MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

Similar documents
MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

SINGLE DUCT VAV TERMINALS MODELS TSS & TSL TSS TSL. New Release Form NOM1 (808) INSTALLATION, OPERATION & MAINTENANCE

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

TSS Single-Duct VAV Terminals

INSTALLATION MANUAL TBH/TBV BELT DRIVE BLOWER-COIL UNITS HORIZONTAL. Redefine your comfort zone.

SDL Single-Duct, Low-Height, VAV Terminals

MANUAL INSTALLATION. Venturi FX. VFX Series. v100 Issue Date: 11/22/ Price Industries Limited. All rights reserved.

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions

University of Delaware

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

MF4E MF4E

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual

ATP-2040 Electric Damper Actuator/Transmitter

MANUAL INSTALLATION. Active Chilled Beam Linear. ACBL Series. v101 Issue Date: 04/10/ Price Industries Limited. All rights reserved.

SECTION CENTRIFUGAL HVAC FANS

Fan Powered Low Profile Variable Volume Terminal Units

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

SECTION AIR TERMINAL UNITS

catalog SDL Single-Duct, Low-Height, VAV Terminals

LDV / LDVQ 5000 AIR VOLUME CONTROL VALVE INSTALLATION MANUAL. Date: 02 / 10 Reference # : F-36. w w w. p r i c e - h v a c. c o m

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

Laboratory Exhaust Air Terminal

SECTION AXIAL HVAC FANS

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC

Dual Duct Variable Air Volume Terminal (Model TDS)

M100F Incremental Motor Actuator R81F Interface Board

General Description. Product Specification. Document Digital Temperature Interlock

catalog SDL Single-Duct, Low-Height, VAV Terminals

Installation Instructions

READ AND SAVE THESE INSTRUCTIONS

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

EDA-8100 Electric Damper Actuator

FN Fan-Coil Units High-Performance, Horizontal

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

AMB24-3(-S) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

Installation Manual for Ecology

Installation Instructions

SBH / SBV Sales Guide BLOWER-COILS HORIZONTAL AND VERTICAL

SECTION HVAC POWER VENTILATORS

Installation, Operation and Maintenance Manual

LMX120-SR. Proportional Control, Non-Spring Return, Direct Coupled,100 to 240 VAC, for 2 to 10 VDC and 4 to 20 ma

Products for Indoor Air Quality and Control

Installation, Operation, and Maintenance Instructions

Inline Fans [ 14 ] * UL is optional and must be specified.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SINGLE DUCT AIR TERMINAL UNITS

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

INSTALLATION VARIABLE FREQUENCY DRIVE THREE PHASE ALX SERIES SPUN ALUMINUM EXHAUSTERS

FAN POWERED TERMINAL UNITS

MA-5200 Series MA-5300 Series


Application Guide TABLE OF CONTENTS: I. Introduction II. LHK Description III. Applications IV. Suggested Specification

RM-1200 Slim Round Control Damper

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST. For Use with Bard 2 2-1/2 Ton Wall Mount T Series Heat Pumps

Tubular Centrifugal Fans

ACCUSTATION SUBMITTAL MATERIALS

Air Handling Unit Construction Checklist

Installation, Operation and Maintenance Manual

Variable Air Volume (VAV) Pressure Independent Control

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

Installation/ Operation Maintenance. VariTrac Dampers

Electric Coil [Make-Up Air / Displacement Ventilation / Space Heating] System

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Modified Downdraft Paint Booth Nut and Bolt Assembly Pre-Punched Panel Flanges

ACCUVALVE MODEL AVC6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVC6000 AVC6 - - DWG. NO: REVISION: REV. DATE:

Slide Gates INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS. 295-E-002 Effective

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile

ACCUVALVE MODEL AVT6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVT6000 AVT6 - - DWG. NO: REVISION: REV. DATE:

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator

Series 10 Actuator. Installation, Operation and Maintenance Manual

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual

Installation Manual. HEPALERT LED LIGHT Kit Installation, Operation, and Maintenance Manual for the TLF Diffuser

Jet Fans. Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY

TABLE OF CONTENTS SPECIFICATIONS 3 INSTALLATION 4. Direct Mount 4. Ducted Installations 5. Installing Plenum 5. Machine Mount Stand 5.

500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT FORM EG3 (404)

AIR ZONE INTERNATIONAL MIXED-FLOW AIR COLUMN UNIT

RBV Sales Guide FAN COIL UNITS FLOOR-MOUNTED, VERTICAL

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm

CCS Zone/Bypass Damper Assembly

Installation, Operation and Maintenance Manual

Table of Contents PAGE General Mounting Standard Reversible Clamp Linear Rotary Retrofit Brackets...275

AIR CLEANERS. Model MX 6000 OWNER S MANUAL CAUTION. Read complete instructions before operating. Please file for future reference.

