Low voltage - Energy, cabling, signalling and control FR-N1X1G1 Construction: NF C 32-323 NF C 32-323/1 Fire propagation: NF EN 60332-3-24 NF C 32-070 C1 IEC 60332-3-24 C Flame propagation: NF EN 60332-1-2 Corrosive gases or halogens: NF EN 50267-2-1 NF EN 50267-2-2 Smoke density (trasmittance): NF EN 61034-2 Low Voltage Directive: 2014/35/EU RoHS Directive: 2011/65/EC www.latrivenetacavi.com review n 003 date 03/12/16
Description Conductor: - plain copper, solid, class 1 (cross-section 4mm 2 ) - plain copper, stranded wire, class 2 (cross-section 6mm 2 ) Insulation: XLPE (cross-linked polyethylene) Filler: LS0H thermoplastic Sheath: LS0H polyolefin Colour: green LS0H = Low Smoke Zero Halogen Functional characteristics Rated voltage Uo/U: 0,6/1 kv operating temperature: 90 C Min. operating temperature: -15 C (without mechanical shocks) short circuit temperature: 250 C Installation conditions Minimum installation temperature: 0 C Recommended minimum bending radius: 12 times the diameter Recommended maximum tensile stress: 50 N/mm² of the cross-section of the copper Use and installation method This is recommended for use in public and industrial settings whenever good fire retardand qualities, reduced fumes, toxic and corrosive gases emissions are required in the case of fire. For use in industrial settings, in the upright columns of buildings when strict safety standards have to be respected. It offers good to low temperatures, chemical agents, solar radiation, and mechanical forces in general. Can be used for static applications in the open air, in pipes, or in trenches. The can be laid directly in the ground for short periods on the condition that the ground is not flooded and that it is provided with suitable mechanical protection. With appropriate mechanical protection, it can be used in areas subject to the risk of explosion, but in this case the permitted current load is reduced by 15%.
Single-core 1 x 1,5 1,4 0,7 1,09 6,6 12,1 45 24 31 1 x 2,5 1,8 0,7 1,09 7,0 7,41 60 33 41 1 x 4 2,3 0,7 1,09 7,6 4,61 80 45 53 1 x 6 3,1 0,7 1,09 8,2 3,08 105 58 66 1 x 10 4,0 0,7 1,09 9,2 1,83 150 80 87 1 x 16 4,8 0,7 1,09 10,5 1,15 220 107 113 1 x 25 6,0 0,9 1,09 12,5 0,727 325 138 144 1 x 35 7,0 0,9 1,09 13,5 0,524 440 169 174 1 x 50 8,1 1,0 1,09 15,0 0,387 585 207 206 1 x 70 9,7 1,1 1,09 17,0 0,268 805 268 354 1 x 95 11,4 1,1 1,18 19,0 0,193 1100 328 301 1 x 120 13,1 1,2 1,18 21,0 0,153 1385 382 343 1 x 150 14,6 1,4 1,26 23,0 0,124 1700 441 387 1 x 185 16,5 1,6 1,26 25,5 0,0991 2120 506 434 1 x 240 18,5 1,7 1,35 28,5 0,0754 2910 599 501 1 x 300 21,0 1,8 1,43 31,0 0,0601 3380 693 565 - a three-phase circuit for single-core s with thermal resistivity of the ground equal to 1 K.m/W and laying depth of 600 mm - a single-phase circuit for two-core s, a three-phase circuit for three-core s with thermal resistivity of the ground equal to 1 K.m/W and laying depth of 600 mm If conditions are different, apply correction factors of NF C 15-100 (tables 52G - 52N - 52O - 52P - 52Q - 52R - 52S - 52T).
Two-core and three-core 2 x 1,5 1,4 0,7 1,43 10,5 12,1 130 26 37 2 x 2,5 1,8 0,7 1,43 11,5 7,41 165 36 48 2 x 4 2,3 0,7 1,43 13,0 4,61 200 49 63 2 x 6 3,1 0,7 1,43 14,0 3,08 280 63 80 2 x 10 4,0 0,7 1,43 16,0 1,83 410 86 104 2 x 16 4,8 0,7 1,43 18,5 1,15 590 115 136 2 x 25 6,0 0,9 1,43 22,0 0,727 900 149 173 2 x 35 7,0 0,9 1,43 24,5 0,524 1135 185 208 3 x 1,5 1,4 0,7 1,43 11,0 12,1 145 23 31 3 x 2,5 1,8 0,7 1,43 12,5 7,41 190 31 41 3 x 4 2,3 0,7 1,43 13,5 4,61 255 42 53 3 x 6 3,1 0,7 1,43 15,0 3,08 350 54 66 3 x 10 4,0 0,7 1,43 17,0 1,83 495 75 87 3 x 16 4,8 0,7 1,43 19,5 1,15 705 100 113 3 x 25 6,0 0,9 1,43 23,5 0,727 1130 127 144 3 x 35 7,0 0,9 1,43 26,0 0,524 1510 158 174 3 x 50 8,1 1,0 1,43 29,0 0,387 1985 192 206 3 x 70 9,7 1,1 1,52 34,0 0,268 2770 246 254 3 x 95 11,4 1,1 1,60 38,5 0,193 3790 298 301 3 x 120 13,1 1,2 1,69 42,5 0,153 4810 346 343 3 x 150 14,6 1,4 1,86 47,5 0,124 5935 395 387 3 x 185 16,5 1,6 1,94 53,0 0,0991 7460 450 434 3 x 240 18,5 1,7 2,11 59,5 0,0754 9510 538 501 3 x 300 21,0 1,8 2,28 66,0 0,0601 12100 621 565 - a three-phase circuit for single-core s with thermal resistivity of the ground equal to 1 K.m/W and laying depth of 600 mm - a single-phase circuit for two-core s, a three-phase circuit for three-core s with thermal resistivity of the ground equal to 1 K.m/W and laying depth of 600 mm If conditions are different, apply correction factors of NF C 15-100 (tables 52G - 52N - 52O - 52P - 52Q - 52R - 52S - 52T).
