Ignition energy enough for igniting the mixture is available, such as sparkles generated by friction and impaction, electric arc or hot surfaces.

Similar documents
Forecourt safety Competent persons

Petroleum industries are dealing with different hazardous materials starting from storing, processing and distributing the petroleum products These he

by Jim Phillips, P. E.

Sources of Ignition and Hazardous Area Classification Core

Hazardous areas, as found around a service station, are classified into three zones as follow: Table 1: Zone Classification for Vapours

EMISSION CONTROL (AUX. EMISSION CONTROL DEVICES) H4DOTC

RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF SHIPS IDENTIFIED BY THEIR MISSIONS CHAPTERS APPROACH

Flow Computer Installation

Fixed or Semi-Fixed Foam Fire Protection Systems for Storage Tanks

EMISSION CONTROL (AUX. EMISSION CONTROL DEVICES) H6DO

EMISSION CONTROL (AUX. EMISSION CONTROL DEVICES) H4SO

Chevrolet Equinox Fuel Cell. Emergency Response Guide

IMMERSION FIRED HOT WATER BOILER

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-10 RX-21 RX-25

Describe Flame Arrestor Operation and Maintenance Human Development Consultants Ltd.

AIRMIX PUMP and LOW-PRESSURE PUMP air motor with reversing block

SPECIFY THE RIGHT HOT OIL PUMP FOR YOUR APPLICATION

Installation, Operation and Maintenance Manual for Flame Check

BCV30 DN20 - Blowdown Control Valve Installation and Maintenance Instructions

Supplementary instructions. Mounting accessories, pressure measurement technology. Document ID: 43478

Vent/Fan Silencers UNIVERSAL. Vent/Fan Silencers ENERGY ENVIRONMENTAL

UNIT IV INTERNAL COMBUSTION ENGINES

Retrofitting of Mitsubishi Low NOx System

CONTENTS. Foreword...iii. 1. Introduction...1

Technical Information

ITVX Series. Stepless control of air pressure proportional to an electrical signal. Supply pressure: 5.0 MPa

ARGONITE Fire Protection Systems

Gauges, Sight Glasses and Vacuum Breakers

Air Trap TATSU2. Copyright 2013 by TLV CO., LTD. All rights reserved ISO 9001/ ISO M-02 (TATSU2) 7 August 2013.

ECTOS Deliverable 4. European Commission. Fifth Framework For Research And Development

PUBLIC WORKS AND SERVICES PETROLEUM PRODUCTS DIVISION STANDARD DETAILED DRAWINGS FOR NORTHERN FUEL STORAGE AND DISTRIBUTION FACILITIES

Separators. industrieblick Fotolia.com. For indoor or below ground installation ACO Light Oil Separators Coalisator-P

Model DDX Deluge Valve 8 (200mm) Features

Metrovick F2/4 Beryl. Turbo-Union RB199

Single Stage Rotary Vane Vacuum Pump Installation and Operation Manual RX-40 RX-63 RX-100

Code Requirements for ASTs at Motor Vehicle-Dispensing Stations

RULE 448 GASOLINE TRANSFER INTO STATIONARY STORAGE CONTAINERS Adopted (Amended , , , , , ) INDEX

Vacuum pump system type

Chapter 2. The Vehicle-Tank Metering System

State of New Jersey. Department of Environmental Protection Air Quality Permitting. General Permit (GP-004A) For FUEL DISPENSING FACILITIES

This document is a preview generated by EVS

Learning Equipment for the Flammability Limits of Liquefied Petroleum Gas

OWS OPERATIONS & MAINTENANCE

Features 1. Differential Latch-type, lightweight, dependable

INFORMATION FOR FIRE SERVICES ON LPG / AUTOGAS VEHICLES

Underground Tank Applications Installation Guide

Installation & Operation Manual

Pumps and pumping units SL i & Micro C


Voltmaster Centrifugal Trash Pumps

Installation manual. Exhaust system. Marine engines DI09, DI13, DI16. 02:04 Issue 9.0 en-gb. Scania CV AB 2017, Sweden

CHAPTER 20: Operation and maintenance

Operating and Installation Instructions Diaphragm Vacuum Pumps and Compressors

AQUATOR Commercial Oil Water Separator Operating, Installation & Maintenance Manual

System Electropneumatic Converters (Proportional Valves) Electronic Process Controllers Signal Converters

A basic layout diagram of a papermaking machine is shown below :

