DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES

Similar documents
DIGITAL EARTH LEAKAGE RELAY

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Components for EEx e Panels

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B. Station Automation & Protection. ABB Substation Automation Products

Metering Products. Metering Products Protection Units April 1, Price List. Price List. With effect from April 1,

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

TECHNICAL SPECIFICATIONS OF PCC PANEL

Metering Products Protection Units Current Transformers. April 1, 2015

KD LV Motor Protection Relay

Inverse-Time Overcurrent & E/F Relays. Type ICM 21, ICM 21B

Electromagnetic Industries LLP

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Functions provided by measuring relays in railway equipment

Miniature Circuit Breaker

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD)

Trip Circuit and Trip coil supervision Relay

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

Guide for Primary Injection Testing WL Circuit Breakers. Document No. : 11-C

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT

GA PLUS Ordering Information. Earth Leakage Motor Protection Relay Kits

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

LA Motor Protection. A South African Company to be Proud of

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

PRODUCT / TEST MANUAL 2C58K2 INSTANTANEOUS OVERCURRENT

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

PRODUCT/TEST MANUAL 2C58K37 INSTANTANEOUS OVERCURRENT RELAY

AA4006 Speed Sensitive Trip Unit. User Manual

M440 MOTOR PROTECTION, EARTH FAULT LOCKOUT & MANAGEMENT RELAY VERSION 3.5 NINGI SERVICES (PTY) LTD

Starting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F

Series Motor Protection

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

REVISED ATM72 Auto Transfer Module

GP/GPA GROUND FAULT PROTECTION

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

Unified requirements for systems with voltages above 1 kv up to 15 kv

Protection and control VIP30, VIP35. Relays technical manual

ELD Earth Leakage Protection Relay

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

M Series 140.D Data Sheet. Two-Point Controller with Moving-Iron or Moving-Coil Movement 90 Dial RW 96 RP 96

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

Breaker failure relay REB 010

Electropneumatic Timing Relays Series 7000 Industrial

MAGNETIC MOTOR STARTERS

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories

Grounding Of Standby & Emergency Power Systems

onlinecomponents.com Compact Coded Magnetic Safety Interlock Switch and Control Unit

WORKSHOP SPECIFICATIONS

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

320 to 327 M Series Low and Medium Voltage Motor Protection Relays

Contents. We build a better future! MCC HCB

MODEL RMS INSTALLATION INSTRUCTIONS. CONTENTS Page A. Introduction 1. Usage 2 2. How it operates 2

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

DPX moulded case circuit breakers

mgard-10 microprocessor-based relay

Bulletin 825 SMM Smart Motor Manager

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

White Paper. Ground Fault Application Guide. WL Low Voltage Power Circuit Breakers

ASYN205B Central Synchronizing Controller

SafeGear TM Motor Control Center Arc resistant metal-clad construction

SDM72 Start on Demand Modules

HIGH POWER RECTIFIER SYSTEMS

Jaeshininformation Co., of Korea Distributor

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

Pretest Module 29 High Voltage Unit 1

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

AIR CORE REACTORS. Phoenix Electric Corporation

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

EST Electrical Service Technician Answer Schedule

INTERPLANT STANDARD - STEEL INDUSTRY

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:

Electric Actuated Ball Valves 3-Piece Stainless Steel, Full Port 1/4 to 3 inch NPT

MX431 Generator Automatic Voltage Regulator Operation Manual

DESIGN CONSIDERATIONS FOR APPLICATION OF SHUNT CAPACITORS IN HEAVY HATER PLANT (TUTICORIN)

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

22AF 40AF AF 150AF 225AF 400AF 800AF

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

PORTABLE CURRENT SOURCE FOR CIRCUIT BREAKER AND MOTOR OVERLOAD TESTING INSTRUCTION MANUAL PI-250B. Release 1.0 April 5, 2013

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

Bolted contact switches. Pringle switches

Range 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000

Renewable Energy Systems 14

WEST BENGAL STATE ELECTRICITY DIST. COM. LTD. ( A

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

DPX Electronic + earth leakage

4.0 OPERATION Type ITH-T Relay

GENERATOR & SINGLE-FUNCTION PROTECTION

Model HEA Multicontact Auxiliary

7000 series. Industrial Electropneumatic Timing Relay AGASTAT. Design Features. On-delay model 7012 (delay on pickup) Design & Construction

Transcription:

