Instruction Bulletin. Jockey Pump Controller

Similar documents
Installation and Operation Instructions

Pressure Makeup Jockey Pump Controller

IM K IM K. Instructions for Cutler-Hammer Jockey Pump Controllers

PATTERSON PUMP COMPANY

Installation Instructions For Motor Control Center (MCC) Units

February, O & M Manual for EATON FDJ Series Jockey Pump Controllers. Instruction Booklet. For more information visit:

MODEL SCA Installation and Operation Manual Important:

JOCKEY PUMP CONTROLLERS

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Mizer Single Pump and Starter Box

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

Owner's/Installation Manual

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

MC2500. Installation and Operation Manual

INSTALLATION AND OPERATION MANUAL ARM-4073 AUTOMATIC REPRESSURE MODULES

PBA Series Prelube Controls

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

MODEL MC1500 Installation and Operation Manual Important:

LED Downlight Ceiling Fixtures

MODEL 422 Submersible Pump Controller

MODEL 10LH SPECIFICATION

450 Series Belt Driven Live Roller Curve Conveyor Installation and Maintenance Manual

Rated for use on 110/120VAC 60Hz and 220/240VAC 60Hz applications

50 AMP TRANSFER RELAY DELAY - DUAL INPUT GENSET

ARC 1850 LIST OF FIGURES

Manual PN: Rev 01. Otterbine Barebo Inc. Fractional Series 50Hz Installation Manual

DRYING SYSTEM ASSEMBLY AND OPERATING MANUAL

COOKSON OWNER'S MANUAL

AIR CLEANERS Model MC 3000 OWNER S MANUAL CAUTION Read complete instructions before operating. Please file for future reference.

Isolation Switch (behind barrier & inspection window) Power Fuses. Load Cable Connection Box. Contactor. Control Power Transformer Secondary Fuse

Electric Reciprocating Compressor. Installation Guide

A25 Series Warm Air Control with Manual Reset

BOLT-ON AND WELD-ON FLUSH FLOOR SLIDEOUT SYSTEMS OPERATION AND SERVICE MANUAL

SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

System 350 P352AB Electronic Pressure Control Series

Model 116 DPI Switch Installation and Operating Instructions

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

3 Phase Smart Controller

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

Electric Vehicle Charging Station

LPT50BRD (8x11x3 Enclosure)

Surepowr Series 100 Installation Manual

Owner s Manual Electric Swivel

RP-4000 Reserve Power Control

70 Series 8700 Coupler 2-pc Hub & Shaft Three Phase Brake Instructions IP43 & IP56 (NEMA 2 & 4) Housing

COM Overcurrent Relay

Technical Manual. DLM Module. This manual should remain with the unit.

Electric Actuator Installation, Operation & Maintenance Manual

TS93 EMF T/PT/TDE. Surface applied door closer

Low Profile Wrenches Operation and Maintenance Manual

Instructions for Replacing

Company Switch Installation Instructions and User Manual

Optimal Series. Automatic Transfer Switch. Installation and User Manual for the OPT2225 Automatic Transfer Switch. Full Version

PCVS Series Control Valve Supervisory Switch

Rated for use on 110/120VAC 60Hz and 220/240VAC 60Hz applications

Prismpack V, Prismalume V, Large Prismpack, Large Prismalume

TIASTAR Motor Control Center Installation And Maintenance Instructions For Units Only

Enclosure for AMP1 Series Energy Meters with Swing Panel Kit

INSTALLATION INSTRUCTIONS Dodge Ram Crew / Mega 2500/3500 2/4WD NOTE: (tow hooks will not be re-attached) PART # P5056

I-BFV.KIT Butterfly Valve Gear Operator Replacement

ASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY

Industrial Control Transformers

Controls Manual Standard 1 Fan Control Panel

**DO NOT EXCEED RECOMMENDED VEHICLE TOWING WEIGHT!**

XCITE Owner s Manual. Reso-not TM Damping System XCITE 1502C HYDRAULIC POWER SUPPLY

Bulletin 1494C Cable Operated Disconnect Switch Kit (600A) Installation Instructions (Cat 1494C- _ Series 2 : 600A)

Best Diversified Products, Inc. Product Manual. BestReach Rigid Belt. Models BRB 230 OS BRB 230 SS BRB 460 OS BRB 460 SS

Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual

MODEL CMS INSTALLATION INSTRUCTIONS A. INTRODUCTION 1. USAGE 2 2. HOW IT OPERATES 2 B. SPECIFICATIONS 1. ELECTRICAL 3 2.