Four-core and five-core 4 x 1,5 1,4 0,7 1,43 12,0 12,1 170 23 31 4 x 2,5 1,8 0,7 1,43 13,0 7,41 225 31 41 4 x 4 2,3 0,7 1,43 14,5 4,61 305 42 53 4 x 6 3,1 0,7 1,43 16,0 3,08 420 54 66 4 x 10 4,0 0,7 1,43 18,5 1,83 610 75 87 4 x 16 4,8 0,7 1,43 21,0 1,15 870 100 113 4 x 25 6,0 0,9 1,43 25,5 0,727 1350 127 144 4 x 35 7,0 0,9 1,43 28,5 0,524 1895 158 174 4 x 50 8,1 1,0 1,52 32,5 0,387 2510 192 206 4 x 70 9,7 1,1 1,60 37,5 0,268 3545 246 254 4 x 95 11,4 1,1 1,69 42,5 0,193 4835 298 301 4 x 120 13,1 1,2 1,86 47,5 0,153 6130 346 343 4 x 150 14,6 1,4 1,94 52,5 0,124 7530 395 387 4 x 185 16,5 1,6 2,11 59,0 0,0991 9710 450 434 4 x 240 18,5 1,7 2,28 66,5 0,0754 12350 538 501 4 x 300 21,0 1,8 2,45 73,5 0,0601 15950 621 565 5 x 1,5 1,4 0,7 1,43 13,0 12,1 200 23 31 5 x 2,5 1,8 0,7 1,43 14,5 7,41 265 31 41 5 x 4 2,3 0,7 1,43 16,0 4,61 365 42 53 5 x 6 3,1 0,7 1,43 17,5 3,08 505 54 66 5 x 10 4,0 0,7 1,43 20,0 1,83 740 75 87 5 x 16 4,8 0,7 1,43 23,0 1,15 1065 100 113 5 x 25 4,8 0,7 1,43 28,0 0,727 1645 127 144 - a three-phase circuit - a with thermal resistivity of the ground equal to 1 K.m/W and laying depth of 600 mm If conditions are different, apply correction factors of NF C 15-100 (tables 52G - 52N - 52O - 52P - 52Q - 52R - 52S - 52T).
Multi-core 7 x 1,5 1,4 0,7 1,43 13,5 12,1 245 15 22 8 x 1,5 1,4 0,7 1,43 14,5 12,1 265 14 20 12 x 1,5 1,4 0,7 1,43 17,0 12,1 385 12,5 18 19 x 1,5 1,4 0,7 1,43 19,5 12,1 545 10,5 15 24 x 1,5 1,4 0,7 1,43 22,5 12,1 750 10 14 27 x 1,5 1,4 0,7 1,43 23,0 12,1 850 9 12,5 37 x 1,5 1,4 0,7 1,43 25,5 12,1 1010 8 12 7 x 2,5 1,8 0,7 1,43 15,0 7,41 330 20,5 28 8 x 2,5 1,8 0,7 1,43 16,5 7,41 370 19 27 12 x 2,5 1,8 0,7 1,43 19,5 7,41 550 17 24 19 x 2,5 1,8 0,7 1,43 22,5 7,41 785 14,5 19,5 24 x 2,5 1,8 0,7 1,43 25,5 7,41 1050 13 18 27 x 2,5 1,8 0,7 1,43 27,0 7,41 1190 12 16,5 37 x 2,5 1,8 0,7 1,43 29,5 7,41 1460 11 15,5 - a single-phase circuit and all cores loaded - a with thermal resistivity of the ground equal to 1 K.m/W and laying depth of 600 mm If conditions are different, apply correction factors of NF C 15-100 (tables 52G - 52N - 52O - 52P - 52Q - 52R- 52S - 52T).