BAPI-Stat 3 Room Sensor

Similar documents
BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

VOC Room Sensor in the BAPI-Stat 3 Enclosure with Differential Ground Configuration

DPS/MPS/RAH/RPS/SWP Space Sensor

Installation and Maintenance Manual IM

VOC Duct and Rough Service Sensor

AD592/592-10K Non-Room Units with a Junction Box, Weatherproof (WP) or Weather Tight (EU) Enclosure

Duct Averaging Transmitters BA/T#-A Temperature Transmitter Installation & Operations

SE8300 Series Installation Guide 24 Vac Low Voltage

Submersible Averaging Duct Transmitters BA/T#SA Temperature Transmitter Installation & Operations

Figure 1: WPR2 Dimensions and Hardware

AD592/592-10K Non-Room Sensors in BAPI-Box, BAPI-Box 2 or BAPI-Box 4 BA/592-x-(BB, BB2, BB4) Temperature Sensor Instructions & Operation

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output

Low Pressure Sensor. Overview. Specifications. Installation and Operation

Digital Room Thermostats with Touch Screen LCD

GE Measurement & Control

Temperature Transmitters

Compact Low Pressure Sensor

INSTALLATION INSTRUCTIONS T-59 SPACE TEMPERATURE SENSOR WITH OVERRIDE & SETPOINT ADJUSTMENT

Installation and Operation Instructions DLP Series

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN

MicroTech III Water Source Heat Pump Wall-Mounted Room Temperature Sensors

YCCS TE-6800 Series Temperature Sensors

A419ABG-3C Electronic Temperature Control

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data

Signet Temperature Transmitter

Induction Power Supplies

Immersion Temperature Sensors

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

Description. functions including single duct pressure dependent or pressure independent systems.

TC62D Installation Instructions

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

SE7200 Series Installation Guide

SIGNET Temperature Transmitter

Electric Actuator Instructions

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 06/18

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 10/14

SetPoint 150 Controller Installation Manual

TM-9100 Series Room Command Module

E.S.P. Embedded Sensing Probes for Motor Brushes

MODEL 422 Submersible Pump Controller

2122H. Arm Field Arm Field 1/8-1/ / /8-1/ / / /

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

Signet Pressure Transmitter

SMT-AZC INSTALLATION / OPERATION MANUAL

SE8300 Series Installation Guide 24 Vac Low Voltage

OE & OE Digital Room Sensor

QUICK START GUIDE VAV CONTROLLERS & WALL SENSORS rue Charles, Suite 100, Mirabel, QC, J7J 1X9

SP-32 & SP-32D SP-33, SP-33D SP-34, SP-34D. Description. Specifications. Single Stage Temperature Control

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

MS Application. Features. Proportional Valve Actuator General Instructions

ELECTRIC ACTUATOR 94OE IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

1100 Series Piston Type Differential Pressure Gauges

LF Series At A Glance

HUMIDITY / TEMPERATURE TRANSMITTER

Temperature Sensors. NTC Thermistors. Descriptions. RTS-Raw 10K NTC Thermistor. Specifications: Dimensions (mm):

Fincor DC Drives. Flexible & Powerful TYPICAL APPLICATIONS. Conveyor Rugged. Extruder Reliable. Conveyor Simple. Mixer Flexible

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Fincor Series 2230 MKII/2240

RDG160TU Commercial Thermostat

GE Sensing & Inspection Technologies

Continental Hydraulics Installation Manual CEM-AA-A

INTECH Micro 2300-RTD6

Installation. Part A, Section 3. This section covers the following unit configurations. Voltage 1, 2, 3. Vista Standard (V) A3EN-04-[3V-A-AAXV]-11

TSMN-90xxx Series TSMN TSMN TSMN Electronic Room Temperature Sensor General Instructions