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

Technical Data. Sizes 2 in. to 24 in. (DN50 to DN600) Approvals UL and ULC Listed FM Approved

Switch Base Replacement Instructions 3-Pole, 60 AMP, Fusible, Heavy Duty Safety Switches

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017

AE012 Enclosure for E5x Series Energy Meters With Swing Panel Kit Product Overview

B CW POWER RELAY

INSTALLATION INSTRUCTIONS Model FPT 50

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

OSYSU Series Outside Screw and Yoke Valve Supervisory Switch

MODULATING SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

MODEL ELC-12/40-CVM-D BATTERY CHARGER

MICRO WELD MODEL DP1 & DP2 HEAVY DUTY NON-FERROUS BUTT WELDERS MICRO PRODUCTS COMPANY SERVICE MANUAL

B21 Series BASOTROL Gas Valve

OWNER S MANUAL MODEL: PT 450 / PT 450M WELDING POSITIONER

Application Engineering

Mandatory X Information Recommended Change. Series/Parts Affected: LS40D, LS40TD, LS50TD and LS60TD Concrete Pumps

EXTREME R MOTOR OWNER'S MANUAL

Feeder Circuit Breaker Units Secure Support Pan and Change Door Latch

Switch Base Replacement Instructions 3-Pole, 60 AMP, Fusible, w Neutral, Visible-Blade, Heavy Duty Safety Switches

**DO NOT EXCEED RECOMMENDED VEHICLE TOWING WEIGHT!** FORD F-250, F-350

SAFE AND SECURE EXTREME R MOTOR OWNER'S MANUAL MODEL PRO-FDG FOR TECHNICAL SUPPORT PLEASE CALL 1-(855) OPERATOR SERIAL#

**DO NOT EXCEED RECOMMENDED VEHICLE TOWING WEIGHT!** FORD F-250, F-350

AIR CLEANERS. Model MX 6000 OWNER S MANUAL CAUTION. Read complete instructions before operating. Please file for future reference.

ATP-2040 Electric Damper Actuator/Transmitter

Model C230 Pump Controller

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

VARNA Products 15 GPM (57 LPM) Prelube Kit for MTU 4000 Series Marine Engines

PORTABLE POWER SUPPLY MODEL NUMBER VMS-1 VERSION 1.0

COVER PLATES & ROLLERS

Transcription:

Instruction Bulletin Jockey Pump Controller Installation Start Up Service This instruction bulletin is a guide for personnel involved with maintenance, engineering and approval of Fire Pump equipment and associated components. It provides an understanding of the Joslyn Clark Controller operation, to aid in installing and start-up. Operation installation and test requirements are specified by the National Fire Protection Association, Publications NFPA 20, NFPA 70, NFPA 25 and FM Global. Joslyn Clark Controls, LLC 2013 W. Meeting St. Lancaster, SC USA 29720-8842 Telephone (803) 286-8491 Toll Free (800) 476-6952 Fax (803) 286-6624 www.joslynclark.com

TABLE OF CONTENTS Introduction 3 Installation 4 Mounting the Controller 4 Electrical Connections 4 Electrical Make Ready 4 Piping 5 Setting the Pressure Switch 6 Energizing the Controller 7 Initial Power Up 7 Controller Operation 7 Controller Tests 8 Disconnecting Means 8 Pressure Switch 9 Renewal Parts 10 2

