S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

Similar documents
Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

Specif ications. Minimum Surge Arrester Rating, kv

S&C Loadbuster Disconnects

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

S&C Recloser Bypass Disconnects

EE 741 Over-voltage and Overcurrent. Spring 2014

GROUP D. Switch & Protective device.

SURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION

K-Limiter high ampere Companion II fuse

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv)

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

Electronic Resettable Sectionalizer

S&C SMD -20 Power Fuses

10DD 10DD-1. Section CAUTION:

S&C Type XS Fuse Cutouts

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

3.2. Current Limiting Fuses. Contents

T HREE-SHOT TYPE MZR F USE CUTOUT

S&C Type XS Fuse Cutouts

Boric Acid Fuse Links

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

Type ICX Interchangeable Cutout kv Outdoor Distribution Cutout Product Bulletin 1VAG DB

Grounding Of Standby & Emergency Power Systems

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

NEW Solutions for Underground System Growth

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

S&C Manual PME Pad-Mounted Gear

High Voltage Surge Arresters Buyer s Guide Section Line Surge Arrester PEXLINK

Selection Guide S&C ELECTRIC COMPANY. For Transformer-Primary Fuses in Medium- and High-Voltage

High Voltage Surge Arresters Buyer s Guide Section Transmission Line Arrester PEXLINK

www. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

Figure 1. Two and Three-phase MagneX.

Type ICX Outdoor open type cutout

Disconnect & ByPass Switches

CMU medium voltage power fuses

Figure 1. HX cutout fuseholders.

SWITCHGEAR DIVISION PRODUCT PROFILES

Tolerance-Based Time-Current Coordination

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

Medium Voltage Metal-Enclosed Switches

Figure 1. HX cutout fuseholders. Positive Interruption

Single phase pole mounted. 11kV. Electrical Engineer KEU ID#:

Chapter 6 Generator-Voltage System

26.3. Power Breakers, Contactors and Fuses. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents.

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT

THE CURVE FOR DOUBLE PROTECTION TRANSFORMER & SYSTEM PROTECTION WITH CHANCE SLOFAST FUSE LINKS

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation

When power interruptions happen.

Medium Voltage Outdoor Apparatus Portfolio 2009

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

www. ElectricalPartManuals. com CPL Station Arrester Controlled Protective Level Page 1 Indoor-Outdoor Altitude 0-10,000 feet KV

Recommended Procedures

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A January 2014

LOW-PEAK Time-Delay Fuses KRP-C Class L 600 Volt A

FUSES. Safety through quality

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

PROJECTS $500K AND OVER FOR 2014

Power Voltage Transformers for Air Insulated Substations

GENERAL. CONSTRUCTION External

University of Houston Master Construction Specifications Insert Project Name

Improving distribution systems reliability with Cutoutmounted single phase Reclosers

TYPE BLT DISCONNECT SWITCHES

DIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast).

Amp-Trap 2000 Fuses FOR TYPE 2, NO DAMAGE CIRCUIT PROTECTION IN ALL THE CONFIGURATIONS YOU NEED. Class J / AJT...A2. AJT Reducer Fuses...

T YPE MZ DISTRIBUTION S TANDARD CUTOUT

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

Product Selection Guide

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Technical Journal September 2012

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

Selective Coordination

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A October 2015

S&C Alduti-Rupter Switches. Outdoor Distribution, 14.4 kv through 69 kv

TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV

NX indoor current-limiting fuses

SPECIFICATION BULLETIN

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, SMD-3, and SMD-50. Outdoor Transmission (34.5 kv through 138 kv)

How to Use Coordinaide to Protect Transformers Against Secondary-Side Arcing Faults.

Medium Voltage Metal-Enclosed Switches

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA March 2013

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

Benefits, typical uses

Transcription:

S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv)

Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles like a cutout, the Fault Tamer s unique design combines the function of a conventional fuse cutout and a backup current-limiting fuse in one powerful package. Fault Tamer is a distribution fuse for overhead distribution systems that better addresses the critical issues facing protection engineers today, such as: minimizing equipment damage, improving service continuity, enhancing power quality, and improving transformer protection. Fault Tamer Fuse Limiters are ideally suited for single-phase transformers, for three-phase banks of single-phase transformers, and for three-phase transformers. Minimizes Equipment Damage Fault Tamer Fuse Limiter is an energy-limiting faultinterrupting device which can be easily incorporated in new or existing installations of overhead distribution transformers to provide short-circuit protection to the system, to limit let-through current to a level which will minimize catastrophic transformer failures from high-magnitude internal faults, and to minimize damage from high-magnitude external faults such as bushing flashovers. As a result, Fault Tamer Fuse Limiter offers an alternative to utilities who are increasingly concerned about the violent operation of fuse cutouts during fault interruption. Moreover, Fault Tamer complies with Spark Production Class A in Australian Standard AS 33-990. To be in compliance with Spark Production Class A, no sparks may be produced during a fault-clearing operation (an extremely significant reduction in fire hazard as compared to fuse cutouts). 20K fuse link 20-ampere Fault Tamer 65K fuse link 40K fuse link B 2400 Amperes B 65K 20K Area of miscoordination 40K Fault Tamer 000 000 000 000 Figure. Limited coordination of transformer fuse with lateral fuse. Figure 2. Complete coordination of Fault Tamer with lateral fuse. 2

