Future Proof Your Arc Flash Assessment

Similar documents
Illinois State University. Electrical Safety Procedure

January 30, Ms. Safety Director Sample Medical Corp. PO Box X Somewhere, CT. Re: NFPA 70E Hazard Assessment. Date of Visit.

NFPA 70E Standard for Electrical Safety Requirements for Employee Workplaces. Table Hazard Risk Category Classification

Integrating Roles Within Electric Utilities to Achieve Arc Flash Safety. MIPSYCON Presenters Neil Stiller & Bob Cooke

BP-Husky Refinery Toledo, OH

Electrical Safety and Overcurrent Protection

Reducing. with Current. arc flash note 2. points of interest. Why Use Current Limiting Fuses. By mike lang, Principal field engineer

Design Considerations to Enhance Safety and Reliability for Service Entrance Switchboards

Application of Sepam Relays for Arc Flash Hazard Reduction at Low Voltage Switchgear

Arc flash hazard mitigation

Two Recent Case Studies in the Mining Industry

Understanding Arc Flash Hazards. White Paper

The New 2017 National Electric Safety Code Overview and Significant Changes. Presented by. Mickey Gunter October 28, 2016

OSHA Update. Electric Power Generation, Transmission and Distribution Standard (Part 1910 & 1926)

take to complete our safety compliance

NESC 2007 FLAME RESISTANT CLOTHING

New 2002 NEC. Arc Flash Hazard Marking Requirement Cooper Bussmann, Inc.

6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton

Not all Low Voltage Switchgear is created equal

3.2. Current Limiting Fuses. Contents

Electrical Safety CSA Z462 & NB Regulations

GE Arc Vault TM Protection System. By Mark Clapper GE Specification Engineer. Introduction. What Variables Contribute To An Arcing fault?

Energized Electrical Work

Outside Link Box PRODUCT CATALOG 2018 EDITION

Secondaries. arc flash note Introduction. By Mike Lang, engineer and. Services Supervisor

Not all Low Voltage Switchgear is created equal

BP OIL -- TOLEDO REFINERY

Pretest Module 29 High Voltage Unit 1

ETAP Implementation of Mersen s Medium Voltage Controllable Fuse to Mitigate Arc Flash Incident Energy

ARC FLASH MANAGEMENT REVIEW. October 2017

Mark Lyvers LLC / Cooper Bussmann Arc Flash Script Script to accompany PowerPoint on New 2002 NEC Arc Flash Hazard Marking Requirement

Ontario Operations MAINTENANCE STANDARD PROCEDURE. Table of Contents. Electrical Electrical Department Energized Electrical Work Procedure

Electrical Safe Work Practices

Safety Working with LV Drives

Unrestricted. S.Mukhopadhyay

Arc Hazard Analysis Report For Lake Worth Generation Plant

TERMS AND DEFINITIONS

Electrical Safety in Die Casting

Why arc-resistant drives need to be considered

Appalachian Power Company Policy No. 2 Cover Up Procedures. Policy Summary:

Zone Selective Interlocking

Descriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Medium Voltage Controllable Fuse

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

Texas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives

Copyright 2003 Advanced Power Technologies, Inc.

UPS Battery Maintenance Training

TECHNICAL TOPICS UNIVERSITY. General Electrical Safety BEST PRACTICES

Study of Fault Clearing by A Circuit Breaker In Presence of A Shunt Capacitor Bank

The Use of Low-Voltage Current-Limiting Fuses to Reduce Arc-Flash Energy

Agenda / ESPS Electrical Safety Program Solutions INC.

2. Panelboards shall have new or updated paper directories printed from the master Excel spreadsheet inserted in the door

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

ELECTRICAL UTILITY COST REDUCTION THROUGH PREDICTIVE CONTROL BACKGROUND

Chapter 6 Generator-Voltage System

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

Backfeed, Safety, and Work Practices

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

IEEE Guide for the Design of Low Voltage AC and DC Auxiliary Systems for Substations

Technical Specification for Pole Mounted Capacitor Rack

University of Vermont Physical Plant Department Burlington, Vermont

The safest, most reliable Switchgear in the market today

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

7. SERVICES OVER 600 VOLTS

Arc flash solutions catalogue Australia. Safety solutions - Protecting employees and the enterprise