INTRODUCTION Joslyn Clark Jockey Pump Controllers are designed for operating the electric motor driven pressure maintenance pumps that are a part of the fire protection system. Please read the instructions prior to installing and operating the controller. If there are any questions, please contact the Joslyn Clark Controls Customer Service Department of the area representative. WARNING THIS EQUIPMENT OPERATES AT DANGEROUS VOLTAGE LEVELS, PERSONAL INJURY, DEATH OR SERVERE PROPERTY DAMAGE MAY RESULT BY CONTACTING ENERGIZED COMPONENTS. ALL INSTALLATION, TESTING AND MAINTENANCE MUST BE PERFORMED QUALIFIED PERSONNEL. BEFORE PERFORMING ANY SERVICE, TURN THE DISCONNECTING MEANS HANDLE FULLY COUNTERCLOCKWISE TO THE OFF POSITION. JOSLYN CLARK CONTROLS IS NOT LIABLE FOR ANY MISAPPLICATIONS OR IMPROPER INSTALLATIONS OR USA AND MAINTENANCE OF ITS PRODUCTS. DISCONNECTING MEANS HANDLE CONTROL SWITCH PRESSURE CONNECTION Figure 1 Typical Jockey Pump Controller DISCONNECTING MEANS HANDLE Operates the disconnecting means to turn the jockey pump controller on or off. Also used to reset the controller if the over current protection has operated. CONTROL SWITCH A three position switch for selecting the mode of operation. In the Hand position, the controller will run the pump continuously. Placing the switch in the Off position will stop the pump and keep it from running. The Auto position is the normal setting and the controller will start and stop the pump depending on system pressure. PRESSURE CONNECTION ¼ FNPT fitting for connecting to the piping system, refer to section A.10.5 of NFPA 20 for proper piping procedures. 3

INSTALLATION The installation must meet the requirements of the National Fire Protection Association publications NFPA 20 and NFPA 70 and any local codes that may apply. Refer to the Outline Diagram for overall controller dimensions, mounting and anchoring details and conduit entry area. MOUNTING THE CONTROLLER The controller must be mounted within sight of the pump motor but so located that it will be away from water escaping from the pump or connections. The controller is intended to be mounted to a wall or a welded structure that is part of the pump package. Refer to the Outline Diagram for mounting hole sizes and locations. If the controller is wall mounted, drill appropriate sized holes and insert wall anchors. If the controller is mounted to a welded structure, drill and tap the mounting holes. Loosely install the mounting bolts, lock washers and flat washers through the holes in the controller. Before tightening the hardware, install shims as necessary to provide an even mounting surface for the controller. After all the hardware is in place, tighten evenly, verify the controller is level and that the door operated freely, add shims as required. ELECTRICAL CONNECTIONS Before making any connections, check the controller rating plate to assure the controller voltage, frequency and motor horsepower ratings are the same as the service voltage and pump motor used. The space available for the entry of electrical conduits is detailed on the Outline Drawing. It is the responsibility of the installing electrical contractor to supply all necessary wiring and install it in accordance with all applicable national and local electrical codes. Refer to the Field Connection diagram for further wiring information. Rotate the Disconnecting Means handle to the Off position. Loosen the two screws securing the door, the screws are captive and will not fall out, swing open the door. Determine the best locations for the incoming power and motor leads. Using a hole saw or punch, cut the holes in the enclosure for the size of the conduit used and install the conduit. Pull the cables through the conduit, connect the incoming lines to the top of the disconnect switch, for three phase controllers, connect to terminal L1, L2 and L3, for single phase controllers, connect to terminals L1 and L3. Outgoing motor wiring connects to the bottom of the motor starter, uses terminals T1, T2 and T3 for three phase motors or terminal T1 and T2 for single phase controllers. Install the neutral or grounded service conductors or the grounding conductors in accordance with all applicable national and local electrical codes for non-metallic enclosures. Refer to Article 250 of the National Electrical Code, NFPA 70. ELECTRICAL MAKE READY Every controller is thoroughly tested and inspected before it leaves the factory, however components and wiring connections can work loose during shipping and installation. Verify the components are securely mounted and that all electrical connections are tight. Clean out any debris that may have gathered during the installation process. 4

