BILL 1 MAINS POWER DISTRIBUTION 2-1 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Supply, install, test, commission and set to work the following:- 1.01 Free-standing purpose made front access sub main switchboard (Fully Type-Tested Assemblies TTA), modular, metal clad, manufactured in 12 SWG galvanised mild steel sheet and finished in cream (or appropriate colour) powder coating as shown on the schematic. The switchboard should consist of a PLC section. The switchboard to be as Merlin Gerin Switchgear or equivalent and approved, complete with the following:- (a) (b) (c) (d) (e) (f) (g) (h) (i) (j) Space for Kenya Power s cut-outs. CTS and meters. The spaces to be provided with punched studs for installing Kenya Power s seals. Digital multimeter type PM820 with CTs and fuse protection capable of measuring voltage in the range 0 1000V, 3-phase, current in the range 0-2000A, 3-phase, and all power system parameters (KW, KVA, KWHr, KVArs, Frequency, P.F., harmonics and all the parameters). The multimeter to have an accessible terminal for connecting an external printer, and should be complete with selector switches for viewing/displaying the various parameters. 415V three-phase surge diverter as Furse ESP 415, wired as shown, complete with enclosure with viewing window. Set of neon phase presence indicator lamps 1 No. 800 A TPN MCCB main incomer type NS 800N with adjustable over current settings and having a short-circuit breaking capacity of 100KA at 415Vac, 50Hz. The MCCB to be adjustable in 630-800A range. The MCCBs to be motorized and have both electrical and mechanical interlock. 5 No. 1000A TPN insulated copper bus bars of 80 x 10 mm cross section. 3 No. Three phase direct Kenya Power meters, Kenya Power cutouts and CTs for Tenants Sufficient capacity for 4No. Meters above Kenya Power cutouts, and all the switch gear CT Chamber 1 No. 200A 3 P TPN motorized MCCBs as shown, but adjustable in the range 150 200A. The Breakers to have Line Protection of 60 KVAr s Power Factor. Total C/F to Page 2-2
BILL 1 MAINS POWER DISTRIBUTION 2-2 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Total C/F from Page 2-1 (k) (l) (m) (n) (o) (p) (q) (r) (s) (t) (u) (v) (w) (x) (y) 2 No. 100A 3 P TPN motorized MCCBs as shown, but adjustable in the range 80 100A. The Breakers to have Line Protection of 30 KVAr s Power Factor. 1 No. 630A TP MCCB, (adjustable in 400 630A range) 1 No. 400A TP MCCB, (adjustable in 320 400A range) 2 No. 150A TP MCCB, (adjustable in 125 150A range) 2 No. 100A TP MCCB, (adjustable in 80 100A range) 2 No. 80A TP MCCB, (adjustable in 63 80A range) 3 No. 63A TP MCCB, (adjustable in 40 63A range) 10 No. 60A TP MCCB, (adjustable in 40 63A range) 2 No. 30A TP MCCB, (adjustable in 20 30A range) Sufficient spare capacity for future development all fitted with 3 No. 80A MCCBs Sufficient Knock-outs for incoming/outgoing cables Sealable studs for all cover plate screws and all necessary accessories 6mm perspex viewing window Heavy duty rubber lining for all the perspex viewing windows An 800A TPN automatic change-over system, with electrical and mechanical interlock. The change-over contactors to be TELE-MECANIQUE, minimum rating 800A. A manual bypass system, rated at 800A TPN should also be provided across the change-over system and it must be capable of bypassing both mains and generator supplies in alternation. All the delay timers for pre-ignition, time to load, and return to mains supply to be provided. An actual setting to be agreed upon before main switchboard is assembled. Clear indicator lamps for mains available, mains on load, generator available, generator on load, together with corresponding permanent labels should also be provided. The change-over and by-pass system to be incorporated in the main switchboard assembly. (Note: The entire switchboard assembly to be Form 4, Type 2 i.e. totally safe with all live parts completely inaccessible on opening the outside cover) Total C/F to Page 2-3