Model DDX Deluge Valves 4" (100 mm), 6" (150 mm) and 165 mm Sizes

I.C Engine Topic: Fuel supply systems Part-1

3. Fuel System FUEL SYSTEM FUEL INJECTION (FUEL SYSTEM) A: GENERAL. FU(STi)-7

Product Manual. EX40, Version Last Updated: 11/7/16. Product Description:

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

627 Series Pressure Reducing Regulators

Storage and Dispensing Locations

Installation, Operation and Maintenance Manual Stancor SSD & SL Series Pumps

LIQUEFIED GAS PUMP INSTALLATION

LACT MEASUREMENT. Total Head = Or PSI = S.G. 2.31

DR Series Reactive Discharge Dampeners For Drilling

State of New Jersey. Department of Environmental Protection Air Quality Permitting

Chapter 6. Supercharging

Requirements and rationale for the acceptance of petrol filling stations located under residential, hotels or commercial property

VB VALVES & AUTOMATION

Flammability of Bakken Crude Oil: Dangerous. Rail Cargo Even When Empty. (by Dr. Gerard Macri, Expert Witness)

Numerical simulation of detonation inception in Hydrogen / air mixtures

Introduction to Circuit Breaker. Working Principle of Circuit Breaker

Applied Fluid Mechanics

Unit D: Agricultural Equipment Systems. Lesson 1: Understanding Applications of Fluids and Lubricants in Agricultural Equipment

APPLICATION for BUSINESS LICENSE Licensing & Permits City of Williston PO Box 1306, Williston, ND

THE KEY RELATIONSHIPS BETWEEN FIRE CODES, NEW YORK AST REGULATIONS AND SPCC PLANS

AUTOGAS 150 SERIES PUMPS INSTALLATION GUIDELINES FOR UNDERGROUND TANK APPLICATIONS

PROMAG SR SERIES SEAL-LESS CENTRIFUGAL PUMPS

The Discussion of this exercise covers the following points:

PUMP TYPE SERIES SLM AVP ACCORDING TO API 685

Proposal for amendments to UN Regulation No. 110 CNG/LNG vehicles

To ensure proper installation, digital pictures with contact information to before startup.

TECHNICAL DESCRIPTION Rescue Rod s AIR DISPLACEMENT UNIT MODEL MEGAVAC LOADER 8000 EVO Wet & dry vacuum

Compressed Natural Gas fuelling stations

M-3025CB-AV Fuel Pump

This document is a preview generated by EVS

Float Dynamic Steam Trap J10

DESIGN, OPERATION & MAINTENANCE OF L.A.C.T. UNITS

5. FUEL SYSTEM 5-0 FUEL SYSTEM UXV 500

XID ENHANCEMENT SYSTEM IMPROVED EFFICIENCY AND PERFORMANCE

Table Summary of Sprinkler System Inspection, Testing, and Maintenance. Reference. Inspection , ,

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

FUNDAMENTALS OF ORIFICE METERING Ken Embry FMC Measurement Solutions

IA HYSAFE & JRC IET WORKSHOP Research Priorities and Knowledge Gaps in Hydrogen Safety. Hydrogen Ignition and Light up Probabilities.

The use of batteries in hazardous areas. 1. Type of batteries and technical evolution. March 2018

Everest. Leaders in Vacuum Booster Technology

Comhairle Chontae Chill Mhantain Wicklow County Council Fire Service.

Separation Seal Upgrade to overcome Repetitive Failures

Transcription:

Elementary knowledge of safety and explosion protection 1.1 Characteristics of explosion A phenomenon, in which substances are converted from one state into another and massive energy and sounds are instantaneously released, is referred to as explosion. Internal characteristics of explosion: When a substance explodes, the massive generated gases and energy are suddenly released and sharply converted within a finite volume, and they are built up within the finite volume within a very short period of time, to lead to high pressure and high temperature. External characteristics of explosion: Under the action of pressure effects, the exploded medium impacts the peripheral objects with sharp and abrupt pressure, or leads to mechanical destructive effects. Acoustic susceptance effects may be generated by peripheral objects and media due to vibration. 1.2 Explosion conditions Explosion may take place only when the following 3 conditions are available: Steam or haze of flammable gas or inflammable liquid exists; Oxygen (air) The above-mentioned gases are mixed with air or oxygen in definite proportions, and form an explosive gas mixture with a concentration falling within the explosion limit. Ignition sources Ignition energy enough for igniting the mixture is available, such as sparkles generated by friction and impaction, electric arc or hot surfaces. Table 28: Explosion limits of some flammable gases and oil products Inflammab le gas Explosion concentration limit/% Explosion concentration Name of oil (volume) limit/% (volume) product Lower limit Upper limit Lower limit Upper limit Methane 4.9 15 Solvent oil 1.4 6.0 Ethane 3.22 12.45 Aviation kerosene 1.4 7.5 Propane 2.1 9.5 Kerosene 0.8 6.5 Butane 1.5 8.5 Natural gas Automobile gasoline 1.0 8.0 1.1 16 Kerosene 0.6 6.5