IEEE Northern Canada & Southern Alberta Sections, PES/IAS Joint Chapter Technical Seminar Series

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

IEEE IAS Atlanta Chapter

CONSIDERATIONS FOR THE APPLICATION OF A MV HIGH SPEED GROUNDING SWITCH FOR ARC FLASH MITIGATION OF LV EQUIPMENT

ENERGIZER BATTERY MANUFACTURING ST. ALBANS, VERMONT

24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)

TABLE OF CONTENTS Page

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

Company Directive STANDARD TECHNIQUE: SD4O/1. Standard HV Connection Arrangements

Static frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids

ACHIEVING MAXIMUM BENEFITS WITH A FUSE PROTECTED MOTOR CONTROL CENTER

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

ELECTRICAL UTILITY COST REDUCTION THROUGH PREDICTIVE CONTROL December 2008 BACKGROUND

Hazards SAFETY CORNER. of Establishing an. Work Condition

ELECTRICAL PERSONAL PROTECTIVE EQUIPMENT STANDARD

4-Day Power System Analysis, Coordination, System Studies

Learning Module 6: Medium Voltage Power Circuit Breakers. 101 Basic Series

Wisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power

ESSENTIAL SAFETY RESOURCES

Louisville Gas and Electric Company

Medium Voltage Metal-Enclosed Switches

Selection Guide S&C ELECTRIC COMPANY. For Transformer-Primary Fuses in Medium- and High-Voltage

NFPA 70E Electrical Safety in the Work Place. R. Casey 2/1/05

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

Transcription:

Future Proof Your Arc Flash Assessment 2017 ENERGY CONNECTIONS CONFERENCE TRADE SHOW Presented by: Keith Mullen, P.E. November 9, 2017

Agenda > Utility requirements > Study objectives > Applicable standards & methods > Example: Impact of system configuration > Conclusions 2

Definition of Arc-Flash Electric Arc-Flashover is defined as the passage of current between two electrodes through ionized gasses and vapors 3

Utility Requirements the employer shall ensure that an assessment is performed to determine potential exposure to an electric arc for employees who work near energized parts or equipment. Source: National Electrical Safety Code (NESC) 410A 4

Utility Requirements > Prepare arc flash assessment to provide a basis for: > Operating procedures > Equipment needs > Inform employees and contractors of potential exposure Priority #1 SAFETY > Train employees on equipment and operating procedures 5

Applicable Standards & Methods > NESC 410.A.3 > NFPA 70E > OSHA 29 CFR, 1910.269 > IEEE Standard 1584 > ARCPRO 6

Applicable Methods IEEE 1584 > Voltages in the range of 208 V-15 000 V, three-phase > Frequencies of 50 Hz or 60 Hz > Bolted fault current in the range of 700 A-106 000 A > Grounding of all types and ungrounded > Equipment enclosures of commonly available sizes > Gaps between conducts of 13 mm-152 mm > Faults involving three phases Note: A theoretically derived model, based upon Lee s paper [B19], is applicable for three-phase systems in open air substations, and open air transmission and distribution systems. This model is intended for applications where faults will escalate to three-phase faults. Where this is not possible or likely, this model will give a conservative result. Where single-phase systems are encountered, this model will provide conservative results. 7

Applicable Methods ARCPRO 8

Applicable Standards NFPA 70E Arc Flash Hazard PPE Category (HC) NFPA 70E PPE Categories Calculated Arc Energy (Cal/cm 2 ) (J/cm 2 ) 1 4.0 16.7 2 8.0 33.5 3 25.0 104.6 4 40.0 167.4 >4 >40 >167.4 > 1.2 Cal/cm 2 is the threshold for a 2 nd degree burn > PPE limits injury to no more than a recoverable 2 nd degree burn 9

Applicable Standards OSHA 29 CFR 1910.269 Table 12 Selecting a Reasonable Incident-Energy Calculation Method 1 Incident-Energy Calculation Method 600 V and Less 2 601 V to 15 kv 2 More than 15 kv 1Φ 3Φa 3Φb 1Φ 3Φa 3Φb 1Φ 3Φa 3Φb NFPA 70E-2004 Annex D (Lee Equation) 3 Y-C Y N Y-C Y-C N N 4 N 4 N 4 Doughty, Neal, and Floyd Y-C Y Y N N N N N N IEEE Std. 1584a-2004 5 Y Y Y Y Y Y N N N ARCPRO Y N N Y N N Y Y 6 Y 6 Key: 1Φ: Single-phase arc in open air 3Φa: Three-phase arc in open air 3Φb: Three-phase arc in an enclosure (box) Y: Acceptable; produces a reasonable estimate of incident heat energy from this type of electric arc N: Not acceptable; does not produce a reasonable estimate of incident heat energy from this type of electric arc Y-C: Acceptable; produces a reasonable, but conservative, estimate of incident heat energy from this type of electric arc 10

