MCBs and RCDs LR TM 6000

Similar documents
Get detailed information on many digital or printed supports, or contact your Area Commercial Manager

New DX 3 High rating & breaking capacity

(p. 47) (p. 155) (p. 155)

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DX³ 4-pole RCBO 6000 A/10 ka

COMPLETE SOLUTIONS FOR POWER PROTECTION

DX³ RCBO 6000 A Phase + Neutral, neutral right side

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on left side

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1.

TX³ RCCBs 2P up to 100 A

DX³ RCCBs - ID 4P up to 100 A

NEW TX³ RANGE PROTECTION YOU CAN RELY ON


, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

DPX moulded case circuit breakers

Vistop TM isolating switches 63 to 160A

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

dx 3 protection that meets your requirements GloBal SpecialiSt IN electrical AND DIgITAl BUIlDINg INFrASTrUCTUreS catalogue pages inside

DX³ RCBO 6000 / 10 ka Phase + Neutral, neutral on left

DX³ RCBO 6000A Phase + Neutral, neutral on right

Power protection solutions

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. .

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

Bulletin 140U R-Frame Molded Case Circuit Breakers

Btdin-RS RCBO 2p Phase + Neutral, neutral on right

DX³ RCBO 6000A Phase + Neutral, neutral on left

3 - Protection components Motor circuit-breakers

R.C.B.O. SP / 1 module

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS

cor Long Run Experience

Switch disconnectors and fuse switch disconnectors

AF40... AF96 3-pole contactors Technical data

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Breaking and protection devices

(1,5 modules per pole)

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE

DPX 1600 Electronic release

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

Din rail power supplies

Btdin RCBO 6000A up to 63A (2P)

DPX earth leakage DPX 3 -I earth leakage

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

C60H-DC. C curve IEC Direct current (DC) Breaking capacity (Icu) according to IEC Type 1P 110 V 220 V 250 V 440 V 500 V

RX 3 MCB 4500 A Phase + Neutral, neutral on left side

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

Cat N 3. OVERALL DIMENSIONS

RX 3 M.C.B A up to 63 A

DPX Magnetic only

DPX 160 Thermal magnetic and trip-free switches DPX-I 160

RX 3 M.C.B A up to 63 A

Protection components

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

DPX 630 Thermal magnetic and trip-free switches DPX-I 630

DPX Thermal magnetic and trip-free switches DPX 3 -I 630

and other modular devices for low voltage installation

SWITCH DISCONNECTORS PLANET -SWITCH.

Panel-mounting components

schneider-electric.com/sg K60 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads schneider-electric.

up to 63 A (1 module per pole)

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Equipment model: auxiliary control. Pack Cat.Nos 10/16 A V± P + T shuttered module module

Polymas Watertight PK Enclosures Product Drawings Last Updated 6/18/2008

DPX 630 Electronic release

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

C60H-DC C curve. Catalogue numbers

Essential equipment for all your requirements

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63

K50H004UP cam changeover switch - 4-pole A - screw mounting

DC Loop Contactors, Contactor Lugs and Dynamic Brakes Technical Data

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors

cabinets and equipment Atlantic, Atlantic stainless steel, Marina

Relax... you re in safe hands CONSUMER UNITS / PRODUCT GUIDE.

K30H001YP cam star-delta switch - 3-pole A - screw mounting

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

Multi 9 TM. Catalogue 2017 Multistandard protection for OEM. schneider-electric.com

DPX Electronic + earth leakage

CS COMPACT ENCLOSURE. CABINETS. method for lifting uses the same eyebolts as ATB8 cabinets. optional 180 hinges available

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

ETA quality, promptly

Btdin RCD Add-on modules 125A for MCBs 1,5 modules per pole

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

ATB8 MONOBLOC CABINET

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals

DRX 125 Circuit breaker (not adjustable)

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

DRX 250 B/N/H Circuit breaker (not adjustable)

ECO/PCI Compact Enclosures Product Drawings Last Updated 6/19/2008

D509E. Manual Motor - Starters


Low Voltage A GE Power Controls Company. General catalogue

Motor Protection Circuit Breakers

Wall mounted switchgear

MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS

Transcription:

