High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development Co., Ltd.

Similar documents
Next-generation SCADA and Control Technologies for Large-scale Use of Photovoltaic Generation on Electric Power Grid

Development of Emergency Train Travel Function Provided by Stationary Energy Storage System

Development and Performance Evaluation of High-reliability Turbine Generator

The Circuit and Control Technology in the Power Conditioner and Converter for Wind Turbine Systems

Environmentally Conscious Green Mobility

Development of Rolling Stock Inverters Using SiC

Energy Storage for Traction Power Supply Systems

Examples of Electric Drive Solutions and Applied Technologies

Featured Articles Utilization of AI in the Railway Sector Case Study of Energy Efficiency in Railway Operations

Power System Stability Solutions for Low-carbon Society

FRENIC-Mega Series of High-performance Multi-function Inverters

Technology from the New Product SANUPS K for a Smart Grid Society

Development of Higher-voltage Direct Current Power Feeding System for ICT Equipment

All-SiC Module for Mega-Solar Power Conditioner

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

VARIABLE FREQUENCY DRIVE AND ITS INDUSTRIAL APPLICATIONS

Next-generation Inverter Technology for Environmentally Conscious Vehicles

Robust Control Technique for Grid-connected Power Conditioner

MX1S Matrix Converter

690-V Inverters Equipped with SiC Hybrid Module FRENIC-VG Stack Series

PVI1000 : Outdoor High-Efficiency Power Conditioners for Mega Solar Projects

Technical Explanation for Inverters

Fig.1 Sky-hook damper

Development of the Single Phase PV Inverter SANUPS P61A

Construction of power supply system using electric vehicle for stable power delivery from PV generation

Development of Large-capacity Indirect Hydrogen-cooled Turbine Generator and Latest Technologies Applied to After Sales Service

The evaluation of endurance running tests of the fuel cells and battery hybrid test railway train

The 1,400-MW Kii-Channel HVDC System

Development of Catenary and Batterypowered

Development of New Model Residential PEMFC micro-chp Systems

Hitachi Electric Drive Solutions that Contribute to Global Environment

Development of Small-capacity OFF-LINE UPS

Development of the Small-Capacity UPS SANUPS A11K Series

Battery-powered Drive Systems: Latest Technologies and Outlook

Operating Results of J-series Gas Turbine and Development of JAC

Hitachi Makes a Significant Contribution to the Construction of Secure and Reliable ETC Systems in Japan

Common Bus and Line Regeneration

VARIABLE FREQUENCY DRIVES

Technology Application to MHPS Large Frame F series Gas Turbine

Guideline for Using IEEE 1547 for Solar PV Interconnection Page 1

.3 Section Waste Management and Disposal.

Power Interchange System for Reuse of Regenerative Electric Power

Autonomous Haulage System for Mining Rationalization

SINAMICS SM150. 4/2 Overview. 4/2 Benefits. 4/2 Design. 4/6 Function. 4/8 Selection and ordering data. 4/8 Options

Multilink Transportation Power Solutions

Development of a High Efficiency Induction Motor and the Estimation of Energy Conservation Effect

Activities of Hitachi Regarding Construction of the J-PARC Accelerator

400/230 Volt 60Hz UPS Power

IGBT Modules for Electric Hybrid Vehicles

DC Arc-Free Circuit Breaker for Utility-Grid Battery Storage System

Development of Variable Geometry Turbocharger Contributes to Improvement of Gasoline Engine Fuel Economy

A Novel DC-DC Converter Based Integration of Renewable Energy Sources for Residential Micro Grid Applications

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

Steering Actuator for Autonomous Driving and Platooning *1

Aurora Single Phase Emergency Lighting Inverters

Shaft Grounding Rings. Protecting VFD Driven Motors from Bearing Currents

APPLICATION OF BOOST INVERTER FOR GRID CONNECTED FUEL CELL BASED POWER GENERATION

Three-phase 200 V series: FRN0025 to 0060C2S-2U Three-phase 400 V series: FRN0013 to 0030C2S-4U

