U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

Similar documents
U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

Installation and Operating Manual

L007 LIQUID LEVEL FLOAT SWITCH. Side-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

S003 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted, Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

L-Series: LIQUID LEVEL FLOAT SWITCH. Single-Point, Vertically-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

For Hazardous Locations

L500 LIQUID LEVEL FLOAT SWITCH. Single or Multi-Point, Vertically-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

L312 LIQUID LEVEL FLOAT SWITCH. Multi-Point, Vertically-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL

L070 LIQUID LEVEL FLOAT SWITCH. Side-Mounted Liquid Level Float Switch INSTALLATION AND OPERATIONS MANUAL. For Industrial Use

Tuffy Liquid Level Controls with Pneumatic Switch

For CRN Installations

Series K Pneumatic Switch Mechanism

LIQUID LEVEL FLOAT SWITCH. F7 Series INSTALLATION AND OPERATIONS MANUAL. Single-Point, Vertically-Mounted Liquid Level Float Switch

Tuffy II Liquid Level Controls with Electric Switches Installation and Operating Manual

J52 Refrigerant Level Switches

ECHOTEL MODELS 915-P / 915-W

OPERATING INSTRUCTIONS PLEASE READ CAREFULLY

ECHOTEL 961/962 LINE POWERED

ECHOTEL 961/962 LOOP POWERED

Series K. Pneumatic. switch mechanism. and housings. Installation and Operating Manual

Echotel Trident 91S/92S Ultrasonic Level Switches

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

INSTALLATION / INSTRUCTION MANUAL

Switch Pro w/ Compact Junction Box A_1_ Series Owner s Manual

Operating Instructions

Installation, Operation, Repair and Parts Manual

NorthStar. brand. Instruction Manual. SLIM Tach SL Thru-Shaft Diameter. Magnetoresistive Encoder Designed for GE Wind Energy

NEO-DYN MODELS 100T AND 100TC ADJUSTABLE TEMPERATURE SWITCHES; ENCLOSURE 3X FOR WEATHERPROOF APPLICATIONS INSTALLATION AND OPERATION MANUAL

Switch-Pak. AU13, AV13 & AZ13 Series Owner s Manual. w/ Compact Relay Controller

NEO-DYN MODEL 100P ENCLOSURE 7 ADJUSTABLE EXPLOSION-PROOF PRESSURE SWITCH

Type 2000 Transducer Product Instructions

MODELS 100T AND 100TC ADJUSTABLE TEMPERATURE SWITCHES,

ECHOTEL 961/962 LOOP POWERED

M-3025CB-AV Fuel Pump

Tuffy Liquid Level Switches

PENBERTHY MODELS GL AND GH GAS OPERATED JET PUMPS INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

A5000GEC-24VDC ZERO SPEED SWITCH

CVR-625. Compact Vibrating Rod Instruction Manual

VP-4124/VP-4124-E 24/48 VOLT DC SWITCHING POWER SUPPLY

INSTALLATION AND OPERATION MANUAL

SOLITEL. Vibrating Rod. Level Switch. for Solids. Installation and Operating Manual. 7xxx. 6xxx. 5xxx. 4xxx. 3xxx. 2xxx. 1xxx

XP88 & XP89 Series Quick Start

AV16, AV26, AV36, AV46, AV56, LH25, LH29, LH35, LV20, LV21, LV35 & LV36 Series Manual

300 Series INSTRUCTION MANUAL. Compressed Air Filters Models 302 (grade) through 317 (grade)

KOBOLD DF-MA Flow Transmitter. User Instructions

Air Curtain. Installation, Operating and Maintenance Instructions

CIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT

LU27 Series Quick Start

A1500, A1500NF SPEED SWITCH SINGLE SET POINT - SELF CONTAINED. Introduction

Levalarm Gold. Installation, Operation, & Maintenance Instructions R500.E253A 03/16/2016

CM3000 SIGNAL TRANSMITTER. Introduction. The MAXIGARD CM3000 is designed to convert shaft speed into a 4/20 ma or 0-10 VDC analog output signal.