MCBs and RCDs LR TM 6000 thermal magnetic MCBs from 6 A to 63 A B and C curves residual current devices from 25 A to 63 A AC and A types ± ± ± ± MCBs Single pole 230/400 V± Single pole neutral 230 V± (1) (1) (1) (1) (1) (1) (1) 2pole 400 V± 3pole 400 V± 1 1 1 1 1 1 1 1 3pole neutral 400 V± 1 (1) 1 (1) 1 (1) 1 (1) (1) 1 (1) 1 (1) 1 (1) 1 (1) 1 (1) MCBs (continued) 4pole 400 V± 1 1 1 1 1 1 1 1 RCDs 2pole 230 V± 30 ma? M 1 1 1 2pole 230 V± 100 ma 1 2pole 230 V± 300 ma 1 1 1 4pole 400 V± 30 ma 1 (1) 1 (1) (1) 1 (1) 4pole 400 V± 100 ma 1 (1) (1) 4pole 400 V± 300 ma 1 (1) 1 (1) 141

MCBs DXE 6000 6 ka thermal magnetic MCBs from 6 A to 63 A B and C curves MCBs DX 10kA thermal magnetic MCBs from 6 A to 63 A B and C curves www.klinkmann.com NEW A A Single pole 230/400 V± 2pole 400 V± 3pole 400 V± 1 1 1 1 1 1 1 1 1 1 A Single pole 230/400 V± 1 1 1 1 1 3pole 400 V± 1 1 1 1 1 1 1 1 1 Auxiliaries and accessories for MCBs Supply busbars 4pole 400 V± 1 1 1 1 1 1 1 1 1 1 144 These products are part of protection and distribution systems > See p. 142143

remote trip isolating switches DX TM IS from 16 A to 125 A isolating switches DX TM IS from 16 A to 125 A Remote trip head isolating switches 2P 400 V± 2 2 2 2 3P 400 V± 1 1 4P 400 V± 1 1 Isolating switches 1P 250 V± 1P with indicator 250 V± 2P 400 V± 2P with indicator 250 V± 3P 400 V± 3 3 3 3 4P 400 V± 2 2 2 2 For threephase version, please consult us 145

RCDs DX TM residual current devices from 16 A to 100 A AC, A and Hpi types Technical characteristics (p. 158) 2pole 230 V± AC type? 10 ma AC type? 30 ma AC type? 100 ma AC type? 300 ma A type M 10 ma A type M 30 ma A type M 300 ma Hpi type MH 30 ma 4pole 400 V± Neutral on righthand side AC type? 30 ma AC type? 100 ma AC type? 300 ma AC type? 300 ma selective AC type? 500 ma A type M 30 ma A type M 100 ma A type M 300 ma Auxiliaries and accessories These products are part of protection and distribution systems > See p. 142143 146

RCDs DX TM residual current devices from 25 A to 100 A AC, A and Hpi types (continued) DX TM IS isolating switches and DX TM RCDs technical characteristics DX IS isolating switches Electrical characteristics Technical characteristics (p. 158) 4pole 400 V± Neutral on righthand side (continued) A type M 300 ma selective A type M 500 ma Hpi type MH 30 ma 1 1 1 4pole 400 V± Neutral on lefthand side AC type? 30 ma A type M 30 ma Thermal rating (Ith) 16 32 A 40 63 A 100 125 A Connection flexible 2 2 2 rigid 2 2 Insulation voltage (Hi) ± ± ± Impulse withstand voltage (Uimp) Category of use (1) Short time withstand current (Icw) Shortcircuit making capacity (Icm) 1 No. of electrical operations Protection index DX RCDs (residual circuit devices) Connection crosssection AC type? Standard applications 2) Cable (mm 2 ) RCDs rigid flexible Connection at top and bottom A type M Specific applications: dedicated lines Hpi type M H Special applications 147

