Operating Instructions for Pressure Transmitter with Digital Display. Model: PDA

Similar documents
Operating Instruction for Electronic Pressure Switch. Model: PDD

Operating Instructions for Torsion Paddle Flow Meter / Monitor. Model: DPT-...

Operating Instructions for Plastic Flow Meter. Model: KSK

Operating Instructions for Polysulfone Paddle Monitor. Model: PPS-..

Operating Instructions for Paddle Bellows Flow Monitor. Model: FPS-P...

Operating Instructions for Float Flow Meter / Monitor. Model: SWK

Operating Instructions for Float Flow Meter / Monitor. Model: SWK

Operating Instruction for Flowmonitor. Model: DF-WM

Operating Instructions for Flow Indicator. Model: DAA

Operating Instructions for Paddle Flowswitch Model: PPS-...

Operating Instructions for Oval Wheel Flowmeter. Model: DOC

Solid State Electronic Pressure Switch with Integral LED Display Model PSD-10

Electronic Pressure Switch EDS 3000

Operating Instructions for Magnetic Filter. Model: MFR-00

Electronic Pressure Switches

Operating Instructions for Viscosity Compensated Flow Meter / Monitor. Model: VKM

Electronic Pressure Switches

Electronic Pressure Switches

Electronic Pressure Switches

Turbine Wheel Flow Meter

Electronic Temperature Sensor ETS 300

Operating Instructions for Oval Wheel Flowmeter. Model: DOE

Flowmeter Ultrasonic Flow Metering / Dosing Device. Operating Manual

Adjustment range. Seal material. Pressure connection

Temperature switch. Switching output 2 transistors PNP Logger Ring buffer: 3518 data points Sampling time: s, Off (0)

Model: TUR with transmitter. Output: pulses, 0-20 ma, 4-20 ma or 0-10 V, LED display, pointer indication, switching output

LTX RF LEVEL SENSOR. Instruction Manual

OEM pressure transmitter with thin-film technology For mobile hydraulics Model MH-2

XMLRM01G1P25 Pressure sensors XMLR -1 bar - G 1/4-24VDC ma - PNP - M12

Flow meters. Flow meters. Flow meters - Continuous and precise measurement of flow rates

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

SPG-DIGI. Operating Instruction. Please read carefully before use!

Portable pressure calibrator, Wally Box III Model CPH7600

JUMO DELOS SI. Precision pressure transmitter with switching contacts and display. Application. Brief description. Key features.

OEM Pressure Transmitters

XMLR400M1N26 Pressure sensors XMLR 400bar - 1/4" 18 NPT - 24VDC ma - NPN - M12

XMLR400M1N75 Pressure sensors XMLR 400bar - G 1/4-24VDC V - NPN - M12

Differential Pressure Sensor

MBS 1200 and MBS 1250

TUR. Turbine Wheel Flowmeter. plastic version for liquids. Measuring ranges: ,0 m 3 /h water. ± 1% of full scale

Signet Pressure Transmitter

OEM Pressure Transmitters for heavy-duty applications Type MBS 1200 and MBS 1250

ST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number

Mounting and Operating Instructions EB 3913 EN. Electropneumatic Converters i/p Converter Type

Differential pressure gauges with Bourdon tube

Model Pressure range ON/OFF output Linear output

Pressure transmitter for general applications Model S-10, standard version Model S-11, flush diaphragm

SSI Technologies Application Note PS-AN7 MediaGauge (Model MG-MD) Digital Pressure Gauge Product Overview

Operating Instructions for Paddle Flow Monitor. Model: PSR-..., PSE-...

Series 7000 Torque Sensor for PTO-shafts

Pressure Transmitter. Pressure transmitter with compact design Model EDC-K. Electronic. Applications. Special Features.

DPT TARGET TYPE FLOWMETERS

Paddle-wheel flow controller for On/Off control

Operating Instructions Dual Pressure Switch BPS3000

Paddle-wheel flow controller with optical principle for On/Off control

Flow - magnetic inductive - probe form

Pneumatic or Electropneumatic Positioner for Rotary Actuators Type Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Operating instructions Flow monitors SI6600 SI6700 SI /02 01/2011

Pressure transmitter for general purpose Type MBS 1700 and MBS 1750

HBLT-C1 Controller. Instruction Manual. For pump control of levels in industrial refrigeration systems

Series 7000 Torque Sensor for PTO-shafts

Pressure transmitter for industrial applications Type MBS 4500

Beck. The differential pressure transmitter for air with IP65

Electronic flow switch With display, for liquid media Model FSD-3

Technical Datasheet P-30/P-31. Standard transmitter.