BMRX Series Rotary Level Indicator

TABLE OF CONTENTS GENERAL SPECIFICATIONS... 3 SAFETY SUMMARY INTRODUCTION INSTALLATION Location and Mounting Input

SPC-PANEL Simplex, Single Phase Pump Control Panel

RESISTIVITY MONITOR/CONTROLLERS

EchoPod. Technical Support. Model: DL14-(XX) Quick Start

INSTALLATION, CALIBRATION & TROUBLESHOOTING MANUAL

AGV5-1, AGV5-2 FORM AGV5 OM 11-02

CTFRP Series Power Supplies

Model GD-K77D4X-XX Supplement to the GD-K77D Operator s Manual

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

Switch-Tek Horizontal and Vertical And Float-Point Float Switches LV20, LV21, LV35, LV36, LH25, LH29, LH35, AV_6 Series 22AUG 08 Rev A

Patient Care Facility

VP-6124/VP-6124-E 24 VOLT DC SWITCHING POWER SUPPLY

Installation Manual. D3600- Series Duplex Grinder Systems. Contents

BMRX Series ROTARY LEVEL CONTROL

Ultrasonic Two-Wire Point Level Control

Drug Testing Labs. Style 2 W/ Ver 4.41 pcb & Pulse Relay pcb(s) Installation, Operations, Start-up and Maintenance Instructions

ECHOTEL 961/962 LOOP POWERED

CRICKET Alphasonic Level Transmitter Model LA12 Owner s Manual

EV-2051-M Electric Motor. Operation and Maintenance Manual

Level Alert Model Multi-Switch Liquid Level Sensor. Assembly and Installation Instructions

EchoPod. DL10, DL14, DL24, DS14 & DX10 Series Quick Start. DL14-00 Shown Flowline, Inc. All Rights Reserved Made in USA

7330 Pro-Stik II Magnetostrictive Level System

PENBERTHY FROST PROOF EXTENSION INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Dimensions 12/800N 12/1200N D. DC to AC Power Inverters. OWNERS MANUAL for Models: OWNERS MANUAL April ISO 9001:2000 Certified Company

Full View Flow Indicator

CRD610 Automatic Fitting Inserter

COMPACT GLYCOL FEED SYSTEMS OPERATION & MAINTENANCE MANUAL

Installation Manual. Q Series Quadplex Grinder Systems. Contents

Model HPX60 Series Automatic Battery Charger User s Manual Rev. 1.0 October 17, 2006

Eclipse AutoTite Automatic Gas Shut-Off Valves

INSTALLATION GUIDE. Universal System for Zero Turn Mowers

Adjustable Angled Incline Conveyor Owners Manual with Operating Instructions

Model GD-70D4A-XX Supplement to the GD-70D Operator s Manual

Airpax Dimensions, Inc.

INSTALLATION & OWNER'S MANUAL

CLEAN ROOM DEVICES, LLC "WHERE TUBING AND FITTINGS COME TOGETHER"

Operating and Installation Instructions

Outdoor Nema Enclosure For Dotworkz CoolDome Power Supply Product Code: NM-CDPS. User Manual

COMPRESSED AIR LOADER MODEL: AL-1

Easytork Solenoid Valve IOM

RF Point Level Control with Sensor Monitor

Installation and Service Manual for SRC25, SRC252, SRC50, SRC502, SRC75, SRC752

Smart Trak. AU18, AU28, AU38, AU48, AV16, AV26, AV36, AV46, AZ18, AZ28, AZ38 & AZ48 Series Owner s Manual. w/ Compact Junction Box

60 Series End-Mount Brake Instructions Standard Housing

Nor East. Instructions Safety Messages. Inspection. Parts. DeZURIK Service. Type 05 Pneumatic Actuator Used With Globe Valves

BroadBand PowerShield. 20 AHr Battery. User Manual

Owner s Manual & Safety Instructions

Eclipse AutoTite Automatic Gas Shut-Off Valves

Transcription:

U00X ULTRASONIC LEVEL SWITCH INSTALLATION AND OPERATIONS MANUAL Ultrasonic Liquid Level Switches For Non-Hazardous Locations For Models: U002, U003 & U004

