LED Emergency Luminaires

Similar documents
EdgeLED TM Range. Installation and Operating Instructions EdgeLED TM RANGE INSTALLATION NON-EMERGENCY LUMINAIRES PRE INSTALLATION

EdgeLED TM Range. Installation and Operating Instructions EdgeLED TM E1, E7, S1 and S7 Recessed Ceiling Luminaires

Doc Ref: WD024/2/11/12 Fern-Howard Ltd. 2 Newman Lane, Alton, Hampshire, GU34 2QR. Reg. No

2D products are warranted for one year, the expected life of the ballast and/or Emergency module is 5 years

MANUFACTURED IN THE UK

Doc Ref: WD029/2/11/12 Fern-Howard Ltd. 2 Newman Lane, Alton, Hampshire, GU34 2QR. Reg. No

MANUFACTURED IN THE UK

Doc Ref: WD027/2/11/12 Fern-Howard Ltd. 2 Newman Lane, Alton, Hampshire, GU34 2QR. Reg. No

icebreaker icebreaker A C G GE Lighting 2D lamps are fitted as standard. I44

Doc Ref: WD030/2/11/12 Fern-Howard Ltd. 2 Newman Lane, Alton, Hampshire, GU34 2QR. Reg. No

LED emergency exit signage from Channel Safety Systems

EXI LED INTRODUCTION APPLICATION PRODUCT SPECIFICATION

NON MAINTAINED TWIN SPOTLIGHT WALL MOUNT LED EMERGENCY LIGHT

BALT5-800 LOW-PROFILE FLUORESCENT EMERGENCY BALLAST

LED AC DRIVERLESS FLOODLIGHTS WITH PIR FOR MODEL: FLAC10BPIR, FLAC20BPIR, FLAC30BPIR & FLAC50BPIR

EMERGENCY ONE-LED TM SOLO TM NON MAINTAINED LED LAMP AND DRIVER KIT

MAINTAINED LED DOUBLE SIDED SUSPENDED CEILING MOUNTED EMERGENCY LIGHT

Central Battery Systems Loadstar AC/DC Systems

MAINTAINED LED EMERGENCY CEILING MOUNT SPOTLIGHT

MAINTAINED LED CIRCULAR EMERGENCY CEILING LIGHT

INSTALLATION & MAINTENANCE MANUAL HBL

Installation and Operation Instructions 10/04/13

Operating Instructions

User Manual Rittal PMC UPS 6kVA

UL AND CODE COMPLIANCE

Emergency lighting units EM series

Archimedes. user instructions. Simple solutions for everyday independence

EMERGENCY ONE-LED TM OMNI-LED DST TM LED DALI EMERGENCY CONVERSION MODULE WITH SELF-TEST

PSU EN54-4 Power Supplies

AXUS AX High Temperature 300 C for 2hr, 400 C for 2 hour

Rental Industry Safety Tester Safe Check 5s

GENERAL INFORMATION. INSTRUCTIONS FOR 500A Lithium Jump Starter

Emergency lighting units EM powerled

2 PORT MOTORISED VALVE (28 mm)

This standard covers the requirements of luminaires for emergency lighting chains. This standard covers safety and performance requirements.

Emergency lighting units EM converterled

Emergency lighting units EM converterled

Grant Grid-Connected Inverter For Grant Solar PV Systems. Installation & User Instructions

Zone 1 Linear Range - Installation Guide

BAL1400 FLUORESCENT EMERGENCY BALLAST Specification-grade One or two-lamp emergency illumination

2 TONNE TROLLEY JACK

Emergency lighting units EM converterled

KD1E Range Potential Indicators

PSU1 Power Supply Unit

The 4HR-UPS 220V ac output is provided via a Pure Sine Wave inverter, allowing it to be backed up by 2x 12V standby batteries.

freedom through lightweight solutions

3 PORT MOTORISED VALVE (22 mm)

EMERGENCY ONE-LED TM UNITY-LED TM LED MAINS/EMERGENCY DRIVER

GL1200T Cut & Seal. (GL1200 Seal only)

Operating Instructions

GL1200T Cut & Seal. (GL1200 Seal only)

3 PORT MOTORISED VALVE (32/38 mm)

Instructions for use. Hawker Premier

Installation Instructions Central Battery Units

Emergency lighting units EM powerled

Nickel Metal Hydride Battery Pack. User Handbook

2 PORT MOTORISED VALVE (22 mm)

ZonePlus Z322 zone valve Installation and commissioning instructions

PCR 6. Operators Manual. Vertical Laminar Airflow Cabinet with U.V. Sterilisation. Issue 05 September 2013