Electronic pressure switch with integrated analogue output

MMA. Insertion Resistance Thermometers. with, or without transmitter. OEconomically-priced O thermometers with optional plug-on display

Operating instructions Flow monitors SI5000 SI / / 2007

Type A-10 General Purpose Pressure Transmitters

Signet Pressure Transmitter

Model Pressure range ON/OFF output Linear output

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

Paddle-wheel flow controller for On/Off control

Operating instructions Flow monitors SI / / 2010

Air Flow Controller M1compact Type-Summary FKM 130

JUMO safetym TB/TW Temperature limiter, temperature monitor according DIN EN

Dusty / Dusty Ex. Low-Cost Broken Bag Detection. Operating Instructions. SWR engineering Messtechnik GmbH

The right choice for your application. Pressure sensors from ifm.

Industrial OG meter series IOG Inline and flanged oval gear meter

Screw-in resistance thermometers with plug connector

EB EN. Type 3372 Electropneumatic Actuator. Translation of original instructions

Electronic Pressure Switches E.

Flow Transmitter / Switch OMNI-RR..32

Industrial Pressure Transmitters

TURCK Inc Campus Drive Minneapolis, MN Application Support: Fax: (763) M2

ECONOMISER SERIES E2T USER MANUAL

Series 430 Type 3430 Pneumatic Indicating Controller for Temperature with Capillary Sensor Type 3432 Controller Station Type 3436 Transmitter Module

Pressure sensors - Nautilus

GEMÜ 549 esydrive Motorized globe valve

OEM Pressure transmitter for industrial applications Type MBS Technical brochure

Flow - dynamic diaphragm

LFT RADAR MICROONDE GUIDATE CONTROLLI DI LIVELLO. LFT level sensor the all-round talent with TDR technology. Dimensional drawing.

Temposonics. M-Series Analog Redundant. Absolute, Non-Contact Positions Sensors. Temposonics MT Measuring length mm

Braking Devices BR 230/ Assembly- and Commissioning Instructions

Flow Transmitter / Switch OMNI-RR..32

Electronic pressure switch with two switching outputs

Max. oil content of compressed air Shock resistance max. (XYZ direction) Vibration resistance (XYZ direction) Quiescent current consumption

Pressure Transmitters

Electronic Limit Switch Type

JUMO MIDAS Pressure transmitter

Transcription:

Operating Instructions for Pressure Transmitter with Digital Display Model: PDA

1. Contents 1. Contents... 2 2. Note... 3 3. Instrument Inspection... 3 4. Operating Principle... 3 5. Regulation Use... 4 6. Mechanical Connection... 4 7. Electrical Connection... 5 7.1. Connector pin assignment PDA-15...... 5 7.2. Connector pin assignment PDA-25, PDA-35... 6 8. Commissioning... 7 8.1. Key function... 7 9. Configuration... 8 9.1. Value setting... 9 9.2. Set-up mode for PDA-15... 10 9.3. Set-up mode for PDA-25 and PDA-35... 11 10. Main Menu Items... 13 10.1. Switching point... 13 10.2. Hysteresis... 13 10.3. Duo point... 13 10.4. Switching characteristic... 14 10.5. Time response... 15 10.6. Contact-type... 15 10.7. Current output... 15 10.8. Filter... 16 10.9. Start adjustment... 16 10.10. Change Code... 16 11. Maintenance... 16 12. Technical Information... 17 13. Order Codes... 18 14. Dimensions... 19 15. Declaration of Conformance... 20 Manufactured and sold by: Kobold Messring GmbH Nordring 22-24 D-65719 Hofheim Tel.: +49(0)6192-2990 Fax: +49(0)6192-23398 E-Mail: info.de@kobold.com Internet: www.kobold.com page 2 PDA 01/06

2. Note Please read these operating instructions before unpacking and putting the unit into operation. Follow the instruction precisely as described herein. The devices are only to be used, maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health & Safety and prevention of accidents. When used in machines, the measuring unit should be used only when the machines fulfil the EWG-machine guidelines. 3. Instrument Inspection Instruments are inspected before shipping and sent out in perfect condition. Should damage to a device be visible, we recommend a thorough inspection of the delivery packaging. In case of damage, please inform your parcel service / forwarding agent immediately, since they are responsible for damages during transit. Scope of delivery: Pressure Transmitter with Digital Display Operating Instructions model: PDA 4. Operating Principle KOBOLD pressure indicator/transmitter series PDA, are cost effective electronic pressure indicator/transmitters with digital indication of actual pressure. An analogue output (0)4-20 ma is available for remote transmission of the measured value. The device is optionally available in addition with a switching output. A piezzo resistive ceramic cell is used. The units can be used where high switching accuracy is needed. Long-term stability, repeatability and the compact, robust design makes it an ideal unit for use in OEM applications. PDA 01/06 page 3