Revised Standards OSHA 29 CFR 1910.269 Table 14 Selecting a Reasonable Distance from the Employee to the Arc Class of Equipment Single-Phase Arc mm (inches) Three-Phase Arc mm (inches) Cable NA* 455 (18) Low voltage MCCs and panel boards NA 455 (18) Low voltage switchgear NA 610 (24) 5 kv switchgear NA 910 (36) 15 kv switchgear NA 910 (36) Single conductors in air (up to 46 kv), work with rubber insulating gloves 380 (15) NA Single conductors in air, work with live-line tools and live-line bare hand work MAD (2 x kv x 2.54) (MAD (2 x kv /10) ) NA * NA = Not applicable The terms in this equation are: MAD = The applicable minimum approach distance kv = The system voltage in kilovolts 11

Revised Standards OSHA 29 CFR 1910.269 Table 13 Selecting a Reasonable Arc Gap Class of Equipment Single-Phase Arc mm (inches) Three-Phase Arc mm 1 (inches) Cable NA 2 13 (0.5) Low voltage MCCs and panel boards NA 25 (1.0) Low voltage switchgear NA 32 (1.25) 5 kv switchgear NA 104 (4.0) 15 kv switchgear NA 152 (6.0) Single conductors in air, 15 kv and less 51 3 (2.0) Phase conductor spacing Single conductor in air, more than 15 kv Voltage in kv times 2.54 (0.1), but no less than 51 mm (2 inches) 3 Phase conductor spacing 1Source: IEEE Std. 1584a-2004 2 NA : Not applicable 3Table 6 of Appendix E of final Subpart V uses a more conservative arc gap that equals the electrical component of the minimum approach distance rather than a value corresponding to the dielectric strength of air for the system voltage which forms the basis for the values in this table. 12

Applicable Standards OSHA 29 CFR 1910.269 Exposure Minimum Head and Face Protection None 1 Minimum Head and Face Protection 1 Arc Rated Faceshield with a Minimum Rating of 8 Cals/cm 2 Arc-Rated Hood or Faceshield with Balaclava Single-phase, open air 2 8 Cal/cm 2 9 12 Cal/cm 2 13 Cal/cm 2 or higher 2 Three-phase 2 4 Cal/cm 2 5 8 Cal/cm 2 9 Cal/cm 2 or higher 3 1. These ranges assume that employees are wearing hardhats meeting the specifications in 1910.135 or 1926.100(b)(2), as possible. 2. The arc rating must be a minimum of 4 Cal/cm 2 less than the estimated incident energy. Note that 1926.960(g)(5)(v) permits this type of head and face protection, with a minimum arc rating of 4 Cal/cm 2 less than the estimated incident energy, at any incident energy level. 3. Note that 1926.960(g)(5) permits this type of head and face protection at any incident energy level. 13

The Curve Method Relays > Prepare curves for specific incident energy levels > Compare with device responses for available fault range 14

Other Operating Scenarios 15

Study Findings Secondary Voltages (2012 NESC) NESC Table 410-1 Equipment Type Nominal Voltage Range & Cal/cm 2 50V-250V 251V 600V 601V-1000V Self-contained meters / cabinets 4 (2) 20 (4) 30 (8) Pad-mounted transformers 4 (9) 4 (9) 6 (8) CT meters and control wiring 4 (2) 4 (5) 6 (8) Metal-clad switchgear / motor control centers 8 (3) 40 (6) 6 (8) Pedestals / pull boxes / hand holes 4 (2) 8 (7) 12 (8) Open air (includes lines) 4 (2) 4 (7) 6 (8) Network protectors 4 (10) (11) (11) Panel boards single phase (all) / three phase (< 100 A) 4 (2) 8 (12) 12 (8) Panel boards three phase (> 100 A) 4 (2) (13) (13) 16

