How to Use Coordinaide to Protect Transformers Against Secondary-Side Arcing Faults.

Similar documents
Source-Side Fuse/Load-Side Recloser Coordination

Selection Guide S&C ELECTRIC COMPANY. For Transformer-Primary Fuses in Medium- and High-Voltage

NX indoor current-limiting fuses

Selective Coordination

3.2. Current Limiting Fuses. Contents

Figure 1. Two and Three-phase MagneX.

PROTECTION AND CONTROL

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

X-Limiter full-range current-limiting fuse

OVERALL LENGTH (B) " ( mm) " ( mm) " ( mm) " ( mm)

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

K-Limiter high ampere Companion II fuse

Design Tests for the 38.0 kv ELSP Current-limiting Fuse per ANSI/IEEE C

8.3kV, 9.9kV, 15.5kV, 17.2kV and 23kV Cooper ELSP Backup Fuses Testing per C

Application of Hi-Tech Trans-Guard EXT and OS Shorty fuses

Product Selection Guide

Companion II 8.3kV, 17.2kV and 23kV 12K - 40K Backup Fuses

Medium Voltage Metal-Enclosed Switches

A. Submit manufacturer's literature and technical data before starting work.

Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers

Recommended Procedures

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Medium Voltage Metal-Enclosed Switches

Published for electrical engineers by EPOWERENGINEERING and available at The ABC s of Overcurrent Coordination

Technical Specification For Outdoor Substation Harmonic Filter Banks

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

Expulsion Fuses. 2.2 Fuse Selection. 2.3 Application. 2.4 BA Type Fuses. 2.5 DBA Type Fuses. 2.6 DBU Type Fuses. 2.7 RBA and RDB Type Fuses

MOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.

Chapter 6 Generator-Voltage System

Protective Device Coordination ETAP Star

Table 1.-Elemsa code and characteristics of Type K fuse links (Fast).

Horizontal Circuit Switchers

Mica Element Support. Compacted Quartz Sand. Length B

4-Day Power System Analysis, Coordination, System Studies

Motor Protection. Presented By. Scott Peele PE

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

Engineering Dependable Protection

Application of Primary Fuses

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

www. ElectricalPartManuals. com Engineering Dependable Protection

SX Full-Range Current-Limiting Fuse. Power & High Voltage Elastimold & Hi-Tech Fuse Products

Elastimold. Cable Accessories. Underground Distribution Switchgear. Molded Vacuum Switches and Fault Interrupters

Service Entrance Methods

Equipment Protection. Transformers 600V or Less

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

Section 1 Introduction to the Presentation

FUSES. Safety through quality

Electromagnetic Industries LLP

Fuse Link Designation

FX Full-Range Current-Limiting Fuse

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

A240R/A480R/A072F/A072B MED. VOLTAGE FUSES / R-RATED

Typical Specification

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

750 kva Transformer V Delta Primary Voltage - 480Y/277 Wye-N Voltage Secondary - NEMA 3R

Using Fuses to Provide Fault Protection of Windfarm Transformers

Each of these factors, as they apply to the selection of Types CLE and CLS current limiting fuses, is briefly outlined on the following pages.

Understanding Arc Flash Hazards. White Paper

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

EE 741 Over-voltage and Overcurrent. Spring 2014

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

CATALOG. Hi-Tech Fuse Products

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Alternator protection, part 1: Understanding code requirements

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

Horizontal Circuit Switchers

STANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General

Limitor -G General Purpose Fuses

Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC

Motor Protection. Voltage Unbalance & Single-Phasing

ECET Distribution System Protection. Overcurrent Protection

Enhancing Short Circuit Selective Coordination with Low Voltage Circuit Breakers

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

BUSSMANN. 8.3kV E-Rated SERIES. Medium voltage fuses for feeder circuit, switchgear and transformer. protection. Technical Data 10352

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Equipment Protection. Transformers 600V or Less

ECE 480 Design Team 3: Designing Low Voltage, Low Current Battery Chargers

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

Power System Solutions (PSS)

