Type FEC Epoxy Encapsulated, Copper-Wound Transformers ISO 900:2008 REGISTERED 0
Transformer Selector Guide Type FEC Transformers...Page 02 Primary Fusing Option...Page 07 Primary Overcurrent Selection...Page 08 Secondary Overcurrent Selection...Page 09 Voltage Index Group Primary Secondary Page A... 240 x 480, 230 x 460, 220 x 440...20//0... 04 B... 240 x 480...24... 04 C... 20 x 240...24... 0 F... 208/277...20... 0 J... 200/220/440, 208/230/460, 240/480...23/0, 24/, 2/20... 06 ` K... 240 x 480...20 x 240... 06 02
Regulation & Inrush Selecting a transformer for industrial control circuit applications requires knowledge of the following terms: INRUSH VA is the product of load voltage (V) multiplied by the current (A) that is required during circuit start-up. It is calculated by adding the inrush VA requirements of all devices (contactors, timers, relays, pilot lights, solenoids, etc.), which will be energized together. Inrush VA requirements are best obtained from the component manufacturer. SEALED VA is the product of load voltage (V) multiplied by the current (A) that is required to operate the circuit after initial start-up or under normal operating conditions. It is calculated by adding the sealed VA requirements of all electrical components of the circuit that will be energized at any given time. SEALED VA requirements are best obtained from the component manufacturer. SEALED VA is also referred to as steady state VA. PRIMARY VOLTAGE is the voltage available from the electrical distribution system and its operational frequency, which is connected to the transformer supply voltage terminals. SECONDARY VOLTAGE is the voltage required for load operation which is connected to the transformer load voltage terminals. To comply with NEMA standards, which require all magnetic devices to operate successfully at 8% of rated voltage, the 90% secondary voltage column is most often used in selecting a transformer. Regulation and Inrush Data Chart Transformer VA Rating 9% Sec. Voltage Inrush VA at 20% Power Factor 90% Sec. Voltage 8% Sec. Voltage 2 00 30 0 0 70 200 240 7 30 40 40 00 370 40 730 0 780 930 0 200 80 0 40 20 400 900 2300 300 900 2700 380 30 300 360 4800 00 4000 300 7000 70 8300 000 4000 Once the circuit variables have been determined, transformer selection is a simple -step process as follows:. Determine the Application Inrush VA by using the following industry accepted formula: Application Inrush VA = (INRUSH VA) 2 + (SEALED VA) 2 2. Refer to the Regulation Data Chart. If the primary voltage is basically stable and does not vary by more than % from nominal, the 90% secondary voltage column should be used. If the primary voltage varies between and 0% of nominal, the 9% secondary voltage column should be used. 3. After determining the proper secondary voltage column, read down until a value equal to or greater than the Application Inrush VA is found. In no case should a figure less than the Application Inrush VA be used. 4. Read left to the Transformer VA Rating column to determine the proper transformer for this application. As a final check, make sure that the Transformer VA rating is equal to or greater than the total sealed requirements. If not, select a transformer with a VA rating equal to or greater than the total sealed VA.. Refer to the specification section of this catalog to determine the proper catalog number based on the transformer VA, and primary and secondary voltage requirements. 03
