INSTRUCTIONS GEK G HIGH-SPEED DIFFERENTIAL RELAYS TYPES CFD22A AND CFD22B. GE Protection and Control

Similar documents
GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA

INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS

GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY HFA151 TYPE. GE Protection and Control 205 Great Valley Parkway Malvern, PA

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA UNDERVOL TAGE RELAYS TYPES: IAV54E IAV55C IAV54F IAV55F

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

P. Sub 4 184A404. Sub 3 876A220

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

INSTRUCTIONS GEI-98305C UNDERVOLTAGE RELAY D-C. Type NGV18A GENERAL ELECTRIC

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

COM Overcurrent Relay

B CW POWER RELAY

INSTRUCT IONS GEH-1 793J INSTANTANEOUS AUXILIARY RELAY TYPES HGA11A, C, H, J, K, P, S, T, V, W, X GENERAL ELECTRIC AUILIARV P A GENERALS ELECTRIC

THERMAL OVER CURRENT RELAY

INSTRUCTION S GEK 7354J AUXILIARY VOLTAGE RELAY TYPE HAA16B, HAA16C GENERAL ELECTRIC

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

INSTRUCTIONS SYNCHRONISM-CHECK RELAYS. GE Meter and Control. 205 Great Valley Parkway Malvern, PA Types IJS51A.

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

DIAC DIFC DSFC Digital Self Powered Overcurrent Protection

INSTRUCTIONS HAA 15A/15B/15C/15D/15E/15F/15G/15H AUXILIARY CURRENT RELAYS. Iso9ooo. GE Power Management

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

GENERAL ELECTRIC INSTRUCTIONS GEK- 2M42. Insert Rooklet GEH 1793 INSTANTANEOUS AUXILIARY RELAY TYPE HGA MODEL 12HGAI1E(-)A I NTRODUCT ION

4.0 OPERATION Type ITH-T Relay

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

CR193 Vacuum Limitamp* Contactors

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GEK-49826D INSTANTANEOUS OVERCURRENT RELAYS TYPES:

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

Installation Sheet January, 2016 Supersedes February, 2013

TABLE I 60 CYCLE BURDEN OF THE CVD RELAY AT CONTINUOUS RATING

INSTRUCTIONS GEI-10190L DC AUXILIARY RELAYS TYPE HGA17A TO F, H, M, R, S, T GENERAL ELECTRIC

GE CONSUMER & INDUSTRIAL

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

GENERAL ELECTRIC INSTRUCTIONS. GE I Supersedes GEI-28802E INSTANTANEOUS VOLTAGE RELAYS TYPES

41-747G. Figure 1: Type DGF Relay without case (Photo)

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

INSTRUCTIONS. GE Protection and Control 205 Great Valley Parkway Malvern, PA GLK 34117G

Type SOQ Negative Sequence Time Overcurrent Relay

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CO CONTACT MAKING AMMETER INSTALLATION OPERATION MAINTENANCE I.. L APPLICATION

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UNION SERVICE SPECIFICATION NUMBER SU A

INSTRUCTIONS TIME OVERCURRENT RELAY TYPE IAC 12IAC77S(-)A INTRODUCTION

Installation Sheet January, 2016 Supersedes June 2013

SecoVac * Ground & Test Device

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:

Chapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits.

AIR COOLED RECTIFIER SPECIFICATION S-50-A

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

Transformer Installation, Operation, and Maintenance Manual

THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Pretest Module 21 Units 1-3 AC Generators & Three-Phase Motors

Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors

Electric Motor Controls BOMA Pre-Quiz

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES

To study the constructional features of ammeter, voltmeter, wattmeter and energymeter.