BILL 1 MAINS POWER DISTRIBUTION 2-3 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Total C/F from Page 2-2 1.02 Carry out comprehensive labelling of all the bus bars. CT chambers, circuit breakers etc. of item No. 1.01 and above, indicating the areas served, outgoing cable sizes etc. 1.03 Comprehensive protective multiple earthing of item No. 1.01 in 1500mm long 12mm diameter pure electrolytic copper earth rod deep driven to permanent moisture level, copper clamp. 100mm² green earth lead complete with all accessories. (Note: Use parallel rods if effective earthing cannot be achieved with 1 No. rod). 1.04 One off free standing 300 KVAr s automatic Power Factor Correction Capacitor Bank comprising the following:- i) 3 No 50 KVAr s 415 V,50Hz, 3-Phase ii) 4 No 25 KVAr s 415 V,50Hz, 3-Phase iii) 5 No 10 KVAr s 415 V,50Hz, 3-Phase iv) 12 No Special contactors for capacitor switching v) 12 No Fuse bases and fuses for each capacitor protection vi) 12 No Step indicator lamps vii) 1 No Control circuit protection fuse/fuse holder viii) 1 No. 12-Step automatic control regulator for maintaining power factor at the set level and regulating the switching of capacitor steps ix) 1 No 800/5A Current transformer (to be mounted after the mains incoming circuit breaker) The bank to be made from low-loss bio-degradable capacitive units, complete with earthed enclosure. 1 No. 1.05a) 2x4C 185mm 2 PVC/SWA/PVC copper cable for the above bank 40 m. 1.05b) Cable glands for the above cable 4 No 1.05c) Cable lugs for the above cable complete with hydraulic crimping 16 No 1.06 An automatic voltage regulator with the following characteristics: - i. i Rating: 500 KVA ii. ii Power Supply: 3 Phase, 415V/240V iii. ii i Input Voltage Tolerance: 20% i.e. from 365-505V 3 Phase from 192-288V 1 Phase iv. iv Operation: Independent correction for each Phase Total C/F to Page 2-4
BILL 1 MAINS POWER DISTRIBUTION 2-4 No. Description Qty Unit Rate Amount Ksh. Cts. Total C/F from Page 2-3 v. Output: + 1% of 415V/240V vi. Frequency 50/60Hz + 5% vii. Rated Current: 696 Amps viii. Admitted Load Variation 0 to 100% ix. Admitted Load unbalance up to 100% x. Correction Speed:16ms/V xi. Waveform distortion <0.2% xii. Efficiency 98% xiii. xiv. xv. xvi. xvii. xviii. xix. xx. xxi. Cooling: Natural air cooled (free convection without fans) Ambient temperature: -10 o C to +40 o C Storage temperature: -20 o C to +60 o C Relative Humidity: 90% (without condensate) Warranty: Not less than 2 Years State Dimensions of the AVR (WxDxH) State Weight of the AVR. State Protection degree of the AVR. State Make, country of origin and model of the AVR. (The AVR to be complete with 7-position selector to read input/output (PH/PH), internal trimmer to adjust output voltage +, Pilot lamps for operating status, Input/Output terminals boards) 1 No Total C/F to Page 2-5
BILL 1 MAINS POWER DISTRIBUTION 2-5 No. Description Qty Unit Rate Amount Ksh. Cts. Total B/F from Page 2-4 1.07a) 1.07b) 800 A TPN Motorized MCCB with adjustable time-delay, enclosed in the Main switchboard Assembly and to be adjustable from 630A- 800A 800A TPN Manual by-pass system across the AVR to be complete with 3 No 800A TPN Manual change over switches and incorporated in the main switchboard assembly 1 No 1 No 1.08a) 2x4C 240mm 2 PVC/SWA/PVC copper cable 60 m. 1.08b) Cable glands for the above cable 4 No 1.08c) Cable lugs for the above cable complete with hydraulic crimping 16 No 1.09 Allow for the following (provisional) lengths of cable (4C PVC/SWA/PVC) to be used for terminating existing circuits onto the new main switchboard. a) 240mm 2 50 m. b) 185mm 2 50 m c) 70mm 2 50 m d) 50mm 2 50 m e) 35mm 2 50 m f) 16mm 2 50 m 1.10 Cable glands for the above cables a) 240mm 2 4 No b) 185mm 2 4 No c) 70mm 2 4 No d) 50mm 2 4 No e) 35mm 2 8 No f) 16mm 2 8 No Total C/F to Page 2-6