MCBs DX TM 6000 10 ka thermal magnetic MCBs from 0.5 A to 63 A B and C curves A A A A Single pole 230/400 V± ± 1 1 1 1 1 1 1 1 1 1 1 Single pole neutral 230 V± Neutral on righthand side ± 1 1 1 1 1 1 1 1 1 1 2pole 230/400 V± ± ± 1 1 1 1 1 1 1 1 1 1 1 3pole 400 V± ± ± 1 1 1 1 1 1 1 1 1 1 1 1 1 3pole neutral 400 V± Neutral on righthand side ± ± 1 1 1 1 1 1 1 1 1 4pole 400 V± ± ± 1 1 1 1 1 Auxiliaries and accessories Addon modules Supply busbars These products are part of protection and distribution systems > See p. 142143 148

RCBO DX TM 6000 10 ka and DX TM 10000 residual current breaking overload from 3 A to 63 A C curve, AC and A types Single pole 230 V± AC type? 30 ma 1 1 1 1 1 1 Single pole neutral 230 V± AC type? 10 ma AC type? 30 ma AC type? 300 ma A type M 10 ma A type M 30 ma 2pole 230/400 V± AC type? 10 ma 2pole 230/400 V± (continued) AC type? 30 ma AC type? 300 ma 4pole 400 V± AC type? 30 ma AC type? 300 ma A type M 30 ma A type M 300 ma 149

MCBs DXH 10000 25 ka thermal magnetic, high breaking capacity MCBs from 2 A to 125 A C curve www.klinkmann.com A A Single pole 230/400 V± ± 1 1 1 1 1 Single pole neutral 230 V± ± 1 2pole 230/400 V± ± ± 1 1 1 1 1 3pole 400 V± ± ± 1 1 1 1 1 3pole neutral 400 V± ± ± 1 4pole 400 V± ± ± 1 1 1 1 1 Auxiliaries and accessories Addon modules B and Z curve, please consult us Supply busbars 150

MCBs DX TM 6000 15 ka thermal magnetic MCBs from 1 A to 125 A D curve A A A Single pole 230/400 V± ± 1 1 1 1 2pole 400 V± ± ± 1 1 1 1 1 1 4pole 400 V± ± ± 1 1 1 1 1 1 1 Auxiliaries and accessories Addon modules Supply busbars 3pole 400 V± ± ± 1 1 1 1 1 1 For DXMA magnetic tripping only version, please consult us 151

addon modules DX TM for DX, DXH, MCBs up to 125 A 2pole 230/400 V± AC type? 30 ma AC type? 300 ma AC type? 300 ma selective AC type? 1 A selective A type M 30 ma A type M 300 ma A type M 300 ma selective Hpi type M H 30 ma 3pole 400 V± AC type? 30 ma AC type? 300 ma AC type? 300 ma selective A type M 30 ma A type M 300 ma A type M 300 ma selective Hpi type M H 30 ma 4pole 400 V± AC type? 30 ma AC type? 300 ma 1 3 AC type? 300 ma selective AC type? 1 A selective A type M 30 ma A type M 300 ma A type M 300 ma selective Hpi type M H 300 ma selective These products are part of protection and distribution systems > See p. 142143 152

MCBs DXL 50 ka thermal magnetic high breaking capacity MCBs from 10 A to 63 A addon modules DXL for DXL 50 ka MCBs MCBs 2pole 400 V± ± ± 3pole 400 V± 4pole 400 V± Add on modules Hpi type (High immunity) MH 2pole 230/400 V± 3pole 400 V± 4pole 400 V± Auxiliaries and accessories These products are part of protection and distribution systems > See p. 142143 153

auxiliaries and accessories DX TM for MCBs, RCDs, RCBOs and isolating switches remote control DX TM for MCBs, RCDs and RCBOs Auxiliaries Signalling auxiliaries 1 ± 1 ± 1 ± Shunt releases ± = 1 ± = Undervoltage release 1 ± Accessories 2 3 Motordriven control modules For 1pole and 2pole devices 1 ± For 2pole, 3pole and 4pole devices ± 1 (1) ± Automatic resetting module 1 ± 1 2 1 154 Bold pack quantities :