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES

Vacuum Circuit Breakers (Vehicle)

KAUAI ISLAND UTILITY COOPERATIVE KIUC Tariff No. 1 Lihue, Kauai, Hawaii Original Sheet 5 RULE NO. 2 CHARACTER OF SERVICE

Horizontal Circuit Switchers

A. Submit manufacturer's literature and technical data before starting work.

HCI 534E/544E - Technical Data Sheet

HCI 434E/444E - Technical Data Sheet

34 th Hands-On Relay School

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Operation and Maintenance Manual

HCI 534E/544E - Technical Data Sheet

SECTION MOTOR CONTROL

UCI224F - Technical Data Sheet

SERVICE MANUAL

UCI274D - Technical Data Sheet

GP/GPA GROUND FAULT PROTECTION

CHAPTER THREE DC MOTOR OVERVIEW AND MATHEMATICAL MODEL

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

UCDI274K - Technical Data Sheet

HCI 434F/444F - Technical Data Sheet

UCI274D - Technical Data Sheet

UCI274G - Technical Data Sheet

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

DIRACT BRAKES 70 SERIES 4 POST BRAKE INSTRUCTIONS

Electrical Theory. Generator Theory. PJM State & Member Training Dept. PJM /22/2018

UCDI274K - Technical Data Sheet

Horizontal Circuit Switchers

SL-6 & SL-6A. I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC Service Manual Field and Shop Maintenance

UCDI224F - Technical Data Sheet

Transcription:

INSTRUCTIONS GEK-341 24G TYPES CFD22A AND CFD22B HIGH-SPEED DIFFERENTIAL RELAYS 205 Great Valley Parkway Malvern, PA 19355-1337 GE Protection and Control

GEK-341 24 CONTENTS PAGE APPLICATION 3 RATINGS 4 INDUCTION UNIT 4 CONTACTS 5 TARGETANDHOLDINGCOILS 5 BURDENS 6 RECEIVING, HANDLING AND STORAGE 7 DESCRIPTION 7 RELAY TYPES 7 INTERNAL CONSTRUCTION 8 CUPANDSTATOR 8 CONTACT STRUCTURE 8 TARGET 8 HOLDING COIL 9 INSTALLATION 9 LOCATION 9 MOUNTING 9 CONNECTIONS 9 CURRENTTRANSFORMER 9 ADJUSTMENTS 9 INSPECTION 10 PRINCIPLES OF OPERATION 10 MAINTENANCE 11 SHAFTANDBEARINGS 11 CUP AND STATOR 11 CONTACTCLEANING 12 PERIODICTESTING 12 RENEWALPARTS 12 2

To the extent required the products described herein meet applicable ANSI, IEEE and NEMA standards; but no 3 TYPE CFD These instructions do not purport to cover all details or variations in equipment nor provide for every possible such assurance is given with respect to local codes and ordinances because they vary greatly. referred to the General Electric Company. contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes, the matter should be is connected. protection cannot be obtained. In this case an overcurrent relay may be used to detect ground faults, provided there is a grounded neutral in the bus circuit to which the machine including a neutral, are brought out from a machine, it is only possible to obtain should have the same ratio as the transformers in the lines. Where only four leads, not respond to open circuits or turn-to-turn short circuits, neither of which affects the connected for phase-to-phase fault protection. The current transformers in the windings difference between current entering and current leaving the winding. Refer to Figure 1. Phase-to-ground protection requires that the neutral of the machine (or another neutral will not be protected, the amount being determined by the voltage necessary to Delta-connected machines with both ends of each winding available can readily be that leaving the other end. When the difference exceeds a certain minimum value due to relays function on the difference between the current entering one end of a winding and alternating-current machines against both phase-to-phase and phase-to-ground faults. The and synchronous condensers. It is desirable that if one machine is differentially protected, an internal fault, the relay will close its contacts. An external fault will not produce machine operating in parallel) be grounded. A small portion of the winding next to the Current-limiting devices in the neutral ground circuit increase this impedance and will of differential protection are recommended for the lower ratings of generators, motors The Type CFD relays comprise a group that is used for differential protection of motors and synchronous condensers of 3000 horsepower (or KVA) and above. Other forms recommended for protection of generators of 2000 KVA capacity and above, and for decrease the coverage of the relay. differential relaying for ground faults. If only three leads are brought out, differential High-speed differential relaying such as that afforded by the Type CFD is cause minimum pickup current to flow through the neutral-to-ground impedance. HIGH-SPEED DIFFERENTIAL RELAYS APPLICATION all machines paralleled with it on the same bus also have similar protection. a difference in current and therefore will not cause relay operation. Likewise, the relay will GEK-34124

