Series 769 FireLock NXT Deluge Valve

Similar documents
FireLock NXT Deluge Valve. With Deluge Trim Grooved x Grooved. System No. Submitted By Spec Sect Para Location Date Approved Date

Series 756 FireLock Dry System Check Valve

Series 758 FireLock Actuated System Valve

30.85 FireLock NXT Actuated Valve with LPCB Approved Preaction Trim

Series 751 FireLock European Alarm Check Valve Stations

FireLock NXT Actuated Valve with Preaction Trim. System No. Submitted By Spec Sect Para Location Date Approved Date

Series W706 AGS Butterfly Valves (300 PSI/2065 kpa)

Series W709 AGS Butterfly Valves (175 psi/1270 kpa)

Series 709 Butterfly Valves (175 psi/1270 kpa)

Series 706 Butterfly Valves (300 PSI/2065 kpa)

Vic-Strainer WARNING. System No. Submitted By Spec Sect Para Location Date Approved Date IPS CARBON STEEL PIPE - GROOVED ACCESSORIES SERIES 730

Style 99 Roust-A-Bout Couplings

Grooved Piping System for Fire Protection Services

Grooved Piping System for Fire Protection Services

Instructions for Installation, Operation, Care and Maintenance

Victaulic Specification Power Industry

DELUGE VALVE DATA SHEET

DELUGE VALVE MODEL: SD-DVA TECHNICAL DATA : VALVE OPERATION TRIM DESCRIPTION DESCRIPTION PRESSURE THREADED OPENING

Q= C. v P S Refer to Table 1 for part numbers and shipping weights. Accessories: Table 1: Valve Part Numbers and Specifications

I-NXT.RBKIT 5-Year Rebuild Kit Instructions for FireLock NXT Valves

Fire Protection Price List

TotalPac 3 Deluge system Pneumatic release

TECHNICAL DATA. Q= C v P S

TotalPac 3 Non interlock Preaction system Pneumatic release

TECHNICAL DATA. Q= C v P Cv = Flow Factor (GPM/1 PSI P)

FIRE PROTECTION EQUIPMENT 2017 DATA SHEETS BSP FIRE RESERVES THE RIGHT TO ALTER INFORMATION CONTAINED IN THIS CATALOGUE AT ANY TIME.

Fire Protection Price List. Piping. Systems. Solutions A FP.

Model DDX Deluge Valve 8 (200mm) Features

Model DDX Deluge Valves 4" (100 mm), 6" (150 mm) and 165 mm Sizes

TotalPac 3 Deluge, Electric release Remote controlled system

TotalPac 3 Firecyle III Wet pipe Remote controlled system

TECHNICAL DATA. Inlet Type Outlet Type OBSOLETE 6 (DN150)

Features 1. Differential Latch-type, lightweight, dependable

TECHNICAL DATA CONCENTRATE CONTROL VALVE APPLICATIONS, PRIMING CONNECTIONS, AND TRIMS 1. GENERAL DESCRIPTION 2. LISTINGS AND APPROVALS.

DV-5a Automatic Water Control Valve Single Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

1-1/2 Inch (DN40) 9 lb (4,1 kg) Groove Groove 1 8 lb (3,6 kg) Flange Groove 1 N/A N/A. Flange Flange N/A N/A

B NPT. Dimensions Inches/millimeters

Stainless Steel Pipe System. System No. Submitted By Spec Sect Para Location Date Approved Date TEMPERATURE ( F/ C)

DV-5a Automatic Water Control Valve Double Interlock Preaction Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

TECHNICAL DATA. Trimpac 249a. September 16, 2013

TECHNICAL DATA. Viking Technical Data may be found on Style: 90 Degree Pattern (inlet to outlet)

Model DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Electric Actuation

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL J-2 HALAR COATED 1-1/2 & 2 (DN40 & DN50) 1. DESCRIPTION

TECHNICAL DATA 1-1/2 (dn40)

Q= C v P S. Flow control valve Model j-2 Halar coated

Worldwide Contacts.