Type FEC Epoxy Encapsulated Copper-Wound Transformers Laminations of the finest silicon steel minimize core losses and increase performance and efficiency. Copper magnet wire assures efficient operation. UL 06 Listed CSA Certified Insulation materials of the highest rating available for the temperature class. Mounting brackets are heavy gauge steel to add strength to core construction and provide stable mounting. Slotted mounting feet permit easy installation. Attractive black finish; easy-to read nameplate with complete rating data and wiring diagram. Features Epoxy encapsulated coils Secondary fuse clips where applicable Optional Primary Fusing Molded terminal barriers 0-32 screw terminals Molded-in terminals Phil-slot screws 04
Construction Diagrams B E C D A Top View Side View Figure A Class 0 C Insulation System C Temperature Rise Epoxy Encapsulated Coils B E C D A Top View Side View Figure B Class 0 C Insulation System C Temperature Rise Epoxy Encapsulated Coils Figure E Class 0 C Insulation System C Temperature Rise Epoxy Encapsulated Coils B E C A D Top View Side View Figure C Class 0 C Insulation System C Temperature Rise Epoxy Encapsulated Coils Figure V Class 0 C Insulation System C Temperature Rise Epoxy Encapsulated Coils 0
Group A Primary Volts...240 x 480, 230 x 460, 220 x 440 Secondary Volts...20 0 and Certified 0 / 60 HZ VA Catalog Construction Output Dimensions Mounting Approx. Rating Number Figure Amps A B C D E Slots Wt. (lbs) 0 FA00JK B 0.43 3 3 2.62 2 2..203 x.37 2.6 7 FA07JK B 0.6 3. 3 2.62 2. 2..203 x.37 3. 00 FA00JK B 0.87 3.37 3.37 2.87 2.37 2.82.203 x.37 4.2 0 FA0JK B.30 4 3.7 3.87 2.87 3.2.203 x.37 6.7 200 FA200JK B.74 4 4. 3.82 2. 3.7.203 x.37 8. 20 FA20JK B 2.7 4.37 4. 3.82 2.87 3.7.203 x.37 0.0 300 FA300JK B 2.6 4.7 4. 3.82 3.2 3.7.203 x.37.3 30 FA30JK B 3.04.2 4. 3.82 3.7 3.7.203 x.37 3.6 00 FA00JK B 4.3..2 4.7 4.2 4.37.32 x.687 9.2 70 FA70JK B 6.2 7.2 4.7.7 4.37.32 x.687 28. JK suffix denotes transformer supplied with primary J-2 jumpers and secondary fuse clips for a 3/32 x - fuse. Construction Figure E units rated for 60 Hz at 240 x 480 input and do not come with secondary fuse clips. Group B Primary Volts...240 x 480 Secondary Volts...24 and Certified 0 / 60 HZ VA Catalog Construction Output Dimensions Mounting Approx. Rating Number Figure Amps A B C D E Slots Wt. (lbs) 0 FB00JK B 2.08 3 3 2.62 2 2..203 x.37 2.7 7 FB07JK B 3.3 3. 3 2.62 2. 2..203 x.37 3. 00 FB00JK B 4.7 3.37 3.37 2.87 2.37 2.82.203 x.37 4.2 0 FB0JK B 6.2 4 3.7 3.87 2.87 3.2.203 x.37 6.7 200 FB200JK B 8.33 4 4. 3.82 2. 3.7.203 x.37 8. 20 FB20JK B 0.42 4.37 4. 3.82 2.87 3.7.203 x.37 0. 300 FB300JK B 2.0 4.7 4. 3.82 3.2 3.7.203 x.37.4 30 FB30JK B 4.8.2 4. 3.82 3.7 3.7.203 x.37 3.4 00 FB00JK B 20.83.62.2 4.7 4.2 4.37.32 x.687 7. JK suffix denotes transformer supplied with primary J-2 jumpers and secondary fuse clips for a 3/32 x - fuse. 06