GEK-341 24 When a generator, and power transformer are operated as a unit, separate relaying is recommended for each. The sensitive protection of a CFD relay can be given to a generator, whereas it would be inadvisable for a power transformer. It is permissible to use one set of current transformers in common between the two differential relays and in such a way, that the transformer protective relay acts as back-up protection for the generator. When current-differential protection is provided for AC machines, the field switch should be tripped automatically at the same time that the machine is disconnected from the system. Electrically operated field circuit breakers, or contactors, are generally used for this application, but in some cases manually operated field switches, consisting of an air circuit breaker with a shunt trip and a field discharge clip, are employed. Where the total rms symmetrical current that would flow in a differential relay coil is excessive, high voltage may result with sensitive differential relays, and a Thyrite limiter may be required across each phase of the current transformer secondaries. Where taps on the current transformer secondary windings are unused or do not exist, currents below 84 amperes are safe without limiters. Where taps are used on the CT secondaries, limiters are not necessary if 2 2 the current is less than 84 x (Active Turns) (Total Turns) Installations not shown to be safe by the approximate rule given above should be referred to the General Electric Company with data on the fault currents, CT ratios, and CT excitation characteristics, to determine whether limiters are actually needed. If the neutral of a machine is grounded, it is advisable to provide a neutral breaker that can be tripped to open the ground-return circuit of the fault current as quickly as possible. It is usually preferable to trip the neutral breaker, main breaker, and field breaker simultaneously, by means of a hand-reset auxiliary relay. A ground alarm should be provided in each station. This is usually connected through an auxiliary switch on each of the neutral breakers so that the alarm will sound only in case all neutral breakers are open. INDUCTION UNIT RATINGS The operating element of the Type CFD relay, the induction cup unit, is rated at 5 amperes continuous current flow in the restraint coils. The operating coils will carry 0.5 ampere continuously without overheating. The 12CFD22B15A relay is rated at SO hertz, with the restraint coils rated at 1 ampere continuously and the operating coils rated at 0.1 ampere continuously. Registered Trademark of the General Electric Co 4

S depends on the current taken by the trip circuit. Separate target and holding coils are the minimum control voltage if the current does not exceed 30 amperes at the maximum through contact circuit of thetype CFD relay. the fact that the target may not operate if used in connection with trip coils taking less than 1.0 ampere. There are two ratings of target and holding coils available. The choice between them provided with these relays, as shown on the internal connection diagrams, Figures 5 and 6. control voltage. When more than 30 amperes will flow, an auxiliary relay must be used to When it is desirable to adopt one type of relay as standard to be used anywhere on a should also be used where it is impossible to obtain trip-coil data, but attention is called to be opened by an auxiliary switch on the circuit breaker, or by another automatic means, Tripping current in both these circuits flows through the target and holding coils (see 0.2 to 1.0 ampere at the minimum control voltage. If these coils are used in circuits that Relay Types CFD22A and CFD22B are supplied with two circuit-closing contacts. control the trip circuit. Connections must be such that tripping current does not flow require 1.0 ampere or more, there is a possibility that the total resistance of the relay coils, as described in the next section. If the total tripping current exceeds 30 amperes, an 250 volts. The current-carrying rating is limited by the two forms of target and holding The CFD relays are supplied with non-bouncing contacts that provide positive contact closing. The current-closing rating of the contacts is 30 amperes for voltages not exceeding since the relay contacts are held closed while the tripping current is flowing. circuit will limit the tripping current to so low a value that the breakers will not be tripped. auxiliary relay must be used with the CFD relay. After tripping occurs, the trip circuit must The 0.2 ampere coils are for use with trip circuits that require currents ranging from The 1.0 ampere coils should be used with trip circuits that take 1.0 ampere or more at Figures Sand 6). The total current musttherefore be used when determining coil ratings. system, relays with the 1.0-ampere target and holding coil should be chosen. These relays CONTACTS TARGET AND HOLDING COILS GEK-341 24