5. Regulation Use Pressure transmitters are used to measure pressure in vessels, hydraulic and pneumatic plant, refrigeration equipment and so forth. The devices may only be used for liquids to which the probe and housing materials are chemically resistant. 6. Mechanical Connection Pressure taps should be prepared according to the following specifications for the screw-in holes. Gaskets to DIN 16 258 or formed gaskets are recommended for sealing British Standard Parallel Pipe thread (BSPP). The required tightening torque depends on the material and shape of the gasket used, and on the pressure port in the pressure sensor. National Pipe Thread (NPT) fittings should be sealed with an appropriate pipe thread sealant. Exposure to violent shocks and heat radiation should be avoided. The permissible service conditions for the pressure sensors should be observed. When the pressure connection has been made and the power supply connected, the sensor is ready for operation. Sealing according DIN 16288 Sealing with Flat gasket 21,3-0,2 G 1/4 A * min. G 1/2 A * min. G 1/2 A * min. R 16 z 9-0,5 +1-0,5 13 16 5 R 16 z 14 5 - +1 0,5 +1 19 24 5 R 16 z 14 5 20,5 24 5 7 +0,2 7 +0,2 7 +0,2 page 4 PDA 01/06

7. Electrical Connection Important! Make sure that the voltages in your plant correspond with the voltages on the nameplate. Make sure that the electrical supply lines are dead. The supply is connected through connector socket M12x1 as shown in the wiring diagram below. Mating plugs with different cable lengths are available as options. Important! The instrument electronics may be damaged if the cable connections are connected incorrectly. 7.1. Connector pin assignment PDA-15... PDA-15 Not connected +Vs/+ Supply 0 V / GND Output 0 V / GND Plug with cable ZUB-KAB-12K002 Plug Connection example PDA-15 Pin M12 +Vs n.c. 2 1 +Vs GND GND 3 4 Analog Out 0(4)-20mA PDA 01/06 page 5

7.2. Connector pin assignment PDA-25, PDA-35 PDA-25... PDA-35... PNP-Output NPN-Output +24 V DC +24 V DC 0 V / GND 0 V / GND 0(4)-20 ma 0(4)-20 ma 0 V / GND 0 V / GND Plug with cable ZUB-KAB-12K002 Plug Connection example +Vs PDA-...P3M Plug M12 Power PNP out 2 1 +24 V DC GND 3 4 5 0(4)-20 ma ma GND page 6 PDA 01/06

8. Commissioning Caution! Please note that if operated at high system temperatures the case surface and controls can become very hot. Connect the pressure transmitter according to the wiring diagram above and supply it with the specified voltage. The measuring range (upper range value) is displayed for 3 seconds after switch on. 8.1. Key function Normal mode (measuring mode) : Press for 3 Sec. set-up mode : Display Low/High current value Set-up mode : Next level : Change value Any time: 3 sec. or 20 sec. Without pressing any key Normal Mode PDA 01/06 page 7

9. Configuration The following values can be programmed on the pressure transmitter: Range of values Factory setting Switch point (Spo) -199 999 50,0 Hysteresis (HYS) -199 0 000 Duo point (duo) Switch point 999 --- (inactive) Filter (Filt) 1/2/4/8/16/32/64 1 Time response (dse, dre) 0,0 99,5 sec. 0,0 Contact-type (Con) Normally open contact (no) or normally closed contact (nc) no (normally open contact) Start current (S-C) zero 0 to upper range value 0 End current (E-C) span 0 to upper range value upper range value Start current selection (SCS) 0 / 4 ma 4 Filter (Filt) 1/2/4/8/16/32/64 1 Start adjustment (S-A,) tare 000 adjusted Change Code (CCo,) 000-999 000 page 8 PDA 01/06

9.1. Value setting Value setting can be selected with the " " key in the main menu item (for example: End current, "E-C"). The standard sequence for changing parameters is given in the flowchart below. [from the main menu item] Set 1st position Set 2nd position Set 3rd position Adjust decimal point Save Save selected value or re-enter [to the next main menu item] PDA 01/06 page 9