BILL 1 MAINS POWER DISTRIBUTION 2-6 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Total C/F from Page 2-5 1.11 Cable lugs complete with hydraulic crimping a) 240mm 2 16 No b) 185mm 2 16 No c) 70mm 2 16 No d) 50mm 2 16 No e) 35mm 2 32 No f) 16mm 2 32 No 1.12 Allow for following works as PROVISIONAL to facilitate connection of existing cables to the new switchboard as necessary: - (Note: Switchboard shop drawings to be prepared with full site understanding as to how the existing cables will be terminated into the proposed positions of the various outgoing circuit breakers) (a) (a) Cable terminal block to be fitted into the switchboard to take up to between 120 mm 2 and 240 mm 2 SWA cable. Cable terminal block to be fitted into the switchboard to take up to between 25 mm 2 and 90 mm 2 SWA cable. 14 No 14 No 1.13 Allow for attendance for connection of the new 500 KVA Standby Generator set 1.14 Allow for the transfer of all existing circuits to the new main Switchboard. Please study the existing arrangement first before pricing this item 1.15 Allow for carrying out comprehensive testing of the installation as per IEE Wiring Regulation, 17 th Edition. 1.16 Carry out very concise load balancing to achieve a maximum imbalance not greater than + 10% between any two phases, measured at the main switch. 1.17 Allow for full load testing of the AVR with variable load Note: The following to be included with the bid:- 1. Detailed technical brochure outlining all the features of the AVR, including environmental conditions. 2. Catalogue showing number of similar equipment installed previously. 3. Detailed shop drawing of the Main switchboard and all the sub switchboard. Total for Bill No. 1: Mains Power Distribution, C/F to Summary Page for Electrical Installations
BILL 2 ELECTRICAL INSTALLATIONS FOR AIR-CONDITIONING INSTALLATIONS 2-7 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Supply, install, test and commission the following:- 2.01a) 2.01b) 2.01c) 150A TP MCCB, (adjustable in 125 150A range) main beaker for the block as Merlin Gerlin or Crabtree, complete with metallic enclosure (Note: BILL/MEM will not be accepted). This breaker is to be fitted in the main branch s switch board in the switch room Carry out solid bonding of the metallic enclosure of the MCCB above to the metallic body of the main switchboard in 6mm 2 green PVC insulated copper cable. Label the above MCCB thus: SUPPLY TO AIR CONDITIONING UNITS ROOF TOP in red 10mm higher permanent traffolyte labels. 1 No 2.02a) Sub mains circuit comprising 4C 50mm 2 PVC/SWA/PVC copper cable from the MCCB to the distribution board located at the roof top. 180 m. 2.02b) Cable glands for the above cable. 2 m. 2.02c) Cable lugs for the above cable. 8 No. 2.03 Free standing purpose made 4 Way Sub main switchboard manufactured in 14SWG galvanised mild steel sheet and finished in cream (or appropriate colour) powder coating complete with the following:- 1 No. (a) 1 No. 150A TP MCCB (adjustable in 125-150A range) main incomer.. (b) (c) (d) (e) (f) (g) 5 No. 200A TPN insulated copper bus bars of 40 x 10mm cross section. 2 No. 100A TP MCBs 2 No. spare capacity for future development all fitted with 100A MCCBs Sealable studs for all cover plate screws and all necessary accessories Carry out comprehensive labeling of all the bus bars, circuit breakers etc. of the board above, indicating the areas served, outgoing cable sizes etc. Comprehensive protective multiple earthing of the above board in 1200mm long 12mm diameter pure electrolytic copper earth rod deep driven to permanent moisture level, copper clamp. 50mm² green earth lead complete with all accessories. (Note: Use parallel rods if effective earthing cannot be achieved with 1). 1 No Total C/F to Page 2-8
