ordered as part number 3463D94G0. The metal mounting bracket is mounted on the contactor base with the hardware provided. The auxiliary contact unit can then be installed. The metal auxiliary contact operator is then mounted on the crossbar with the hardware provided. Adjust the operating arm so that it strikes the auxiliary contact push rod beyond the beveled edge. For proper auxiliary contact unit operation, when the contactor is fully closed, the auxiliary contact push rod can be manually depressed /6 inch further. If adjustment is necessary, open or close the slot in the end of the operator to obtain this /6 inch. Auxiliary contacts mount by means of a spring clip and retainer. To remove the Type J, loosen the retainer screw several times (counterclockwise) and then slide the auxiliary contact unit out of the bracket cavity. Table 8. Type J auxiliary contacts Contact type Catalog number normally closed J0 normally open J0 normally open and normally closed J normally open and normally closed, delayed break JC Type J contact ratings (A600, R300) Voltage Continuous Make Break 0 600 Vac 0A 700 VA 70 VA 7 0 Vac 0A 60A 70 VA 8 7 Vac 0A 60A 0A 8 300 Vdc A 8 VA 8 VA Line and load terminals Both line and load terminals have 7/3-inch diameter holes for /-inch diameter hardware. Dual-wire pressure type lugs, when used, should be assembled on the front of the copper connection straps, using the mounting pattern shown in Figure 4. Table 9. Power circuit terminals NEMA size Wire size 6 () /0 AWG () 500 MCM Note: Wire with copper conductors only. Use 75 C wire. Table 0. Mechanical interlocks Upper controller Lower controller Use mech. Intlk. Type Vertically mounted controllers (A50) A0 size 5 or 6 A0 size 6 M47 A0 size 6 A0 size 7 M5 Left controller Right controller Use mech. Intlk. Type Horizontally mounted controllers (A0) A0 size 5 or 6 A0 size 6 M48 Mounting Surface Cable Entry Figure 4. Assembly of pressure type line terminals Mechanical interlocks An A00 Size 6 controller, when used in combination with other contactors, may be mechanically interlocked to protect against the closing of one when the other is already closed. Mechanical interlock combinations, for both vertical and horizontal assemblies, are listed in Table 0. Maintenance Terminal Collar Locking Edge Control Connection Screw Terminal Adapter Plate This industrial-type control is designed to be installed, operated, and maintained by adequately trained workmen. These instructions do not cover all details, variations, or combinations of the equipment, its storage, delivery, installation, check out, safe operation, or maintenance. Care must be exercised to comply with local, state, and national regulations as well as safety practices for this class of equipment. 6

Instructions for A00, A0, A50 size 6, two- or three-pole Instruction Leaflet IL0330300E Magnet suspension Both the stationary and moving magnet assemblies are flexibly mounted to ensure proper sealing of the magnet for quiet operation. Both helical compression springs and flat leaf springs are in back of each magnet part. The moving armature has less spring force and restraint than the stiffer stationary magnet assembly. In case these magnets are ever disassembled, particular care must be used to make sure that the flat leaf springs are centered on the laminated magnet assemblies and are not jammed between the magnets and the molded guide projections. After reassembly, be sure to check that both the stationary and moving magnets can be manually depressed or rocked in their mountings. Again, the moving armature assembly can be rocked with much less force and more freedom than the stationary assembly. Contact overtravel and replacement The initial contact overtravel, with new contacts, is 5/3 to 3/64 inches and is measured with the power off as shown in Figures 5 and 6. Contact replacement is necessary when the overtravel on any pole has been reduced to 3/64 inch. The contacts must be replaced on all poles at the same time. Contact replacement is then achieved by the following procedure with the power off:. Remove the arc box and gently lower the crossbar.. Disconnect shunts from moving contact. 3. Remove the three contact springs and their protectors. Remove the nameplate. 4. Remove the moving contacts by removing their bearing pins. (A 5/3-inch allen wrench is required for the #0 socket head cap screws.) 5. Remove the stationary contacts. (A /4-inch allen wrench is required for the 5/6-inch socket head cap screws.) To install new contacts, reverse the procedure, making sure all bolts and screws are tight (the stationary contact mounting bolts must be tightened to 50 75 pound inches), the crossbar is raised into its proper position with the moving contacts inside the arc box, and the arc box is securely in place. Check to be sure both kickout and contact springs are properly seated and the nameplate is in place. The moving contacts should touch the stationary contacts at the same instant within /6 inch maximum error on all poles as the contactor is closed. Contact face misalignment of approximately /6 inch (measured with the contactor fully closed) will not be detrimental to the operation of the contactor. Arc box The arc box provides the mechanical stop for the moving contact assembly while maintaining the proper open gap for the main contacts. The molded box also supports the De-ionT type arc quenchers that are contained within the arc box. Two front accessible bolts hold the arc box in place. This arc box requires no maintenance except for a periodic inspection for grid damage or zircon liner burn-through by fault conditions. The contactor must never be operated in a power circuit unless the arc box is securely bolted in place. Kickout springs Normally no maintenance is required for these springs other than to make sure they are properly seated on the molded crossbar assembly. In case they are inadvertently removed from the molded base where they are captivated in a hole slightly smaller than the free spring outside diameter, they can be reinstalled readily with needlenose pliers. Hold the front end of the spring, insert the pliers inside the spring, and rotate the offset pin end of the spring in a direction to decrease its outside diameter. Keep the spring restrained until the pin end has been inserted into the molded base. Pull Spring Scale String or Wire Initial Length Moving Contact Scale Stationary Contact Mounting Surface Thin Paper Feeler Folded Under Moving Contact Armature Open Figure 5. Initial contact force and spring length measurement Contact forces With new contacts, the total contact forces per pole should be: Initial force 7.5 to 8.5 pounds (Figure 5) Final force 9 to 0 pounds (Figure 6) After turning off the power, contact forces per pole may be measured by exerting a measured pull until the paper is allowed to move using the method shown in Figures 5 and 6. Pull Contact Spring Moving Contact Final Length Thin Paper Feeler Stationary Contact Contact Overtravel = Initial Length Final Length Power Off Armature Held Fully Closed Manually Figure 6. Final contact force and spring length measurement 7