TECHNICAL DATA TRIMPAC MODEL B-4, B-4B & B-4S SINGLE INTERLOCK PREACTION SYSTEM WITH PNEUMATIC RELEASE

TotalPac 3 Double interlock Preaction, Electric/Pneumatic release Remote controlled system

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Remote controlled system

AGCX Bulletin 519 C/Alfoz de Bricia nº4 P.l. Villalonquéjar Burgos (Spain) Tlfno: PAG 1 de 50

TotalPac 3 Non interlock Preaction, Electric release Remote controlled system

Model CV-1FR Grooved-End Riser Check Valves 2 Inch to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data

70.03 Victaulic Vortex TM

REQUEST PUBLICATION 18.11

TECHNICAL DATA. Trimpac 244a. April 15, 2011

SHORTER. LIGHTER. MORE VERSATILE. 1 VALVE 10 TRIM CONFIGURATIONS 4" AND 6" MODEL RCW WATER CONTROL VALVE FOR DRY, PREACTION AND DELUGE APPLICATIONS

Instructions for Installation, Operation, Care and Maintenance

Instructions for Installation, Operation, Care and Maintenance

MODEL RCW NON-INTERLOCK PREACTION SYSTEM

TotalPac 3 Double interlock Firecyle III Preaction Remote controlled system

Pressfit System for Carbon Steel Pipe

DV-5 Deluge Valve Aluminium Bronze Diaphragm Style General Description

Section R Foam Systems

Section R Foam Systems

Sl. No. Description Pages

Deluge Valves. Model 68 DE\ HM-MR. Hydraulically Actuated Manual-Reset Deluge Valve. Dorot Fire Protection Division

VICTAULIC Shouldered Solutions

Deluge Pressure Reducing Valves. Model 68 DE\ RCL\ PR. Electrically Actuated, Manual-Reset, Pressure Reducing, Deluge Valve

GW MKIII DELUGE VALVE - ALUBRONZE EXTERNAL RESET, PNEUMATIC

50-01 (Full Internal Port) (Reduced Internal Port) Pressure Relief. & Pressure Sustaining Valve MODEL

TECHNICAL DATA CAUTION

Instructions for Installation, Operation, Care, and Maintenance

MODEL RCW DELUGE SYSTEM ELECTRIC, WET PILOT, AND DRY PILOT ACTUATION

From the world s leader in mechanical piping systems... The complete system for stainless steel piping.

Deluge Valves. Model 68 DE\ HRV-MR. Hydraulically Actuated, Anti-Columning, Manual-Reset Deluge Valve. Dorot Fire Protection Division

Deluge Pressure Reducing Valves. Model 68 DE\ EL\ PORV\ PR. Electrically and Pneumatically Actuated, Pressure Reducing, Remote-Reset, Deluge Valve

Easy Riser swing check valve Models E-1 & F-1

DV-5 Deluge Valve, Diaphragm Style, 1-1/2 thru 8 Inch (DN40 thru DN200), Deluge System Wet Pilot Actuation General Description

FIRE PROTECTION PRODUCTS

Valves & Flow Control Components Valves & Flow Control Components

TECHNICAL DATA 2-1/2-8 (dn65 - dn200)

LEAD FREE * LFF113RFP Wireless Smart Flood Protection Shut Down Valve with SentryPlus Alert Technology

TECHNICAL DATA. Q= C v P S FLOW CONTROL VALVE MODEL H-2 HALAR COATED 2 (DN50) - 6 (DN150)

Victaulic Fittings, Couplings, Valves & Sprinkler Heads for the Fire Sprinkler Market Keeping the art of distribution simple

DV-5A Automatic Water Control Valve Remote-Resetting Deluge Fire Protection Systems 1-1/2 Inch to 8 Inch (DN40 to DN200) General Description

Victaulic Suction Vibration Isolation Pump Drop Series 337 Korea Only

TECHNICAL DATA P S. Q= Cv MODEL E-2 DELUGE VALVE HALAR COATED ANGLE STYLE

TECHNICAL DATA. Q= C v P S. Table 1 - Valve Part Numbers and Specifications

Sludge Dewatering and Odor Control at Plant 1 CONFORMED

BS 5163 Resilient Wedge Gate Valve

TECHNICAL DATA. Table 1: Model F1 Dry Valve Part Numbers and Specifications

Wet pipe low flow foam/water manifold system

TECHNICAL DATA OBSOLETE

Victaulic Discharge CBV Vibration Isolation Pump Drop Series 383/383G

Grooved End Fittings. System No. Submitted By Spec Sect Para Location Date Approved Date CARBON STEEL PIPE - GROOVED FITTINGS