BILL 2 ELECTRICAL INSTALLATIONS FOR AIR-CONDITIONING INSTALLATIONS 2-8 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Total C/F from Page 2-7 2.04a) 10-way TP/N distribution board complete with 125A TPN integral isolator and all accessories as MK, CRABTREE or MERLIN GERLIN or approved equivalent 2 No 2.04b) TP MCB s for the above board 16 No 2.04c) TP blanking plates for the above board 4 No 2.04d) Earthing for the boards above. Lot 2.04e) Comprehensive Labelling of the boards above. Lot 2.05a) Sub mains circuit comprising 4C 25mm 2 PVC/SWA/PVC copper cable 30 m. 2.05b) Cable glands for the above cable. 4 m. 2.05c) Cable lugs for the above cable. 16 No. 2.06a) Outlet for three phase VRF out door units, comprising box, concealed H/G PVC conduit, wiring in 5 x 6.0 mm² SC-PVC-CU cables and all accessories including 32A isolator. 8 No 2.06b) 32A TPN local isolator as MK or approved equivalent. 8 No. 2.06c) Outlet for three phase VRF out door units, comprising box, concealed H/G PVC conduit, wiring in 5 x 4.0 mm² SC-PVC-CU cables and all accessories including 20A isolator. 8 No 2.06d) 2.07a) 2.07b) 2.07c) 20A TPN local isolator as MK or approved equivalent. 200A TP MCCB, (adjustable in 150 2000A range) main beaker for the block as Merlin Gerlin or Crabtree, complete with metallic enclosure (Note: BILL/MEM will not be accepted). This breaker is to be fitted in the main branch s switch board in the switch room Carry out solid bonding of the metallic enclosure of the MCCB above to the metallic body of the main switchboard in 6mm 2 green PVC insulated copper cable. Label the above MCCB thus: SUPPLY TO AIR CONDITIONING UNITS MEZZANINE II in red 10mm higher permanent traffolyte labels. 8 No. 2 No Total C/F to Page 2-9
BILL 2 ELECTRICAL INSTALLATIONS FOR AIR-CONDITIONING INSTALLATIONS 2-9 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Total C/F from Page 2-8 2.08a) Sub mains circuit comprising 4C 70mm 2 PVC/SWA/PVC copper cable from the MCCB to the distribution board located at the Mezzanine II. 80 m. 2.08b) Cable glands for the above cable. 2 m. 2.08c) Cable lugs for the above cable. 8 No. 2.09 Free standing purpose made 6 Way Sub main switchboard manufactured in 14SWG galvanised mild steel sheet and finished in cream (or appropriate colour) powder coating complete with the following:- 1 No. (a) 1 No. 2000A TP MCCB (adjustable in 150-200A range) main incomer.. (b) (c) (d) (e) (f) (g) (h) 5 No. 250A TPN insulated copper bus bars of 40 x 10mm cross section. 1 No. 63A TP MCBs 3 No. 100A TP MCBs 2 No. spare capacity for future development all fitted with 100A MCCBs Sealable studs for all cover plate screws and all necessary accessories Carry out comprehensive labeling of all the bus bars, circuit breakers etc. of the board above, indicating the areas served, outgoing cable sizes etc. Comprehensive protective multiple earthing of the above board in 1200mm long 12mm diameter pure electrolytic copper earth rod deep driven to permanent moisture level, copper clamp. 50mm² green earth lead complete with all accessories. (Note: Use parallel rods if effective earthing cannot be achieved with 1). 1 No 2.10a) 12-way TP/N distribution board complete with 125A TPN integral isolator and all accessories as MK, CRABTREE or MERLIN GERLIN or approved 2 No 2.10b) As above but 6 Way located on Mezzanine Floor 1 No 2.10c) TP MCB s for the above board 24 No 2.10d) TP blanking plates for the above board 6 No 2.10e) Earthing for the boards above. Lot 2.10f) Comprehensive Labelling of the boards above. Lot Total C/F to Page 2-10
BILL 2 ELECTRICAL INSTALLATIONS FOR AIR-CONDITIONING INSTALLATIONS 2-10 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Total C/F from Page 2-9 2.11a) Sub mains circuit comprising 4C 25mm 2 PVC/SWA/PVC copper cable 40 m. 2.11b) Cable glands for the above cable. 4 m. 2.11c) Cable lugs for the above cable. 16 No. 2.12a) Sub mains circuit comprising 4C 16mm 2 PVC/SWA/PVC copper cable 30 m. 2.12b) Cable glands for the above cable. 2 m. 2.12c) Cable lugs for the above cable. 8 No. 2.13a) Outlet for three phase VRF out door units, comprising box, concealed H/G PVC conduit, wiring in 5 x 6.0 mm² SC-PVC-CU cables and all accessories including 32A isolator. 16 No 2.13b) 32A TPN local isolator as MK or approved equivalent. 16 No. 2.13a) Outlet for three phase VRF out door units, comprising box, concealed H/G PVC conduit, wiring in 5 x 4.0 mm² SC-PVC-CU cables and all accessories including 20A isolator. 8 No 2.13b) 20A TPN local isolator as MK or approved equivalent. 