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

SafeGear TM Motor Control Center Arc resistant metal-clad construction

Elastimold & Hi-Tech Fuse Products

Technical Specification for Pole Mounted Capacitor Rack

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

POW ER EN G IN EER S, L LC

ELASTIMOLD & HI-TECH FUSE PRODUCTS

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT

SWITCHGEAR DIVISION PRODUCT PROFILES

Transcription:

How to Use Coordinaide to Protect Transformers Against Secondary-Side Arcing Faults. This is the second in a series of articles describing how Coordinaide The S&C Protection and Coordination Assistant can be used to select the optimal S&C fuse or Vista Underground Distribution Switchgear TCC curve to protect transformers, capacitor units, lines, cables, or motors, or to selectively coordinate with one or more protective devices in series. This installment explains how to select a transformer-primary fuse to protect against arcing secondary-side faults. Two properly selected fuses, a solid-material power fuse and a current-limiting power fuse, will be considered. A Brief Discussion of Transformer Protection The most important principle to be considered when selecting a primary fuse for a three-phase power transformer is that it must protect the transformer against damage from mechanical as well as thermal stresses resulting from secondary-side faults that are not promptly interrupted. A properly selected primary fuse will operate to clear such a fault before the magnitude and duration of the overcurrent exceed the through-fault current duration limits recommended by the transformer manufacturer, or published in the standards. Curves representing these limits can be found in the latest issue of ANSI/IEEE Standard C37.91, Guide for Protective Relay Applications to Power Transformers, and ANSI/IEEE C57.109, Guide for Transformer Through-Fault Current Duration. Although the through-fault protection curves are only a guide, they are nonetheless recommended as a criterion against which to measure the degree of transformer protection provided by the primary fuse. To meet this criterion for highmagnitude secondary-side faults, the total-clearing curve of the primary fuse should pass below the point on the appropriate through-fault protection curve (commonly called the ANSI Point) at the current level corresponding to a maximum threephase secondary-side fault based solely on the transformer impedance (i.e., a bolted fault assuming an infinite source). In addition, to provide maximum protection for the transformer against faults located between the transformer and the nearest secondary-side overcurrent protective device as well as maximum backup protection for the transformer in the event the secondary-side overcurrent protective device fails to operate, or operates too slowly due to an incorrect (higher) rating or setting the total clearing curve of the primary fuse should intersect the appropriate through-fault protection curve at the lowest possible value of current. The results of published studies [ 1 ] [ 2 ] [ 3 ] indicate that, under arcing conditions, secondary-switchboard and other nearby faults on 480/277Y-volt circuits may have magnitudes as low as 40% of the maximum available phase-to-ground fault current level at the point of the fault. You can determine if the transformer-primary fuse will protect against an arcing secondary-side fault by referring to Table 1 (below) which lists primary-side line current values for various types of secondary-side faults and for various transformer connections and impedances, expressed in percent of the transformer fullload current. The desired protection is obtained if the current value at which the total-clearing curve of the primary fuse intersects the transformer through-fault protection curve is less than the values shown in Table 1.

Table 1. Secondary Fault Currents Reflected to Primary Lines Transformer Connection Impedance Arcing Phase-to-Ground Fault Maximum Primary-Side Line Current for Various Types of Secondary Faults, Percent of Transformer Full-Load Current Three-Phase Phase-to-Phase Phase-to-Ground 1000% 700 500 % 2180% 1580 1510 1340 1090 % NA 2180 1580 1510 1340 1090 NA 580 400 290 1450 1050 1010 890 730 NA Not Applicable Commonly accepted arcing-fault-current values for secondary-switchboard and other nearby faults. For transformers with medium-voltage secondaries (2.4 kv or 4.16 kv), the entries in the Phase-to-Ground column apply. REFERENCES 1. J. R. Dunki-Jacobs, The Effects of Arcing Ground Faults on Low-Voltage System Design, article reprinted from the May/June 1972 issue of IEEE Transactions on Industry and General Application. 2. J. R. Dunki-Jacobs, State of the Art of Grounding and Ground Fault Protection, article reprinted from the 1977 Conference Record of the IEEE 24th Annual Petroleum and Chemical Industry Conference, September 13-14, 1977, Dallas, Texas, Catalog No. 77CH1229-4-lA. 3. L. E. Fisher, Resistance of Low-Voltage Alternating Current Arcs, IEEE Transactions on Industry and General Applications, Vol. IGA-6, November/December 1970, pages 607-616. Doing the Exercise To complete the transformer protection exercise describe above, you ll need to launch Coordinaide. Then you ll be directed to the Coordinaide opening page, which contains a brief description of the protective applications Coordinaide is designed to handle. When you launch the program, you ll be directed to a second page that contains a brief Conditions of Use disclaimer, followed by a short note detailing minimum web browser requirements and a link to a