6 Carry for tripping duty 30.0 5.0 Carry continuously 2.5 0.5 Minimumtargetrelease 1.0 0.2 and Holding Coils and Holding Coils The ratings of the two forms of target and holding coils are as follows: GEK-341 24 AMPERES AC or DC 1.0 Amp Target 0.2 Amp Target 50 5.0 220 0.034 0.048 0.059 1.47 0.58 50 1.0 42 1.14 1.64 2.00 2.00 0.57 50 0.5 0.2 140 24 42 48 1.9 0.5 50 0.1 0.04 25 60 0.5 0.2 140 29 50 58 2.3 0.5 The burden of the operating circuit at minimum pickup is given below: by the two current transformers. 60 5.0 220 0.040 0.057 0.070 1.75 0.57 The burden of the restraint coils at rated amps is given below. The burden is shared FUNCTION (0.50 ohm total) (14 ohms total) BURDENS FREQUENCY RATING--AMPS RATING--AMPS R X Z VA PF FREQUENCY RATING--AMPS PICKUP RATING--AMPS R X Z VA PF RATED CONTINUOUS ONE-SECOND RATED CONTINUOUS MINIMUM ONE-SECOND

V GEK-341 24 The operating circuit saturates as the current increases. The circuit impedance is given below: IMPEDANCE IN OHMS CURRENT MULTIPLES OF AMPERES MINIMUMPICKUP 6OHERTZRELAY 5OHERTZRELAY 0.2 1.0 58 48 0.6 3.0 29 24 2.0 10 11 9.1 4.0 20 6.3 5.2 5.0 25 5.4 4.5 RECEIVING, HANDLING AND STORAGE These relays, when not included as part of a control panel, will be shipped in cartons designed to protect them against damage. Immediately upon receipt of a relay, examine it for any damage sustained in transit. If injury or damage resulting from rough handling is evident, file a damage claim at once with the transportation company and promptly notify the nearest General Electric Sales Office. Reasonable care should be exercised in unpacking the relay in order that none of the parts are injured nor the adjustments disturbed. If the relays are not to be installed immediately, they should be stored in their original cartons in a place that is free from moisture, dust and metallic chips. Foreign matter collected on the outside of the case may find its way inside when the cover is removed, and cause trouble in the operation of the relay. RELAY TYPES DESCRIPTION The Type CFD22A relay is a three-unit relay for providing differential protection for a three-phase generator. Each unit is provided with a double contact arrangement, which allows tripping of two circuit breakers without paralleling the trip circuits. If only one breaker is to be controlled, the contacts should be connected in parallel. The Type CFD22B is similar to the CFD22A except that it has only one unit and is applicable to only one phase. It can be used for single-phase generator protection provided that one line is grounded, or for a three-phase generator application where flexible panel mounting is required. 7

INTERNAL CONSTRUCTION 8 cylinder offers a high ratio of torque to inertia and results in a ast operation time. makes contact with a rear extension of the moving contact arm. A shock backstop absorbs resistance to slippage is controlled by adjusting the pressure between the felt surface and shock and reduces the tendency of the moving contact to close if the mounting panel is of the relay cover against a selected sapphire jewel. The jewel is spring mounted to protect it from shocks. one phase on each side of the generator winding (see Figure 1). The other set carries the determines the minimum differential current that will operate the relay. It serves to keep differential current between the two current transformers. mounting a second stationary contact at the back of the induction unit (see Figure 3). This jarred. Figure 4 shows the arrangement of the contact mechanism. The stationary contact fitting stainless steel ball (B). The energy of the moving contact is transferred to the spring and steel ball with the result that there is little or no rebound or vibration of the closing rotor shaft through a clutch arrangement. The clutch acts as a shock absorber when the current flows, It is reset manually by a reset lever which extends through the lower edge (G) is mounted on a flat spiral spring (F) that is spaced from a thin diaphram (C) by a washer CONTACT STRUCTURE through a bronze guide bearing mounted in the end of the shaft. the poles in two sets of three. One set carries the currents from the current transformers in feature to ensure a positive circuit closure. Two-circuit closing action is obtained by The axis of the cylinder is supported at the lower end by a steel pivot that rotates The stator of the induction unit is of the eight-pole construction, but uses only six of The contacts are silver-to-silver elements and are constructed with a non-bounce CUP AND STATOR a vertical axis in the air gap between the stator and core. The lightweight aluminum a felt-lined cylinder between the shaft and moving contact arm. The amount of frictional contacts close under fault conditions, and reduces their tendency to rebound. It consists of The CFD relays are of the induction cylinder construction. The unit consists of a multipole stator, a stationary central core, and a cup like induction rotor. The cup rotates about contacts. trips a breaker. This indicator is unlatched by a solenoid through which the tripping the contact circuit open when the relay is de-energized. the shaft by means of a screw on the side of the contact arm. The upper end of the shaft is held in place by a polished steel pivot that projects down The moving contacts are supported on a molded plastic arm that is attached to the The contact arm is held from rotating freely by a control spring. This spring The target mechanism (Figure 2) drops on an orange-colored surface when the relay GEK-341 24 (D). The cap (E) holds these in place on a slightly inclined tube (A), which contains a close TARGET