08.08 Vic-Check Valves

Preaction System with DV-5 Deluge Valve Double Interlock Electric/Electric Actuation. General Description. Page 1 of 14 DECEMBER 2014 TFP1465

Technical Data. UL Listing is based on the following criteria:

Grooved End Fittings. System No. Submitted By Spec Sect Para Location Date Approved Date CARBON STEEL PIPE - GROOVED FITTINGS

Operators: Lever Handle: 1 1/2 3"/40 80 mm Carbon steel, zinc plated, plastic grip. 4 & 6"/100 & 150 mm Carbon steel, enamel paint

Transcription:

IPS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS Series 79 FireLock NXT Deluge Valve With Deluge Trim Grooved X Grooved 30.81 VICTAULIC IS AN ISO 9001 CERTIFIED COMPANY PRODUCT DESCRIPTION The patent-pending Victaulic Series 79 FireLock NXT Deluge Valve controls the water supply entry into the deluge system piping and open sprinklers. The Series 79 is a low differential, latched clapper valve that uses a unique direct acting diaphragm to separate system water supplies from deluge pipe sprinkler systems. The positive latching mechanism uses the supply s water pressure from upstream (city side) of the main control valve to hold the clapper shut. A low system air pressure controls the supply water pressure on the latch from the diaphragm chamber. When the system air pressure is released, the decreasing air pressure activates the Low Pressure Actuator and releases the latch mechanism, which allows the clapper to open. Clapper Seat FM APPROVED See Victaulic publication 10.01 for details. Victaulic Series 79 Deluge Valves feature a high-strength, low-weight, ductile iron body with pneumatic, hydraulic, and electric actuation methods. The straight-through body design provides superior flow and low-pressure drop. It offers simple access to all internal parts for easy maintenance. All internal parts are replaceable. The valve is painted inside and out to increase corrosion resistance. Maintenance and service can be performed from the installed position. The rubber clapper seal is replaced easily without removing the clapper from the valve. The body is tapped for main drain and all available trim configurations. The low differential, unique latch and actuator design of the valve allows the device to be reset without opening the valve. The low differential design is not subject to water columns. The valve allows the water to operate a water motor alarm and/or electric pressure alarms, which continue until the flow of water stops. The valve is rated to 300 psi/05 kpa water working pressure for sizes 4 8"/40 00 mm. The valve is factory tested hydrostatically to 00 psi/4135 kpa for sizes 4 8"/40 00 mm. Required air pressure is 13 psi/90 kpa. The Series 79 is available grooved x grooved. Standard grooved dimensions conform to ANSI/AWWA C0. The Victaulic Series 79 FireLock NXT Deluge Valve is available bare, pre-trimmed, as a Vic -Quick Riser or in a Series 745 FireLock Fire-Pac Cabinet. Pre-trimmed The pre-trimmed valve comes completely assembled with all necessary trim components including any optional accessories for quick assembly and set up. Vic-Quick Riser The Vic-Quick Riser comes completely pre-trimmed and includes a shut off Latch valve (uses a Series 705W FireLock Butterfly valve request publication 10.) for system shut off, pressure switches, and a drain kit for ease of installation. For complete Vic-Quick Riser information request publication 30.0. Clapper Seal Diaphragm Assembly Series 745 FireLock Fire-Pac The Fire-Pac is a completely pre-assembled fire protection valve that provides maximum service in a minimal enclosed space. The unit includes a water supply shutoff valve, the sprinkler system fire protection valve, alarm line pressure switches, air supervisory pressure switches, supervisory pump switches, and digital pressure gauges that are easily viewed through a window in the cabinet door. For complete Fire-Pac information request publication 30.3. Exaggerated for Clarity NOTE: Valve is shown above in the set position REGISTERED TRADEMARK OF VICTAULIC COPYRIGHT 005 VICTAULIC PRINTED IN U.S.A. SKU #WCAS-DRKXP 41 REV A United States Phone: 1-800-PICK-VIC (1-800-74-584) Fax: 10-50-8817 e-mail: pickvic@victaulic.com Canada Phone: 905-884-7444 Fax: 905-884-9774 e-mail: viccanada@victaulic.com Europe Phone: 3-9-381-1500 Fax: 3-9-380-4438 e-mail: viceuro@victaulic.be UK Phone: 44(0)1438741100 Fax: 44(0)1438313883 e-mail: viceuro@victaulic.be Central and South America Phone: 10-559-3300 Fax: 10-559-308 e-mail: vical@victaulic.com Australasia Phone: 8-1-5453300 Fax: 8-1-545371 e-mail: vicap@victaulic.com