READ THIS MANUAL PRIOR TO INSTALLATION This manual provides information on the U00X Ultrasonic Liquid Level Switch. It is important that all instructions are read carefully and followed sequentially. Detailed instructions are included in the Complete Installation section of this manual. Conventions Used in this Manual Certain conventions are used in this manual to convey specific types of information. General technical material, support data and safety information are presented in narrative form. The following styles are used for notes, cautions and warnings: Notes Notes contain information that augments or clarifies an operating step. Notes do not normally contain actions and often follow the procedural steps to which they refer. Cautions Cautions alert the technician to special conditions that could injure personnel, damage equipment, or reduce a component s mechanical integrity. Cautions are also used to alert the technician of unsafe practices, the need for special protective equipment, or specific materials. In this manual, a caution indicates a potentially hazardous situation which, if not avoided, may result in minor to moderate injury. Warnings Warnings identify potentially dangerous situations, or serious hazards. In this manual, a warning indicates an imminently hazardous situation which, if not avoided, may result in serious injury or death. Safety Messages Follow all standard industry procedures for servicing electrical and computer equipment when working with, or around high voltage. Always shut off the power supply before touching any components. Although high voltage is not present in this system, it may be present in other systems. Electrical components are sensitive to electrostatic discharge. To prevent equipment damage, observe all safety precautions when working with electrostaticsensitive components. WARNING! EXPLOSION HAZARD! DO NOT CONNECT OR DISCONNECT THE TRANSMITTERS UNLESS THE POWER HAS BEEN SWITCHED OFF. Low Voltage Directive If the equipment is used in a manner not specified by the manufacturer, protection provided by equipment may be impaired. Notice of Copyright and Limitations Copyright 2016 Solutions With Innovation, LLC; All rights reserved. Solutions With Innovation reserves the right to make changes to the product described in this manual at any time without notice. Solutions With Innovation makes no warranty with respect to the accuracy of the information in this manual. Warranty All Solutions With Innovation Electronic Level and Flow Controls are warranted free of defects in materials and workmanship for one full year from the date of the original factory shipment. If returned within the warranty period; and, upon factory inspection of the control, the cause of the claim is determined to be covered under the warranty; then, Solutions With Innovation will repair or replace the product at no cost to the purchaser (or owner) other than transportation. Solutions With Innovation shall not be liable for misapplication, labor claims, direct or consequential damage, or expenses arising from the installation or use of the equipment. There are no other warranties expressed or implied, except special written warranties covering specific Solutions With Innovation products. Quality Assurance The Quality Assurance System in place at Solutions With Innovation guarantees the highest level of quality throughout the company. Solutions With Innovation is committed to providing full customer satisfaction; both in quality products and in quality service. Contacts Phone: 203-729-6434 Mon-Fri, 9 AM - 5 PM EST Fax: 203-729-0541 for General Inquiries Email: sales@innovativesensing.com 2 U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS

TABLE OF CONTENTS U00X ULTRASONIC LEVEL SWITCH For Non-Hazardous Locations 1.0 Installation 1.1 Unpacking...4 1.2 Electrostatic Discharge Handling Procedure...4 1.3 Before You Begin...4 1.3.1 Site Preparation...4 1.3.2 Equipment and Tools...4 1.4 Mounting...5 1.4.1 Horizontal Installation...5 1.4.2 Vertical Installation...5 1.4.3 Nozzle or Pipe Installation...5 1.5 Wiring...6 1.5.1 U002: Current Shift Output...6 1.5.2 U003: Relay Output...6 1.5.3 U004: Relay Output with Fail-Safe Option...7 2.0 Preventative Maintenance 2.1 Maintenance Procedure...8 2.1.1 Inspect Unit Periodically...8 2.1.2 Inspect Connections Monthly...8 2.2 What To Avoid...8 3.0 Reference Information 3.1 Description...9 3.2 Theory of Operation...9 3.3 Troubleshooting...10 3.3.1 Unit Problems...10 3.3.2 Replacement Units...10 3.4 Specifications...11 3.4.1 Functional...11 3.4.2 Physical...11 3.5 Model Configurator...12 3.5.1 Additional Options...12 3.6 Notes...13 U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS 3