GEK-341 24 HOLDING COIL The holding coil is used to hold the contacts in the closed position while current is flowing through them. It acts on an armature that is carried by the moving contact arm. The coil is connected in series with the trip circuit, and therefore must be de-energized by opening the trip circuit at a point external to the relay. LOCATION INSTALLATION The location should be clean and dry, free from dust and excessive vibration, and well lighted to facilitate inspection and testing. MOUNTING The relay should be mounted on a vertical surface. The outline and panel drilling for either surface or semi-flush panel mounting is shown in Figure 10 for the three-unit case, (CFD22A), and in Figure 11 for the single-unit case (CFD22B). CONNECTIONS The internal connection diagrams are shown in Figures 5 and 6 for the Types CFD22A and CFD22B respectively. Studs 13, 15 and 17 on the double-end cases are used for test purposes only. A typical external-wiring diagram is shown in Figure 1. The contact circuits should be paralleled when only one trip circuit is controlled. This can be done by jumpering terminals 11 and 12 on the CFD22A or terminals 2 and 3 on the CFD22B. One of the mounting studs or screws should be permanently grounded by a conductor not less than No. 12 B&S-gage copper wire or its equivalent. CURRENT TRANSFORMERS Proper differential protection requires that the current transformers to which Type CFD relays are connected be accurate to within 1% or 2%, up to twice (2x) normal current. Above twice normal current, accuracy is not so important because of the CFD characteristics. See PRINCIPLES OF OPERATION. ADJUSTMENTS Minimum Pickup These relays are adjusted at the factory to close their left front contacts with 0.2 ampere or more in one current circuit and no current in the other. Apply current, at rated frequency and good wave form, to the appropriate studs listed below for the relay model under test. The current magnitude for setting pickup is Stud Connections Contact Studs Relay Model Top Middle Bottom Left Front Right Rear CFD22A 3-13 6-15 9-17 1-12 1-11 CFD22B - 6-8 1-2 1-3 9