5001TCP SPEED CONTROLLER

Combined Ventilation Controller RVWS-T-224HA

PRODUCT INFORMATION BULLETIN

INSTALLATION INSTRUCTION

LTX RF LEVEL SENSOR. Instruction Manual

Series 1000 Room Temperature Sensors, 1K Ω Platinum (375α) RTD (MBC/RBC/MEC/UC)

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Informational Distribution List:

INSTALLATION/OPERATING INSTRUCTIONS TSC

Motor Controllers AC Semiconductor Motor Controller Type RSHP Flexy

TI23 Pre-Instructional Survey

2-PHASE STEPPING MOTOR DRIVER FE Z5 DISPENSE

TEMPERATURE - HUMIDITY VAISALA HMP155

Installation. Part A, Section 3. This section covers the following unit configurations. 3400V 3500V. Voltage 4. Pump Piston (E, F, G)

Signet Pressure Transmitter

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

Table of Contents. Carrier Sensors

User Manual. T6 Tachometer. Online: Telephone: P.O. Box St. Petersburg, Florida 33736

TS , -850 Series TS , -850 Series TS-57031, TS

MF-22xx3. Application. Features. Floating Valve Actuator General Instructions

Model 124 Filter Minder & Model 124

INSTALLATION INSTRUCTION

Spyder BACnet Programmable Controllers

TRAC-3 TENSION READOUT AND CONTROL

MAGPOWR Spyder-Plus-S1 Tension Control

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

P445 Series Electronic Lube Oil Control

Transcription:

Overview and Identification The BAPI-Stat 3 is a multiple output transmitter for temperature and humidity with setpoint capability for both and occupied/unoccupied override switching. The large easy-to-read display is ideal for cross room viewing and membrane pushbuttons are designed for easy operation and cleaning. A fully featured unit can have 4 active channel outputs, override and a passive sensor output. All ranges are factory set, however each temperature and humidity sensor channel has a local offset adjust for fine tuning. The display can be locally customized to the customer s preference. Fig. 1: BAPI-Stat 3 with temperature and humidity setpoint and override. (Units without humidity setpoint will only have three buttons.) Specifications Power Supply: 10 to 35 VDC (15 to 24 VDC Recommended) for 4 to 20 ma or 0 to 5 VDC s 15 to 35 VDC (15 to 24 VDC Recommended) for 0 to 10 VDC s 12 to 28 VAC (Requires a separate pair of shielded wires) for 0 to 5 VDC s 15 to 28 VAC (Requires a separate pair of shielded wires) 0 to 10 VDC Power Consumption: 60 ma maximum DC: 4 to 20 ma or 0 to 5 VDC s 10 ma maximum DC: 0 to 10 VDC 1.44 VA maximum AC: 0 to 5 VDC s 0.2 VA maximum AC: AC: 0 to 10 VDC s: 4 active output channels plus 1 passive temp. sensor Volts 0 to 5 VDC or 0 to 10VDC, Imp. >10KΩ (CH 1, 2, 3, 4) Current 0, 4-20 ma, Imp. <500 W @ 24 VDC (CH 1, 2) Resistance E-POT, 1K, 10K, 50K or 100KΩ, 5 VDC @ 5 ma max (CH 3, 4) - Factory selected per application Contact N.O. reed switch, 250 ma @ 29 V max Temp. Sensor Passive RTD, thermistor or semi-conductor (CH 5) Sensing Elements: Temperature Humidity Active output and display 10K-2 Thermistor, Capacitive Polymer, ±2%RH Optional Passive Temperature Sensors: Thermistor: Thermal resistor Temp. Resistance, NTC Accuracy (std) ±0.36ºF, (±0.2ºC) RTD: Resistance Temperature Device Temp. Resistance, PTC PT Accuracy (std) 0.12% @Ref, or ±0.55ºF, (±0.3ºC) Semiconductor: Temp. Accuracy Solid State (AD592) 2 wire, 1uA/ºC (0.556uA/ºF) Offset correction given to 0.1ºC (0.18ºF) Mounting: 2 by 4 J-box or drywall mount - screws provided Controls: (Buttons required for technician adjustments) 0, 3 or 5 wipe down buttons (Configuration dependent) Display: Main Minor Other LCD multi-segment 3.5 digit, 0.8 tall 2.5 digit, 0.25 tall BAPI-Man, units Ambient Specifications: Temperature: 32 to 122ºF (0 to 50ºC) Humidity: 0 to 95%, non-condensing Wiring: 2 to 5 pair of 16 to 22 AWG (Configuration dependent) Material: ABS Plastic Material Rating: UL 94, V-0 1 of 6