RETROFIT TERMINAL UNITS

Installation Instructions

Operating Instructions & Parts Manual. Energy Recovery Ventilators. Models 2RB84A and 2RB85A

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499]

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

Safety & Installation Instructions

PC-125x Counter-Balanced Backdraft Damper

Installation, Operation and Maintenance Manual

System 350 P352AB Electronic Pressure Control Series

Installation, Operation and Maintenance Manual

M9208-AGx-x Series On/Off and Floating Point Electric Spring Return Actuators

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Transcription:

BY JOHNSON CONTROLS INSTALLATION OPERATION & MAINTENANCE MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS New Release Form ET130.13-NOM4 (908) In conjunction with the use of these instructions, obtain and refer to the construction, fan performance, and control wiring drawings submitted for the specific project. The equipment covered in this document is designed for safe and reliable operation when installed and operated within its design specification limits. Observe the following cautionary statements. Electrical Shock Hazards. All power must be disconnected prior to installation and servicing this equipment. More than one source of power may be present. Disconnect all power sources to avoid electrocution or shock injuries. All assemblies must be adequately secured during lifting and rigging by temporary supports and restraints until equipment is permanently fastened and set in its final location. All unit temporary and permanent supports must be capable of safely supporting the equipment s weight and any additional live or dead loads that may be encountered. All supports must be designed to meet applicable local codes and ordinances. INSPECTION 1. Upon receipt of the equipment, carefully check all items against the bill of lading to ensure that all of the equipment has been received (including shipped loose items). Note any discrepancy on the bill of lading before signing for the shipment. 2. Inspect all equipment for any signs of damage caused during transit. Note any visual damage on the bill of lading before signing. Immediately report all visual and concealed damage to the carrier and file a claim with the carrier. 3. Locate the model number on the unit label and check that the correct units have been received. Verify that all options have been included. Also check that the unit voltage agrees with the building parameters. If a discrepancy is discovered between what was ordered and what was received, contact your local representative immediately. Check assembly and component weights to be sure that the rigging equipment can handle them safely. In addition, check the centers of gravity and any specific rigging instructions. Check for adequate ventilation so fumes do not migrate through ductwork to occupied spaces when welding or cutting around the unit. All fastening devices must be designed to mechanically lock the assembly in place without the capability of loosening or breaking away due to system operation and vibration. Secure all dampers when servicing damper, actuator or linkages. Dampers may activate automatically; disconnect control circuits to avoid injury.

FORM ET130.13-NOM4 (908) STORAGE If equipment is to be stored for more than two weeks prior to installation, observe the following storage precautions: Choose a dry storage site that is reasonably level and sturdy to prevent undue stress or permanent damage to the equipment. Set the equipment off of the ground if in a moisture prone area. Remove all loose parts from the job site to minimize theft. Tag and store the loose parts in a safe place until needed. Cover all of the equipment with a protective tarp or moisture proof cover. Extend the cover under the equipment if it is stored on the ground. Secure the cover with adequate tie downs and store indoors. PRE-INSTALLATION INSPECTION 1. Check the coupling that connects the actuator to the damper shaft to ensure that the nuts are tight. 2. While viewing the damper from the discharge of the unit, rotate the shaft fully. The damper should close fully and there should be no gaps between the damper gasketing and the inside of the valve. Sequence of Operation The basic unit consists of an air valve, which is used to modulate the air being delivered into the occupied zone. These units are designed to modulate either cooling or heating air between 40ºF (4ºC) or 140ºF (60ºC). Air enters the air valve inlet and exits to the occupied zone through ductwork attached to the discharge of the unit. Galvanized steel air valves come in diameters of 4, 5, 6, 8, 10, 12, 14, and 16 inches; an adapter must be used for metric ductwork. Size 6 through 16 utilize the FlowStar airflow sensor, while sizes 4 and 5 feature a single axis averaging airflow sensor. INSTALLATION Clearances Observe the following clearance requirements. All equipment covered in this document are ETL listed for 0.0 clearance to combustibles. Refer to National Fire Protection Association (NFPA) 70 in the National Electrical Code (NEC) requirements and/or local codes for minimum electrical clearances required for service. Equipment should not make contact with any structure located above the equipment without appropriate isolation. Hanging and Mounting Equipment Observe the following hanging and mounting requirements: Although the basic equipment is generally light enough that it can be supported by the ductwork, it is strongly recommended that all equipment be suspended from the upper most ceiling or a structural element of the building, independent of the false ceiling grid. Suspension devises are field supplied, sized and designed by others. Johnson Controls, Inc. will not accept responsibility for unit support. Equipment must be installed in a level horizontal plane. Provisions for proper support in seismically active regions is the responsibility of others. SeeTable 1 for more information on unit weights. Hanger straps may be utilized as a means of suspending the equipment. Do not secure hanger straps to control enclosures. Hanger straps can be mounted directly to the unit, such that they do not interfere with the damper assembly, using screws that are no longer than 1. When hanging equipment, always use the support method as prescribed in the job specifications. Stainless steel air valves come in diameters of 6, 8, 10, 12, 14 and 16 inches and utilize a stainless steel single axis averaging flow sensor. See calibration charts on page 5. 2 JOHNSON CONTROLS