1.0 INSTALLATION This section provides detailed procedures on properly installing and configuring the U00X Ultrasonic Liquid Level Switch. CAUTION! IF THE EQUIPMENT IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER, PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED. 1.1 UNPACKING Unpack the instrument, carefully. Make sure that all components have been removed from the packing material. Inspect all components for damage. Report any concealed damage to the carrier within 24 hours of receiving. Compare the contents with the packing slip and report any discrepancies to the factory immediately. Record the sales order number and/or serial number for future reference when ordering parts. Before Proceeding to Installation, Complete the Following: Inspect all components for damage. Report any damage to the carrier within 24 hours of receiving. Record the model and serial numbers for future reference when ordering parts. Model Number Serial Number 1.2 ELECTROSTATIC DISCHARGE (ESD) HANDLING PROCEDURE Solutions With Innovation s electronic instruments are manufactured to the highest quality standards. These instruments use electronic components that may be damaged by static electricity present in most work environments. Make sure that all electrical connections are completely secure and none are partial or floating. Ground all equipment to a good, earth ground. 1.3 BEFORE YOU BEGIN 1.3.1 Site Preparation 1 Verify that the designated mounting area for the U00X Ultrasonic Liquid Level Switch is clean and free of any particulate matter. Refer to Section 1.4: Mounting. 2 Ensure that the wires are mounted properly to prevent kinks and pinching between components. When installing the U002, U003 or U004, all applicable electrical codes and wiring procedures must be observed. Refer to Section 1.5: Wiring. 1.3.2 Equipment and Tools No special equipment or tools are required to install the U00X Ultrasonic Liquid Level Switch. The Following Are Recommended: Adjustable Wrench Proper Gasket (For Flanged Units) 4 U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS

1.4 MOUNTING The U002, U003 and U004 Ultrasonic Liquid Level Switches can be mounted in a variety of positions. By ensuring the vertical orientation of the transducer gap, the unit will facilitate maximum performance in difficult applications. 1.4.1 Horizontal Installation 1 Apply thread tape or pipe compound onto the unit s mounting thread. 2 Carefully, thread the transducer into the opening and tighten with a wrench. DO NOT OVER-TIGHTEN. 3 Orient the transducer gap as vertical as possible to allow for the proper drainage of fluid from the gap. DO NOT OVER-TIGHTEN. vertically-positioned transducer gap (Bottom View) 1.4.2 Vertical Installation 1 Apply thread tape or pipe compound onto the unit s mounting thread. 2 Carefully, thread the transducer into the opening and tighten with a wrench. DO NOT OVER-TIGHTEN. transducer gap 1.4.3 Nozzle or Pipe Installation 1 Apply thread tape or pipe compound onto the unit s mounting thread. 2 Carefully, thread the transducer into the opening and tighten with a wrench. For flanged connections, bolt the unit to the mating flange with a proper gasket. DO NOT OVER-TIGHTEN. gap must clear nozzle 1 3 Position the transducer gap to extend at least 1 into the interior tank wall. If the switch is mounted horizontally, orient the transducer gap as vertical as possible to ensure proper drainage from the gap. DO NOT OVER-TIGHTEN. vertically-positioned transducer gap (Bottom View) U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS 5

1.5 WIRING WARNING! DO NOT DISCONNECT THE EQUIPMENT UNLESS THE POWER IS SWITCHED OFF. DO NOT ATTEMPT TO WIRE THE EQUIPMENT UNLESS THE POWER IS SWITCHED OFF. CAUTION! ALL WIRING, CONDUIT AND ELECTRICAL FITTINGS MUST CONFORM TO ALL LOCAL ELECTRICAL CODES CORRESPONDING TO THE INSTALLATION LOCATION. 1.5.1 U002: Current Shift Output The three (3) wiring terminations for the U002 are 18 AWG. Connect the wires to field wiring that is 14 to 22 AWG. Field Wiring Connection: 1 Install the conduit into the 3/4 NPT connection. 2 Use an approved seal fitting to prevent moisture from entering the internal switch. 3 Connect the loop power to the unit via the red (+) and black (-) wires. 4 Connect the green wire to grounded earth. 1.5.2 U003: Relay Output The six (6) wiring terminations for the U003 are 18 AWG. Connect the wires to field wiring that is 14 to 22 AWG. Field Wiring Connection: 1 Install the conduit into the 3/4 NPT connection. 2 Use an approved seal fitting to prevent moisture from entering the internal switch. 3 Connect a 12 to 35 VDC power supply to the unit via the red (+) and black (-) wires. 4 Connect the green wire to grounded earth. 5 The SPDT relay wire connections (dry sensor tip): orange wire: N.O. (Normally-Open) blue wire: N.C. (Normally-Closed) yellow wire: COM (Common) 6 U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS

1.5.3 U004: Relay Output with Fail-Safe Option The six (6) wiring terminations for the U004 are 18 AWG. Connect the wires to field wiring that is 14 to 22 AWG. Field Wiring Connection: 1 Install the conduit into the 3/4 NPT connection. 2 Use an approved seal fitting to prevent moisture from entering the internal switch. 3 Connect a 12 to 16 VDC or 24 to 30 power supply to the unit via the red (+) and black (-) wires depending on the input. 4 Connect the green wire to grounded earth. Power On: Normal Operation Input Voltage: 12 to 16 VDC or 24 to 30 VDC Power Consumption: Less Than 1 Watt Relay Contact Ratings: 1 Amp at 30 VDC; 0.5 Amp at 125/150 VDC DRY SENSOR OUTPUT red wire black wire normally-closed common normally-open blue wire yellow wire orange wire green wire (ground) - + 12-16 vdc or 24-30 vdc WET SENSOR OUTPUT open common closed blue wire yellow wire orange wire Power Loss: Fail-Safe Operation If the Input Voltage drops to less than 3 VDC or 16 VDC, the Fail-Safe mode engages. If the Input Voltage is restored to greater than 12 VDC or 24 VDC, Normal operation resumes. DRY SENSOR OUTPUT WET SENSOR OUTPUT open blue wire open blue wire common yellow wire common yellow wire closed orange wire closed orange wire U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS 7

2.0 PREVENTATIVE MAINTENANCE Periodic inspections are necessary to maintain the proper functionality of the U00X Ultrasonic Liquid Level Switch. The switch is an extremely compact level device with its electronics enclosed directly above the stainless steel transducer inside the extension piece. A systematic program of preventative maintenance should be implemented at the time of installation. If the following instructions are completed routinely, the ultrasonic switch will provide continuous liquid level detection. 2.1 MAINTENANCE PROCEDURES 2.1.1 Inspect Unit Periodically The U002, U003 and U004 Ultrasonic Liquid Level Switches are designed to operate in various fluids. Over time, media can build up in or around the transducer gap. As a result, their level detection capabilities may be impaired. Inspect the transducer gap for dense foam, dried product or any other potential build-up. Inspect all electrical connections and seals for possible damage. Replace the unit, if necessary. TRANSDUCER GAP KEEP SPACE CLEAN & CLEAR OF CONTAMINANTS 2.1.2 Inspect Connections Monthly U00X Ultrasonic Liquid Level Switches may be vulnerable to excessive heat and moisture. Under these conditions, the electrical wire insulation can periodically break or peel away. As a result, the bare wires may become exposed to the elements and incur damages. Inspect all wiring and remove the unit from service if any wires exhibit signs of brittle insulation. Inspect all electrical connections to ensure tightness. 2.2 WHAT TO AVOID NEVER ATTEMPT TO FIX ANY OF THE UNIT S INTERNAL COMPONENTS. There are no replacement parts for the unit. Tampering with the unit will void the manufacturer s warranty. NEVER USE A UNIT THAT SHOWS EVIDENCE OF SURFACE OR ELECTRICAL DAMAGE. Remove the unit from service immediately and replace it with a new one. NEVER CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF. Potential explosion hazard. Always verify that the area is non-hazardous when connecting or disconnecting the unit. 8 U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS

3.0 REFERENCE INFORMATION This section illustrates an overview of the U00X Ultrasonic Liquid Level Switch operation, as well as information on troubleshooting common problems, agency approval listings and detailed physical, functional and performance specifications. 3.1 DESCRIPTION The U002, U003 and U004 Ultrasonic Liquid Level Switches are compact integral units that utilize pulsed signal technology to perform high or low level measurement in a wide variety of fluid applications. The U00X Ultrasonic Liquid Level Switch is intended for use in non-hazardous locations, however, additional models are available for use in hazardous locations. 3.2 THEORY OF OPERATION U00X Series Liquid Level Switches utilize ultrasonic energy to detect the presence or absence of liquid within a tip-sensitive transducer gap. Their operation is based on the principle of Contact Ultrasonic Technology, where high-frequency sound waves are easily transmitted across a wet transducer gap, but become attenuated if the gap is dry. Two piezoelectric crystals (one transmitter and one receiver) are encapsulated at the tip of the transducer. If a voltage is applied to the crystals, their ceramic composition vibrates. The transmitter crystal converts the voltage into an ultrasonic signal that travels across the liquid-filled gap where it is detected by the receiver crystal. The ultrasonic signal is then converted back into an electrical signal that indicates the presence of liquid to the electronic components. If no liquid is present, the transmitted signal fails to travel across the dry gap. TRANSMITTER CRYSTAL WET TRANSDUCER GAP UNIT INSTALLED VERTICALLY IN TANK RECEIVER CRYSTAL DRY TRANSDUCER GAP U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS 9