Mounting JUNCTION BOX 1. Pull the wire through the wall and out of the junction box, leaving about six inches free. 2. Pull the wire through the hole in the base plate. 3. Secure the backplate to the box using the #6-32 x 1/2 inch mounting screws provided. 4. Terminate the unit according to the guidelines in the Termination section. 5. Attach Cover by latching it to the top of the base, rotating the cover down and snapping it into place. 6. Secure the cover by backing out the lock-down screw using a 1/16 allen wrench until it is flush with the bottom of the cover. DRYWALL MOUNTING 1. Place the base plate against the wall where you want to mount the sensor. 2. Using a pencil, mark out the two mounting holes and the area where the wires will come through the wall. 3. Drill two 3/16 holes in the center of each marked mounting hole. Insert a drywall anchor into each hole. 4. Drill one 1/2 hole in the middle of the marked wiring area. 5. Pull the wire through the wall and out the 1/2 hole, leaving about six inches free. Pull the wire through the hole in the base plate. 6. Secure the base to the drywall anchors using the #6 x 1 mounting screws provided. 7. Terminate the unit according to the guidelines in the Termination section. 8. Attach cover by latching it to the top of the base, rotating the cover down and snapping it into place. Secure the cover by backing out the lock-down screw using a 1/16 allen wrench until it is flush with the sides of the cover. Note: In any wall-mount application, the wall temperature and the temperature of the air within the wall cavity can cause erroneous readings. The mixing of room air and air from within the wall cavity can lead to condensation, erroneous readings and sensor failure. To prevent these conditions, BAPI recommends sealing the conduit leading to the junction box with fiberglass insulation. Front Panel Description Humidity Setpoint: When the left set of s or t buttons are pressed, the relative humidity setpoint will display. As the buttons are pressed again, the display will change in 1% increments with each press. The setpoint will change only within the specified range ordered. Temperature Setpoint: When the right set of s or t buttons are pressed, the temperature setpoint will display. As the buttons are pressed again, the display will change in one degree increments with each press. The setpoint will change only within the specified range ordered. Pressing and holding any setpoint button will auto increment/decrement the setpoint value The setpoint will change only within the specified range (as ordered). Override: When the button is pressed, the Occupied/Unoccupied Icon will show for a few seconds. Fig. 2: Mounting hardware is provided for both junction box and drywall installation (Junction box installation shown). To retain the Occupied/Unoccupied Icon, you must energize J6*. (*For more information on Occupied/Unoccupied Icon, see the Termination and the Display Occupancy Mode Termination sections) Fig. 3: Front View of BAPI-Stat 3 2 of 6