10 MAINTENANCE. recalibration or contact replacement. Any trouble should be corrected as described under should be necessary. The adjustment procedures need be followed only in special cases of set less than 0.1 ampere (this may be as high as 0.18 ampere for the rear contact to close) in with the test connections shown in Figure 9 with the current 10 equal to zero (switch open). loose screws that may have resulted from storage and handling. No further adjustments The relay should be inspected at the time of installation for tarnished contacts and INSPECTION contact and backstop barrels in place. The screw should be loose enough only to allow the not to be mounted on swing doors and are free from shock, the contact gap can be contact barrel and sleeve as a complete unit, and unscrew the cap. The contact and spring rotor shaft, it will be necesssary to readjust the clutch pressure. The adjustment is made contact arm should be loosened from a nosiip position until the rotor shaft does sup. Relays are shipped from the factory with contacts set for 0.100 inch gap. If relays are that the circuit is completed at the same time the front contacts close. Tighten the screws that secure the shock stop and contact barrels. will provide a gap of approximately 0.100 inch. Adjust the rear stationary contact barrel so rotated until it just closes the contact circuit, and then backed away 3.2 revolutions. This The contact gap may be adjusted by loosening the locking screws that clamp the Contacts barrels to rotate in their sleeves. The shock backstop should be positioned so that it holds all. any case. If the relay is mounted on a swinging panel, the pickup should not be reduced at With 20 amperes flowing in the restraint circuit, the screw on the side of the moving If for any reason the moving contact arm has been removed or loosened from the Clutch contact arm, and sliding it from under the screw head. may then be removed. tightened after the adjustment has been made. It is not recommended that the pickup be the moving contact arm pointing directly forward. The stationary contact barrel should be prevents unintentional motion of the ring. The hexagonal locking screw should again be reduced to 0.050 inch, and the time will be as shown by the lower curve in Figure 8. offered by the control spring. Friction from a spring wire around the adjusting ring of the adjusting ring. The operating ring can than be rotated to change the restraint The moving contact may be removed by loosening the screw that secures it to the The clutch should remain tight enough so that, as the current is reduced, slipping stops at a spring. To do this, it is necessary to loosen the hexagonal locking screw that holds the back greater sensitivity is desired, it can be obtained by reducing the tension of the spiral control To close the right rear contact, a current as high as 0.25 ampere may be required. If unit/s under test. Should it be necessary to change the stationary contact mounting spring, remove the minimum of 10 amperes. determined from the nameplate stamping under Minimum Differential Pickup for the GEK-341 24

GEK-341 24 PRINCIPLES OF OPERATION Differential protective relays, Type CFD, function on a product-restraint principle. The restraint torque is proportional to the product of the current entering one side of the protected equipment and the current leaving the other side. The operating torque is proportional to the square of the difference between the two currents. The operating and restraining torques balance when the differential current is 10% of the smaller of the other two, up to approximately normal current. This 10% slope, as it is called, allows small differences to exist, due primarily to current transformer errors. Above normal current the differential-current circuit will saturate before enough operating torque is produced to close contacts on a 10% slope basis (see Figure 7). This characteristic increases the margin for current transformer error at high currents due to external faults. Should the current at either terminal of the protected equipment reverse direction with respect to the current at the other, the product-restraint principle causes the restraining torque to reverse direction also, and it becomes an operating torque. This condition exists in the case of an internal fault in a generator paralleled with another power source. Under these circumstances saturation of the operating circuit is immaterial, since the relay does not depend on this circuit to operate its contacts. Figure 7 illustrates the fault conditions covered by the relay. The Type CFD relay is a cup-type induction unit. This type of construction results in a fast-operate protective device, even at currents only slightly in excess of pickup value. A typical time-current characteristic is shown in Figure 8. MAINTENANCE The relays are adjusted at the factory, and it is advisable not to disturb the adjustments. If for any reason they have been disturbed, the following points should be observed in restoring them: SHAFT AND BEARINGS The lower jewel screw may be removed, and the jewel tested for cracks by exploring its surface with the point of a tine needle. The bearing should then be screwed all the way in until its head engages the end of the threaded core support. The upper bearing should be adjusted to allow 1/64 inch end play to the shaft. To check the clearance between the iron core and the inside of the rotor cup, press down on the contact arm near the shaft, and thereby depress the spring-mounted jewel until the cup strikes the iron. The shaft and cup should move about 1/16 inch. CUP AND STATOR If it is necessary to remove the rotor from the unit, the following procedure should be followed: The leads should first be disconnected and tagged for identification in reconnecting. The unit can then be removed with its mounting plate attached. The saturating transformer should next be removed from the back of the mounting plate so that the upper of the three flat-head screws holding the unit to the mounting plate can then be removed. Then the entire top structure can be taken off, after removal of the four corner screws holding the unit together. This will give access to the cup and stator assembly. 11