3.3 TROUBLESHOOTING The U00X Ultrasonic Liquid Level Switch is designed and manufactured for trouble-free performance across a wide range of operating conditions. Common transmitter problems are discussed in terms of their symptoms and recommended corrective actions. WARNING! DO NOT CONNECT OR DISCONNECT THE EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS. 3.3.1 Unit Problems SYMPTOM PROBLEM SOLUTION THERE IS NO CHANGE IN OUTPUT BETWEEN THE WET AND DRY GAP. THE TRANSDUCER GAP IS CLOGGED. VERIFY THAT THE TRANSDUCER GAP IS NOT PLUGGED WITH SOLIDS, DENSE FOAM ON THE SURFACE OR DRIED PRODUCT IN THE GAP. THE UNIT MAY NOT FUNCTION PROPERLY IF THIS CONDITION EXISTS. THERE IS NO CHANGE IN OUTPUT BETWEEN THE WET AND DRY GAP. ELECTRICAL FAILURE. CHECK THE WIRING TO ENSURE THE PROPER INPUT VOLTAGE IS SUPPLIED. THE SWITCH IS CHATTERING. TURBULENCE. CHECK FOR TURBULENCE. RELOCATE THE SWITCH OR ISOLATE IT TO PREVENT INTERFERENCE. THE SWITCH IS CHATTERING. THERE IS EXCESSIVE AERATION. CHECK FOR EXCESSIVE AERATION. THE SWITCH IS CHATTERING. ELECTRICAL FAILURE. CHECK THE WIRING TO ENSURE THE PROPER INPUT VOLTAGE IS SUPPLIED. If you are still in doubt about the condition or performance of your control, consult the factory for further instructions. 3.3.2 Replacement Units Due to the epoxy-cured design of the U002, U003 and U004 Ultrasonic Liquid Level Switches, replacement parts cannot be installed into the existing unit. If the transducer becomes damaged or loses functionality, consult the manufacturer to order a unit replacement. When Ordering Replacement Units: Identify the unit s model number and/or serial number. Refer to the information listed in Section 1.1: Unpacking. Reference the detailed listing of model number specifications and additional options in Section 3.6 Model Configurator. 10 U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS

3.4 SPECIFICATIONS 3.4.1 Functional INPUT OUTPUT ENVIRONMENTAL PERFORMANCE MEASUREMENT PRINCIPLE: MEASURED VARIABLE: INDICATION LENGTH: POWER: SIGNAL: CABLING: Ultrasonic Sound Waves Converted to Output Signal Wet or Dry Gap Actuation 2 ⅛ to 100 (5.39 cm to 254 cm) U002: 12 to 35 VDC U003: 12 to 35 VDC U004: 12 to 16 VDC or 24 to 30 VDC U002 Current Shift: Dry Gap: 8 ma (± 1 ma) Wet Gap: 16 ma (± 1 ma) U003 Relay Output: SPDT: 1 Amp at 30 VDC; 0.5 Amp at 150/125 VAC/DC U004 Relay Output: SPDT: 1 Amp at 30 VDC; 0.5 Amp at 150/125 VAC/DC 12 (305 mm) Flying Leads of 18 AWG Wire OPERATING TEMPERATURE: -40 to +185 F (-40 to +85 C) AMBIENT TEMPERATURE: -40 to +185 F (-40 to +85 C) PRESSURE: INGRESS PROTECTION: CRYSTAL FREQUENCY: RESPONSE TIME: POWER CONSUMPTION: MATERIALS OF CONSTRUCTION ENCLOSURE (OPTIONAL): MOUNT, EXT. TUBE & SENSOR TIP: 316 Stainless Steel: 2,000 PSIG (138 bar) Hastelloy C: 2,000 PSIG (138 bar) CPVC: 200 PSIG (13.8 bar) PVDF: 50 PSIG (3.4 bar) NEMA 4X 2 MHz, Pulsed Less Than ½ Second Less Than 1 Watt Die-Cast Aluminum 316 Stainless Steel, Hastelloy C, CPVC, or PVDF 3.4.2 Physical 4 ⅞ ¾ NPT CONDUIT 1 ⅜ HEX 4 ⅞ ¾ NPT CONDUIT 1 ⅜ HEX 4 ⅞ ¾ NPT CONDUIT 1 ⅜ HEX U002 U003 U004 ¾ NPT MOUNT ¾ NPT MOUNT ¾ NPT MOUNT LO LO LO ¼ REF ACTUATION Ø ⅞ ¼ REF ACTUATION Ø ⅞ ¼ REF ACTUATION Ø ⅞ U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS 11