Improves Service Continuity It is usually not possible to achieve complete fuselink-to-fuse-link coordination close to substations where fault currents can be high. For example, a 20K fuse link will not coordinate with a 65K fuse link above 2,400 amperes, as shown in Figure. As a consequence, a primary fault at a transformer, such as a bushing flashover due to a squirrel, can result in both the transformer fuse and the lateral fuse operating so that all customers on the lateral will be exposed to an extended outage instead of just those customers served by the transformer involved. By contrast, the fast clearing characteristics of Fault Tamer provide complete coordination with typically sized lateral fuses even at high levels of available fault current. In fact, Fault Tamer coordinates with lateral fuses having ampere ratings as low as 40K, as shown in Figure 2. Reduces Momentary Outages Typical clearing characteristics of fuse links are also too slow to coordinate with the instantaneous settings of substation circuit breakers. As shown in Figure 3, when the available fault current exceeds the instantaneous setting of the breaker, not only will a 20K fuse link protecting a transformer operate for a transformer fault but so will the breaker resulting in a momentary outage to the entire feeder. The currentlimiting action of the Fault Tamer, illustrated in Figure 4, prevents these unnecessary instantaneous breaker operations for transformer faults... There s no longer a need to compromise coordination in high fault areas a major improvement in service continuity. 20K fuse link 20K fuse link Grounded relay Grounded relay B Relayed circuit breaker Phase relay Instantaneous setting B Relayed circuit breaker Phase relay Instantaneous setting 20K Area of miscoordination 40K Fault Tamer 000 000 000 000 Figure 3. Limited coordination of fuse link with sourceside relays. Figure 4. Complete coordination of Fault Tamer with source-side relays. 3

Enhances Power Quality High-magnitude faults near a substation can suppress the voltage at the substation bus as well as on the feeders that emanate from that substation. Voltage dips that last long enough can cause sensitive electronic equipment to shut down. Or, worse yet, they can cause a process to malfunction, potentially resulting in the manufacture of defective parts. The current-limiting action of Fault Tamer clears highmagnitude transformer faults before sensitive equipment can be affected. Further, laterals downstream from the faulted transformer will be at essentially zero volts until the upstream fault is cleared. In that Fault Tamer will clear faults greater than 2,000 amperes in less than 8.3 milliseconds, power quality is thus maintained to customers on downstream laterals. Improves Transformer Overvoltage Protection Recent studies have shown that a major cause of overhead transformer failure is voltage surges. Maximum overvoltage protection can be achieved by mounting the surge arrester on the transformer tank, thus minimizing the lead length from the arrester to the transformer winding and to ground. However, with the surge arrester mounted on the load side of the transformer fuse, the fuse is more susceptible to nuisance fuse operations due to lightning surges. But with Fault Tamer s high adiabatic I 2 t withstand capability approximately equal to that of a 20K or a 2T fuse link the probability of operation due to lightning surges is less than %, even in high isokeraunic areas. Thus, the surge arrester can be located on the load side of a Fault Tamer without any added susceptibility to nuisance fuse operations. A Note on System Voltage Rating Fault Tamer Fuse Limiter should be selected so that its system maximum three-phase voltage rating is equal to or greater than the system line-to-line voltage. To ensure proper coordination of Fault Tamer with system surge arresters, it is also important that the system voltage not be too low relative to the Fault Tamer s system voltage class rating. To satisfy both of these requirements, the following specific systemvoltage and minimum surge arrester recommendations should be observed: 3 5 7 5 20 S&C Fault Tamer System Voltage Class Rating, kv, ANSI (IEC) Applicable 60-Hz System Voltage, kv Applicable 50-Hz System Voltage, kv Minimum Surge Arrester Rating, kv 5 (2) through 5 through 5 9 25 (24) 22 through 29 20 through 26 8 High adiabatic I 2 t withstand capability approximately equal to that of a 20K or 2T fuse link 000 000 Figure 5. Fault Tamer Fuse Limiter Cartridges provide excellent transformer protection and less than % probability of operation due to lightning surges. 4