Group C Primary Volts...20 x 240 Secondary Volts...24 and Certified 0 / 60 HZ VA Catalog Construction Output Dimensions Mounting Approx. Rating Number Figure Amps A B C D E Slots Wt. (lbs) 0 FC00JK B 2.08 3 3 2.62 2 2..203 x.37 2.6 7 FC07JK B 3.3 3. 3 2.62 2. 2..203 x.37 3.6 00 FC00JK B 4.7 3.37 3.37 2.87 2.37 2.82.203 x.37 4.4 0 FC0JK B 6.2 4 3.7 3.87 2.87 3.2.203 x.37 6.7 200 FC200JK B 8.33 4 4. 3.82 2. 3.7.203 x.37 8.3 20 FC20JK B 0.42 4.37 4. 3.82 2.87 3.7.203 x.37 0. 300 FC300JK B 2.0 4.7 4. 3.82 3.2 3.7.203 x.37.2 30 FC30JK B 4.8.2 4. 3.82 3.7 3.7.203 x.37 3.2 00 FC00JK B 20.83.62.2 4.7 4.2 4.37.32 x.687 7. JK suffix denotes transformer supplied with primary J-2 jumpers and secondary fuse clips for a 3/32 x - fuse. Group F Primary Volts... 208 / 277 Secondary Volts...20 and Certified 0 / 60 HZ VA Catalog Construction Output Dimensions Mounting Approx. Rating Number Figure Amps A B C D E Slots Wt. (lbs) 0 FF00XK B 0.42 3 3 2.62 2 2..203 x.37 2.9 7 FF07XK B 0.63 3. 3 2.62 2. 2..203 x.37 3.8 00 FF00XK B 0.83 3.37 3.37 2.87 2.37 2.82.203 x.37 4. 0 FF0XK B.2 4 3.7 3.87 2.87 3.2.203 x.37 6.9 200 FF200XK B.67 4 4. 3.82 2. 3.7.203 x.37 8.7 20 FF20XK B 2.08 4.37 4. 3.82 2.87 3.7.203 x.37 0.2 300 FF300XK B 2.0 4.7 4. 3.82 3.2 3.7.203 x.37.4 30 FF30XK B 2.92.2 4. 3.82 3.7 3.7.203 x.37 3.7 00 FF00XK B 4.7.37.2 4.7 4.2 4.37.32 x.687 7.2 70 FF70XK B 6.2 7.2 4.7.7 4.37.32 x.687 2.7 XK suffix denotes transformer supplied with secondary fuse clips for a 3/32 x - fuse; primary jumpers not applicable. 07
Group J Primary Volts...200 / 220 / 440, 208 / 230 / 460, 240 / 480 Secondary Volts... 23 / 0, 24 /, 2 / 20 and Certified 0 / 60 HZ VA Catalog Construction Output Dimensions Mounting Approx. Rating Number Figure Amps A B C D E Slots Wt. (lbs) 0 FJ00XK B 2.08/0.44 3.2 3 2.62 2.2 2..203 x.37 3.4 7 FJ07XK B 3.3/0.6 3. 3.37 2.87 2. 2.82.203 x.37 4.8 00 FJ00XK B 4.7/0.87 3.62 3.7 3.87 2. 3.2.203 x.37.9 0 FJ0XK B 6.2/.30 4.37 3.7 3.87 3.2 3.2.203 x.37 7.9 200 FJ200XK B 8.33/.74 4. 4. 3.82 3 3.7.203 x.37 0.6 20 FJ20XK B 0.42/2.7.2 4. 3.82 3.7 3.7.203 x.37 3.9 300 FJ300XK B 2.0/2.6.2.2 4.7 3.87 4.37.32 x.687. 30 FJ30XK B 4.8/3.04.37.2 4.7 4.2 4.37.32 x.687 6.8 00 FJ00XK B 20.84/4.3 6.87.2 4.7.2 4.37.32 x.687 23.4 XK suffix denotes transformer supplied with secondary fuse clips for a 3/32 x - fuse; primary jumpers not applicable. Group K Primary Volts...240 x 480 Secondary Volts...20 x 240 and Certified 0 / 60 HZ VA Catalog Construction Output Dimensions Mounting Approx. Rating Number Figure Amps A B C D E Slots Wt. (lbs) 0 FK00JJ B 0.42/0.2 3 3 2.62 2 2..203 x.37 2.6 7 FK07JJ B 0.63/0.3 3. 3 2.62 2. 2..203 x.37 3. 00 FK00JJ B 0.83/0.42 3.37 3.37 2.87 2.37 2.82.203 x.37 4.2 0 FK0JJ B.2/0.63 4 3.7 3.87 2.87 3.2.203 x.37 6.7 200 FK200JJ B.67/0.83 4 4. 3.82 2. 3.7.203 x.37 8. 20 FK20JJ B 2.08/.04 4.37 4. 3.82 2.87 3.7.203 x.37 0.0 300 FK300JJ B 2.0/.2 4.87 4. 3.82 3.37 3.7.203 x.37.8 30 FK30JJ B 2.92/.46.2 4. 3.82 3.7 3.7.203 x.37 3.6 00 FK00JJ B 4.7/2.08.2.2 4.7 4.2 4.37.32 x.687 7. 70 FK70JJ B 6.2/3.2 7.2 4.7.7 4.37.32 x.687 26.4 JJ suffix denotes transformer supplied with primary and secondary J-2 jumpers ; secondary fuse clips not applicable. 08