Verify the overload setting (see Figure 2) matches the full load current of the motor. If the full load current is not known, set the pointer to the value shown on the recommended setting chart located on the inside of the controller door. SET DIAL TO MATCH MOTOR FULL LOAD CURRENT Figure 2 Overload Setting PIPING The pressure connection is located in the bottom of the controller, refer to the Outline Diagram. A ¼ FNPT fitting is supplied for connection to the sprinkler system. When tightening the piping, hold the hex part of the pressure fitting with a wrench to avoid spinning the fitting and putting undo strain on the pressure switch. Refer to figure 3 for typical piping arrangement. Figure 3 Pressure Sensing Line Arrangement 5

SETTING THE PRESSURE The pressure is set using the adjustment screws located on top of the pressure switch and scale on the face of the unit, see figure 4. Set the cut out pressure first using the left hand adjustment screw, turning the screw counterclockwise increase the cut out pressure. The cut out pressure must be less than the churn pressure of the jockey pump otherwise the pump will not stop. The cut in pressure is the difference between the cut out pressure and the differential setting, for example, if the cut out pressure is set at 175 PSI and the differential is set at 15 PSI then cut in pressure is 175 15 or 160 PSI. The setting is made using the right hand adjustment screw, turning the adjustment screw clockwise increases the differential. All settings should be verified to a pressure gauge. CUT OUT ADJUSTMENT DIFFERENTIAL ADJUSTMENT CUT OUT SCALE DIFFERENTIAL SCALE Figure 4 Pressure Switch 6

ENERGIZING THE CONTROLLER Before closing and securing the controller door, motor rotation and pressure settings should be checked. WARNING: Energizing the controller with the door open exposes personnel to dangerous voltages levels; only qualified personnel shall perform the following. INITIAL POWER UP 1. Verify all necessary valves are in their proper positions and water is available to the suction side of the jockey pump. 2. Verify the Hand-Off-Auto switch is in the Off position. 3. Rotate the disconnecting means clockwise to the On position. 4. Momentarily place the Hand-Off-Auto switch in the Hand position to check the pump rotation. If the rotation is incorrect, rotate the disconnecting means to the Off position, reverse any two of the motor leads on the bottom of the starter. 5. Rotate the disconnecting means clockwise to the On position and repeat. 6. Place the Hand-Off-Auto switch is in the Auto position to check the pressure switch settings to a test pressure gauge. 7. The pump should start when pressure is less than the cut in setting and continue to operate until the pressure exceeds the cut out setting. 8. Adjust the pressure switch as necessary. 9. Place the Hand-Off-Auto switch is in the Off position. 10. Rotate the disconnecting means to the Off position. 11. Close and secure the controller door. CONTROLLER OPERATION The jockey pump controller has a Hand-Off-Auto selector switch on the right hand side of the controller. Placing the switch in the Hand position will energize the motor starter and the motor will run continuously until the switch is placed in the Off position. When the switch is in the Auto position, the controller will operate the jockey pump as demanded by the system pressure. If the controller is equipped with the running period timer option, the pump will stop after the pressure is satisfied and the running period time has elapsed. If the switch is in the Off position, the jockey pump will not start regardless of system pressure. 7

CONTROLLER TESTS Individual components may be tested to confirm proper operation of each. Because of the risk of electrical shock, these tests must be performed by qualified personnel. To do any of the following tests, first turn the disconnecting means to the Off position, undo the two screws holding the controller door closed and open the door. DISCONNECTING MEANS The disconnecting means provides motor overload and short circuit protection; each function can be individually tested to confirm its operation. Because either condition will cause the disconnecting means to turn off, a small flag indicator will extend if a short circuit condition was detected. A small screwdriver or probe shall be inserted into the appropriate slot on the face of the disconnecting means, see figure 5. SHORT CIRCUIT FLAG SHORT CIRCUIT TEST SLOT Figure 5 Disconnecting Means Test Slots MOTOR OVERLOAD TEST SLOT To test motor overload protection: 1. Rotate the disconnecting means to the On position. 2. Insert a screwdriver or probe into the TEST slot. 3. The disconnecting means handle should immediately snap to the Off position removing power from the controller. 8