Study Findings Secondary Voltages (2012 NESC) NESC Table 410-1 Notes 1. This table was developed from fault testing based on equipment type and is independent of fault current unless otherwise noted. Calculations and test data are based on a 46 cm (18 in) separation distance from the arc to the employee. See IEEE Std 1584-2002. Other methods are available to estimate arc exposure values and may yield slightly different but equally acceptable results. The use of the table in the selection of clothing is intended to reduce the amount or degree of injury but may not prevent all burns. 2. Industry testing on this equipment by two separate major utilities and a research institute has demonstrated that voltages 50 V to 250 V will not sustain arcs for more than 2 cycles, thereby limiting exposure to less than 4 Cal/cm 2. (See 208-V Arc Flash Testing [B1].) 3. Value based on IEEE 1584 formula for Motor Control Centers. [Gap = 2.54 cm (1 in)] (Xd = 1.641) [46 cm (18 in) distance] 51 ka (Based on a 208 V, 1000 kva, 5.3% Z, served from a 500 MVA system). Maximum duration without circuit protective device operation from industry testing (see 208-V Arc Flash Testing [B1]) is 10 cycles: 46.5 Cal/s/cm 2 x 0.167 s = 7.8 Cal/cm 2. 4. Industry testing on 480 V equipment indicates exposures for self-contained meters do not exceed 20 Cal/cm 2. 5. Industry testing on 480 V equipment indicates exposures for CT meters and control wiring does not exceed 4 Cal/cm 2. 6. Value based on IEEE 1584 formula for Motor Control Centers. [Gap = 2.54 cm (1 in)] (Xd = 1.641) [46 cm (18 in) distance] 12.7 ka at 480 V (worst-case energy value from testing). (See Eblen and Short [B31].) Maximum duration without circuit protective device operation from tests is 85 cycles: 26.2 Cal/s/cm 2 x 1.42 s = 37 Cal/cm 2. 7. Incident analysis on this equipment indicates exposures do not exceed the values in the table. 8. Engineering analysis indicates that applying a 150% multiplier to the 480 V exposure values provides a conservative value for equipment and open air lines operating at 601 V to 1000 V. 9. Industry testing on 480 V equipment indicates exposures on pad-mounted transformers do not exceed 4 Cal/cm 2. (See Eblen and Short [B31].) 10. Industry testing on 208 V network protectors indicates exposures do not exceed 4 Cal/cm 2. (See 208-V Arc Flash Testing [B1].) 11. Industry testing on 480 V network protectors indicates arcs will not self-extinguish and heat flux rates will exceed 60 Cal/cm 2 /s at 24 in working distance. Perform arc hazard analysis. (See Eblen and Short [B31].) 12. Industry testing on 480 V panels with non-edge mounted bus bars indicates exposures do not exceed 8 Cal/cm 2. (See Eblen and Short [B31].) 13. Industry testing on panelboards with edge-mounted, parallel bus bars indicate arcs will not self-extinguish and heat flux rates will exceed 60 Cal/cm 2 /s at 46 cm (18 in) working distance. Perform arc hazard analysis. (See Eblen and Short [B31].) 14. IEEE 1584 original test data indicates there is no significant difference between heat flux rates for 400 V class equipment verses 600 V class equipment. 17

Sample Model System Normal Minimum 3ph fault on Feeder A: 3,200 A 18

Arc Flash Results for System Normal > Max Incident Energy: 7.36 Cal/cm 2 19

Sample Model Contingency Minimum 3ph fault 1,500 A 20

Arc Flash Results for Contingency > Max Incident Energy: 14.95 Cal/cm 2 21

Field Condition Alerts Standard Standard w/ Faceshield Standard Standard w/ Faceshield Standard Standard 22

Conclusions > Utility compliance can be maintained by incorporating arc flash assessments into: > System planning and standards > Equipment purchasing > Operations and procedures > The Arc Flash Assessment needs to be a living document > Establish process to manage critical information > Adopt methods to share requirements with field staff and contractors > Stay current on industry regulations and standards 23

Thank you! Keith Mullen MANAGING DIRECTOR, SYSTEM PLANNING 131 Saundersville Road Suite 300 Hendersonville, TN 37075 Office: 615.431.3212 Mobile: 615.878.6139 paul.k.mullen@leidos.com Visit us at energy.leidos.com 24