R FOR INDOOR OR OUTDOOR US E NC - () B LUE SW ITCH No. 1 NO - () B ROW N C - () YE LLOW NC - B LUE W/ STRI PE SW ITCH N o. NO - B ROW N W/ STRI PE C - Y ELLOW W/ ST RIPE R 30.81 TRIM DIMENSIONS THE 4-INCH/114.3-mm CONFIGURATION IS SHOWN BELOW 4 8-INCH/114.3 19.1-mm CONFIGURATIONS CONTAIN -INCH/50-mm DRAIN VALVES. E A *A1 B F D *D1 H Nominal Size In./mm G Actual Outside Dia. In./mm C *E1 J Dimensions Inches/mm A A1 B C D D1 E E1 F G H J Aprx. Weight Each Lbs./kg 4 4.500 15.03 19.79 3.50 15.5 15.50 0.50 5.50 8.75 10.75.5 8.50 8.50 59.0 95.0 100 114.3 381.7 50.7 8 387 394 51 140 73 159 1 1.7 43.0.5 1.00.01 33.75 15.75 1.75 1.50 5.5 8.75 11.5.5 8.50 8.75 80.0 11.0 150 18.3 40.40 559.05 857 387 45 54 133 8 159 1 3. 5. 8 8.5 17.50 3.10 33.75 17.00 19.75 5.50.5 9.00 1.50.5 8.5 10.5 1.0 158.0 00 19.1 444.50 58.74 857 43 50 48 159 9 3 159 10 0 55.3 71. NOTES: The drawings shown above reflect the dry pilot trim with Series 77 Low-Pressure Actuator. In addition, these dimensions can be applied to hydraulic (wet pilot) release and electric release trim. The A dimension coupling and the optional sensor switch are not shown for clarity. Components shown as dotted lines denote optional equipment. * Measurements denoted with an asterisk take optional equipment into account. Optional drain connection kit is shown for reference and takeout dimensions. Without Trim With Trim Series 79 FireLock NXT Deluge Valve

PERFORMANCE.0 5.0 4.0 3.0 HYDRAULIC FRICTION LOSS FLOW OF WATER AT +5 F (+ C) THROUGH FULL OPEN VALVE SERIES 78/79 PRESSURE DROP PSI.0 1.0 0.9 0.8 0.7 0. 0.5 0.4 4" " 8" 0.3 0. 0.1 10 The chart below expresses the frictional resistance of Victaulic Series 79 FireLock NXT Deluge Valve in equivalent feet of straight pipe. FRICTIONAL RESISTANCE C V Values Nominal Size Inches C V values for flow of water at +0 F/+1 C through a fully open valve are shown in the table below. Formulas for C V Values: Q ΔP = --------- C V 0 30 40 0 80 100 00 300 400 00 Equivalent Length of Pipe Feet 4 1 8 50 Q = C V ΔP FLOW RATE GPM Where: Q = Flow (GPM) ΔP = Pressure Drop (psi) 1,000,000 4,000,000 10,000 0,000 800 3,000 C V = Flow Coefficient Nom. Size In./mm Actual Outside Dia. In./mm C V/K v (Fully Open Valve) 4 4.500 350 100 114.3 30.8.5 1000 150 18.3 85.0 8 8.5 1500 00 19.1 1499.1 Series 79 FireLock NXT Deluge Valve 3

