Oil / air cooler Series BLK-DC

Similar documents
Oil/air cooler BLK. Fluidcontrol

Oil/air cooler BLK ATEX-3GD

Oil/air cooler BLK. Fluidcontrol

Off-line filter / cooler unit FGSL

Oil / water cooler Series BWT

Circulation pumps BFP-ATEX-T3/T4

LKI LKI-HYD COOLING. Series. advanced quality customized designs made in europe. Oil/Air heat exchangers. Low noise level. High performance.

Off-line filter / cooler unit BKF

Oil/Air Cooler Units. Mobile series with DC motor OK-ELD Type. Test procedure certified following EN 1048

Oil/Air Cooler Units. Standard series OK-P type. Test procedure certified following EN

Off-Line Filter BNF. FluidControl

Oil/Air Cooler Units. Compact application with AC Motor OK-ELC Type. Test procedure certified following EN 1048

BYPASS SERIES GLOBAL STANDARD COOLER

Oil/Air Cooler Units. Compact application with AC Motor OK-ELC Type

OFFLINE SERIES GLOBAL STANDARD COOLER

GLOBAL STANDARD COOLER

GLOBAL STANDARD COOLER

GLOBAL STANDARD COOLER

GLOBAL STANDARD COOLER

HEAT EXCHANGERS AIR/OIL TYPE LAC. - ATEX Version. Approved for applications where there may be an explosive environment above ground.

Oil/Air Cooler Units. Mobile application and Hydraulic motor OK ELH Type. Test procedure certified following EN 1048

GLOBAL STANDARD COOLER

Oil/Air Cooler Units. Standard series EL Type. Test procedure certified following EN 1048

GLOBAL STANDARD COOLER

A-L A C AIR OIL COOLER LUFT/ÖL-KÜHLER OLAER COOLERS. Olaer A-LAC with A.C. motors for industrial hydraulic systems

GLOBAL STANDARD COOLER

Feed Pumps VP / VPB / VPBM

AKG 2009 (changes and errors expected) HC- series. Classic

GLOBAL STANDARD COOLER

Drive module. Table of contents. Features. Applications. RE 51145/06.12 Replaces: Type UPE 5

Oil/Air Cooler Units

GLOBAL STANDARD COOLER

GLOBAL STANDARD COOLER

Air Cooler Industry AC-LN 8-14 / ACA-LN 8-11 / ACAF-LN 8-11

DCS- series. Classic

Off-line filter units BNF. Installation and Operation Instructions. Original instructions. Fluidcontrol BE /2019

A-L O C COOLING SYSTEM OLAER COOLERS. Olaer A-LOC with integrated circulation pump for industrial hydraulic systems

GLOBAL STANDARD COOLER

Compressor Aftercoolers GLOBAL STANDARD COOLER

GLOBAL STANDARD COOLER

Air Cooler Mobile AC-LNH 8-14 with hydraulic motor

IPVP High-pressure Internal Gear Pumps for Variable Speed Drives

Connection Ports: 3/4 1 1/4 BSP (other thread options on request)

4/3, 4/2 proportional directional valves solenoid operated (for open loop control)

Sample gas pumps P2.x ATEX

Servo-operated 2/2-way solenoid valves Type EV220A

Cooler Bellhousing KPV series

AKG 2009 (changes and errors expected) GLOBAL STANDARD COOLER

4/3-4/2 Proportional directional valves L5080 solenoid (LC04P) operated (for open loop control) L5080 (LC04P)

Filtrec elements are tested according to ISO 2941, ISO 2942 and ISO 23181

Extremely compact in size to allow direct flange-mounting on vehicle engine or gearbox PTOs.