SINAMICS GM150 IGCT version

Development and Demonstration of Redox Flow Battery System

Hybrid Wheel Loaders Incorporating Power Electronics

Protection of Power Electronic Multi Converter Systems in AC and DC Applications

ABB n.v PQF LV Active Filters: Bringing energy savings to you

Development of Emission Control Technology to Reduce Levels of NO x and Fuel Consumption in Marine Diesel Engines

Development of Motor-Assisted Hybrid Traction System

Components and Systems for Electric Vehicles (HEVs/EVs)

Energy Saving Technologies for Elevators

JOINT SERVICE POWER EXPO CLARY CORPORATION

ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS)

Control System for a Diesel Generator and UPS

AC/DC FFE converter power module

A Study on the Measurement of Contact Force of Pantograph on High Speed Train

Pump Coupling & Motor bearing damage detection using Condition Monitoring at DTPS

High Efficiency SiC Power Semiconductor. May 20, 2014 Toyota Motor Corporation

Reducing Train Weight and Simplifying Train Design by Using Active Redundancy of Static Inverters for the Onboard Supply of Rolling Stock

Development of Uninterruptible Power Supply SANUPS A11J Three-phase, Four-wire Model

Optimum Operation Control of Distributed Energy Resources Using ENERGYMATE-Factory

Facility Employing Standard Converters for Testing DFIG Wind Generators up to 30kW

Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER

Design and Control of Lab-Scale Variable Speed Wind Turbine Simulator using DFIG. Seung-Ho Song, Ji-Hoon Im, Hyeong-Jin Choi, Tae-Hyeong Kim

Sustainable Energy Mod.1: Fuel Cells & Distributed Generation Systems

Development of a Clutch Control System for a Hybrid Electric Vehicle with One Motor and Two Clutches

Enhanced Breakdown Voltage for All-SiC Modules

STUDY OF LARGE VSI DRIVE SYSTEM FOR OIL AND GAS INDUSTRY

Interruption Technology of Breakers for High-voltage Direct Current

Using energy storage for modeling a stand-alone wind turbine system

SIMINE DRAG. Innovative solutions for maximum productivity and reliability. Mining Technologies

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.

Fuji Medium-voltage IGBT Inverters

Functional PCS power supply system with EV battery storage for stable PV power delivery

Microgrid System for Isolated Islands

Development of New Megasolar PCS Models and Functions Conforming to Feed-in-Tariff System in Japan

SHIMADEN SINGLE-PHASE THYRISTOR POWER REGULATOR

Uptime. All the time.

Varispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES

Renewables from a TSO Perspective. M.BENA, SmartGrids Director, RTE, French TSO Vienna, 18 May 2015

PowerFlex 6000 Medium Voltage AC Drives

E-15 Uninterruptible Power Systems (UPS)

Drive system for high pressure grinding rolls Increased roller life and productivity

Core Components for Large-scale PV Generation Systems

Transcription:

Hitachi Review Vol. 53 (2004), No. 3 121 High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development Co., Ltd. Hiroaki Yamada Kiyoshi Arayama Shigetoshi Okamatsu Koichiro Nagata, Ph.D. OVERVIEW: Finding ways to save energy has become an increasingly urgent concern of the power industry. One strategy with enormous energy saving potential is to reduce the supply power of large auxiliary motors at power plants. Inverters have been used in the past for variable speed control over auxiliary motors, but the output voltage and capacity of conventional inverters are relatively small, so there has been little incentive to apply inverters to the larger scale auxiliary motors used by commercial thermal power plants. This motivated a joint research project between Electric Power Development Co., Ltd. and Hitachi, Ltd. to develop an 8,250-kVA highvoltage direct inverter that could be applied to high-voltage high-capacity large auxiliary motors. The direct inverter was connected to a 7,000-kWcapacity induced draft fan motor at Electric Power Development Co., Ltd.'s Takehara Thermal Power Station No. 3 and subjected to extensive field trial testing. In pursuing the project we also developed a system configuration and control methods to ensure that the plant continues to operate stably even when disturbances occur from the system, and the system demonstrated a high degree of reliability. It was found that substantial energy could be saved by using the inverter. For example, compared to a conventional configuration, motor power consumption could be reduced by as much as 70% when operating at an output capacity of 50% by using the inverter. INTRODUCTION POWER output of power stations is adjusted to accommodate varying demand for power by opening and closing dampers and values that are used to adjust large fans and pumps. The drive motor that performs this work runs all the time at a constant speed which is unrelated to the power output of the station. Consequently, substantial energy is lost when the power output level is low because the damper and values are closed. Since the energy consumed by the motor is proportional to rotation speed cubed, the power consumption can be greatly reduced by using an inverter to regulate the speed of the drive motor (see Fig. 1). The primary drawback of conventional inverters is that their output voltage and capacity are too small. This means that a boost-up transformer must be separately implemented, an approach that yields only a modest efficiency gain, so there has been little incentive and little progress to incorporate inverters in large-scale equipment. Power consumption (kw) 6,000 5,000 4,000 3,000 2,000 1,000 Damper control Damper opening 20% Rotation speed 100% Damper opening 60% Rotation speed 100% Damper opening 100% Rotation speed 86% Inverter control Energy saving effect Damper opening 100% Rotation speed 49% Energy saving effect 0 10,000 20,000 30,000 40,000 Capacity (m 3 /min) Fig. 1 Power Consumption Reduction Effect with Inverter Control. Reducing the rotation speed with the inverter control reduces the power consumption more than the damper control.