Helpful Hints page. One final click launches the program and takes you to the General Information page. Please follow these directions to select the lateral (section-alizing) fuse, the transformer fuse, and, finally, to determine the value of current up to which the two fuses coordinate. Values in italics are to be entered into Coordinaide. Enter the Project s General Information Project Name: Transformer Protection Exercise Date: [provided by Coordinaide] By: Optional Voltage, kv (Three-Phase): 12.47 (default value) Available Fault Current (RMS Symmetrical Amperes): 15000 (no comma) Select Device #1 Type Power Fuse Select Device #2 Type Transformer Click Continue after specifying Devices #1 and #2. Select Parameters for Device #1 Manufacturer: S&C Type: SMU-20 Speed: Standard kv range: 7.2-14.4 Rating: 65E Preload Adjustment, Percent: 0 (default value) Ambient Temperature Adjustment: 25 Degrees Celsius (default value) Click Continue after selecting the parameters for Device #1. The time-current characteristic curve for Device #1 will display. Select Parameters for Device #2 3-Phase Primary kv: 12.47 (default) 3-Phase Secondary kv: 0.48 3-Phase Rating kva: 1000 Impedance in Percent (1% - 15%): 5.75 Fault Current in Sym RMS Amps: 15000 (from General Information Page)

Connection: Delta / Grounded-Wye Click Continue after selecting the parameters for Device #2. The time-current characteristic curve for Device #2 will display. Results Page Click on the tab at the top labeled Results. If desired, you can change the current scale of the grid from the default, 5 to 100,000 amperes, to 0.5 to 10,000 amperes. You can also zoom in on a particular section of the grid by entering the upper and lower current and time values into the appropriate cells. To determine the exact value of current down to which the 65E-ampere Standard Speed solid-material power fuse will protect the transformer, place the cross hair cursor over the intersection of the total-clearing curve of the 65E-ampere primary fuse, and either one of the two transformer through-fault protection curves, and click once. The current value down to which the fuse will protect the transformer is displayed at the top of the grid, approximately 140 amperes for a three-phase secondary-side fault, and approximately 150 amperes for a phase-to-ground secondary-side fault. For convenience, these values are automatically computed by Coordinaide, expressed as a percentage of the transformer s full-load (i.e., nameplate) current, and are displayed on the summary page. They are given the name Transformer Protection Indices (TPIs). For a three-phase secondary-side fault, the 65E-ampere Standard Speed fuse will protect the transformer down to 305% of its full-load current. Referring to Table 1, for a bolted three-phase secondary-side fault on this transformer ( impedance, delta / grounded-wye connection), the maximum value is % of the nameplate current. Clearly, the 65Eampere primary fuse will protect against this type of fault. It will also protect against a bolted phase-to-ground secondaryside fault since the TPI is 322%, whereas the maximum index value for this fault, shown in Table 1, is 1010% of nameplate. In fact, the subject fuse will also protect against an arcing phase-to-ground secondary-side fault since the TPI is less than the maximum value for an arcing fault shown in Table 1, which is 400% of the transformer s nameplate current. See Figure 1. The excellent protection provided by the solid material power fuse is due, in large part, to its tight tolerances and also because of the inverse-time shape of its time-current characteristic curve. As you will discover in short order, because of its broad tolerances and very steep time-current characteristic curve, a current-limiting fuse having a similar ampere rating will not provide much in the way of transformer protection, all other factors being equal.

Figure 1. Now repeat this exercise using a Cooper Power Systems NX style current-limiting fuse rated 60C amperes for Device #1. As you will see, this fuse barely protects against a bolted phase-to-ground secondary-side fault, and it will not protect against an arcing secondary-side fault. Clearly, a fuse that can protect against arcing secondary-side faults would be preferred over one that cannot provide such protection.