BAPI-Stat 3 Room Sensor Termination BAPI recommends using twisted pair of at least 22 AWG. Larger gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device s wiring in the same conduit as AC power wiring of NEC class 1, NEC class 2, NEC class 3 or with wiring used to supply highly inductive loads such as motors, contactors and relays. BAPI s tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines. BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity, and wiring connections are important to a successful installation. Not observing these recommendations may damage the product and will void the warranty. Power Supply Ground Table 1: Termination Table Terminal Name See Table 1 for terminal descriptions Power Supply Hot Supply Power Input Power Occupied/ Unoccupied Icon power (see Table 2, Fig 5 & 6) Fig. 4: BAPI-Stat Circuit Board Internal Grounding CG=Com. GND Factory setup switch Temperature Humidity Terminal Notes: (Related to table 1), [ ] = Terminal designation 1. Only one variable and output type per channel. [CH3] and [CH4] can be overridden. 2. The [GND] terminal is always the reference for [V+], [CH1] and [CH2] terminals. 3. The temperature output range is limited to between 32º to 158ºF (0º to 70ºC). 4. Humidity setpoint range is limited between 0 to 100% RH. 5. The override is available on [CH3], [CH4] and [TEMP+/TEMP-] only. 6. Voltage outputs are limited to between 0 to 10 VDC and are only referenced to [GND]. 7. Current outputs are limited to between 0 to 20 ma and are only referenced to [GND]. 8. Resistive E-POT outputs are limited to a 1K, 10K, 50K or 100KW linier POT, ±30%. 9. Resistive sensor [TEMP+/TEMP-] outputs may be any BAPI passive or solid state sensor. 10. When using a 592/334 sensor, [TEMP+] is the supply (5 to 30 VDC) [TEMP-] is the current output to the analog input @ 1µA/ºC and requires S1-4 to be set for (DF). Reversal of the power will damage the sensor. 11. The Test and Balance option (-TB) cannot be used with the 592/334 sensor. 12. If the BAPI-Stat has the external sensor option (-EXT), then it must be a 10K-2 thermistor purchased separately. The external sensor is wired to the temp + and temp - terminals. A humidity signal or passive sensor are not allowed in this configuration. Variable (See your unit label for your configuration) Temperature Setpoint Humidity Setpoint Passive RTD or Thermistor DF=Isolated Sensor Sensor GND Pwr- & Sig- -------------- Sensor Power Connection--------- Sig- Sig- * ** ^ ** *** V+ DC or AC -------------- Sensor Power Connection--------- CH1 CG X X X Sig+ ma + CH2 CG X X X Sig+ ma+ CH3 CG/DF* per order X X ^^E-POT Sig+ ^^*<100KΩ *E-POT CH4 CG/DF* per order X X ^^E-POT/^N.O. Sig+ ^^*<100KΩ *E-POT/^N.O. TEMP+ Sensor ^^^N.O ~ ~ N.O. Sensor V+ TEMP- CG/DF, S1-4** Sensor ^^^N.O. ~ ~ **N.O. Sensor ***V- * [CH3] and [CH4] are referenced to [GND] if (CG) is selected at time of order. [CH3] and [CH4] are referenced to each other if (DF) is selected at time of order. ** S1-4, Position (CG) connects [Temp-] terminal to the [GND] terminal internally. The (DF) position makes the [TEMP -] terminal floating. (See Fig.10) *** This is the current output of the solid state sensor and must be configured as S1-4 set to (DF) to allow the 592 or 334 sensor to operate. ^ The reed contact to override [CH4] can be set up for (CG) which shorts the [CH4] output to [GND] or (DF) shorting the output terminals [CH3/CH4]. ^^ The E-POT controls the output resistance setpoint and during override, the E-POT controls the resistance to <100 ohms for 3-5 seconds. ^^^ A reed dry contact across the sensor [TEMP+/-] is configured at time of order as a (-61) option. ~ The [TEMP] terminals are used for an external 10K-2 thermistor connection if the [EXT option] is selected. (wire=25 max) Override Voltage Signal (See your unit label for your configuration) Current Resistive Signal Override Contact 592/334 Solid State 3 of 6