High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development. Co., Ltd. 122 Cell inverter (diode converter + IGBT inverter) Fig. 2 High-voltage Direct Inverter Panel (a), Multiplex Transformer (b), and the Circuit Configuration (c). The high-voltage direct inverter panel consists of many cell inverters including IGBT elements. It converts a multi-phase to a three-phase variable-frequency for output. The multiphase transformer inputs a commercial and converts it to a multi-phase power supply. (a) (b) Multiplex transformer Commercial 6.6 kv High-voltage direct inverter panel (c) IGBT: insulated gate bipolar transistor IM: induction motor U: 1st phase V: 2nd phase W: 3rd phase U V W IM Variablefrequency 6.6 kv This motivated Electric Power Development Co., Ltd. and Hitachi, Ltd. to jointly develop a high-voltage high-capacity direct inverter that can also be applied to large auxiliary motors (see Fig. 2). The new inverter was applied to Electric Power Development Co., Ltd. s Takehara Thermal Power Station No. 3 and excellent results have been obtained in the trial operation. Here we will present an overview of this highvoltage director inverter and its performance. FEATURES AND RELIABILITY OF HIGH- VOLTAGE DIRECT INVERTER Features The new high-voltage direct inverter can be applied to large auxiliary motors up to 6,600 V, and has a number of significant advantages beyond its impressive efficiency and large capacity: (1) Can be used with existing motors Applying a multi-stage connection to a single-phase inverter, near sine wave voltage is output. The harmonic can also be controlled so there is no concern that the inverter might cause motor insulation to deteriorate, and it can be used to drive existing motors. (2) Minimal restraint affecting power system Using a multiple winding transformer, the harmonic component input current is suppressed. This minimizes the impact on the power system. (3) Enhanced Inverter efficiency By eliminating the need for a boost-up transformer on the output side, inverter efficiency is enhanced to 98%. Excellent Reliability When Applied to Large Auxiliary Equipment at Power Plants Considering the enormous adverse effects that can result when power plant equipment fails, a very high standard of reliability is critically important. The system was designed to provide very high reliability with special consideration for the following conditions: (1) Plant control and stable operation Control methods were implemented that permit stable inverter operation when starting and stopping and when running under normal load conditions. (2) Continuous operation when disturbances occur Control methods were implemented enabling the plant to continue operating even in the event of a power system outage or other disturbance or in the event that the inverter fails. SYSTEM CONFIGURATION, PLANT CONTROL METHODS, AND SYSTEM RELIABILITY System Configuration (1) The high-voltage direct inverter was connected to an IDF (induced draft fan), an auxiliary system in power plants of the largest capacity and thus offering the greatest potential energy savings (see Table 1). (2) Legacy equipment has been retained for the generating equipment and the IDF (rated: 7,000 kw 2 units, voltage: 6,600 V), and the inverter system consisting of multiple winding transformer and highvoltage direct inverter panel is installed close to the IDFs.