8 No. 2.14a) Outlet for three phase Air Handling Unit, comprising box, concealed H/G PVC conduit, wiring in 5 x 10.0 mm² SC-PVC-CU cables and all accessories including 63A isolator. 1 No 2.14b) 2.15a) 2.15b) 2.15c) 32A TPN local isolator as MK or approved equivalent. 200A TP MCCB, (adjustable in 150 2000A range) main beaker for the block as Merlin Gerlin or Crabtree, complete with metallic enclosure (Note: BILL/MEM will not be accepted). This breaker is to be fitted in the main branch s switch board in the switch room Carry out solid bonding of the metallic enclosure of the MCCB above to the metallic body of the main switchboard in 6mm 2 green PVC insulated copper cable. Label the above MCCB thus: SUPPLY TO AIR CONDITIONING UNITS MEZZANINE ROOF TOP in red 10mm higher permanent traffolyte labels. Total C/F to Page 2-11 1 No. 2 No
BILL 2 ELECTRICAL INSTALLATIONS FOR AIR-CONDITIONING INSTALLATIONS 2-11 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Total C/F from Page 2-10 2.16a) Sub mains circuit comprising 4C 35mm 2 PVC/SWA/PVC copper cable from the MCCB to the distribution board located at the Mezzanine Roof Top 100 m. 2.16b) Cable glands for the above cable. 2 m. 2.16c) Cable lugs for the above cable. 8 No. 2.17a) 8-way TP/N distribution board complete with 125A TPN integral isolator and all accessories as MK, CRABTREE or MERLIN GERLIN or approved equivalent 1 No 2.17b) TP MCB s for the above board 6 No 2.17c) TP blanking plates for the above board 2 No 2.17d) Earthing for the boards above. Lot 2.17e) Comprehensive Labelling of the boards above. Lot 2.18a) Outlet for three phase VRF out door units, comprising box, concealed H/G PVC conduit, wiring in 5 x 4.0 mm² SC-PVC-CU cables and all accessories including 20A isolator. 6 No 2.18b) 20A TPN local isolator as MK or approved equivalent. 6 No. 2.19a) 2.19b) 6-way TP/N floor distribution boards complete with 125A TPN integral isolator and all accessories as MK, CRABTREE or MERLIN GERLIN or approved equivalent 8 No 4-way TP/N floor distribution boards complete with 125A TPN integral isolator and all accessories as MK, CRABTREE or MERLIN GERLIN or approved equivalent 3 No 2.19c) SP MCB s for the above board 140 No 2.19d) SP blanking plates for the above board 40 No 2.19e) Earthing for the boards above. Lot 2.19f) Comprehensive Labelling of the boards above. Lot Total C/F to Page 2-12
BILL 2 ELECTRICAL INSTALLATIONS FOR AIR-CONDITIONING INSTALLATIONS 2-12 ITEM DESCRIPTION QTY UNIT RATE AMOUNT Total C/F from Page 2-11 2.20a) 2.20b) Outlet point for in-door units comprising 20mm diameter conduit, wiring in 3 x 4.0 mm² SC-PVC-CU cables and all accessories including 20A DP switch with neon light as MK or Crabtree. 30A voltage switch for air-conditioning unit as Sollateck AVS 30, wired to the A/C unit above 140 No 140 No 2.21 63 A Tap offs from the existing rising Bus bar Mains 11 2.22a) Sub mains circuit comprising 4C 16mm 2 PVC/SWA/PVC copper cable 220 m. 2.22b) Cable glands for the above cable. 22 m. 2.22c) Cable lugs for the above cable. 88 No. 2.23a) 150 x 50mm 3-compartment angle trunking to details shown, in 14-gauge galvanized steel sheet with cream powder coating finish to approved colour, complete with cover, screws, and all accessories. 180 m. 2.23b) 2.23c) Additional 150 x 50mm, factory-made corner-bends for the above trunking, in same material and colour finish. Carry out bonding throughout the entire length of the above trunking in 6mm 2 green PVC insulated copper cable. 20 No. 2.14 Single-outlet plates on the trunking, same colour finish 100 No. Total for Bill No. 2: Electricals Installations for Air conditioning Installations C/F to Summary Page
SUMMARY PAGE: 2-13 ITEM DESCRIPTION AMOUNT KSHS. CTS. S.1 Bill No. 1: Mains Power Distribution, B/F from Page 2-6 S.2 Bill No. 2: Electrical Installations for Air Conditioning Installations, B/F from Page 2-12 S.3 Allow for contractors charges for liaison with Kenya Power during the works:- Total Carried Forward to Main Summary Page