STOP&GO automatic resetting for DX TM STOP&GO automatic resetting for DX TM STOP&GO automatic resetting Standard 1 A Autotest 1 A Voltage surge protectors Alarm Heating Swimming pool Refrigerator Access control Freezer Aquarium Watering These products are part of protection and distribution systems > See p. 142143 155

performance of MCBs and auxiliaries Breaking capacity in the event of a shortcircuit to earth and insulation voltage DX DX DXH DXL Single pole B and C curves B and C curves C curve Neutral D curve < 63 A DX D curve 80 to 125 A Icn 1 4500 A 6 ka 10 ka 25 ka Ui 250 V 500 V 500 V 500 V Icn 1: Breaking capacity on 1 pole for multipole MCBs in the event of a shortcircuit to earth Ui: rated insulation voltage Connection crosssection for screw terminals (in mm 2 ) Copper cable rigid flexible with or without addon modules 16 10 63 A DXL addon modules 32 25 DXL 70 50 2.5 2.5 Technical characteristics of DX auxiliaries Max. connection crosssection: 2.5 mm 2 Operating temperature: 5 to 50 C Current shunt releases Ph N C1 12 C2 Min. and max. voltage: from 0.7 to 1.1 Un Tripping time: < to 20 ms Power consumption: at 1.1 x 48 V = 121 VA at 1.1 x 415 V = 127 VA Impedance : 12 to 48 V = 23 110 to 415 V = 1640 Ω Consumption U min. U max. 12 to 48 V 522 ma 2610 ma 110 to 415 V 69 ma 259 ma U nominal voltage (Un) 12 to 48 V± and = 110 to 415 V± 110 to 125 V= Fitted with automatic breaking contact Undervoltage releases Release curves of MCBs t (time) Ph/ N/ D1 D2 U nominal voltage (Un) 24 V= 48 V= 230 V± 1 h Thermal (low overvoltage: slow release) Pullin voltage: 0.55 Un Tripping time: from 100 to 400 ms ± 10% (adjustable) Power consumption: 24 V= 0.1 VA 48 V= 0.2 VA 230 VA 1 VA MA Z B C D Magnetic (high overvoltage: fast release) 0.01 s 1 2 3 4 5 10 20 30 50 100 200 1.31.45 B C D x In (rating) Thermal release for an ambient temperature 30 C Curves Z (1) B C D MA (1) (1) Please consult us Magnetic threshold setting 2.4 to 3,6 In 3 to 5 In 5 to 10 In 10 to 14 In (10 to 20 depending on standard) 12 to 14 In 156