In reassembly, the rotor will go into the air gap easily if the parts are held in the a superfine file. The polishing action is so delicate that no scratches are left, yet corroded 12 PERIODIC TESTING RENEWAL PARTS It is recommended that sufficient quantities of renewal parts be carried in stock to Since the last edition, the Periodic Testing section and Figures 1, 8 and 10 have been changed. Electric Company requisition number on which the relay was furnished. material will be removed rapidly and thoroughly. The flexibility of the tool ensures the cleaning of the actual points of contact. contacts, thus preventing contact closing. Abrasive paper or cloth may leave minute particles of insulating abrasive material in the Fine silver contacts should not be cleaned with knives, files or abrasive paper or cloth. Knives or files may leave scratches, which increase arcing and deterioration of the contacts. For cleaning fine silver contacts, a flexible burnishing tool should be used. This CONTACT CLEANING proper alignment. current through the restraint-circuit should be reversed and a second check of the obtainable from the factory. operational characteristic made. The target operation should be checked by passing 85% nameplate data. Refer to renewal parts publication GEF-3S69. If possible, give the General of rated current through the contact circuits. Company, specify quantity required, name of part wanted, and give the complete restraint-circuit currents I and 12 correspond to the same current shown on the operating characteristic given in Figure 7. l represents the differential current. The dire.ction of When ordering renewal parts, address the nearest Sales Office of the General Electric enable the prompt replacement of any that are worn, broken or damaged. An operation test is recommended. The test connections are shown in Figure 9. The The rotor should be handled carefully while it is out of the unit, and the stator should be protected to keep it free from dust or metallic particles. The burnishing tool described above is included in the standard relay tool kit consists of a flexible strip of metal with an etched roughened surface, resembling in effect the molded contact arm. top of the shaft must be pulled out and the clutch-adjusting screw and spring taken out of To remove the shaft and rotor from the contact-head assembly, the spring clip at the G EK-341 24

TC TRIF COIL T TARGET COIL HC HOLOING COIL 41 FIELD CIRCUIT BREAKER 52--FOWER CIRCUIT BREAKER 86 HAND RESET AUXILIARY RELAY 87 DIFFERENTIAL RELAY TYPE CFD 13 Wye-Connected Generator with Six Leads Brought Out or three Type CFD22B Relays for Protection of a Figure 1 (K-6507g30 [41) Typical External Connections for one Type CFD22A Relay ( ) TC 86 41 a 86 41 F? THREE PHASE RELAY (CFD22A). STUD NUMBERS IN PARENTHESES APPLY TO G EK-341 24

14. u MOVING CON TACT ASSEMBLY STATIONARY TARGET GEK-34! 24, EL[CTi SPIRAL CONTROL SPRING Figure 2(8010627) Type CFD22B Relay Removed from Case (Front View) cup SHAFT CONTACT CUP UNIT INDUCTION BACKSTOP SHOCK

15 Figure 3 (8041410) Type CFD22B Relay Removed from Case (Top View) CONTACT STATIONARY F RONT SHAT BEARING TARGET COIL - SHOCK BACKSTOP SHAFT PIVOT LOCKING SCREW ADJUS11NG RING CONTROL SPRING HOLDING COIL SUPPORT CO N TACT REAR STATIONARY RESISTOR TRANSFORMER AUTO GEK-341 24

16 C- DIAPH RAM F-FLAT SPIRAL SPRING B- STAINLESS STEEL BALL E- CAP U8E D5PACER GEK-34124 Figure 4 (K-6077069-4) Stationary-Contact Assembly for Type CFD Relays A- INCLINED T G - CONTACT F

I 17 GEK-34124 17 Type CFD22A Relay (Front View) Figure 5 (0227A71 54-1) Internal Connections forthe * SHORT FINGERS SHORT BRUSH 3-5 7! 9 - /,., LZ (_ 1 ( -.V, L4 1 COILS OPERATI NC T Er ] ; E 1 U COIL TARGET HOLDING 11 T nm 0 T I RESTRAINT COILS 0 I TRANSFORAER AU TO 12 I.

