CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

Similar documents
C1000 Series Automatic Cap Bank

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Technical Specification For Outdoor Substation Harmonic Filter Banks

Technical Specification for Pole Mounted Capacitor Rack

Ultravar TM AUTOMATIC POWER FACTOR CORRECTION & HARMONIC SOLUTIONS

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

A. Submit manufacturer's literature and technical data before starting work.

Design Standard. Purpose: Design Standard:

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 480 Volts, 60Hz. Page 1 of 14. April 15, 2010: updated capacitor UL File number)

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SWITCHGEAR DIVISION PRODUCT PROFILES

AIR CORE REACTORS. Phoenix Electric Corporation

POWER FACTOR CORRECTION MOTOR LOAD (ML) FIXED CAPACITOR

Medium Voltage. Power Factor Correction Reactive Compensation Harmonic Filters. Electrical Power Quality Management at its best.

GE 8000-Line Motor Control Centers

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

Metal-enclosed medium voltage power factor correction system

BUSWAY Low Voltage (Pow-R-Flex)

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Publication No.: PSG

Medium Voltage Metal-Enclosed Switches

Horizontal Circuit Switchers

Horizontal Circuit Switchers

Metal-enclosed medium-voltage power factor correction system

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual

OTEC Transfer switch open transition

Indoor or Outdoor 2400 to 14,400 Volts 600 to 14,400 Kvac, 3 Phase, 60 Hz

Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

Quik-Spec Coordination Panelboard Specifications

Capacitors. Individual & fixed bank. Individual & fixed capacitor banks. Low Voltage Network Quality

Medium Voltage Capacitors

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Medium Voltage Metal-Enclosed Switches

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

Applications. Trim are flat gauge steel per code. Standard painted finish ANSI 61 gray. Directory card with plastic cover on front of trim

Medium Voltage Metal Enclosed Thyristor Switched Harmonic Filter Banks

Beaver Power Factor Correction Capacitors

SWITCHED POWER FACTOR AND *********HARMONIC CORRECTION EQUIPMENT MEDIUM VOLTAGE SECTION 16280E

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Specification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Design Standard. Capacitor Bank. Detailed specifications follow. PART 1 - GENERAL

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT

Customer Requirements Downtown Secondary Network Service

SECTION MOTOR CONTROL

Transfer switch OTEC and OTECSE open transition

SUBSTATION EQUIPMENT - Page 1 of 8

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX

SECTION MOTOR STARTERS (AMPGARD) MEDIUM VOLTAGE

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Critical Power Switchboards. Selection and Application Guide

CALTRAP INSTALLATION AND OPERATIONS MANUAL

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

Transfer switch OTEC open or delayed transition

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

WARREN COUNTY, N.Y. M/E REFERENCE

Typical Specification

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

Power System Solutions (PSS)

MEDIUM VOLTAGE METAL ENCLOSED CAPACITOR BANKS

PHASE PERFECT PHASE CONVERTERS OPERATION & INSTALLATION MANUAL PHASE TECHNOLOGIES, LLC

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

Individual & fixed bank capacitors

Low & Medium Voltage Power Factor Correction Capacitors, Harmonic Filters and Line/Load Reactors

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

43-SDMS-04 REV. 00 SPECIFICATIONS FOR

EMPAC Metal enclosed capacitor bank for wind applications

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH

Product Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher

University of Houston Master Construction Specifications Insert Project Name

A. This section includes unit capacitors for power factor correction.

REVISIONS App PC. App Sud. App Thom TC 2014/03/25

Power Break II Switchboard

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

SECTION 16426B. RELATED SECTIONS Section 16671A Transient Voltage Surge Suppression Section Microprocessor-Based Metering Equipment

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

34-SDMS-02 SPECIFICATIONS FOR

CP Automatic capacitor bank

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less.

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Transcription:

LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low voltage (600 Volt and below), capacitor banks. b. The equipment described in these specifications shall be furnished by the manufacturer and installed by others in accordance with the manufacturer s recommendations. II. GENERAL CONSTRUCTION FEATURES a. The capacitor cells, contactors, controller, and related equipment shall be mounted in the same enclosure to minimize field installation. b. Current transformers and associated wiring necessary for VAR sensing are to be supplied and installed by others. c. The capacitor cells, fuses and switching contactor in each step of the capacitor assembly shall be mounted on a removable tray for ease of removal and replacement. d. The standard enclosure shall be rated NEMA 1. This enclosure is intended for indoor use primarily to provide a degree of protection against contact with the enclosed equipment in locations where unusual service conditions do not exist. The following options shall be available: i. Optional NEMA 3R enclosure with a gasketed control door. This enclosure is intended for outdoor use primarily to provide a degree of protection against falling rain; and to be undamaged by the formation of ice on the enclosure. ii. Optional NEMA 12 enclosure to include a thermostatically controlled, 10 inch, forced air, direct drive roof ventilator capable of moving 470 cubic foot per minute of free air at 1500 RPM. Air filter elements shall be provided on all external louvers used for cooling air intake. iii. Optional door mounted, blown fuse indicating lights, 1 per phase per step. Low Voltage Auto Switched Capacitor Bank Specs Page 1 of 6