performance of MCBs and auxiliaries Protection of DC circuits Lexic DX and DXH MCBs (1P/2P/3P/4P In 63 A) designed for use in 230/400 V± supplies, can also be used in DC circuits In this case, the following deratings and precautions must be taken into account 1 Protection against shortcircuits Max. magnetic tripping threshold: multiplied by 1.4 Example: For a C curve MCB for which the AC tripping threshold is between 5 and 10 In, the DC tripping threshold will be between 7 and 14 In 2 Protection against overloads The time/current thermal tripping curve is the same as for AC 3 Operating voltage Max. operating voltage: 80 V per pole (60 V for singlepole N MCBs) For voltages higher than this value, several poles must be wired in series Example: for a 110 V voltage, use a 2pole MCB and connect the 2 poles in series 4 Breaking capacity 4000 A for a single pole MCB at max. voltage (80 V= per pole) At other voltages, the breaking capacities are as follows: Example: circuit earthed via the negative polarity / U = 110 V= / Isc = 10 ka / In = 32 A Protect the positive polarity using an MCB capable of breaking 10 ka at 110 V (DXH 2P 32 A with 2 poles on the positive polarity) For isolation, use a DXH 3P 32 A with 2 poles on the positive polarity and one pole on the negative polarity DXH LEXIC voltage singlepole 2P 3P 4P Acc. to 48 V 10 ka 10 ka IEC 60947.2 Icu 110 V 10 ka 10 ka DXH 32 A 2P 230 V 15 ka If isolation required DXH 32 A 3P Network earthed via a middle point: Place on each polarity the number of poles necessary for max. Isc breaking at half voltage (1) UIsc max. U/2 U/2Isc max. U/2 (1) U/2Isc max. DX voltage singlepole 2P 3P 4P Acc. to 48 V 6 ka 6 ka IEC 60947.2 Icu 110 V 6 ka 6 ka 230 V 10 ka 48 V 100 % 100 % Ics (1) 110 V 100 % 100 % 230 V 100 % DXH voltage singlepole 2P 3P 4P Acc. to 48 V 10 ka 10 ka IEC 60947.2 Icu 110 V 10 ka 10 ka (1) As a % of Icu U 230 V 15 ka 48 V 100 % 100 % Ics (1) 110 V 100 % 100 % MCB (UIsc max.) (1) (1) Only if isolation required 230 V 100 % UIsc max U=0 5 Distribution of breaking poles To choose the MCB and determine the pole distribution necessary for breaking on each of the polarities, it is necessary to know how the installation is earthed Supply with one polarity earthed: Place all the poles necessary for breaking on the other polarity If isolation is required, an additional pole must be added on the earthed polarity (1) MCB (U/2Isc max.) Example: circuit earthed via a middle point / U = 230 V= / Isxc = 6 ka / In = 10 A Protect each polarity using an MCB capable of breaking 6 ka at half voltage, i.e. 115 V (DX 4P 10 A with 2 poles on each polarity) DX LEXIC voltage singlepole 2P 3P 4P Acc. to 48 V 6 ka 6 ka IEC 60947.2 Icu 110 V 6 ka 6 ka DX 10 A 4P U UIsc max. UIsc max. Isolated earth supply: Distribute the poles necessary for breaking over the 2 polarities to provide protection in the event of a double earth fault (particularly if there are a number of circuits in parallel) (1) (1) (1) MCB (UIsc max.) 230 V 10 ka 1 st earth fault : I = O 2 sd earth fault : U and I Isc max. Example: isolated earth circuit / U = 48 V= / Isc = 4,5 ka / In = 40 A Protect the installation with an MCB capable of breaking 4.5 ka at 48 V and protect each polarity (DX MCB 2P 40 A with one pole on each polarity) DX LEXIC voltage singlepole 2P 3P 4P Acc. to 48 V 6 ka 6 ka IEC 60947.2 Icu 110 V 6 ka 6 ka 230 V 10 ka DX 40 A 2P 157

performance of MCBs and auxiliaries (continued) www.klinkmann.com Specific case of continuity of service In certain locations, where there are no personnel, in which particular care is required to ensure continuity of service, false tripping of MCBs is not permissible (isolated telephone/tv/radio relay stations, pumping stations, etc.) and a recloser provides optimum continuity of service (p. 155) 2P and 4P RCDs: withstand to shortcircuits Caution: Downstream RCD 2P/ 4P Upstream cartridge fuse gg Upstream MCB DX (B/C) DXH (B/C) 40 A 63 A 80 A 100 A DXL 1PN 63 A 80 < 125 A DPX 125 16 A 100 ka 50 ka 15 ka 10 ka 6 ka 10 ka 20 ka (1) 12.5 ka 50 ka 25 ka 25 A 100 ka 50 ka 15 ka 10 ka 6 ka 10 ka 20 ka (1) 12.5 ka 50 ka 25 ka 40 A 100 ka 50 ka 15 ka 10 ka 6 ka 10 ka 15 ka (1) 12.5 ka 50 ka 25 ka 63 A 100 ka 50 ka 15 ka 10 ka 10 ka 12.5 ka (1) 12.5 ka 50 ka 25 ka 80 A 100 ka 50 ka 15 ka 10 ka 12.5 ka (1) 12.5 ka 25 ka 100 A 100 ka 50 ka 15 ka 10 ka 12.5 ka (1) 12.5 ka 25 ka DX RCBOs residual current breaking capacity IΔm according to EN 610091 Addon modules 6000 A DXL 30000 A Motordriven control Cat.No 073 73 RCD tripping curves Automatic reclosing control device Cat.No 073 83 RCBOs P N 3000 A 2P (4 modules) 6000 A 4P 10 to 32 A (4 modules) 4500 A 4P 40 to 63 A (7 modules) 6000 A 1 t(s) 0.5 10mA 30mA 300mA 1A 0.1 0.05 A, AC or Hpi type selective (s) Hpi type A or AC type instantaneous 0.01 10 0 10 1 10 2 10 3 I (ma) 10 4 come and be trained at Innoval www.legrandelectric.com 158