Handling The Fault Tamer has been designed to retrofit into all vintages of S&C Type XS Fuse Cutout mountings with base catalog numbers 8902, 8903, 8907, and 8922 for the 5-kV class Fault Tamer, 89022, 89032, 89042, 89052, 89072, 89092, and 89222 for both the 5-kV class Fault Tamer with extension adapter and the 25-kV class Fault Tamer, and 89033 and 89053 for 25-kV class Fault Tamer with extension adapter. A Fault Tamer that has operated can be easily identified from the ground since it drops open. Both the fuse tube and the backup limiter can be quickly removed from the mounting with a telescoping hot stick. By contrast, climbing the pole or using a bucket truck is required to re-fuse bolted-in backup currentlimiting fuses. Re-fusing Re-fusing is quick and easy. Backup limiters are offered in only one ampere rating size, 20 amperes. Fuse cartridges have ratings of 3, 5, 7,, 5, and 20 amperes, all specifically designed to coordinate with the 20-ampere backup limiter. See Figure 5. Warehouse and line truck stocking problems are kept to a minimum. And, the backup limiter and fuse cartridge cannot be mismatched, as is possible when fuse cutouts and backup current-limiting fuses are used. The Fault Tamer is also designed to work perfectly with the Loadbuster Tool, S&C s portable loadbreak tool. Loadbuster switching helps keep service interruptions to a minimum. Live switching can be done at the point that minimizes the length of planned outages and at the point where the fewest customers will be involved. Fault Tamer Components Fault Tamer consists of four basic components mounting (not shown), backup limiter, fuse tube, and fuse cartridge. The fuse cartridge is replaced after each fault-clearing operation. The backup limiter is replaced after a high-magnitude fault-clearing operation. The backup limiter, with integral exhaust control, prevents fuse cartridge parts from being expelled during a fault-clearing operation. (By contrast, fuse cutouts and even fuse cutouts connected in series with backup current-limiting fuses can expel hot gases and fuse link particles at high velocity during an operation resulting in a potential exhaust hazard to operating personnel.) Dropout mechanism provides dropout indication of operation Fuse tube cap Backup limiter replaced after a high-magnitude fault-clearing operation Fuse tube Spring-and-cable assembly stainless-steel spring provides high-speed elongation of arc when fuse cartridge operates. Copper cable inside spring carries load (and fault) current Fuse cartridge replaced after all fault-clearing operations Trunnion 5

Catalog Number 9802-D rated for 5-kV, -kv BIL systems. Also available with composite-polymer silicone insulator. Catalog Number 98072-D rated for 5-kV, 25-kV BIL systems. Includes extension adapter to allow 5-kV Fault Tamer components to be installed in 25-kV mounting. Fault Tamer Fuse Limiter For new installations. Includes mounting, backup limiter, and fuse tube (less mounting bracket, connectors, and Fault Tamer Fuse Cartridge) Rating Catalog Number System Class, ANSI (IEC) Three- Phase2 Voltage, kv System Maximum 60 Hz 50 Hz Phase-to- Neutral Three- Phase2 Phase-to- Neutral BIL Amperes, RMS Max Interr., Sym. Leakage Distance to Ground Minimum, Inches (mm) Porcelain Insulator Polymer Insulator 5 (2) 5 8.7 5 8.7 20 2 000 8½ (26) 9802 9802-P 5 (2) 5 8.7 5 8.7 25 20 2 000 (279) 98072 25 (24) 29 6.8 26 5 25 20 2 000 (279) 98022 25 (24) 29 6.8 26 5 50 20 2 000 7 (432) 98052 98052-P 25 (24) 29 6.8 26 5 50 20 2 000 26 (660) 98053 98053-P 22/38 (20.8/36) 22 20.8 50 20 2 000 7 (432) 98044 98044-P TCC No. 450-8. 2 Also applies to phase-to-phase applications. Applications involving single-phase transformers connected phase-to-phase, as well as threephase applications require the use of a Fault Tamer in each lead. Includes extension adapter for use in mounting with porcelain insulator having -inch (279 mm) leakage distance to ground. Includes extension adapter for use in mounting with porcelain insulator having 26-inch (660 mm) leakage distance to ground, or compositepolymer silicone insulator having 30-inch (762 mm) leakage distance to ground. Meets 70 kv BIL rating requirement of IEC Publication 282 2. Applicable only for protection of single-phase transformers in solidly grounded-neutral (multi-grounded-neutral) 34.5-kV systems. Uses 29-kV, 50-kV BIL mounting. 6

Catalog Number 98022-D rated for 25-kV, 25-kV BIL systems. Catalog Number 98052-D rated for 25-kV, 50-kV BIL systems. Similar in appearance to Catalog Number 98044 D rated for 25-kV, 50-kV BIL mounting on solidly grounded neutral (multi-grounded neutral) 34.5-kV systems. Both models are available with compositepolymer silicone insulator. Catalog Number 98053-D rated for 25-kV, 50-kV BIL systems. Includes extension adapter for use in 25-kV mounting with porcelain insulator having 26-inch (660 mm) leakage distance to ground or composite-polymer silicone insulator having 30-inch (762 mm) leakage distance to ground. 7

Descriptive Bulletin 45-30 November 7, 204 Offices Worldwide www.sandc.com