Sample gas pumps P 2.3, P 2.3C, P 2.83, P 2.4, P 2.4C, P 2.84

Directional Control Valve Series D3W Soft Shift

Heat exchanger AB-E oil / water system: single tube. 1 Area of application. 2 Model. Company standard. Replaces: Issue

Air Cooler Mobile OK-ELD 0-6 with DC motor

RA / Internal Gear Pump Model GP2, Series 2X Fixed Displacement. Typical application:

OFFLINE SERIES GLOBAL STANDARD COOLER. p f

AKG A World Class Supplier. Your innovative partner to design and supply engineered cooling packages

Specification. Oil/Air- Cooling Systems AKG-Range T1 - T11. AKG A World Class Supplier

Connection Ports: 1/2 1 1/2 BSP (other thread options on request) aluminium alloy NBR (FKM on request)

NCF fans 50 Hz. Protection class IP 55

RA / Internal Gear Pump Model GP3, Series 3X Fixed Displacement. Typical application:

IPVS High-pressure Internal Gear Pumps Technical Data Sheet

NCF fans 60Hz. Protection class IP 55

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/

Air Cooled Exchangers With Aluminium Cooling Elements

MINI POWER PACKS WITH SUBMERSED MOTOR AND PUMP

Hydraulic piston PA PAC PAD. Series

IPV catalog High-pressure internal gear pumps

Cooling Systems CC Series TT rail 20/30lpm

Air Cooled Exchangers With Aluminium Cooling Elements

HTC. Air cooled Condensers. Capacities kw. Ripple Fin tubing Floating coil block suspension

Compact hydraulic power unit Type BKA

P2060 P2075 P2105 P2145 P3105 P3145

By-pass: 1,7 bar (24.6 psi) setting N.B. Cartridge with integrated bypass valve and antidrainback membrane

DSE /117 ED DIRECTIONAL VALVE WITH PROPORTIONAL CONTROL SERIES 11 SUBPLATE MOUNTING ISO p max 350 bar Q max 40 l/min

Duct mounted fans. axial flow. Pacific HVAC Engineering Tel. Australia NZ

FNA 045 Operating pressure up to 7 bar / 101 psi Nominal flow rate up to 45 l/min / 12 gpm

IPCA Medium-pressure Internal Gear Pumps Technical Data Sheet

FILTERS. PUMP CARE - Suction filters TECHNICAL DATA ORDERING AND OPTIONS CHART CLOGGING INDICATORS. PRESSURE DROP ( p) CURVES CROSS FUNCTIONAL VIEW

V.I.R.T.U.O. Ventilation boxes. Comfort ventilation boxes

IPVP High-pressure Internal Gear Pumps for Variable Speed Drives Technical Data Sheet

IPC Medium-Pressure Internal Gear Pumps Technical Data Sheet

Hydraulic primary unit Type ABPAG

Coolers. Air Cooled / Liquid Cooled

Pressure: Max working 110 bar (1600 psi) (acc. to NFPA T ) Burst 330 bar (4800 psi) (acc. to NFPA T ) Wire mesh µm

MANN+HUMMEL ProVent. Oil separator for closed and open crankcase ventilation

Pressure: Max working 8 bar (116 psi) (acc. to NFPA T ) Burst 16 bar (232 psi) (acc. to NFPA T )

Versatility. Features. By installing the SILENT MV, you will never experience the disturbance of noisy ventilation again. Benefits

Inline Filter LPF D A Flange-Mounted up to 280 l/min, up to 25 bar

Variable Vane Pump, Direct Controlled PV7...A Series 1X / 2X

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS SERIE BV

RE / Gerotormotors (Low Speed High Torque Motors) Type GMP, GMR, GMVD. Hydraulik Nord. Contents 1/32. Replaces:

DL /116 ED SOLENOID OPERATED DIRECTIONAL CONTROL VALVE COMPACT VERSION SERIES 10 SUBPLATE MOUNTING ISO p max 320 bar Q max 125 l/min

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BV SERIES

Inline Filters NF. Flow rates up to 3,500 l/min Pressure range 25 bar Material: Aluminium / Aluminium-Cast Iron

Change-Over Pressure Filter DFDK

In line high pressure filters. HF 725 series

Directional Control Valve Series 4D01 (DENISON)

Pressure: Max working 280 bar (4000 psi) (acc. to NFPA T ) Burst 840 bar (12200 psi) (acc. to NFPA T )

Transcription:

Oil / air cooler Series BLK-DC maintenance friendly design broad performance range compact dimensions rugged cooling matrix low noise emissions comprehensive accessoires DE 35 0002 09/2000 Bühler Technologies GmbH D - 40880 Ratingen, Harkortstr. 29 Tel.: + 49 (0) 2102 / 49 89-0 Fax: + 49 (0) 2102 / 4989-20 e-mail: fluidcontrol@buehler-ratingen.com

