I Fan Powered Terminal Unit VARIABLE VOLUME PARALLEL FLOW
Fan Powered Terminal Unit Variable volume parallel flow Product Overview Variable Volume/Parallel Flow Fan Powered Terminal Units Honeywell parallel fan-powered terminal units are designed to provide superior comfort by intermittent parallel fan operation.conditioned primary air is varied during cooling while the fan cycles on during heating. Parallel fan-powered terminal units allows for recovery of waste heat from the return plenum and a potential reduction in central fan energy, thereby lowering operating costs. In the heating mode with fan energized parallel fan-powered terminal units improve air circulation through better diffuser performance. Benefits of Variable volume Fan Powered Terminal Units The primary air valve is sized for cooling demand similar to single duct terminal design requirements. The recirculating air section is typically sized at 50% of the maximum primary air valve demand which results in lower noise, lower unit cost and reduced energy when compared to constant volume terminals. Construction Compact, durable zinc-coated steel casing means reduced ceiling plenum space requirements and protection from corrosion. Terminal casing is internally lined with fiberglass insulation. The insulation s high density skin provides erosion resistance while effectively attenuating noise. Insulation meets requirements of UL181 and NFPA-90A Proven reliable primary air section with heavy gauge damper and low leakage blade seal. Honeywell terminals come standard with SCR fan speed control for efficient, quiet adjustment of fan capacity. Electric motors are specially designed to operate with SCR controls ensuring reliable maintenance free operation. Fan motor is isolated from the blower housing to reduce noise. Additional vibration isolators and heavy duty motor mounts are provided on large unit sizes. Energy efficient, fan motor is designed to meet consistent torque specifications providing reliable and repeatable performance. ECM - Elecrtonically Commutated Motors are available as an option. Large removable bottom access panel provides access to the interior of the unit for cleaning, inspection and service. Quality Assurance Each Price fan powered terminal unit receives a full operational check before shipment and arrives factory calibrated in accordance with project specifications. This means costly labor and setup delays are avoided. Options: ECM energy efficient motor option Discharge attenuator section (DAS) for reduction of discharge noise Inlet attenuator section (IAS) for reduction of radiated noise Merv 8 and 13 filter bank for enhanced filtration of recirculated air Hanger brackets and spring isolation
Fan Powered Terminal Unit Variable volume parallel flow Product information Features Recirculating fan section operated only on a demand for heat from the space thermostat. Primary air section controls are pressure independent. ACTUATOR PRIMARY AIRFLOW INLET DIA RETURN AIR C x D Filter location HANGER BRACKET Size 20 and 30-22 gauge construction (optional 20 gauge available) Size 40-60--20 gauge construction. L Zinc-coated steel housing, mechanically sealed,leak resistant. Damper constructed of double layer of 24 ga. galvanized steel with sandwiched flexible gasket to provide tight seal (<1% at 3" static pressure). 250 Back darft damper Factory calibrated controls per each job requirement. Honeywell multi-quadrant averaging flow sensor provides highly accurate +/- 5% flow readings after certified balancer has balanced terminal. Energy efficient six pole single speed PSC motors with adjustable SCR solid state fan speed controllers are standard. Flanges 140 AIR FLOW DISCHARGE OUTLET W TOP VIEW Electronically Commutated Motors (ECM) available as an option. B 215 H Single point electrical connections. Round inlets available in sizes 150mm through 400mm. Rectangular flanged discharge with flange connection A FRONT VIEW C D A B Electric coil section Auto reset thermal cutout (one per element) 80/20 Nickel chrome heating elements. Airflow safety switch Flange connection. Control transformer for DDC or Analog electric controls Fan relay for DDC fan terminals Modulating heating control Manual reset thermal cutout as optional 20 30 40 50 60 750 150, 200, 250 300 395 360 320 800 450 650 1350 200, 250, 300 300 395 360 320 800 450 650 2000 250, 300, 350 400 395 400 380 900 450 750 2400 300, 350, 400 530 460 510 450 1075 550 900 3000 350, 400 530 460 610 460 1075 550 900
Fan Powered Terminal Unit Variable volume parallel flow Typical Selection Guide - Cooling Cycle- 100% Primary Performance Notes: 1) NC's are derived from sound power levels, which are obtained in accordance with AHRI Standard 880-2011 and ASHRAE Standard 130-2008 2) NC's are derived from sound power levels which include duct end corrections per AHRI Standard 880-2011. 3) Blank Spaces(-) indicates NC's less than 20. 4) Airflow is given in L/s and cfm. 5) Ps is the difference in static pressure from inlet to discharge of the unit. 6) Pt is the difference in total pressure from inlet to discharge of the unit. 7) Min. Ps is the minimum static pressure required to achieve rated airflow. 8) Pressure is given in Pa and in W.g 9) Fan external static pressure is 63 Pa (0.25 in W.g.) in all cases 10) NC values are calculated based on typical attenuation values outlined in Appendix E, AHRI Standard 885-2008. " A Procedure for Estimating Occupied Space Sound Levels in the application of Air Terminals and Air outlets." Typical Attenuation Values
Fan Powered Terminal Unit Variable volume parallel flow Typical Selection Guide -Heating Cycle-Fan Only Typical Attenuation Values 1. NCs are derived from sound power levels, which are obtained in accordance with AHRI Standard 800-2011 and ASHRAE Standard 130-2008. 2. NCs are derived from sound power levels which include duct end corrections per AHRI Standard 880-2011. 3. Blank spaces(--) indicate NCs less than 20. 4. Fan external static pressure ins 63 Pa (0.25 in.w.g.) in all cases. 5. NC values are calculated based on typical attenuation values outlined in Appendix E,AHRI Standard 885-2008."A Procedure for estimated occupied space sound levels in the Application of Air terminals and air outlets."
Performance curve / acoustics Unit size: 20 RH22V-6IP.0B.1R 113247 Portfolio STD-WW measured in standard nozzle in installation type A according to ISO 5801 measurement density 1.16 [kg/m³] Air performance p sf Unit size: 30 RH25V-6IK.BA.1R 163226 Portfolio STD-WW Air performance p sf
Performance curve / acoustics Unit size: 40 RH31V-6IK.BD.1R 114836 Portfolio STD-WW measured in standard nozzle in installation type A according to ISO 5801 measurement density 1.16 [kg/m³] Air performance p sf Unit size: 50 RH40V-4EK.4F.1R 113306 Portfolio STD-WW Air performance p sf
Performance curve / acoustics Unit size: 60 RH50V-6EK.6F.1R 113381 Portfolio STD-WW measured in standard nozzle in installation type A according to ISO 5801 measurement density 1.16 [kg/m³] Air performance p sf Honeywell Environmental & Energy Solutions (E&ES) Honeywell Automation India Limited Pune: Plot No. 56/57, Hadapsar Industrial Estate, Pune- 411 013, India Tel: +91-20-66039400 Fax: +91-20-66039800 Email: eccpune@honeywell.com WhatsApp Number +91 81306 91299 Website: www.honeywell.com Customer Care Number - 1800 103 3848 2016 Honeywell International Inc. All rights reserved