GEK-341 24 HOLDING (DI L RESTRAINT co I LS TARGET OPERATING cx3 I LS 2 5 6 BIJSH * Si-IORTFINGER Figure 6 (0227A7153-1) Internal Connections for the Type CFD22B Relay (Front View) 18

C ) m w r%j 8 S 0 K.1 0 C - 1 7c C C - C p.. (. S QQ D 0 9 Q.) C K C 0 1 1-1 0.1 C I-.

I rr L:.J.cI - 1I i:: I. F 1 F1; It I I ] ii C 11111 ttti: I TYPICAL TIME CURRENT CHARACTERISTIC FOR TYPE CFD ttffh fh -DIFFERENTIAL RELAY FOR GENERATOR PROTECTION 1 ij!ilir (CURRENT IN ONE CONSTRAINT ONLY) L TIME TOLERANCE ± 20% 0 co w -I.lw 00 -I (D P <C - -I to D 0) 0) 4 td - 4 12O 8 I I t C 8 m S U 6 40 0 1 I,:.1. I J[llhillh1fl lit: itillh11llif. 04. E It S. * I E II :1 t I E1 Rh E II II I: t l1i c I I I I I III II.1 III III III I. ILi iuuil, U1i.iIilL:. liii ii!liitiiii I1I1IIlIIIII1IllhI1 I IIIIIIIIlIi.111 II IiIfl.I in :i:ijitllililiilllhi I:: ti I Il i J il. ii Ii J11 1.l lt.flh1i1ii liii I ii!iiiiiiiiiii! I I I liii :1 II 1 t11111illllh1[fft 0:050 GAP1T1111Ji! 1IFffif111Ht1 I1 :.; 1 : fttulldli I I I I 11. 11...:. Eli I 1i11W I:, r;11t I I I I 1.L I..:i 1 ti. ij.._l.2.5 1 2.10.2.4 5 1.0 1111 1111 II CURRENT IN OPERATING - COIL (AMPERES) 1i1ii:ii 10 2.0 II I 11111111 III 1 II 11111111] jjay ii RATING 20 5A - 4.0 1 A

GEK-341 24 21 Figure 9 (K-6507933-5) Test Connections for the Type CFD Relay DIAZRA1. INTERNAL CDNN. TERMINAL csee o INDICATES RELAY RESTRAINT COILS IN CFD.L:A NNOT PRESENT COIL HOLDING > TARGET FREQUENCY SOURCE, RATED 230 VOLT

the Type CFD22A Relay Figure 10 (K-6209276 [SI) Outline and Panel Drilling for VIEW FUR 3.0 SURFACE MTG. ON STEEL PANELS SHOWING ASSEMBLY OF HARDWARE 76MM 5/16 18 STUD FRONT VIEW FOR SEMI FLUSH MOUNTING PANEL DRILLING PANEL DRILLING FRONT ViEW H-- Wjl7lMM k 251MM FOR SURFACE MOUNTING 9. 875 (6) 10-32 X 3/8 22 MM INCHES TYPICAL DIM. GLASS / 97531 <TYPICAL) 5MM 133MM 396MM CU ThU T 19.875 12MM 218.500 37MM 1, 468 15 DRILLED HOLES BACK VIEW 10 8 6 4 2 MTG. SCR[JS STUD NUMBERING 20 18 16 14 12 00000 00000 00000 00000 1917151312 168MM 6 625 5 04MM 50MM 19. 75 CUTOUTS MAY REPLACE OR SURFACE MTG, PANEL LOCATION SEMI -FLUSH 1 0-32 4) 5/16-18 STUITh GEK-341 24

GEK-341 24 PANEL LOCATION SEMI FLUSH SURFACE 5/16 IS STUDS SURFACE MTG. PANEL DRILLING SEMI-FLUSH MOUNTING FRONT VIEW PANEL IJRILLNG FOR SURFACE MOUNTING FRONT VIEW TYPICAL DIM. INCHES MM 3.0 76MM VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE MTG. ON STEEL PANELS Figure 11 (K-6209271-8) Outline and Panel Drilling for the Type CFD22B Relay 23

GE Power Management 215 Anderson Avenue Markham, Ontario Canada L6E 1B3 Tel: (905) 294-6222 Fax: (905) 201-2098 www.ge.comli ndsyslpm