9.2. Set-up mode for PDA-15 3 sec Code input Code= Value setting Start current End current Start current Selection 7sec Store Start current 7sec Store End current 7sec Value setting Value setting 0-20 ma Filter 7 levels 4-20 ma Value setting Start adjustment Code change 7sec Store start point Value setting Value setting page 10 PDA 01/06

9.3. Set-up mode for PDA-25 and PDA-35 3 sec Codeeingabe Code= Setting parameter Switch Point Hysteresis Duo-Point Setting parameter On-Delay Setting parameter Off-Delay Setting parameter Contact type N.O. contact N.C. contact Save PDA 01/06 page 11

Start current 7sec Setting parameter End current 7sec Setting parameter Start current range 7sec 0-20 ma 4-20 ma Filter 7 levels Set-up Startpoint 7sec Setting parameter Change code Setting parameter page 12 PDA 01/06

10. Main Menu Items 10.1. Switching point In menu option, "SPo" the switch point can be set. A value between -199 and 999 can be selected. Additionally, a decimal place can be assigned to this value. The decimal point can be set after the first or the second place (e.g. 10.0 or 1.00). If the displayed value exceeds or equals the adjusted switch point and the window point is not set, then the switch will be active. An active switch is signalled by the LED being lit. In case the hysteresis is set to zero, then the switch will be inactive if the value is lower than the switch point. 10.2. Hysteresis After setting the switch point, a hysteresis HYS can be entered as a negative value in the menu. The hysteresis default value is zero. However, this can lead to an unwished switching behaviour during the operation, if the measuring signal keeps varying around the switch point or the window point. An increase in hysteresis will suppress the effect. The hysteresis refers to both the switch point and the window point (switch point minus hysteresis, window point plus hysteresis). Example: Switch point: 100 bar; Hysteresis: -2.5 bar The switch will become active at and above 100 bar when the indicated value goes up, and will become inactive at 97.5 bar when the value goes down. 10.3. Duo point Apart from the switch point a window point ( duo ) can be defined. It must be larger than the switch point. With both the "window point" and the "switch point" set, the measured value can be monitored within a certain range. If a window point is set, the state of the switch underneath the switch point is similar to the one above the window point. If the window point (duo) is smaller or equal to the switch point, an error message (Er4) is momentarily displayed. Afterwards its value is deleted and thus its function becomes ineffective (this is valid for the window point as well as for the switch point setting). This parameter setting is similar to the switch point setting. The window point is needed for processes, during which the pressure must be monitored within or outside a certain range. PDA 01/06 page 13

Example: Switch point: 100 bar; Window point: 150 bar; Hysteresis: -1 bar The switch changes state when pressure exceeds 100 bar. At this moment, if the pressure remains between 99 (100-1) bar and 151 (150+1) bar, the switch remains in the active state (LED on). If the pressure increases crossing 151 bar limit or (decreases to go below 99 bar limit), the switch will revert to an inactive state. 10.4. Switching characteristic The following diagram clarifies the switching behaviour of the pressure switch. The contact closes (type of contact: N.O.) when exceeding the switch point or falling short of the window point. It opens again only after exceeding the window point plus the hysteresis or falling below the switch point minus the hysteresis. An LED signals the switching status of the pressure switch. Display bar ( C) LED on Switching point Hysteresis Time / t Display bar ( C) Hysteresis Duo point LED on LED on Switching point Hysteresis Time / t page 14 PDA 01/06

10.5. Time response PDA Using the menu items dse, dre it is possible to set the switch-on-delay (delay set) and the switch-off-delay (delay reset). The delay set causes delayed switching of the output if the switching point is exceeded. The delay reset causes a delayed resetting of the output when falling short of the switching point hysteresis. The setting range for both parameters is 0.0... 99.5 seconds. The step rate is 0.5 seconds. With these two functions, it is also possible to suppress temporary disturbances. 10.6. Contact-type In menu option "Con", the transistor switching output function is set. The switching function changes from N.O. contact to N.C. contact and back. N.O. contact means: Contact closes on exceeding the switch point. N.C. contact means: Contact opens on exceeding the switch point. 10.7. Current output The current output is set in menu items "S-C" Start current indicated value < > 0(4) ma "E-C" End current indicated value < > 20 ma "SCS" Start current selection (0-20 ma or 4-20 ma). The indicated value at which 0(4) ma is transmitted is entered in menu item Start current. The indicated value at which 20 ma is transmitted is entered in the menu item End current. PDA 01/06 page 15