1.3 Explosion protection measures The coexisting of three essential conditions preventing the chemical explosion of flammable substances is the elementary theory of explosion protection and the essence of all technical measures taken to prevent chemical explosion of flammable substances. The bottom-most thinking is to replace the flammable substance or oxygen with non flammable substances, or reduce their quantity in so far as possible such that they cannot form explosive mixture. The hazard area shall be additionally ventilated by setting up blowers or applying some architectural changes. Measures: Reduce the concentration of explosive substances by additional ventilation Use casings full of inert substances Take detection measures such that an alarm may be given in time once the specified range is exceeded, and the system may be cut off. As per the grades of explosion hazard areas and grades and grouping of explosion gas mixture, adopt electrical equipment of corresponding types, or adopt electrical equipment the corresponding items of which are higher than those mentioned above. 1.4 Division of explosion hazard areas Division of gas-explosion hazard areas Grade-0 area (abbreviated as "area 0"): It refers to an environment where explosive gas mixture may occur continuously or chronically, or occur frequently for a spell under normal condition. Grade-1 area (abbreviated as "area 1"): It refers to an environment where explosive gas mixture may occur periodically or occasionally under normal condition Grade-2 area (abbreviated as "area 2"): It refers to an environment where explosive gas mixture may not occur under normal condition, or only occur for a spell.

1.5 Explosionproof electrical equipement Types of explosion protection Isolation type (Ex d): An explosion isolation casing is adopted to envelope the components, and the casing may withstand the internal explosion pressure and prevent the flames from spreading outward. Increased safety type (Ex e): No electric arcs, sparkles or high temperature, which may ignite the explosive mixture, occur under normal operating conditions, and some suitable structural measures may be taken so as to improve its safety. Intrinsic safe type (Ex i): No sparkles or heating effects generated in normal operation or faulty state under standard experiment conditions may ignite the explosive mixture (Ex i). Pressurized type (Ex p): A casing, which may maintain the pressure of non-explosion gas inside electrical equipment at a level higher than that of the peripheral explosive gas, is adopted so as to prevent the external explosion gas from entering into the casing. Oil immersed type (Ex o): It indicates that all or some live parts are immersed in oil such that it cannot ignite the explosive mixture above the oil level or around the casing. Sand filled type (Ex q): The casing is filled with non-inflammable particulate material, such that the electric arcs and sparkles generated inside the casing, and the superheating temperature of casing walls or surfaces of particulate material cannot ignite the explosive mixture around the casing.

Warning type Increased safety type Intrinsic safe type Positive pressure type Sand-filled type Oil-filled type Fig. 9.5 Simplified diagram of the types of explosion protection 1.6 Basic principle of division of hazard areas of gas station Basic principles of classification of hazard areas The grades of explosion hazard areas shall be defined as per the current national standard GB50058 Design specifications for electrical installations in environment with explosion and fire hazards. The division of hazardous areas shall be performed as per the principle of "Distinguish the hazard sources, conduct detailed global analysis, and perform division rationally", such that the locations with hidden explosion hazards or potential hazards may be authentically rated as hazardous area, and the locations whose hazard level may be reduced by measures may be rated as low-level hazard areas or safety areas. Since gasoline is a type of inflammable liquid, and its vapor may be mixed with air and the mixture may easily develop into explosive gas mixture that falls within type-ii explosive mixture; therefore, the filling stations shall be rated as environmental explosive-gas hazard areas. As per GB50058-92, the explosive-gas environment of gas stations shall be zoned in accordance with the occurrence frequency and duration time of explosive gas mixture. Area 0: It refers to a type of environment where explosive gas mixture occurs continuously or chronically. For example, inside the fixed-type storage tanks that are presently adopted by most of the gas stations, the space not filled up with inert gas above the inside-tank liquid surface may be rated as area 0;