3.5 MODEL CONFIGURATOR TECHNOLOGY MODEL CONFIGURATION CUSTOM IDENTIFICATION U00 Ultrasonic Level Switch 2 Current Shift Output C Custom Design YYYY-ZZZZ Custom Design Number 3 Relay Output 4 Relay Output with Fail-Safe Option U 0 0 3 C Y Y Y Y - Z Z Z Z 3.5.1 Additional Options AVAILABLE ENCLOSURES No Junction Box: Standard Probe & Mount Assembly With Junction Box: Die-Cast Aluminum Enclosure AVAILABLE PROCESS CONNECTIONS ¾ NPT 1 #150 ANSI Flange 1 NPT 1 ½ #150 ANSI Flange 1 ¼ NPT 2 #150 ANSI Flange 1 ½ NPT 2 ½ #150 ANSI Flange 2 NPT 3 #150 ANSI Flange 2 ½ NPT 4 #150 ANSI Flange 3 NPT 1 #300 ANSI Flange 4 NPT 1 ½ #300 ANSI Flange 1 Sanitary Flange 2 #300 ANSI Flange 2 Sanitary Flange 2 ½ #300 ANSI Flange 2 ½ Sanitary Flange 3 #300 ANSI Flange 3 Sanitary Flange 4 #300 ANSI Flange 4 Sanitary Flange 12 U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS

3.6 NOTES U00X ULTRASONIC LIQUID LEVEL SWITCH FOR NON-HAZARDOUS LOCATIONS 13

ASSURED QUALITY & SERVICE COST LESS Service Policy Owners of Solutions With Innovation products may request a return of the product, or any part of the product for complete rebuilding or replacement. Units will be rebuilt or replaced promptly. Products returned under the SWI Service Policy must be returned by prepaid transportation. Solutions With Innovation will repair or replace the product at no cost to the purchaser (or owner) other than transportation if: 1 Returned within the warranty period; and 2 Factory Inspection finds the cause of the claim to be covered under the warranty. If the problem is due to circumstances beyond Solutions With Innovation s liability, or is NOT covered by the warranty, there will be charges for labor in addition to the parts required to rebuild or replace the equipment. In rare cases, it may be expedient to ship replacement parts; or in extreme cases, an entire product before the damaged product is returned. If a quick replacement service is necessary, notify the manufacturer of the damaged product s model and serial number. In such cases, credit for the returned materials will be determined on the applicability of the warranty. Return Material Procedure In order to efficiently process any returned materials, it is essential that a Return Material Authorization (RMA) number be obtained from the manufacturer prior to an item s return. RMA s can be issued through local representatives, or by contacting the factory directly. Please supply the following information: 1 The Company s Name 2 Description of the Material 3 Product Serial Number 4 Reason for Return 5 Product s Application Used units must be properly cleaned in accordance with OSHA standards before it is returned to the manufacturer. A Material Safety Data Sheet (MSDS) must accompany units or materials that were used in any type of media. All return shipments to the factory must be by done via prepaid transportation. All product replacements will be shipped F.O.B. manufacturer. No claims for misapplication, labor, direct or consequential damage will be allowed. BULLETIN: IS-9410.6 EFFECTIVE: 4/16