To test the short circuit indicator: 1. Insert a screwdriver or probe into the CK slot. 2. The short circuit flag should extend, see figure 6. 3. Push the flag back to the normal position. 4. After the tests are completed, close and secure the controller door and turn the disconnecting means to the On position. Figure 6 Short Circuit Flag PRESSURE SWITCH The pressure switch can be manually tested without having to lower or raise the system pressure. To test the pressure switch: 1. Loosen the cover screw on the face of the pressure switch. 2. Pull the cover forward slightly then up to remove the cover. 3. The test lever can be operated with a screwdriver, see figure 7, push down to start the pump, up to stop. 4. Replace the cover and secure. TEST LEVER Figure 7 Pressure Switch Test Lever 9

RENEWAL PARTS When ordering renewal or spare parts, the following information is required: 1. Controller Catalog Number. 2. Controller Serial Number. 3. Description of the part(s) required. Description Motor Protector 0.10-0.16 Amp 0.16-0.25 Amp 0.25-0.40 Amp 0.40-0.63 Amp 0.63-1.00 Amp 1.00-1.50 Amp 1.60-2.50 Amp 2.50-4.00 Amp 4.00-6.30 Amp 6.30-9.00 Amp 9.00-12.5 Amp 12.5-16.0 Amp 16.0-20.0 Amp 20.0-25.0 Amp Motor Contactor, 24 VAC Coil 9 Amp 11 Amp 17 Amp 28 Amp Control Transformers TR1 120/24 VAC 200/24 VAC 230/24 VAC 380/24 VAC 400/24 VAC 460/24 VAC 575/24 VAC Pressure Switch - PS 15-290 PSI 90-450 PSI Special Range Running Period Timer RPT Joslyn Clark Part Number A10-466330-1 A10-466330-2 A10-466330-3 A10-466330-4 A10-466330-5 A10-466330-6 A10-466330-7 A10-466330-8 A10-466330-9 A10-466330-10 A10-466330-11 A10-466330-12 A10-466330-13 A10-466330-14 A10-466334-1 A10-466467-1 A10-466468-1 A10-466739-1 A10-466337 A10-466337 A10-466337 A10-466469 A10-469469 A10-466337 A10-466469 A10-466335-1 A10-466335-2 Consult Factory A10-466340-5 Recommended Quantity Continental Outside USA USA - - - 1 - - - 1 - - - 1 - - - - - - - - - - - - Stop Delay Timer Opt D1 A10-466843-4 Start Delay Timer - ST A10-466341-5 - - - - - - Power Loss Relay PA1 A10-466342-1 - - - - - - Power Loss Relay PA 120 Volt 200 Volt 230 Volt 400 Volt 460 Volt 575 Volt JMRA022AT-J JMRA022AT-M JMRA022AT-N JMRA022AT-U JMRA022AT-W JMRA022AT-Y - - - - - - 10

Description Recommended Quantity Joslyn Clark Continental Part Number Outside USA USA Hand-Off-Auto Switch Operator SS1 N5CSMZ0N - - - - - - Normally Open Contact Block SS1 N5B10VN - - - - - - Green Lens and Block PL1 N5CLVD - - - - - - Red Lens and Block PL2 N5CLRD - - - - - - Socket with Lamp PL1, PL2 N5PDNVD - - - - - - Lamp Only, 24 Volt PL1, PL2 A22-351305-3 2 4 Disconnecting Means Handle Type 3R/12 A10-459183 - - - - - - Type 4/4X A10-456271-2 Line Terminal Block A10-466332 - - - - - - Contactor Coupler (9-16 Amp) A10-466333 Contactor Coupler (28 Amp ) A10-466740 - - - - - - 11