Emergi-Lite EMEX central power supply solutions

Mangar Archimedes Instruction & Safety Manual

Emergency lighting units EM converterled

Guidance to Installers of Viridian EV Charging Stations

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT

Emergency lighting units EM converterled

INSTRUCTION MANUAL IMPORTANT SAFEGUARDS. When using electrical equipment, basic safety precautions should always be followed, including the following:

Emergency lighting units EM converterled. EM converterled ST 90 V SELFTEST series

EMERGENCY LIGHTING TESTING

Emergency lighting units EM converterled. EM converterled ST 50 V SELFTEST series

These operating instructions apply for: NCX 380 NCZ 300 NCX 480 NCZ 370 NCX 580 L NCZ 480 NCX 660 K NCZ 560 NCZ 660 NCZ 800

EM converterled BASIC Installation and wiring instructions

BAL3000 FLUORESCENT EMERGENCY BALLAST Specification-grade: Up to 3500 lumens One or two-lamp emergency illumination

EMERGENCY ONE-LED TM UNITY-LED TM LED MAINS/EMERGENCY DRIVER

INSTRUCTION MANUAL IMPORTANT SAFEGUARDS. When using electrical equipment, basic safety precautions should always be followed, including the following:

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

OEM Emergency Portfolio. Product Guide. Emergency components for LED, fluorescent and auxiliary purpose

X20020 INFRESCO P 4kW Issue 4 User manual Date 16/02/16. Page 1 of 9 KEY FEATURES

3 TONNE TROLLEY JACK

LEAD ACID BATTERY CHARGER

Installation, Operation & Maintenance Instructions 250 C Laboratory Fan Ovens Apex Range models AX30, AX60 & AX120

Emergency lighting units EM converterled. EM converterled PRO 200 V PRO series

LED light engines ready2apply. Engine SLA AC G2 50mm SNC Engine SLA ESSENCE

LED Area Light. This is the fixture of choice for all of our dealerships. Contact Us:

HE-PSU(4.0) Power Supply & Battery Charger Installation, Commissioning & Operating Manual

Emergency lighting units EM converterled. EM converterled BASIC 200 V BASIC series

superstart starter/chargers

freedom through lightweight solutions

Emergency lighting units EM converterled. EM converterled BASIC 90 V BASIC series

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS SOLAS LED Luminaire ATEX & IECEx

LED Area Light. scratch that. This is the fixture of choice for all of our dealerships. Contact Us:

Emergency lighting units EM powerled

Floodlight Range Installation Guide

SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS

Single Phase Electronic Speed Controllers

INSTRUCTION MANUAL. IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed, including the following:

04979, 04980, 04981, 04982, 04983, 04984, 39054, 39055, 39056, 39057, 39225, 81459,

Specification Sheet for 2D LED Light

10W LED Die Cast Small Rectangle Bulkhead Light

BATTERY STARTER/CHARGER MODEL NO: BC125, BC190

Transcription:

LED Emergency Luminaires THIS FITTING SHOULD NOT BE USED IN AREAS EXCEEDING 25 C AMBIENT AIR TEMPERATURE This fitting must be installed by a qualified electrician and wired in accordance with the latest edition of the IEE Electrical Regulations. Information regarding Part Number, Description, Voltage, Frequency and IP Rating is shown on the label affixed to the luminaire. PRE INSTALLATION ALWAYS TURN OFF THE MAINS SUPPLY BEFORE COMMENCING INSTALLATION Make sure that the mains supply is compatible with the fitting. If IP rating has to be retained. A cable gland of the correct IP rating must be used and any fixing holes must be filled with a proprietary silicon sealing compound. High voltage insulation test equipment MUST NOT be used on High Frequency, Emergency or Dimming luminaires. The luminaire is suitable for use within ambient temperature range of -10ºC to + 25ºC ONLY. Particular attention should be paid to the temperature range for emergency fittings. Installations that regularly drop below 0º C for prolonged periods, particularly when the luminaire is not illuminated are likely to result in a shortened battery life. In such applications a regular testing and battery replacement schedule is recommended. Page 1 of 5