Display Occupancy Termination Mode (Remote Control) When the override button is pushed, the override output is active for 3 to 5 seconds. Simultaneously, the outline and center of the Occupied/ Unoccupied Icon on the display will be filled in for 3 to 5 seconds and then go blank. If you need visual indication of the override on the LCD display, the controller must have a digital output connected to the sensor s threepin EXT OVR terminal block, J6. When appropriate power is connected between the EXT OVR common and either 5 VDC or 24 VDC/VAC, both the outline and center of the Occupied/ Occupied Icon Filled In Unoccupied Icon Outline BAPI-Stat 3 Room Sensor Terminal Name COMMON 5VDC 24V DC/VAC ICON ON 5VDC Unoccupied Icon will be filled in. When the external override is canceled, the Occupied/ Unoccupied Icon s outline will remain filled in to show that the external override was used. If power to the sensor is removed, the outline will be blank until the next time the external override is used. This input is optically isolated from the rest of the device s circuitry. - + ICON ON 24VDC Table 2: Override Display Termination Table ICON ON 24VAC - ~N This [COMMON] is isolated from the other [GND] terminal. See Figures 5 & 6 for more details. + ~H Controller OPEN = Controller CLOSED (Override) = Fig. 5: 5VDC Wiring Example Fig. 6: 24VDC/VAC Wiring Example EXT OVR Display Input Controller Digital EXT OVR Display Input Controller Digital 5VDC Customer Power Supply 24DC/AC Customer Power Supply Optional Communication Jack Wiring Optional Communication Jack Termination Wiring Fig. 7: C11 Jack Fig. 8: C35 Jack Table: 3 C11/22 Wiring Comm Jack Pin Wire Color 1 Not Connected 2 Black 3 Red 4 Yellow 5 White or Green 6 Not Connected Table: 4 C35 Female Jack Wiring Comm Jack Pin Wire Color Ground Black Tip White Ring Red Fig. 9: View of BAPI-Stat 3 wallplate C11 C35 Note: Male Jack shown for clarity Optional Test & Balance Switch (SW1), For Passive Sensor Ouput Only ( at Temp+ and Temp- Terminals) Optional Test and Balance Switch (SW1) ( at Temp+ and Temp- Terminals) Low: Will set the sensor value low Norm: Thermistor/RTD will operate normally High: Will set the sensor value high Sensor Type Low Temp (40 F) High Temp (105 F) Resistance Value Resistance Value 1000Ω RTD 1.02KΩ (41.20 F) 1.15KΩ (101.5 F) 3000Ω Thermistor 7.87KΩ (39.8 F) 1.5KΩ (106.8 F) 10K-2 Thermistor 30.1KΩ (34.9 F) 4.75Ω (109.1 F) 10K-3 Thermistor 26.7KΩ (35.9 F) 5.11KΩ (108.4 F) 10K-3(11K) Thermistor 7.32KΩ (43.7 F) 3.65Ω (105.2 F) 4 of 6