2 Why coolers? There are basically two main concepts in the development of fluid power systems. One is to design systems without any cooler and if the operational conditions show in practice that the system needs a cooler to install it later. This however requires compromises that usually result in financial overspend. The other concept recognizes that a system originally designed with an integrated cooler can be designed more compactly, needs less installation space and runs more reliably due to the stabilized temperature of the fluid. Why Bühler? Todays requirements for an oil/air cooler demand for an effective and compact design with low noise emission and very easy maintenance. The development of the new BLK-DC series is based on over 30 years of experience in design and sales of air/oilcoolers. In particular the fatigue life of the cooling matrix was highlighted in the development as the matrix has to withstand pressure peaks in the return line. Due to the exposure to the various ambient conditions air/oil cooler matrixes inevitably require some maintenance. Therefore the cooling matrix can be easily separated from the fan case without the need to dismantle the ventilator or motor or any other parts. If our comprehensive standard range of products does not have an answer for your application we will be pleased to find special solutions for your application. The data contained in this leaflet is sufficient to determine the right cooler for your application. However, we can offer you a computer program which makes this sizing easier for you. BNF, BKF Description The BLK-DC series consist of the following components: cooler matrix fan case with mounting feet fan motor assembly consisting of DC motor, fan and finger guard The cooling matrix and fan can be separated from the fan case individually without the need to dismantle other components. The cooling matrix of the BLK-DC series is made from aluminium. The matrix is suitable for use with hydraulic fluids (also return lines) but is not suitable for clean water or water based fluids. Please pay attention to the chapter installation. BNK

3 Sizing the right cooler The determination of a cooler follows two steps: - determination of cooler size - determination of expected pressure loss Nomen clature töe [ C] inlet oil temperature tle [ C] inlet air temperature ETD [K] temperature differential: ETD = töe - tle Pspez [kw / K] specific cooling performance (see performance curves) P spez = P / ETD P [kw] cooling performance in kw Q [l/min] oil flow rate CÖl [kj/kgk] specific heat capacity of oil (approx. 2,0 kj / kgk) [kg/dm³] specific gravity of oil 0,9 kg/dm³ Calculation sample: assumptions: tank capacity start up temperature of oil The oil is heated up approx. ( V) ( T1) ca. 200 l 15 C 25 minutes to required oil temperature inlet air temperature oil flow rate ( T2) ( t ÖE) ( tle) ( Q) 45 C 60 C 30 C 80 l/min Pressure loss curves determined with an average viscosity of 30 cst bar 3,000 Calculation 1. calculation of P P= 2. ETD=t -t =60 C-30 C=30K ÖE LE 3. required specific performance: P = P / ETD = 7,2 kw / 30 K = 0,24 kw/k spez 200 x 0,9 x 2,0 x (45-15) 25x60 =7,2 kw 4. choose in curve at 80 l/min a cooler with: Pspez 0,24 kw/k: select BLK-DC-B-1 Temperature/viscosity table 2,500 2,000 1,500 1,000 0,500 B-2 C-2 D-2 A-1 E-2 B-1 C-1 D-1 E-1 Type of oil at 50 C at 60 C at 70 C VG 16 9,4 5,6 3,3 cst VG 22 15 11 8 cst VG 32 21 15 11 cst VG 46 29 20 14 cst VG 68 43 29 20 cst VG 120 68 44 31 cst VG 220 126 77 51 cst VG 320 180 108 69 cst 0,000 20 40 60 80 100 120 140 160 180 200 220 l/min Correction factor k(visc) viscosity ( cst) k(visc) viscosity (cst) k(visc) 10 0,6 60 1,6 20 0,8 80 2,1 30 1,0 100 2,7 40 1,2 150 4,2 50 1,4 Determine of real pressure loss: Attention: If the coolers are used in open air or the oil has even higher viscosity the installation of by-pass valves may be necessary. Please check the section function schemes. 1. select in graph the p at Q of a choosen cooler type 2. determine real viscosity from temperature/viscosity table 3. take correction factor k(visc) according to real viscosity and multiply with p in bar