FORM ET130.13-NOM4 (908) TABLE 1 - SINGLE DUCT ROUND AIR TERMINAL WEIGHTS Duct Connections SIZE WEIGHT (LBS) 04 15 [7] 05 15 [7] 06 15 [7] 08 17 [8] 10 19 [9] 12 20 [9] 14 21 [10] 16 24 [11] Note: Weights in Lbs. [Kg.] Electrical Connections Observe the following electrical connection guidelines: All field wiring must comply with NEC and all local codes. Electrical and control wiring diagram is located on the control enclosure box. The installing electrician should rotate the incoming electric service by phase to help balance the building electrical load. Use copper conductors only. OPERATION When fastening ductwork to the unit, make sure that fasteners do not penetrate the unit in a location that interferes with damper assembly operation. Observe the following duct connection guidelines: Start-Up IMPORTANT: Thorough safety precautions should always be taken when performing startup and service. Only qualified individuals should perform these tasks. All duct connections should be configured and installed in accordance with Sheet Metal and Air Conditioning Contractors National Association (SMACNA) guidelines and all local code requirements. Fasten and seal all ductwork connections in accordance with project specifications. Allow a minimum of 1½-duct diameters of straight duct prior to equipment inlet and equipment discharge. The diameter of the inlet duct for round valves must be equal to the listed size of the equipment. The round air valve inlet collar of the equipment is 1/8 smaller then the listed size in order to allow the round ductwork to slip over the air valve inlet collar. Do not insert ductwork into the air valve inlet collar. If the equipment is to be installed in a location with high humidity, external insulation around the unit should be installed. After all connections are made, check that the entire ductwork system is airtight. In some high pressure systems, duct sealer may be necessary. 1. Check that all electrical work is finished and properly terminated. 2. Check that all electrical connections are tight and that the proper voltage is connected. Damper Shaft There is an indicator on the end of the damper shaft that can be used to determine the position on the damper blade. If the indicator is horizontal, the damper is completely open. The damper shaft is ½ diameter. MAINTENANCE Optional Damper Actuator An optional factory mounted floating type actuator is available, which mounts directly to the damper operating shaft. The actuator is not provided with and does not require any limit switches but is electronically protected against overload. See ACT 24 ACTUATOR IOM. Manual Override A button on the side of the actuator cover disengages the gear train so the drain shaft can be moved manually. Releasing the button will re-engage the gear train. JOHNSON CONTROLS 3

FORM ET130.13-NOM4 (908) External Terminal Strip The external terminal strip is located on the top of the actuator. Connections are numbered. The terminals are designed for 26 to 16 gauge wires. For most installations, 18 or 16 gauge wire will work well with the actuator (see table 2 for maximum wire lengths). TABLE 2 - MAXIMUM WIRE LENGTHS WIRE SIZE MAX FEET 16 GA 1225 FT 18 GA 725 FT 20 GA 400 FT 22 GA 200 FT Overload Protection The actuators are electronically protected against mechanical overload. In the actuator, an electronic circuit maintains the current at a level that will not damage the motor while providing adequate holding torque. Checkout Instructions 1. Disconnect actuator from the controller. 2. Apply 24 VAC to the COM and CW terminals on the actuator. Actuator should rotate in a clockwise direction. 3. Apply 24 VAC to the COM and CCW terminals on the actuator. Actuator should rotate in a counter clockwise direction. 4. If actuator moves in both directions, it is operational. 5. If the actuator does not rotate, it may be at an end stop or there is a problem with the damper. 6. Loosen the set screw to free the actuator from the damper shaft. Check to make sure that the damper shaft rotates freely. 7. Check to make sure that actuator is not against stop. Repeat steps 2 and 3. 8. If actuator does not rotate, replace. 4 JOHNSON CONTROLS

CALIBRATION CHARTS FORM ET130.13-NOM4 (908) Notes: UNIT SIZE 400 SERIES (PNEUMATIC) STANDARD CON- TROLLER 7000 SERIES ANALOG ELECTRONIC DDC CONSIGNMENT CONTROLS (See Notes Below) MIN. MAX. MIN. MAX. MIN. MAX. Min. transducer differential Max. transducer differential pressure (in. w.g.) pressure (in. w.g.) 0.015 0.03 0.05 1.0 1.5 4 43 250 35 250 30 43 55 250 250 5 68 350 50 350 48 65 88 350 350 6 75 490 60 550 53 75 97 435 530 8 145 960 115 1000 105 145 190 840 1000 10 235 1545 185 1600 165 235 305 1355 1600 12 340 2250 285 2300 240 340 440 1975 2300 14 475 3100 390 3100 335 475 615 2750 3100 16 625 4100 520 4100 440 625 805 3595 4100 19 1180 6500 1025 6500 845 1180 1510 6375 6500 22 1730 8000 1450 8000 1260 1730 2200 8000 8000 1. Minimum and maximum airflow limits are dependent on the specific DDC controller supplied. Contact the control vendor to obtain the minimum and maximum differential pressure limits (inches w.g.) of the transducer utilized with the DDC controller. 2. Maximum CFM is limited to value shown in General Selection Data. 3. FlowStar differential pressure tubing connections: High side indicated by red tubing; Low side indicated by black tubing. JOHNSON CONTROLS 5

2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203 www.johnsoncontrols.com Printed in USA ET130.13-NOM4 (908) New Release