Instruction Leaflet IL0330300E Instructions for A00, A0, A50 size 6, two- or three-pole Operating coil When installing a new coil, check the identification label for the correct part number, voltage, and frequency. Table lists the more commonly used coils and shows the connection diagram for each voltage. To replace an operating coil, proceed as follows:. Remove all power to the contactor and operating coil.. Remove coil leads. 3. Remove the arc box ( screws). 4. Gently lower the crossbar assembly. 5. Remove the old coil from the magnet by removing the two mounting screws. 6. Place the new coil on the contactor and replace the two mounting screws. 7. Raise the crossbar into its proper position with the moving contacts inside the arc box. 8. Replace the arc box on the contactor and securely tighten both mounting screws. Make sure both kickout springs are properly seated. 9. Reconnect the leads to the new coil. Move crossbar by hand and make sure it moves freely with no mechanical friction. Table. Operating coils for size 6 controllers Label marking Control volts 60 Hz Connect to 0 0 08 0 40 440 480 550 600 0 40 A B C D A B C D A B C D A B C D A B C D Operating coil part number and color of label 050AG05 Red 050AG0 Green 050AG5 Yellow 050AG7 Gray 050AG0* Gray Note: Supplied connected for 40V with both jumpers wired A to B. For 0V, reconnect the jumpers A to D and B to C as shown on coil label. Table. Coil data (typical values) Power Inrush VA Sealed VA Sealed watts AC 900 0 4 AC/DC coils AC/DC coil conversion kits are available for use with Size 6 contactors and controllers where low dropout voltage or exceptionally quiet operation is desired. The low dropout voltage characteristic may be required where the voltage applied to the contactor coil is reduced by the effect of motor inrush current. The AC/DC coil accepts AC control voltage and rectifies it to DC. An interposing control relay is required to accommodate the higher coil current involved. To order, select kit from Table 3. Table 3. AC/DC coil conversion kits Contactor AC/DC Coil Kit Voltage Frequency Part Number 0 0V Any 7864A9G0 0 40V Any 7864A9G0 440 480V Any 7864A9G03 Table 4. Recommended driving torque Location Quantity Driving torque (lb in) Arc box screw 90 00 Coil terminal screw 5 8 Coil mounting screw 5 8 Stationary contact screw 3 50 75 Power wire lugs four-pole 400 440 Lug mounting bolt two-pole 400 440 Armature mounting screw 4 00 0 Moving contact pivot screw two-pole 70 80 Shunt screws two-pole 50 75 Magnet mounting screw 5 75 Table 5. Accessories Fuse block kits meet requirements of NECT concerning common control fusing Order catalog number Quantity Description FKR Panel mounted fuse holder for class CC (Bussmann KTKR) fuses see use when available fault current exceeds 0,000A Order fuses separately by ampere rating Minimum wire size in Controller size control circuit Suggested fuse size 6 #4 AWG 5A Use when available fault current exceeds 0,000A. When using a control transformer, select fuse size per the National Electrical Code. 8

Instructions for A00, A0, A50 size 6, two- or three-pole Instruction Leaflet IL0330300E Table 6. Renewal parts Item Fig. refer. Part number Contact kit, single-pole A 066A0G Operating coil C See Table Auxiliary contact units See Table 8 Arc box assy., two- or three-pole B 066A0G45 Overload relay See Table 4 Control relay See Page 5 Line connector kit, single-pole D 066A0G50 Shunt replacement kit, single-pole E 066A0G48 Shunt/load connector assy., single-pole F 066A0G49 9

Instruction Leaflet IL0330300E Instructions for A00, A0, A50 size 6, two- or three-pole 0

Instructions for A00, A0, A50 size 6, two- or three-pole Instruction Leaflet IL0330300E

Instruction Leaflet IL0330300E Instructions for A00, A0, A50 size 6, two- or three-pole Eaton Corporation Electrical Group 000 Cherrington Parkway Moon Township, PA 508 United States 877-ETN-CARE (877-386-73) Eaton.com 009 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL0330300E / Z8 February 009 PowerChain Management is a registered trademark of Eaton Corporation. All other trademarks are property of their respective owners.