4 Performance curves KW/ C 0,700 0,600 0,500 E-2 D-2 E-1 D-1 0,400 C-2 C-1 0,300 B-2 B-1 0,200 A-1 0,100 0,000 20 40 60 80 100 120 140 160 180 200 220 l/min Type code BLK-DC-A-1-12V-T60 standard 1 path / 12V 1path / 24V 2 path / 12V 2 path / 24V type part - no. part - no. part - no. part - no. temperatur switch voltage path model temperatur switch TSE-BLK-DC-T* technical data see below BLK-DC-A BLK-DC-B BLK-DC-C BLK-DC-D BLK-DC-E 35DCA112 35DCA124 - - 35DCB112 35DCB124 35DCB212 35DCB224 35DCC112 35DCC124 35DCC212 35DCC224 35DCD112 35DCD124 35DCD212 35DCD224 35DCE112 35DCE124 35DCE212 35DCE224 General data material / surface protection cooler matrix aluminium, gray RAL 9006 house: steel, black RAL 9005 fan: PPG Fluids mineral oil to DIN 51524 water glykol HFC according to CETOP RF 77 H Operating pressure static max. 26 bar dynamic: max. 20 bar temperature operating max.120 C ambient max. 50 C max. viscosity 100 cst average viscosity, higher viscosity upon request electrical motors 12 oder 24 V DC protection class IP 64 temperatur switch TSE-BLK-DC-* * Switch point T60 = 60 C ( 140 F) T70 = 70 C ( 158 F) voltage max. 230 V AC/DC current load max. 2 A function n.c. ( opener) hysteresis approx 15 C ( 27 F) protection class IP 65

A M H BLK-DC-A 12,5 350 332 9 280 35 105 117,5 235 105 ø10(6x) M22x1,5(2x) 35 310 240 5 164 45 25 16 air 5 ø32 F000004D BLK-DC- B-E E Ø8,5x12 D G1(3x) Oil in with temperatur switch air F H H Ø7(4x) G L K J 105 B Oil out with C temperatur switch F000003D dimension A B C D E F G H J K L M BLK-DC-B BLK-DC-C BLK-DC-D BLK-DC-E 420 342 220 63 317 360 110 100 83 302 17 47 420 342 251 94 317 360 110 100 114 302 17 47 520 480 213 63 455 460 95 110 83 390 12 42 520 480 241 94 455 460 95 110 114 390 12 42 full load current air noise noise weight [ A ] flow emission emission [ kg ] 12 V 24 V m³/s 1 m [db(a)] 7 m [db(a)] BLK-DC-A BLK-DC-B BLK-DC-C BLK-DC-D BLK-DC-E 10,5 5,2 0,24 73 63 6 18,5 10 0,49 79 64 10 18,5 10 0,45 79 64 13 21,8 10,7 0,84 84 67 17 21,8 10,7 0,74 84 67 24

6 Installation Location The cooler must be located in such a way that the air flowing through the matrix has free flow on entry and exit. The distance between air intake or air outlet to the nearest surrounding obstacle should be a minimum of half the height of the matrix (dimension A). Free air flow must be provided. If the cooler is to be usited near to working personnel the effect of hot draught and noise emissions must be taken into account. If the ambient air is carrying impurities or other particulates the cooling matrix could become clogged quite quickly thus reducing the cooling efficiency. If this situation is unavoidable we recommend cleaning the matrix on a regular basis (see operation manual). Mounting The BLK's are mounted with four bolts through their mounting feet to an adequate support structure. The cooler can be mounted over head or to walls with no restriction. Connection of oil circuit The connections from the cooler to the system should be stress and vibration free. The use of flexible hoses is highly recommended. Please comply with local safety requirements and avoid any risk to the environment from oil spills etc. Always provide good accessability for inspection or maintenance. The series BLK is a product designed by BÜHLER company The company BÜHLER MESS- UND REGELTECHNIK GmbH, Ratingen was founded in 1969. BÜHLER s corporate philosophy is to offer products and solutions representative of the state of the art. BÜHLER also specialises in producing level and temperature measuring equipment, particularly for the fluid power industry. The products Our commitment to customers has given rise to a production program which comprises specialized products for fluid technology. Although these products were initially developed entirely as specials many of them have now become industry standards. Bühler quality Bühler has achieved accreditation from Lloyd s register to be in compliance with ISO 9001 and therefore consider it our obligation to offer our customers not only excellent products, but also the best service possible. We reserve the right to amend specification