10.8. Filter The filter function "Filt" generates the sliding average value from the measured values. This acts to dampen the output in a system that has pressure pulsations. The following values are available (see Section 9 Settings): 1 / 2 / 4 / 8 / 16 / 32 / 64 The filter value determines the dynamic behaviour of the indicated value: high values mean a slow display with smoother response. The filter is disabled if a filter value of "1" is selected. In other words, the indicated value is equal to the unfiltered measured value (no dampening occurs). The integrated step detector responds to a measured-value step change greater than approximately 6.25% of the upper range value. When a measured-value step change is detected, the actual measured value is displayed immediately. 10.9. Start adjustment The zero-point can be recalibrated when the sensor is in the unpressurised state. As a security precaution, the operator must press and hold the " " key for 7 seconds. This must be done before he can activate the value setting menu item "S-A". 10.10. Change Code Change code "CCo" protects the device against unauthorised changing of the set device parameters by allowing the operator to enter a secret code. If the code set is different then 000, the operator must enter the set code Cod before entering the set-up mode. 11. Maintenance The instrument requires no maintenance when properly used. Deposits, due to fouled media, can give rise to invalid measured values. page 16 PDA 01/06

12. Technical Information Housing: Stainless Steel 1.4305 Connections: G 1/4 or G 1/2 male; St. St. 14404 Option: 1/4 or 1/2 NPT, others on request Gasket: FPM (Option: EPDM) Sensor element: piezzo resistive ceramic cell Indication: Resolution: 3-digit LED, 7mm max. 0.01 bar (depending on measuring range and measured value) Max. temperature: Media: -20 to +80 C Ambient: -20 to +80 C Max. over pressure: up to 60 bar: 3 times from 100 bar: 2 times of the range 400 bar: 1.5 times of the range Supply voltage: 24V DC ± 20% Power consumption: approx. 120 ma (without switching output) Electr. connection: Plug M12x1 Settings: programmable with 2 buttons: (standard) - Switching point - Hysteresis - 4-20 or 0-20 ma - Start point/ end point (current) - Filter - Zero point - Security code Over range/ under range indication: on LED-display Load: max. 500 Ω Switching output: PNP or NPN semiconductor (factory set), max. 300 ma, short-circuit proof Contact: N/O / N/C, duo programmable Output indicator: 1 LED ON/OFF-switch. delay: 0,5...99,5 s (separately adjustable) Response time: 0.5 s Accuracy: ±0.5 % f. s., (±1 % of full scale for spans 1,6 bar) Protection: IP 65 PDA 01/06 page 17

13. Order Codes Example: PDA-15 3 R2 C315 Model/Output PDA-15=Standard 0(4)-20 ma PDA-25=0(4)-20 ma, PNP-Switching output PDA-35=0(4)-20 ma, NPN-Switching output Electrical Connection 3=St. M12x1 Connection Measuring range R2=G ¼ R4=G ½ N2=1/4 NPT N4=1/2 NPT C315=-1...0 bar B025= 0...1 bar B035= 0...1,6 bar B045= 0...2,5 bar B055= 0...4 bar B065= 0...6 bar B075= 0...10 bar B085= 0...16 bar A095= 0...25 bar A105= 0...40 bar A115= 0...60 bar A125= 0...100 bar A135= 0...160 bar A145= 0...250 bar A155= 0...400 bar Additional: Electrical connection Description Model M12x1 socket with terminal ZUB-KAB-12D500 M12x1 socket with 2 m cable ZUB-KAB-12K002 M12x1 socket with 5 m cable ZUB-KAB-12K005 M12x1 socket with Quickon-plug ZUB-KAB-12Q000 page 18 PDA 01/06

14. Dimensions Info! The matching M12x1 box with 2 m cable for the M12x1 plug connector is available under order code ZUB-KAB-12K002. (Fig. with box) PDA 01/06 page 19

15. Declaration of Conformance We, KOBOLD-Messring GmbH, Hofheim-Ts, Germany, declare under our sole responsibility that the product Pressure Transmitter with Digital Display model PDA to which this declaration relates is in conformity with the standards noted below: EN 61326: 1997 +A1: 1998 +A2: 2001 Electrical equipment for measurement, control, and laboratory use - Noise immunity: according EN 61326/A1 Amendment A table A.1 Criteria: according table 2, continuos not monitored operation - Generic emission standard: according EN 61326/A1 Limit values: according table 4, equipment of class B EN 61010-1 1993 Safety requirements for electrical equipment for measurement, control and laboratory use Also the following EWG guideline is fulfilled: 2004/108/EC EMC Directive Hofheim, 16. Jan. 2007 H. Peters M. Wenzel General Manager Proxy Holder page 20 PDA 01/06