MPCBs motor protection circuit breakers from 0.16 A to 32 A MPCBs motor protection circuit breakers from 0.16 A to 32 A 028 06 028 17 028 22 028 22 028 06 028 17 Conform to EN/IEC 609471, EN/IEC 609472, EN/IEC 6094741 Pack Cat.Nos Triple pole MCBs Depth: 82.5 mm Enable control and protection of motors up to 15 kw (400 V) Nominal Thermal adjustement Numbers of rating (A) range (A) modules 1 028 00 0.16 0.1 0.16 2.5 1 028 01 0.25 0.16 0.25 2.5 1 028 02 0.4 0.25 0.4 2.5 1 028 03 0.63 0.4 0.63 2.5 1 028 04 1 0.63 1 2.5 1 028 05 1.6 1 1.6 2.5 1 028 06 2.5 1.6 2.5 2.5 1 028 07 4 2.5 4 2.5 1 028 08 6.5 4 6.5 2.5 1 028 09 10 6.3 10 2.5 1 028 10 14 9 14 2.5 1 028 11 18 13 18 2.5 1 028 12 23 17 23 2.5 1 028 13 25 20 25 2.5 1 028 14 32 24 32 2.5 Auxiliaries Failure contact Contact Capacity Numbers of modules 1 028 16 N/C N/O 6 A/690 V 0.5 Signal contacts 1 028 17 N/C N/O 6 A/690 V 0.5 1 028 18 2 N/C 6 A/690 V 0.5 Undervoltage trips Coil voltage Consumption Numbers of trip/hold modules 1 028 22 230 V± 12/3.5 VA 1 1 028 23 400 V± 12/3.5 VA 1 Shunt trips 1 028 25 230 V± 3.5 VA 1 1 028 26 400 V± 3.5 VA 1 Accessories IP 65 box 1 028 29 (1) For motor MCB with auxiliary contact (Cat.Nos 028 16/17/18) and/or a trip (Cat.Nos 028 22/ 23/25/26) With knock out entries for PG 16 cable glands 4 modules Emergency stop button 1 028 30 Fits on IP 65 box for replacement of etancheity membrane Ensures IP 65 protection Pilot lights Fixing in front of box Cat.No 028 29 Voltage Color 1 028 31 230 V± Colourless 1 028 32 400 V± Colourless Padlock 1 028 34 Padlock in "off" position 3 padlocks max Ø4.5 (1) Use cable gland Cat.No 980 24 with locking nut Cat.No 980 34 The motor MCB has a signalling system for magnetic tripping that prevents all dangerous shutdown following a shortcircuit previously isolated by the device Takes 3 auxiliaries mounted simultaneously by clipping on Electrical characteristics Impulse withstand voltage: 6 kv Dissipated power per phase: 0.571.46 W Magnetic tripping: 12 max. Mechanical lifespan: 100000 cycles Electrical lifespan: 32 A (AC3): 100000 cycles Operating temperature: 20 C to 70 C Use class: A Protection index: IP 20 Connection cable crosssection (1 or 2 conductors): flexible wire 16 mm 2 or AWG 1610 Breaking capacity Cat. Nos Short circuit rated breaking capacity (ka) Rating 230 V 400 V 500 V 690 V (A) Icu Ics Icu Ics Icu Ics Icu Ics 028 00 0.16 100 100 100 100 100 100 100 100 028 01 0.25 100 100 100 100 100 100 100 100 028 02 0.4 100 100 100 100 100 100 100 100 028 03 0.63 100 100 100 100 100 100 100 100 028 04 1 100 100 100 100 100 100 100 100 028 05 1.6 100 100 100 100 100 100 100 100 028 06 2.5 100 100 100 100 100 100 8 8 028 07 4 100 100 100 100 100 100 8 8 028 08 6.5 100 100 100 100 100 100 8 8 028 09 10 100 100 100 100 42 21 8 8 028 10 14 100 100 25 12.5 10 5 2 2 028 11 18 100 100 25 12.5 4 2 2 2 028 12 23 100 100 25 12.5 4 2 2 2 028 13 25 100 100 25 12.5 4 2 2 2 028 14 32 100 100 25 12.5 4 2 2 2 IP 65 box 028 29 equipped with stop button 028 30 85.4 Ø 4.5 170 181.2 173.2 110 Thermalmagnetic tripping curve Tripping time (second) 10 000 1 000 100 10 1 0.1 0.01 0.001 0.6 1 0.8 B Electrical diagrams 028 00 to 028 14 Threephase L1 L2 L3 T1 T2 T3 A 2 3 4 6 8 10 20 30 40 60 80 x le Singlephase L1 L2 T1 T2 Approximate cold tripping time. To obtain the hot tripping time, multiply the graph value by 0.75 A = Balanced operation over 3 phases B = Operation over 2 phases (phase absence) 028 16 028 17 028 18 57 65 33 41 33 43 58 66 34 42 34 44 159