INSTALLATION EMERGENCY LUMINAIRE For all non-maintained and maintained emergency light fittings, the driver is electronic, consisting of a high frequency inverter, battery charger, charge indicator, and battery deep discharge protection circuit. These fittings are self-contained without Rest Mode facility. All emergency versions are 3 hour duration. The mains supply and the battery connection must be disconnected before servicing or maintenance. The battery connections must be left disconnected during installation if the site supply is switched off at the end of the day. CIRCUITS The emergency mains supply must be connected to a direct source via a Key Switch (for test purposes only). The switched line must be wired so that it disconnects from the luminaire if the Key Switch is switched off (no power to the fitting). NOTE: The incoming supply earth MUST be connected. NOTE: Both luminaire supplies must be broken simultaneously (switched and un-switched) when testing. Connections into the driver must not exceed 2.5mm2. Emergency Wiring Neutral N After connecting the mains supply, check that the green charge indicator is illuminated. The luminaire should operate when it is switched on (maintained and sustained only). Incoming Supply Earth Un-switched live Switched live 1 2 Green/Yellow Luminaire Wiring An initial uninterrupted minimum charge period of 24 hours should always be allowed before testing the module for its rated duration. To make the fitting Non-Maintained leave out the Switched Live Close the gear tray (make sure that all cables are clear of the gear tray components) and if applicable secure with the screw(s) provided. Screw on the diffuser making sure that it is correctly tightened to locate in the seal. The recommended maximum battery storage period of one year should not be exceeded. If batteries have been left in a discharged state, one or more full charge / discharge cycles may be necessary to restore them to their normal capacity. Stick the supplied rating label to the luminaire where it can be seen! It MUST NOT be fitted on the diffuser. X 1 180 Page 2 of 5

GENERAL ROUTINE MAINTENANCE At commissioning and handing over of the installation, ensure that a copy of this data is presented to the authority responsible for the operation, maintenance and repair of the luminaires. Cleaning of the Luminaire must only be carried out after the fitting has been isolated from the electrical supply. ALWAYS check before servicing. Cleaning should be carried out at regular intervals to ensure that contaminants do not accumulate to an extent that will impair the thermal safety of the luminaire, or degrade the optical performance. DO NOT use spirit based cleaners. Notes: This luminaire should not be modified or repaired by any persons other than those nominated by the manufacturer. Any unauthorised modification or repair may render the luminaire unsafe and will invalidate the warranty and conformance to any safety or safety standards that may apply. The company will accept no responsibility for any modified fittings or for any damage caused as a result of modifications. All details are given as guidance only and do not constitute a contract. We reserve the right to change or withdraw products without notice. Installation Details Installation Date: Contact Details: Installer Name: Installation Site Details: Amount and Type of Fittings installed: Page 3 of 5

ROUTINE MAINTENANCE FOR EMERGENCY LUMINAIRES Routine maintenance must be carried out in compliance with the requirements of the British Standards Institute Code of Practice BS5266: Part 1 - Emergency Lighting of Premises. The following tests assume a three-hour system Daily 1. Check that any recorded faults have been rectified. 2. Check that the charge indicator Monthly 1. Check that luminaire operates in emergency mode. 2. Simulate a mains failure and immediately and remains on for three minutes. 3. After reverting back to mains Six Monthly 1. Simulate a mains failure and immediately and remains on for at least one hour. 2. After reverting back to mains 3. On restoring the mains supply the unit will require 24 hours to recharge before becoming fully operational. Annually 1. Simulate a mains failure and immediately and remains on for at least 3 hours. 2. After reverting back to mains 3. On restoring the mains supply the unit will require 36 hours to recharge before becoming fully operational. It is recommended that battery packs are replaced every 4 years or sooner if the unit performance requirements fail to be met. To maintain optimum unit performance, only approved replacement battery packs must be used. All routine maintenance checks must be recorded on the unit Test Record / Installation sheet and must be made available for inspection at all times. INSTALLATION/ COMMISSIONING AND TEST RECORD Model No Type Installed by Commissioned by Location Serial No (on gear tray) Date Date Routine Test Report First Year Second Year Third Year Fourth Year Fifth Year Monthly Test Signed Date Signed Date Signed Date Signed Date Signed Date 1 Hour Duration 1 Hour Duration Full Duration Page 4 of 5

DISPOSAL The disposal of any electrical equipment, including this fitting may be subject to Local Authority Regulations and therefore should be consulted for specific guidance. The batteries within this fitting are Nickel Cadmium and must be disposed of as per Local Authority Regulations for the disposal of toxic waste. Fern-Howard products are manufactured in the UK at our modern factory in Alton, Hampshire. Luminaires are manufactured and tested in accordance with BS EN60598. Incorporated control gear and components comply with BS/VDE standards. Luminaires are tested in accordance with IES LM-79-08. Fern-Howard, 2 Newman Lane, Alton, Hampshire, GU34 2QR, United Kingdom. FHD-IOI03 ISSUE 1 MAR2015 Registered in England Reg. No. 3202749. We reserve the right to alter specifications without notice in accordance with our policy of continuous product improvement. Design and copyright reserved and our standard Term & Conditions apply. Full details of our warranty can be found on our website.