Hitachi Review Vol. 53 (2004), No. 3 123 TABLE 1. High-voltage Direct Inverter Specifications With high-voltage large-capacity specs, speed control can be applied to power plant large auxiliary equipment. Model Hitachi s high-voltage direct inverter Steam Steam turbine Generator Control system Rated capacity Rated voltage Speed control range Inverter efficiency Robust speed sensorless vector control 8,250 kva 6,600 V, 60 Hz 20 100% 98% Boiler Feed-water pump Additional equipment Multiplex transformer Three-phase commercial Multi-phase Input side transformer 24-phase (8 stages 3 phases) transformer, separate installation Air Fuel FDF Feed water IDF Chimney Exhaust gas (3) Commercially available circuitry has also been retained so, in the event that the inverter fails, the inverter is bypassed and the IDF continues to operate (see Fig. 3). Plant Control System Conventional IDFs rotate at a constant rate, the inlet damper is activated by commands from APC (automatic plant control) system, and the furnace draft is controlled to be stable even if the boiler load fluctuates. However, with the installation of the inverter, the furnace draft fluctuations are absorbed by IDF inlet damper, and the IDF speed is regulated by a program control scheme to match the boiler load. Moreover, the IDF speed is programmed to reduce the IDF speed when the inverter is operating to maximize the energy savings. Superior System Reliability The inverter includes sophisticated circuitry to detect any kind of problem as well as protect-interlock circuitry which permits highly stable plant operation and excellent system reliability even if a disturbance from the system should occur. (1) Operation monitoring and fault detection Displays and alarms have been implemented so the operational state of the inverter system can be monitored from the station s central control room. The inverter equipment also features a comprehensive set of built-in fault detection circuits [momentary power failures, overcurrent spikes, fuse breaks, overloading, cooling fan breakdowns, power failures, problems with the CPU (central processing unit), etc.] that enable early detection of any abnormality. Plant automatic control system Motor Damper opening control signal FDF: forced draft fan IDF: induced draft fan : alternating current circuit breaker High-voltage direct inverter Three-phase variable-frequency control signal Commercial operation side Fig. 3 System Configuration. The multiplex transformer and high-voltage inverter are installed between the commercial and the legacy motor. Signals from the automatic plant control system enable variable-speed control of the IDF motor. (2) Inverter reliability functions Excellent reliability is achieved by enhancing the protect-interlock and control functions so the plant continues to operate normally even if voltage fluctuations or ground faults occur, or if a part fails. The primary functions supporting this enhanced reliability are a voltage fluctuation correction function, an overload control function, speed rate control function, and a motor trouble detection function. (3) Restarting after momentary outages A method of estimating the motor rotation speed under free-running conditions has been implemented, so the motor can be smoothly restarted within a short period after the power source experiences a momentary outage. (4) Inverter/commercial operation switching control When switching to commercial, the rotation speed increases rapidly, and this results in large furnace draft

High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development. Co., Ltd. 124 opening, (%) 100 0 Inverter in operation opening opening bias during IDF rotation natural deceleration Inverter during commercial operation switching During commercial operation Inlet damper opening program switch operation temporarily suspended when furnace draft variation is large. opening Time Motor starting current (%) 500 100 (590 A) (2,966 A) Starting Approx. 90 s Starting current during commercial use Current when starting the inverter (measurements done in June 2002) Elapsed time Fig. 5 IDF Starting Current Test Results with Inverter. Compared to commercial operation, motor starting current is reduced by the inverter. Fig. 4 Overview of Inverter and Commercial Operation Switching Control. The switching control effectively suppresses furnace draft fluctuations when IDF speed increases by closing down the IDF inlet damper opening. fluctuations. We have implemented a control method that effectively minimizes the furnace draft fluctuations (see Fig. 4). TEST RESULTS AND APPLICATION EFFECTS Test Results The high-voltage direct inverter was connected to an IDF motor at a power plant in May 2001, subjected to extensive in-operation testing, and it performed very well. In evaluating the inverter, we conducted the following tests: (1) Performance verification testing (voltage fluctuation, temperature increase) (2) Operability, controllability verification testing (starting and stopping, load fluctuations, restarting after momentary outages, harmonics measurement) (3) Abnormal operation testing (inverter and commercial operation switching, half-side operation) (4) Verification of other effects (noise verification, speed deceleration effect) Current was also measured when starting up the inverter. It was found that the inverter starting current was relatively small and the inverter started up smoothly even though the starting current when starting the motor and during commercial operation was about 5 times the rated current (see Fig. 5). Based on actual measurements of the content of power harmonics included in the output, it was confirmed that the range of operating values fell well within the Guideline for Reduction of Harmonic Emission published by the Ministry of Economy, Trade and Industry (see Fig. 6). Energy Saving Effects Comparing the operation using the inverter with commercial operation, it was found that power consumption was reduced by 70% when operating at 50% power output and by 20% when operating at a power output of 100%. Moreover, considering that the IDF gas flow and opening vary depending on the season and type of coal, it was found that the energy savings could be further improved by adopting a control method that supports operation while reducing the rotation speed of the IDF as much as possible. Other Effects from Adopting Inverter In addition to the energy saving effects already mentioned, installing the inverter had a number of other beneficial effects: (1) Reduced power reduces CO 2 emissions and thus has a beneficial environmental effect. (2) Reduced motor speed means less noise. (3) Reduced motor startup current mitigates disturbance on the power system and results in less stress on the motor. CONCLUSIONS This paper detailed a number of significant beneficial effects that were achieved by connecting a high-pressure direct inverter to a forced-draft fan motor at No. 3 of Takehara Thermal Power Station operated