Area 1: It refers to a type of environment where explosive gas mixture occur possibly during normal operation, such as the locations where flammable substances may possibly leak due to product drawing-off or cap opening/closing when necessary during normal operation, for instance a space (of 1.5m in radius) around the exhaust outlet of a tank centering round the vent; Area 2: It refers to an environment where explosive gas mixture may impossibly occur under normal condition, or only occur for a spell, such as the locations where flammable substances may possibly leak due to erosion and aging etc. Principle of releaase source grading and division of ventilation types: The release sources shall be divided into 3 grades as per the release frequency, duration time and quantities of inflammable substances, namely, the continuous release sources, grade-1 release sources and grade-2 release sources. Continuous release source: It refers to the release sources that are estimated to have chronicle release or short-time frequent release, including the space between inflammable liquid surface and tank deck inside a fixed-roof storage tank. The surface of inflammable liquid directly exposed to the atmosphere of oil-water separator, and the open vent holes and other ports that frequently or chronically release inflammable liquid into the atmosphere. Grade-1 release sources: It refers to the release sources estimated to conduct occasional release during normal operation (the sealed positions of pumps, compressors and valves that may release inflammable substances during normal operation, drainage systems that are installed on vessels containing inflammable fluid and may release inflammable substances to the atmosphere, and sampling points that may release inflammable substance to the atmosphere during normal operation). Grade-2 release sources: It refers to the release sources that may not conduct release under normal operation, or only conduct occasional short-time release (sealing positions of pumps, compressors and valves that may not release inflammable substances during normal operation), flanges, junction pieces and conduit joints that may not emit released substances during normal operation, relief valves, vent holes and other orifices that may not release substances into the atmosphere during normal operation, and sampling points that may not release inflammable substances to the atmosphere during normal operation.

There may be release sources provided with the characteristics of two (2) or three (3) of the three (3) grades i.e. continuous release source, grade-1 release source and grade-2 release source at some sites, and they may be referred to as multistage release sources. The root factors for determining the types of hazard areas are exactly to distinguish the release sources and determine the grades of release sources. The division of hazard areas of explosive gas environment shall be determined as per the grades of release sources and the draft conditions, and shall conform to the following provisions: Firstly, divide the areas as per the levels of release sources: The areas where continuous release source exists may be rated as area 0; The areas where grade-1 release source exists may be rated as area 1; The areas where grade-2 release source exists may be rated as area 2. Secondly, adjust the area division as per draft conditions: (1) When the site is well-ventilated, the grade of explosive hazard area shall be lowered. When the site is poorly ventilated, the grade of explosive hazard area shall be raised. (2) When local mechanical ventilation is more effective on reducing the concentration of explosive gas mixture than natural ventilation and general mechanical ventilation, local ventilation may be adopted to lower the grades of explosion hazard areas. (3) For the obstacles, potholes and corner pockets, the grades of explosion hazard area shall be locally raised. (4) Obstacles such as dyke or wall may be used to restrict the diffusion of explosive gas mixture heavier than air to reduce the range of explosion hazard areas. Possible release sources of gas stations The places or locations where substances capable of forming explosive mixture may be released are referred to as release sources. Before analysis is conducted, we shall learn about the overall layout of a gas station. In other words, the layout chart of gas station building, facilities and

peripheral facilities shall be surveyed and mapped first. Presently, most gas stations are composed of underground horizontal storage tanks, gasoline filling islands (fuel dispensers), oil unloading yard and station building (power distribution room, office rooms etc.). The fueling system is composed of fuel tanks, fuel dispensers and fuel pipelines. Therefore, mainly three facilities of a gas station may give rise to release sources, namely filling tank (including oil filling opening), fuel dispensers and fuel pipelines (including gate valves etc.). (1) Possible release sources of filling tank Presently, most gas stations are equipped with underground horizontal fixed-type storage tanks the possible release sources of which include: manhole seal, exhaust outlet (guided to atmosphere at a height higher than 4m), oil inlet (led to oil unloading yard through steel pipe) and oil outlet (led to delivery port of fuel dispenser through steel pipe). Relative specific gravity of fuel vapor and air is greater than 2.5, and the fuel vapor may easily be built up on the ground and may be diffused from relatively a low place to quite distant places. Therefore, the division of hazard areas of inflammable substance (heavier than air) storage tanks and buried gasoline storage tanks shall conform to the following provisions. 1 The space above in-tank oil surface may be rated as area 0. 2 3 4 5 6 For the inner space of manhole (valve) pit, the spherical space of 1.5m (0.75m) in radius centered on the breather pipe orifice and the spherical space of 0.5m in radius centered on the sealed oil unloading port shall be rated as area 1. The cylindrical space 1m above the ground surface and less than 1.5m away from the external rim of the manhole (valve) pit, the spherical space of 3m (2m) in radius centered on the breather pipe orifice, and the spherical space (extending to the ground surface) of 1.5m in radius centered on the sealed oil unloading port shall be rated as area 2. (Note: For the explosion hazard areas of breather pipe of gasoline tank equipped with oil-unloading vapor recovery system, the bracketed figures shall be adopted) If the periphery of storage tanks is provided with a border dike, the range ranging from outer wall of storage tanks to the border dike and with a height equal to the dike top height shall be rated as area 2. Oil unloading yard: The space of 1.5m in radius centered on the oil filling opening of fuel tank (oil unloading port of tank truck) shall be rated as area 1.