Optional Technician Adjustments The four DIP switches on the bottom of the board called S1 configure four different parameters (see Fig: 10). 1) Fahrenheit or Celsius temperature display F/C Switch. 2) Display Reading Offset Mode Switch for temperature and humidity appearance and output offset. 3) User Setpoint Lockout Enable SPLO Switch. 4) Passive temperature sensor differential ground or common ground configuration TEMP Switch. ADJUSTMENT PROCEDURE FOR EACH DIP SWITCH IN S1: F OR C DISPLAY SELECTION [F/C Switch] The F/C Switch allows for either F or C operation. Remove the cover from the backplate and set the switch to the desired position. DISPLAY READING OFFSET [MODE Switch] (3 to 5 button sensor required) The Display Reading Offset Mode Switch lets you adjust the reading of the BAPI- Stat display. For example if the display reads 70 but you wish it to display and Fig. 10: Configuration Switches S1 send a signal to your controller of 70.5, you will enter an adjustment of 0.5. If the display reads 40 %RH and you wish it to display and send a signal to your controller of 38% RH, you will enter -2.0. 1) Remove cover from backplate & slide the MODE switch on S1 to the OFFSET position. The screen in figure 11 will appear on the display. If you previously entered an offset, the offset you entered will show on the display. Either the F or C annunciator will be lit depending on the position of F/C Switch 2) Press the Override button on the front of the sensor to advance to the screen for the parameter you wish to change. a. TEMPERATURE OFFSET - Screen P26 (figure 11) b. HUMIDITY OFFSET - Screen P27 (figure 12) c. DISPLAY MODE - Screen P28 (figure 13) d. ACTIVE TEST & BALANCE MODE - Screen P29 (figures 14 & 15) 3) Use the Temperature Setpoint up and down arrows on the front of the sensor to select the calibration needed. a. TEMPERATURE OFFSET - Adjust the temperature ± 5 in 0.1 increments b. HUMIDITY OFFSET - Adjust the humidity ± 5% in 0.1% increments c. DISPLAY MODE - Adjust to 0 through 7 depending on the display mode you desire. 0 - Temperature in the main portion and %RH in the upper section 1 - %RH in the main portion and Temperature in the upper section 2 - The LCD toggles the locations at a ~5 second rate 3 - Temperature Only. 4 - Setpoint Display Only (SDO), Temp Setpoint in the main portion and %RH Setpoint in the upper section 5 - Setpoint Display Only (SDO), %RH Setpoint in the main portion and Temp Setpoint in the upper section 6 - Setpoint Display Only (SDO), The LCD toggles the setpoints between the locations at a ~5 second rate 7 - Setpoint Display Only (SDO), Temperature Setpoint only. (Note: Selecting options 1, 2, 5 or 6 with units without %RH will default to mode 0) d. ACTIVE TEST & BALANCE MODE - Setpoint buttons up or down toggles between LO and HI on the LCD. This mode is active only for models which use Channel 1 as a temperature output. LO will drive Channel 1 to it s lowest voltage or current output. HI will drive Channel 1 to it s highest voltage or current output. (figures 14 & 15) 4) Press the Override button on the front of the sensor to enter and store the change. Set the MODE switch on S1 back to RUN and put the cover on the backplate. SETPOINT LOCK OUT [SPLO Switch] The SPLO Switch allows the setpoint buttons to be disabled. A switch setting of ON disables the buttons. Fig. 11: Temp Offset Fig. 12: %RH Offset Fig. 13: Display Mode Fig. 14: T&B Mode Lo PASSIVE TEMPERATURE SENSOR GROUNDING [TEMP switch] Adjust DIP switch to CG for [TEMP ] connected to common ground [GND] Adjust DIP switch to DF for [TEMP ] differential floating without connection to any ground. Fig. 15: T&B Mode Hi 5 of 6

Diagnostics POSSIBLE PROBLEMS General Diagnostics POSSIBLE SOLUTIONS: - Determine that the input is set up correctly in the controller s and building automation software. - Check wiring for proper termination - Check for corrosion at either the controller or the sensor. Clean off the corrosion, re-strip the interconnecting wire and reapply the connection. In extreme cases, replace the controller, interconnecting wire and/or sensor. - Label the terminals that the interconnecting wires are connected to at the sensor end and the controller end. Disconnect the interconnecting wires from the controller and the sensor. With the interconnecting wires separated at both ends measure the resistance from wire-to-wire with a multimeter. The meter should read greater than 10 Meg-ohms, open or OL depending on the meter you have. Short the interconnecting wires together at one end. Go to the other end and measure the resistance from wire-to-wire with a multimeter. The meter should read less than 10 ohms (22 gauge or larger, 250 feet or less). If either test fails, replace the wire. Unit does not operate - Check power for proper polarity. - Disconnect the power wires at the controller. Measure controller output for proper power (see specifications), if the voltage is outside the limits troubleshoot controller. Reconnect power wires to controller when finished. If the measured voltage is above the specification limit, you may have damaged the unit, contact your BAPI representative. - Disconnect the power wires at the sensor. Measure the wires for the same voltage as at controller. If the voltage is different from that measured at the controller, then troubleshoot the wire. Reconnect power wires to sensor when finished. - Measure the power at the sensor with the power connected for proper power (see specifications). If the voltage is outside the specification limits, call your BAPI representative. 6 of 6