select your V.S.P. and its associated protection STEP 3 4 Optimize protection against lightning effects (V.S.P cascading) and Protect the installation against shortcircuits and overloads LEVEL 1 MAIN BOARD LEVEL 2 DISTRIBUTION BOARD STEP 1 Define the type of building STEP 2 Define the risk level and the network type RESIDENTIAL BUILDINGS AND SMALL OFFICES RISK LEVEL Very high NETWORK TYPE V.S.P ASSOCIATED PROTECTION Icc 6 ka 1PN 2 x 039 10 064 72 V.S.P ASSOCIATED PROTECTION Icc 6 ka 039 41 064 69 3P 3 x 039 10 064 92 3 x 039 40 064 89 INDIDUAL HOUSES 3PN 4 x 039 10 065 67 039 43 065 64 AND High 1PN 039 31 064 69 039 41 064 69 3P 039 32 064 89 3 x 039 40 064 89 BLOCKS OF FLATS 3PN 039 33 065 64 039 43 065 64 AND OFFICE Medium 1PN 039 41 064 69 039 41 064 69 3P 3 x 039 40 064 89 3 x 039 40 064 89 SMALL OFFICES 3PN 039 43 065 64 039 43 065 64 OFFICES AND INDUSTRIAL BUILDINGS RISK LEVEL NETWORK TYPE V.S.P ASSOCIATED PROTECTION Icc 50 ka V.S.P ASSOCIATED PROTECTION Icc 25 ka Very high 1PN 039 31 069 21 OFFICE BUILDINGS AND High 3P 3PN 030 22 3 x 173 65 (T1) (IT earthing system: 3 x 030 00 3 x 173 65 (T1)) 030 23 3 x 173 65 (T1) (ITN earthing system: 4 x 030 00 4 x 173 65 (T1)) 1PN 039 32 069 41 039 33 070 01 039 31 069 21 3P 039 22 071 33 039 32 069 41 3PN 039 23 071 48 039 33 070 01 Medium 1PN 039 31 069 21 INDUSTRIAL BUILDINGS 3P 039 22 071 33 039 32 069 41 3PN 039 23 071 48 039 33 070 01 www.klinkmann.com 160