MATERIAL SPECIFICATIONS Body: Ductile iron conforming to ASTM A-53, grade 5-45-1. Ductile iron conforming to ASTM A-395, grade 5-45-15, is available upon special request. Clapper: Aluminum bronze UNS-C95500 Latch: Aluminum bronze UNS-C95500 Clapper Seal: Peroxide cured EPDM, ASTM D000 Seat O-rings: Nitrile Springs: Stainless steel (300 Series) Shafts: Stainless 17-4 Diaphragm: Peroxide cured EPDM with fabric reinforcement 0 19 17 11 15 1 1 1 17 10 13 3 11 1 14 9 4 5 8 7 BILL OF MATERIALS 1 Valve Body 9 Clapper Spring 1 Latch Spring Clapper 10 Clapper Shaft 17 Latch Shaft Bushing and O-ring (Qty. ) 3 Clapper Seal 11 Clapper Shaft Bushing and O-ring (Qty. ) Diaphragm 4 Seal Ring 1 Cover Plate 19 Diaphragm Cover Plate 5 Seal Washer 13 Cover Plate Gasket 0 Diaphragm Cover Plate Cap Screws (Qty. 8) Seal Retaining Ring 14 Cover Plate Bolts (Qty. 7) 1 Latch Shaft 7 Seal Assembly Bolt 15 Latch Drain Plug 8 Bolt Seal 4 Series 79 FireLock NXT Deluge Valve

TRIM PACKAGES Trim Packages Available for Vertical Installation: 1 Pneumatic (Dry Pilot) Release Hydraulic (Wet Pilot) Release 3 Electric Release Trim Packages Include: 1 Actuator Air Feed Manifold 3 All Required Pipe and Fittings 4 All Standard Trim Accessories 5 All Required Gauges Optional Trim Package for Vertical Installations: 1 Black Trim for Foam Systems If the valve is intended for use in a foam system, black trim must be ordered, per NFPA requirements. Specify this requirement on the order. Actuators: Series 77 Low-Pressure Actuator The Series 77 Low-Pressure Actuator is pneumatically actuated and requires only 13 psi/90 kpa minimum air pressure, regardless of the system supply pressure. This actuator allows the system to operate with a low air or gas pressure of 7 psi/48 kpa. Request submittal 30.4. Series 753-E Solenoid Valve The Series 753-E Solenoid Valve is designed for use with systems that require electrical activation. Request submittal 30.3. Optional Accessories: Series 70 Water Motor Alarm The Series 70 Water Motor Alarm is a mechanical device that sounds when a sustained flow of water occurs (such as with an open sprinkler). Request submittal 10.38. Alarm Pressure Switch Alarm Pressure Switches are designed to activate electrical alarms and control panels when a sustained flow of water occurs (such as with an open sprinkler). Air Supervisory Pressure Switch Air Pressure Supervisory Switches are used to monitor system air pressure and are available as low-pressure and high-pressure sensitivity. Air Supply System The air supply system contains all components for establishing and maintaining air in a pneumatic system. The compressor, low-pressure alarms, ball valves, and required trim are included in the air supply system. Air Compressor Air Dryer Air Maintenance Device Alarm Panels Drain Connection Kit Series 79 FireLock NXT Deluge Valve 5