PROK DEVICES PRIVATE LIMITED B-80, 2 nd & 3 rd Floor, KSSIDC Industrial estate, 4 th Main Road, 6 th Block, Rajaji Nagar, Bengaluru -560010 Ph no: 080-41480777, 080-41157700, Email:,, www.prokdvs.in DIP SWITCH BASED EARTH LEAKAGE RELAY (ELR) WITH CORE BALANCE CURRENT TRANSFORMER (CBCT / ZCT) EL SERIES IEEE Device Code-64 Introduction: Earth Leakage Current give rise to generation of heat and result in progressive failure of insulation, which leads to earth faults sparking flashovers, deterioration of earthing and finally results into catastrophic fires which destroys costly equipments, gadgets and precious lives. It is therefore essential to detect earth leakage current well before they cross the threshold limits and isolate the circuit in the event of leakages. Conventional over current and short circuit protection device are not designed detect earth leakage currents. Prok dv s make Earth Leakage Relay (ELR) with Core Balance Current Transformer ( CBCT / ZCT) are used to detect the leakage current in an Electrical Power System. Earth Leakage Relay (ELR) transmits a signal to activate the trip coil of the MCCB/ACB/OCB CONTACTOR in the event of Earth leakage, resulting in automatic isolation of the electrical power system. Earth leakage relay (ELR) and core balance current transformer (CBCT / ZCT) have been widely used and accepted because these have field adaptability and are economic. Features Consistent reliability with accuracy. Fixed or variable current sensitivity by Dip Switch selection LED s for visual indication of fault. High Barrier connector at rear for easy termination and safety standards. Tamper proof polycarbonate cover in the front. Test & Reset Facility for testing healthiness of the relay Applications Frame Leakage protection for L.T. Control Panels and switch boards. Earth Leakage protection for Feeders / Motors / Generators / Transformers / Mobile Operating Equipments. Protection for hazardous sensitive environments like Oil Refineries/ Cement Plant/Steel Plant /Chemical Platforms/Pulp industries and General Electrical Distribution. Protection for Mining & Control Engineering 1

Specifications Input auxiliary voltage: 110V/230V/415V/ 550V AC 50H or 60HZ 48V/110V/220V VDC Current Sensitivity range: Variable:30-300mA, 50-2000mA, 300-3000mA 1-4 Amps, 1-8 Amps, 1-10 A,12A. Fixed: 30mA, 100mA, 300mA, 500mA, also user specified ranges(sensitivity) Tripping time: Variable: 0.15 3 sec Fixed: 100 millisec, 500 millisec, 1 sec & 3 sec Core balance: current transformer type: Tape wound or Resin cast CBCT / ZCT: Standard size I.D. Circular: 40mm, 65mm, 100mm, 150mm, 200mm 250mm, and 300mm Rectangular: User specified Relay contacts: One pair of potential free NO & NC contacts or Two change over Potential free NO & NC Contacts Contact Rating: 8 Amps/ 250V AC/ 8 Amps, 30 V DC Mounting Type: Flush / Din Dimensions (in mm): Flush: 96mm x 96mmx70mm Panel Cutout size: 90x90+ 2 mm Din: 75x95x75 mm (LxHxD) (fixing on 35mm din channel) Note: 30-300 ma, 50-2000mA & 30-3000 ma, ELR is available upto 150 mm I.D. CBCT / ZCT only Principle of Operation Earth Leakage Relay(ELR) employs a Core Balance Current Transformer (CBCT / ZCT) to sense the leakage current. The CBCT / ZCT mounted externally and load current carrying cable is passed through the CBCT / ZCT. Ideally in a leakage free system the incoming and outgoing currents are equal and opposite in direction, which means that the vector sum of three phase currents is zero and can be expressed as: Ir + Iy + Ib= 0 for 3 phase 3 wire system. Ir + Iy + Ib + In =0 for 3 phase, 4 wire system. For the above condition the CBCT / ZCT produces zero resultant magnetic flux keeping the system healthy. In case of the Earth Leakage due to insulation failure of direct line to ground fault, the vector sum of currents is not zero and therefore generates resultant magnetic flux in the CBCT / ZCT, and signal is fed to the electronic circuit of Earth Leakage Relay (ELR). This signal is compared with internal reference determined by the selected position of the leakage current scale in the front fascia of the relay. This energizes the output when the signal crosses the preset level. The potential free contacts of the relay is connected to the Shunt Trip/ No volt coil of the main trip device like MCCB/OCB/ACB/CONTACTOR etc., Under fault condition the output relay gets activated by cutting off or tripping against Earth Leakage /Faults. It is worthwhile to emphasize that the unequal/ unbalanced loading on the phases does not effect the 2