select your V.S.P. and its associated protection For a complete protection all incoming lines (entering into the buildings) should be protected with V.S.Ps. LEVEL 3 PROXIMITY COMMUNICATION LINES Define the risk level (STEP 2) Irrespective of the requirements in the standards, the use of a voltage surge protector is strongly recommended in most cases (continuity of service, cost of equipment, etc.). Voltage surge protectors can be chosen for any type of installation based on the risk levels, which are defined as follows: Very high risk: installation equipped with external lightning conductors (L.P.S.), with a metal structure higher than surrounding buildings (or any object that can act as a lightning conductor), an installation that is isolated and located at a high point, or an installation that has been subject to previous lightning strikes IEC 60364: V.S.P. compulsory at the origin of the installation (main board) with L.P.S. (lightning protection system) PROXIMITY V.S.P.; INSIDE COMMUNICATION DISTRIBUTION BOX High risk: installation with overhead power supply, in a mountainous area, isolated, at the end of a line, near a body of water, trees, etc. IEC 60364: V.S.P. compulsory with overhead lines in AQ2 areas (see p. 163) Medium risk: other types of installation (installations in urban areas, in low, flat areas and low and medium height mountainous areas, underground power supplies, etc.) Celiane Cat.No 671 93 (p. 542) or Mosaic Cat.No 775 40 (p. 806) or Multioutlet extensions Cat.Nos 6946 40/42/44/51/56 (p. 762) PROXIMITY V.S.P.; Protection of all the lines entering the building is strongly recommended (including communication lines: telephone, data, etc.) INSIDE COMMUNICATION DISTRIBUTION BOX Optimize protection (STEP 3) Protection of an installation against transient overvoltages can only generally be guaranteed with several levels of voltage surge protectors used together in cascade (see also p. 164). In addition to the energy aspect explained below, 2 or 3 levels of voltage surge protectors are in fact usually necessary in order to limit overvoltages connected with the fact that lightning is a high frequency phenomenon. In order to limit overvoltages as much as possible, a voltage surge protector must always be installed as close as possible to the equipment to be protected. However, proximity protection (Level 3) on its own can only protect the equipment connected to it downstream, and above all, it cannot adequately limit the energy. To do this, a voltage surge protector is necessary at the head of the installation (Level 1) to shunt the majority of the energy to earth. Likewise, a voltage surge protector on its own at the head of the installation (Level 1) cannot protect the whole installation and the equipment connected to it, due to the fact that it allows residual energy to pass and that lightning is a high frequency phenomenon (see p. 164). For these reasons, depending on the scale of the installation and the types of risk (exposure and sensitivity of equipment, criticality of continuity of service), circuit protection (Level 2) is necessary in addition to protection of the head of the installation Celiane Cat.No 671 93 (p. 542) or Mosaic Cat.No 775 40 (p. 806) or Multioutlet extensions Cat.Nos 6946 40/42/44/51/56 (p. 762) Protection of all the lines entering the building is strongly recommended (including communication lines: telephone, data, etc.) Protect the installation against shortcircuit and overloads (STEP 3) The supply circuit of the VSP must always be protected against shortcircuits and overloads by its associated protection device in accordance with discrimination rules. Select the associated MCB (DX, DXH or DXL) with the shortcircuit rating adapted to your installation requirements V.S.P. Cat.Nos 039 10/20/21/22/23 039 30/31/32/33/40/41/43 Icc 2P 3P 4P 2P 3P 4P 10 ka 064 72 064 92 065 67 064 69 064 89 065 64 15 ka 069 24 069 44 070 04 069 21 069 41 070 01 25 ka 071 18 071 33 071 48 069 21 069 41 070 01 50 ka 071 18 071 33 071 48 Not allowed Not allowed Not allowed Legrand_Protection_LR_DXIS_DX_DXH_DXD_Curve_DXL_en_0811.pdf Helsinki tel. 358 9 540 4940 automation@klinkmann.fi St. Petersburg tel. 7 812 327 3752 klinkmann@klinkmann.spb.ru Moscow tel. 7 495 641 1616 moscow@klinkmann.spb.ru www.klinkmann.com Yekaterinburg tel. 7 343 376 5393 yekaterinburg@klinkmann.spb.ru Samara tel. 7 846 273 95 85 samara@klinkmann.spb.ru Кiev tel. 38 044 495 33 40 klinkmann@klinkmann.kiev.ua Riga tel. 371 6738 1617 klinkmann@klinkmann.lv Vilnius tel. 370 5 215 1646 post@klinkmann.lt Tallinn tel. 372 668 4500 klinkmann.est@klinkmann.ee Мinsk tel. 375 17 200 0876 minsk@klinkmann.com