;AIR SUPPLY REQUIREMENTSFOR DRY PILOT DELUGE SYSTEMS The required air pressure for Series 79 FireLock NXT Deluge Valves with dry pilot trim is 13 psi/90 kpa, regardless of the system supply pressure. If multiple Series 79 FireLock NXT Deluge Valves with dry pilot trim are installed with a common air supply, isolate the systems with a spring-loaded, soft-seated ball check valve to ensure air integrity for each system. Good practice is to include a ball valve for isolation and service of each individual system. Set the air pressure to the required system air pressure. Air pressure differing from the required system air pressure could reduce system operation response time. The engineer/system designer is responsible for sizing the compressor so that the entire system is charged to the required air pressure within 30 minutes. DO NOT oversize the compressor to provide more airflow. An oversized compressor will slow down or possibly prevent valve operation. If the compressor fills the system too fast, it may be necessary to restrict the air supply. Restricting the air supply will ensure that air being exhausted from an open sprinkler or manual release valve is not replaced by the air supply system as fast as it is being exhausted. Compressor Sizing 1 10 0 psi/138 kpa 13 psi/90 kpa COMPRESSOR REQUIREMENTS Required Flow Rate (CFM) 8 4 0 50 300 550 800 1050 System Capacity (in gallons) 1300 1550 00 Base or Riser-Mounted Compressors For base or riser-mounted compressors, the recommended air pressure of 13 psi/90 kpa is the on or low pressure setting for the compressor. The off or high pressure setting should be psi/14 kpa. When a base or riser-mounted air compressor supplies air to a Series 79 FireLock NXT Deluge Valve with dry pilot trim, it is not necessary to install the Victaulic Series 757 Regulated Air Maintenance Trim Assembly (AMTA). In this case, the airline of the compressor connects to the trim at the fitting where the Series 757 Regulated AMTA is normally installed (refer to the applicable trim drawing). If the compressor is not equipped with a pressure switch, the Series 757P Air Maintenance Trim Assembly with Pressure Switch should be installed. Shop Air or Tank-Mounted Air Compressors In the event a compressor becomes inoperative, a properly sized tank-mounted air compressor provides the the greatest protection for systems. When shop air or a tank-mounted air compressor is used, the Series 757 Regulated AMTA must be installed. The Series 757 Regulated AMTA provides proper air regulation from the air reservoir to the sprinkler system. For tank-mounted air compressors, the recommended air pressure of 13 psi/90 kpa should be used as the set point for the air regulator. The on pressure of the compressor should be at least 5 psi/34 kpa above the set point of the air regulator. Series 79 FireLock NXT Deluge Valve

Victaulic Series 757 Regulated Air Maintenance Trim Assembly NOTICE Victaulic recommends a maximum of two Series 79 FireLock NXT Deluge Valves with dry pilot trim per Series 757 Regulated AMTA. Victaulic Series 757P Air Maintenance Trim Assembly with Pressure Switch NOTICE Victaulic recommends a maximum of two Series 79 FireLock NXT Deluge Valves with dry pilot trim per Series 757P AMTA with Pressure Switch. 1 1 3 3 5 4 5 4 BILL OF MATERIALS BILL OF MATERIALS Item Description Item Description 1 1 / 8-inch/3.-mm Restrictor 1 1 / 8-inch/3.-mm Restrictor Slow-Fill Ball Valve (Normally Open) Pressure Switch 3 Air Regulator 3 Slow-Fill Ball Valve (Normally Open) 4 Strainer (100 Mesh) 4 Fast-Fill Ball Valve (Normally Closed) 5 Spring-Loaded, Soft-Seated Ball Check Valve 5 Strainer (100 Mesh) Fast-Fill Ball Valve (Normally Closed) Spring Loaded, Soft Seated Ball Check Valve Settings for Air Supervisory Pressure Switches and Alarm Pressure Switches 1. Air supervisory pressure switches are required for dry systems and must be set according to the following notes. NOTE: Switches for Vic-Quick Risers are pre-set at the factory. 1a. Wire the air supervisory pressure switches to activate a low-pressure alarm signal. NOTE: In addition, the local authority having jurisdiction may require a high-pressure alarm. Contact the local authority having jurisdiction for this requirement. 1b. Set the air supervisory pressure switches to activate at 4 psi (14 8 kpa), but not lower than 10 psi/ 9 kpa, below the minimum air pressure required. 1c. Wire the alarm pressure switch to activate a water flow alarm. 1d. Set the alarm pressure switch to activate on a pressure rise of 4 8 psi/8 55 kpa. Series 79 FireLock NXT Deluge Valve 7