Sealed discharge port oil Zone 0 Zone 2 Zone 1 Fig. 9.6.1 Division of explosion hazard zones of underground horizontal tank Fig. 9.6.2 Division of explosion hazard zones of fuel dispenser

(2) Possible release sources of fuel dispensers Fuel may possibly leak from a fuel dispenser either under normal operating conditions (including fueling waiting state) or in fault status. Major positions where leakage may possibly occur and the causes are listed below: 1 During normal operation As shown by the operating principle of a fuel dispenser, the oil-gas separator may implement continuous venting and release fuel vapor when the dispenser works in its fueling state. The liquid oil accumulated to a definite amount inside the oil-gas separator may return to the low-pressure chamber when the oil drain valve float inside the normal-pressure chamber floats up. However, liquid oil inside the normal-pressure chamber may be subjected to outward venting due to spontaneous evaporation exactly during that period of time. When the dispenser is conducting fueling, oil-gas may be released from the oil-supply head due to nozzle fueling; when fueling is over, residual fuel inside the nozzle may be subjected to spontaneous evaporation, and the residual fuel inside the hose may leak through the nozzle mouth. 2 Fault status The joint packing of oil suction pipe and lower flange is untight; the sealing elements of pump or oil-gas separator are aged; bearing sleeves of oil pumps or flow meters are worn, or reinforced seal is worn; built-in fuel transfer line is broken due to erosion or vibration; oil-gas separator is faulty and oil flows out of vent-pipe; oil leaks from the commissure of the mechanical parts; and oil leakage occurs because the nozzle cannot be self-sealed. As per the above analysis, the interior release sources of a fuel dispenser are determined as follows: Continuous-grade release source: nil Grade-1 release sources: exhaust outlet of oil-gas separator and oil filling opening of nozzle, which are chronically opened in fueling state; Grade-2 release sources: the sealed positions, commissures and pipeline adapting/connecting positions of fuel dispenser pump, oil-gas separator, flow meter, solenoid valve, sight glass and bellows oil inlet, which are estimated not to release fuel in non-fueling state.

Therefore, the division of explosion hazard areas of gasoline dispensers shall conform to the following provisions: 1 The space inside fuel dispenser case may be rated as area 1. 2 The truncated cone space, which takes the fuel-dispenser center line as center line, takes the ground area of 4.5m (3m) in radius as bottom surface, and takes the plane 0.15m above the top of fuel dispenser and of 3m (1.5m) in radius as top surface, may be rated as area 2. (Note: For the explosion hazard areas of fuel dispenser equipped with fueling vapor recovery system, the bracketed figures shall be adopted) (3) Possible release sources of fuel delivery pipeline When any pipelines, components or mouthpieces of the whole hydraulic system (from tank oil taking to oil receiving vessel) of a fuel dispenser are leaking, malfunctioned or even are broken, there bound to be discharged fuel that may be then vaporized, and they may be rated as grade-2 release sources. Therefore, the cylindrical space of 1.5m in radius and taking the pipeline axial as its axial may be rated as area 2. Division of hazardous areas of gas station To sum up, for division of hazardous areas of a gas station, the layout charts, elevation views and the relative positions shall be surveyed and mapped as per the positions of the tanks (including the oil unloading yard), fuel dispensers, fuel pipeline (including the gate valves), station building and switching house (including the diesel engine room), and then the layout charts and elevation views of areas 1 and 2 shall be plotted as per the positions of release sources described above. It is worth notice that the pits and trenches beneath the floor of explosion hazard areas of gasoline facilities shall be rated as area 1. Finally, explosion-proof electrical equipment applicable to the hazard areas shall be selected.