vector sum and as such there is no difficulty in the use of Earth Leakage Relay (ELR) with Core Balance Current Transformer (CBCT / ZCT) on electrical distribution systems with unbalanced loading. INSTALLATION PROCEDURE FOR EARTH LEAKAGE RELAY WITH CBCT 1. Check the sensitivity of Earth Leakage Relay and also the inner diameter of core balance current transformer. 2. The Serial No. of the ELR and CBCT should match for better performance (the performance shall be guaranteed if the serial no. of the ELR and CBCT are matched). 3. Check the Auxiliary Supply of ELR and proper Voltage i.e. the rated Auxiliary Voltage. 4. The ELR have one pair of potential free change over contact for tripping purpose. Use rated current and rated voltage (refer the specification of our product). One pair of change over contact i.e., N/O Contact and N/C Contact can be used depending upon the tripping management. 5. The ELR can be flush mounting or Din mounting type and CBCT can be tape wound or resin cast type. 6. The CBCT can be mounted at the incoming or outgoing side of the breaker. 7. The ELR has low burden on CBCT. 8. The ELR is fitted in/outside the Panel depending on the type of mounting. The Auxiliary rated voltage is brought to the relay from the incoming supply source. The CBCT outputs are wired up to relay. The tripping arrangement like Shunt trip / Under Voltage Coil can be chosen and accordingly the wiring can be done using potential free contact 9. The connections scheme as per the following : A. For ELR the Auxiliary supply should be given from incoming i.e. from mains side only. The reason being the relay should indicate that the systems is healthy or fault. B. The CBCT can be mounted at the incoming cable entry or at the 3

incoming of tripping mechanism. Alternatively the CBCT can be mounted at the outgoing side or at Bus Bar side. Care should be taken at the cable entry that the cable sheath / shielding should be terminated or Earthed before connecting the CBCT. C. Use C and N/O Contact for shunt trip and C and N/C Contact for under voltage coil. After the successful completion of above mentioned scheme the Earth Leakage Relay is ready for use and installation is completed. TESTING AND SIMULATION OF FAULT Method 1: 1. The Earth Leakage Relay has two settings current setting and trip time setting. The same can be set by selecting any one dip switch in on position at a time as shown in the front fascia of the static earth leakage relay. 2. Having selected current sensitivity and trip time. The leakage current can be injected, slightly above set value at load side. ELR trips after the set time delay. To simulate the fault connect a bulb/suitable load between a phase and ground using a switch (of suitable rating). The load/bulb should be such that the current drawn by it should be greater than leakage current set in the relay. 3. After making doubly sure of correct wiring and setting of the relay, close the switch and observe tripping of the relay. Note: The Test should be conducted at the load side of the control panel and not at incoming side. And all the simulation of the leakage current should be done after the CBCT at load side and not before the CBCT. Preferable use the Resistive load and use hand gloves when you are simulating the fault current. The proper earthing should be done before testing and make doubly sure of earthing. The Tripping arrangement should be made properly and ensure the tripping coils are in working conditions, before doing the actual test. ELR SHALL BE TEST ALONG WITH CBCT (Don t inject the fault current directly to the S1& S2 terminals of ELR) HV 2KV shall be applicable for all live terminals connected together & body. Method 2: Steps: Connect the suitable Aux. supply to ELR (85 275 V AC/DC, Line Line 380V, 440V, 550V) Connect CBCT to ELR terminal S1 & S2 of the relay. 4

Set the leakage current in the relay and the corresponding time for tripping. Inject the current (AC) through CBCT (bar primary) by passing a wire of suitable capacity.connect a suitable calibrated ammeter in series to observe the leakage or fault current. Increase the current gradually above the set value, set in the ELR ELR picks up and operates The magnitude of the current at tripping instant will be displayed by the ELR and the ammeter After observing the operation of the ELR for the SET value of current, reset the relay, select a different value of current and repeat the steps mentioned above. Method 3: By operating the TEST button in ELR Connect the suitable Aux. supply to ELR (85 275 V AC/DC, Line Line 380V, 440V, 550V) Operate the test button to check the operation of the - relay trip. (This test is not the actual simulation, but the test ensures the correct operation of the miniature relay and the trip circuit mechanism.) Note: If the system frequency is 60Hz accuracy is ±5% on maximum current setting and for 50Hz accuracy is ±2% on maximum current setting FRONT FASCIA Operation & Indication: 5

The relay has two indications: Healthy and Fault In order to check the connection of the relay and CBCT, the Test button has been provided. In case the relay trips/fault indication is on, the reset button to resets the relay Wiring diagrams: 6