iv. Optional breaker with a door interlock. See section 9.2 for breaker specifics. e. Provision shall be made for top or bottom conduit entry into the incoming cable compartment of the enclosure. f. A door mounted, solid state, multi step, adjustable power factor controller shall be provided as part of this equipment. This controller shall automatically switch the steps in and out to provide power factor correction to a desired set point. g. Current limiting fuses shall be provided on all three phases of each step. h. A voltage transformer of suitable rating shall be provided for control power and voltage sensing. Protection shall be provided with two primary current limiting fuses. i. All internal buswork shall be bare tin plated copper, or insulated copper conductor. All buswork shall be braced for 65,000 Amperes momentary current. j. All flexible power cable shall be copper conductor, 1050C insulation, installed in accordance with the latest revision of the National Electrical Code. III. CAPACITOR CELLS a. The capacitor elements shall be Underwriters Laboratories (UL) listed. b. Each capacitor cell shall be equipped with a Pressure Sensitive Interrupter. The PSI protects the cell from rupture by interrupting capacitor current when the internal pressure forces the cover up, breaking an under cover contact. This provides visual indication of end of life. c. A discharge resistor shall be provided on each capacitor cell to discharge the residual voltage to 50 volts or less within one minute after deenergization. Low Voltage Auto Switched Capacitor Bank Specs Page 2 of 6

d. The capacitor cells shall be impregnated with a biodegradable, environmentally friendly and non-toxic dielectric fluid. e. The capacitor cells shall be suitable for continuous operation over a temperature range of -400C to +700C. f. The capacitor cells shall be of low loss design with losses not to exceed 0.5 watts per KVAR. g. The capacitor cells shall be designed to withstand the duties described in ANSI/IEEE Standard 18 and NEMA CP-1. IV. CURRENT LIMITING INDUCTORS a. A three phase, air core inductor shall be connected in series with each of the capacitor steps to minimize inrush current during switching of steps. b. The inrush limiting inductors shall be wound with 900C insulated, copper conductor cable. V. SHORT CIRCUIT PROTECTION a. A 600 V, current limiting fuse shall be provided in each phase of each step of the capacitor assembly. These fuses shall provide the necessary protection against short circuit currents. b. The interrupting rating of the current limiting fuse shall be 200,000 Amperes. c. The fuses for each step shall be mounted in a fuse block located on the same tray as the capacitor cells. VI. CONTACTORS a. The individual capacitor steps shall be switched using a contactor suitable for switching capacitive currents. b. The contactor shall use a control voltage of 120 VAC. c. The minimum life expectancy of the contactor shall be one million switching operations. Low Voltage Auto Switched Capacitor Bank Specs Page 3 of 6

d. The switching operation of the contactor shall be controlled by the power factor controller described in Section 8.0 below. VII. CONTROLLER a. A door-mounted controller shall be provided that complies with the following: i. Microprocessor based adjustable control. ii. Manual or Automatic selector switch. iii. Adjustable target power factor setting from 0.8 inductive (lagging) to 0.95 capacitive (leading) iv. Adjustable switching time delay from 10 to 60 seconds. v. Fault signaling output relay if target power factor is not reached. vi. Continuous front panel display indicating which steps are on. vii. Digital display of actual power factor. viii. No volt release of all output contacts when the supply voltage has been interrupted for 35 ms. This serves to protect the capacitors after the power has been restored. ix. Rotational switching program to assure that the steps are used equally. The first step turned on is the first step turned off. x. Operating range from 14 F (-10 C) to 131 F (55 C). As an adder, the operating range shall be extendable to -31 F (- 350C) to 158 F (70 C). VIII. INCOMING POWER CONNECTION a. If a main circuit breaker is not specified, the incoming power connection shall be to a 1200 Ampere lug capable of accommodating the following incoming cables: Four 250-500 kcmil Aluminum conductors Low Voltage Auto Switched Capacitor Bank Specs Page 4 of 6

Four 250-350 kcmil Copper conductors suitable for 500 kcmil copper, 1200 amp rating b. If a main circuit breaker is specified, it shall comply with the following: i. GE Spectra RMS current limiting design. 8.2.2 600 Volt, 65KA interrupting capacity. 8.2.3 Solid state trip mechanism, with interchangeable rating plugs. 8.2.4 Safety door interlock to trip breaker if enclosure door is opened while unit is energized. 8.2.5 The incoming power cable connections shall be appropriately sized for the breaker. IX. ENCLOSURE a. The capacitor enclosure shall be of NEMA 1 construction. b. The structure of the capacitor enclosure shall be constructed of 11 gauge steel. c. The capacitor enclosure shall be painted with ANSI 61 gray, acrylic urethane paint. d. The enclosure shall be equipped with louvered side panels to provide cooling air intake. e. The enclosure shall be front access with removable side and back panels. f. The enclosure door handle shall be provided with a key lock. g. The enclosure shall be provided with four, top mounted lifting eyes. X. WARRANTY/DISCLAIMERS a. The switched capacitor assembly shall be warranted by the manufacturer to be free from defects for a period of 18 months from factory shipment or a period of one year after the unit is energized, whichever occurs first. Low Voltage Auto Switched Capacitor Bank Specs Page 5 of 6

b. The manufacturer shall not be held liable for improper operation of the switched capacitor assembly due to harmonic resonance conditions that may result from application of the capacitor assembly to a system that contains harmonic currents and/or voltages. XI. SUBMITTALS a. After receipt of order, but before fabrication, the manufacturer shall submit up to four sets of outline drawings and one line diagrams to the purchaser for approval. b. The equipment manufacturer shall furnish one set of instruction and maintenance manuals located in a door pocket inside the equipment. Low Voltage Auto Switched Capacitor Bank Specs Page 6 of 6