Primary Fusing Primary Fusing Capability In compliance with the requirements of UL08 and the National Electrical Code, Intertran transformers, rated 0VA and larger, can be ordered with the provision for factory-mounted dual primary class cc fusing capability. The primary fuse block is mounted on the transformer and wired to the primary terminals. To indicate this option, replace the standard part number suffix with the appropriate interchange as shown below. The primary fusing option will add -3/8" to the "C" dimension of the transformer. Primary Fuse Kit In addition to factory installed primary fusing capability, Federal Pacific offers a primary fuse kit for field installation. The primary fuse kit includes a 2-pole class cc fuse block, instructions and all associated mounting and wiring hardware. Additionally, this fuse kit will fit most competitor's units. To order this kit, use catalog number FPFK-. The primary fuse kit, when installed, will add a maximum of /6" to the transformer "A" dimension and -/6" to the "C" dimension. To indicate Primary Fusing Capability, the part number suffix should be changed as shown. Dual Primary Standard P/N Fused P/N Suffix Suffix JK >> RB XK >> RK XX >> RX XJ >> RJ JJ >> RR JM >> RY XM >> RG JQ >> RL XQ >> RN JX >> RC - >> -8 Typical Primary Fuse Kit Installation 09
Primary Overcurrent Protection for Transformers Overcurrent protection on both the primary and secondary sides of transformers is specified in UL08 and the National Electrical Code. The maximum acceptable ratings are shown below. Due to high inrush currents present when a transformer is initially energized, it is recommended that the primary fuse be time delay, to prevent nuisance trips during startup. Primary Voltage 20 200 208 220 230 240 277 380 400 4 440 460 480 0 7 600 MAXIMUM ACCEPTABLE RATING OF PRIMARY OVERCURRENT PROTECTION 0 7 00 0 200 20 300 30 00 70 3/4 () (-/8) (-/8) () () () () () () () () /4 (4/0) /4 (4/0) 2/0 (4/0) (3-2/0) -/8 () () (-) (-) (-) () 4/0 4/0 (3/4) 4/0 () () () - () -4/0 () () () 3/4 () 3/4 () (-/8) (-/8) () () () 2 () 2 (3-2/0) (3-2/0) - () -/8 () -/8 () () (-) (-) (-) () 3/4 () 3/4 () (8) (8) 3 () 2- (4-) (4-) 2 () - () - () -4/0 () () () (-) (-) 6-/4 7-0 6-/4 7 0 (6) 3-2/0 (-) 3-2/0 () 3 () (4-) (3-2/0) - (2-) - () - () () 4- (7-) 4 (7) 4 3-2/0 () () () 2 () 2 (3-2/0) (3-2/0) - () - () - () (8) (8) 4- (7-) 4- (7-) 4 (7) (6//4) (4-) () () 2 () - (2-) 6-/4 9 6 9-8 8 7- (9) (6--4) (6) 3-2/0 (-) 3-2/0 () 3 () (4-) If the rated primary current is less than 2 amps, the maximum rating of the overcurrent device is 300% for power circuits, shown above, or 00% for control circuits, shown above in (brackets). If the rated primary current is 2 amps or more, the maximum rating of the overcurrent device is 20%. All figures assume secondary overcurrent protection per UL/NEC. Reference: NEC 430-72(c) exception #2, 40-3(b) & 2, UL08 32.7, UL84.6 &.7 6-/4 - (9) - (9) (9) (8) 4- (8) 4- (7-) 4 0
Secondary Overcurrent Protection for Transformers MAXIMUM ACCEPTABLE RATING OF SECONDARY OVERCURRENT PROTECTION Primary Voltage 0 7 00 0 200 20 300 30 00 70 23 7 0 2 20 20 30 4 24 3-2/0 6-/4 0 2 20 20 30 40 2 3-2/0 6-/4 0 2 20 2 40 90 4-6-/4 9 2 9-4 6 8 2 00-3-2/0 4-8 2 0 3/4 -/8-3 4-7- 0-4/0 2 2-4 7 0 20 2 3-2/0 4 4-6-/4 0 220 3/4 -/8 - - 230-4/0 2 240-2 3-2/0 If the rated secondary current is less than 9 amps, the maximum rating of the overcurrent device is 67%. If the rated secondary current is 9 amps or more, the maximum rating of the overcurrent device is 2%. If 2% does not correspond to a standard fuse rating, the next highest standard rating may be used. Reference: NEC 430-72(c) exception #2, 40-3(b) & 2, UL08 32.7, UL84.6 &.7.