WET PILOT LINE CHARTS 10.0 Heights are based on 1 / " schedule 40 pipe and a 1 / " sprinkler. MAXIMUM ALLOWABLE PILOT LINE HEIGHTS FOR SPECIFIC EQUIVALENT LENGTHS 4-inch/114.3-mm NXT Deluge Valve 100.0 300 psi 80 psi Maximum Pilot Line Height (ft.) 80.0 0.0 40.0 0 psi 40 psi 0 psi 00 psi 0 psi 10 psi 140 psi 10 psi 0.0 100 psi 80 psi 0 psi 40 psi 0 psi 0.0 10 5 50 100 00 300 400 500 1000 Length of Pipe (ft.) 00.0 MAXIMUM ALLOWABLE PILOT LINE HEIGHTS FOR SPECIFIC EQUIVALENT LENGTHS -inch/18.3-mm NXT Deluge Valve 0.0 300 psi 10.0 80 psi 0 psi Maximum Pilot Line Height (ft.) 140.0 10.0 100.0 80.0 0.0 40 psi 0 psi 00 psi 0 psi 10 psi 140 psi 10 psi 40.0 100 psi 80 psi 0.0 0 psi 40 psi 0 psi 0.0 10 5 50 100 00 300 400 500 1000 Length of Pipe (ft.) 8 Series 79 FireLock NXT Deluge Valve

00.0 MAXIMUM ALLOWABLE PILOT LINE HEIGHTS FOR SPECIFIC EQUIVALENT LENGTHS 8-inch/19.1-mm NXT Deluge Valve 0 psi 0.0 00 psi 10.0 140.0 0 psi Maximum Pilot Line Height (ft.) 10.0 100.0 80.0 0.0 10 psi 140 psi 10 psi 100 psi 80 psi 40.0 0.0 0 psi 40 psi 0 psi 0.0 10 5 50 100 00 300 400 500 1000 Length of Pipe (ft.) Series 79 FireLock NXT Deluge Valve 9

EXPLODED VIEW DRAWING TRIM COMPONENTS Series 79 FireLock NXT Deluge Valve with Pneumatic Release (Dry Pilot) Deluge Trim (Optional Accessories Also Shown) From System Air Feed To Pilot Line 15 1 0 14 13 Cup or Drain Cup or Drain 1 17 1 Cup or Drain To System 1 3 From Drip Cup 10 19 1 1 11 9 8 7 Cup 3 5 4 Water Supply To Drain Connection Assembly or Drain BILL OF MATERIALS 1 Series 79 FireLock NXT Deluge Valve 13 Series 749 AutoDrain FireLock Rigid Coupling (Optional) 14 Series 77 Low-Pressure Actuator 3 Series 705W Butterfly Valve (Optional) 15 Air Manifold 4 Drain Swing Check Valve 1 EPS40- Supvervisory Switch (Optional) 5 Drip Cup 17 System Pressure Gauge EPS10- Alarm Pressure Switch (Optional) (0-80 psi/0-55 kpa with retard) 7 Series 79 Drip Check Valve Water Supply Main Drain Valve - Flow Test 8 Diaphragm-Charge-Line Ball Valve (Normally Open) 19 Water Supply Pressure Gauge (0-300 psi/0-08 kpa) 9 Strainer/Check/Restrictor Assembly 0 Drain Connection Kit (Optional) 10 Series 70 Water Motor Alarm (Optional) 1 Gauge Valve 11 Three-Way Alarm Ball Valve System Main Drain Valve 1 Diaphragm-Charge-Line Pressure Gauge 3 Series 755 Manual Pull Station (0-300 psi/0-08 kpa) 10 Series 79 FireLock NXT Deluge Valve

EXPLODED VIEW DRAWING TRIM COMPONENTS Series 79 FireLock NXT Deluge Valve with Hydraulic Release (Wet Pilot) Deluge Trim (Optional Accessories Also Shown) 17 To Wet Pilot System 13 To Drain or Drip Cup 1 14 19 To System 0 From Drip Cup 10 1 15 1 11 9 8 7 Cup 3 5 4 Water Supply To Drain Connection Assembly or Drain BILL OF MATERIALS 1 Series 79 FireLock NXT Deluge Valve 1 Diaphragm-Charge-Line Pressure Gauge FireLock Rigid Coupling (Optional) (0-300 psi/0-08 kpa) 3 Series 705W Butterfly Valve (Optional) 13 Series 749 AutoDrain 4 Drain Swing Check Valve 14 System Pressure Gauge 5 Drip Cup (0-80 psi/0-55 kpa with retard) EPS10- Alarm Pressure Switch (Optional) 15 Water Supply Main Drain Valve - Flow Test 7 Series 79 Drip Check Valve 1 Water Supply Pressure Gauge (0-300 psi/0-08 kpa) 8 Diaphragm-Charge-Line Ball Valve (Normally Open) 17 Drain Connection Kit (Optional) 9 Strainer/Check/Restrictor Assembly Gauge Valve 10 Series 70 Water Motor Alarm (Optional) 19 System Main Drain Valve 11 Three-Way Alarm Ball Valve 0 Series 755 Manual Pull Station Series 79 FireLock NXT Deluge Valve 11