Hitachi Review Vol. 53 (2004), No. 3 125 5.00 Fig. 6 Harmonic Component Test Results. The harmonic component is reduced by the inverter to well below the figure recommended in the Guideline for Reduction of Harmonic Emission. Harmonic content (%) 4.00 3.00 2.00 1.00 0.00 When commercial operation When inverter operation Guideline for Reduction of Harmonic Emission 1 3 5 7 9 11 13 15 17 19 21 23 27 29 31 33 35 37 39 41 43 45 47 49 51 Harmonic degree by Electric Power Development Co., Ltd. It was shown that substantial energy savings were realized by using the inverter, and the system performed very well (starting, stopping, and various other functions) in extensive long-term trials. Developed as a joint research project by Electric Power Development Co., Ltd. and Hitachi, Ltd., the inverter was subjected to extensive field trials that were concluded in October 2003, and has performed flawlessly since the inverter was subsequently put into service. The high-pressure direct inverter saves considerable energy and thus has a beneficial effect on the environmental, so we intend to deploy the system at other power plants. REFERENCES (1) S. Shimizu, et al., Energy Saving by Application of High- Voltage Direct Inverter to the Thermal Power Plant, 14th Conference of the Electric Power Supply Industry, proceedings paper (Nov. 2002). (2) S. Sugiyama, et al., Energy-Saving Tracking-Type Variable- Speed Drive System, Hitachi Hyoron 82, pp. 273-278 (April 2000) in Japanese. ABOUT THE AUTHORS Hiroaki Yamada Joined Electric Power Development Co., Ltd. in 1992, and now works at the Plant R&D Group, Thermal Power Department. He is currently engaged in R&D of thermal power technology. Mr. Yamada can be reached by e-mail at Hiroaki_Yamada@jpower.co.jp. Kiyoshi Arayama Joined Hitachi, Ltd. in 1978, and now works at the Power Plant Control Systems Engineering Department, the Information & Control Systems Division, the Information & Telecommunication Systems. He is currently engaged in engineering work on thermal power plant control systems. Mr. Arayama can be reached by e-mail at kiyoshi_arayama@pis.hitachi.co.jp. Shigetoshi Okamatsu Joined Hitachi, Ltd. in 1974, and now works at the Electrical Control Systems Engineering Department, the Information & Control Systems Division, the Information & Telecommunication Systems. He is currently engaged in the design and development of inverter drive systems. Mr. Okamatsu is a member of The Institute of Electrical Engineers of Japan (IEEJ) and can be reached by e-mail at shigetoshi_okamatsu@pis.hitachi.co.jp. Koichiro Nagata Joined Hitachi, Ltd. in 1995, and now works at the High Power Drive Systems Unit, the Fifth Department of Systems Research, Hitachi Research Laboratory. He is currently engaged in the development of motor drive control systems. Dr. Nagata is a member of IEEJ, and The Physical Society of Japan, and can be reached by e-mail at knagata@gm.hrl.hitachi.co.jp.