EXPLODED VIEW DRAWING TRIM COMPONENTS Series 79 FireLock NXT Deluge Valve with Electric Release Trim (Optional Accessories Also Shown) 17 1 13 Cup or Drain 1 14 19 To Drain To System 0 From Drip Cup 10 1 15 1 11 9 8 7 Cup 3 5 4 Water Supply To Drain Connection Assembly or Drain BILL OF MATERIALS 1 Series 79 FireLock NXT Deluge Valve 1 Diaphragm-Charge-Line Pressure Gauge FireLock Rigid Coupling (Optional) (0-300 psi/0-08 kpa) 3 Series 705W Butterfly Valve (Optional) 13 Series 749 AutoDrain 4 Drain Swing Check Valve 14 System Pressure Gauge (0-80 psi/0-55 kpa with retard) 5 Drip Cup 15 Water Supply Main Drain Valve - Flow Test EPS10- Alarm Pressure Switch (Optional) 1 Water Supply Pressure Gauge (0-300 psi/0-08 kpa) 7 Series 79 Drip Check Valve 17 Drain Connection Kit (Optional) 8 Diaphragm-Charge-Line Ball Valve (Normally Open) Gauge Valve 9 Strainer/Check/Restrictor Assembly 19 System Main Drain Valve 10 Series 70 Water Motor Alarm (Optional) 0 Series 755 Manual Pull Station 11 Three-Way Alarm Ball Valve 1 Series 753-E Solenoid Valve 1 Series 79 FireLock NXT Deluge Valve

OPERATION The Victaulic Deluge System utilizes the Series 79 Actuated Valve to control the water supply s entry into the deluge system s piping and open sprinklers. The Series 79 Actuated Valve is constructed with a clapper, which has a replaceable rubber face. The clapper makes contact with the valve seat ring, which has access holes to the intermediate chamber of the valve. The clapper is contacted by the latch, which is contacted by the diaphragm. In the closed position, water supply pressure from upstream of the water supply control valve is maintained in the diaphragm chamber, which holds the clapper in the closed position. The water is maintained in the diaphragm by one of the system release mechanisms (pneumatic, hydraulic or electric). Upon detection of an actuating event of the deluge system, such as an actuated pilot sprinkler or heat detection, the water supply pressure in the diaphragm chamber is released. This release allows the latch to move to its open position, permitting the clapper to pivot freely, thus allowing water into the system. Water will flow from all open sprinklers in the piping. Also, water enters the intermediate chamber of the valve through the holes in the seat ring. The water flows from the intermediate chamber to the alarm line, which activates the system s alarms. These alarms continue to sound until the flow of water is stopped. Important Note: If air pressure in a pneumatic system is lost, a low air alarm (optional) will activate. If air pressure is not restored, the valve will actuate. If a pilot sprinkler in either a pneumatic or hydraulic system is damaged, the valve will actuate and water will flow from all open sprinklers in the deluge system. Water motor alarms and alarm pressure switches will activate. Manual Operation Any time the manual release handle is pulled, water will be released, and the valve will actuate, thus allowing water into the deluge system. Water motor alarms and alarm pressure switches will activate. WARNING This product must be installed by an experienced, trained installer, in accordance with the instructions provided with each valve. These instructions contain important information. Failure to follow these instructions may result in serious personal injury, property damage, or valve leakage. If you need additional copies of this product literature or the valve installation instructions, or if you have any questions about the safe installation and use of this device, contact Victaulic Company, P.O. Box 31, Easton, PA 044-0031 USA, Telephone: 001-10-559-3300. This product shall be manufactured by Victaulic to to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. Series 79 FireLock NXT Deluge Valve 13