YCCS TE-6800 Series Temperature Sensors

Similar documents
TM-11x1 Series Room Temperature Module

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

YCCS Zone/Bypass Damper Assembly

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

TM-9100 Series Room Command Module

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

YCCS Zone/Bypass Damper Assembly

VA-7450 Series. Electric Valve Actuators

A419ABG-3C Electronic Temperature Control

VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators

VA9203-AGx-2Z Series On/Off and Floating Point Electric Spring Return Valve Actuators

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

VA-715x Electric Valve Actuator

M9300 Series Switch Kits

M9208-AGx-x Series On/Off and Floating Point Electric Spring Return Actuators

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

M9208-Bxx-3 Series On/Off Electric Spring Return Actuators

System 350 P352AB Electronic Pressure Control Series

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

M9208-xxx-x Series Electric Spring Return Actuators

M9203-xxx-2(Z) Series Electric Spring Return Actuators

M9203-xxx-2(Z) Series Electric Spring-Return Actuators

M9300 Series Potentiometer Kits

MicroTech III Water Source Heat Pump Wall-Mounted Room Temperature Sensors

D24-53 Series Electric Non-Spring Return Actuators 53 lb in Models (6 N m)

M9216 Series Electric Spring Return Actuators

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

M9208-xxx-x Series Electric Spring Return Actuators

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

M9210-xxx-3 Electric Spring Return Actuators

M9208-xxx-x Series Electric Spring-Return Actuators

VA-715x Electric Valve Actuator

System 350 S350C Temperature Slave Stage Module

M9208-xxx-x Series Electric Spring Return Actuators

TE-6300 Series Temperature Sensors

CSD Series Current Devices Split Core

BAPI-Stat 3 Room Sensor

SEN and SEN Outdoor Air Temperature Sensors

P445 Series Electronic Lube Oil Control

VA-4233-GGx Series Electric Valve Actuators

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators

VA9905 Actuator and VG1600 Series Six-Way Valves

M9220 Series Electric Spring-Return Actuators

Commerical Comfort System (CCS) Variable Air Volume (VAV) Zone Pressure Independent Damper Controller

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

Combined Ventilation Controller RVWS-T-224HA

System 350 S350P Proportional Plus Integral Temperature Stage Module

M9206-GGx-2S Series Proportional Electric Spring Return Actuators

M9220-xxx-3 Electric Spring Return Actuators

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

M9220-xxx-3 Electric Spring Return Actuators

A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

Digital Room Thermostats with Touch Screen LCD

TE-6300 Series Temperature Sensors

MP-5400 Series. Application. Features. Applicable Literature. Electronic Positive Positioning Hydraulic Actuator General Instructions

Digital Fan Coil Thermostats with 0(2)-10 VDC Fan Output

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure

TS , -850 Series TS , -850 Series TS-57031, TS

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

QUICK START GUIDE VAV CONTROLLERS & WALL SENSORS rue Charles, Suite 100, Mirabel, QC, J7J 1X9

VA9203-AGx / VA9203-Bxx / VA9203-GGx

VA-720x Electric Valve Actuator

M x Series Valve Linkage Kits

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

SLC-811X Series. Single Loop Proportional Temperature Controller General Instructions APPLICATION SPECIFICATIONS

MA-5200 Series MA-5300 Series

M9102-AGA-3S and M9104-xGA-3S Series Electric Non-Spring Return Actuators

MF4E MF4E

LOW AMBIENT ACCESSORY INSTALLATION INSTRUCTION

MF /MS Series

M100F Incremental Motor Actuator R81F Interface Board

M9104-AGP-2S Series Electric Non-Spring Return Actuator with Pressure Sensor for VAV Applications Part No , Rev. B

M9300 Series Electric Non-Spring Return Actuators

ES177B2(-S) Series Proportional Electric Spring Return Actuators

MA40-704X Series MA41-707X Series MA41-715X Series

WPT Installation Manual. Wireless Pneumatic Thermostat- WPT-800 Series. 1. Overview. 1.1 Parts Included. 1.2 Prerequisites for Installation

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

Powers TM Controls SW 134 Pressure Electric Switch (Adjustable Differential)

Damper Actuator Installation

General Description. Product Specification. Document Digital Temperature Interlock

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

F261 Series Fluid Flow Switches

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

A25 Series Warm Air Control with Manual Reset

VA-8020 Floating Valve Actuator

A91 Series Thermistor Temperature Sensors For Duct, Immersion and Space Sensing

OPERATING INSTRUCTIONS

9142-B-P-156/AF. User s Guide. Field Metrology Well. Distribution is limited to DoD and U.S. DoD contractors only.

AV-8020 Series Floating Control Actuated Valve

VA2202-xxx-2 Series Electric Spring Return Valve Actuators

High Frequency SineWave Guardian TM

SetPoint 501 and 501s Controllers Installation and Operation Manual

ASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY

APPLICATION GUIDE. Simplicity LINC GATEWAY OVERVIEW. 24 must be grounded close to the Simplicity LINC

INSTALLATION INSTRUCTION

M9109 Series Electric Non-spring Return Actuators

M Ball Valve Linkage Kit

METROLOGIC INSTRUMENTS, INC. MX001 Industrial Control Interface Installation and User s Guide

Transcription:

YCCS TE-6800 Series Temperature Sensors TE-68xx-xNN0S Installation Instructions 85-YIM-B-070 Applications The York Commercial Comfort System (YCCS) TE-68xx-xNN0S Series Temperature Sensors provide temperature sensing in room wall-mount applications. The temperature sensor features local setpoint temperature adjustment and temporary occupancy override. A warmer/cooler dial is included on certain models for minor temperature adjustments from the setpoint. An occupancy override button allows the user to signal the controller that the space is occupied, to request an override of time-of-day scheduling when the space is occupied outside of the normal occupied schedule. All models include DIP switches to enable or disable unit functions. The wires connecting the sensor to the controller are terminated using a screw terminal block, which offers wiring flexibility. IMPORTANT: Use the TE-6800 Series Temperature Sensor only to provide input to equipment under normal operating conditions. Where failure or malfunction of the TE-6800 Series sensor element could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the TE-6800 Series sensors. Installation Special Tools Needed A /6 in. (.5 mm) hex wrench or a T-000-9 hexhead adjustment tool is required during installation. Mounting Location Considerations Locate the TE-6800 Series sensor: on a partitioning interior wall, and approximately 5 ft (.5 m) above the floor in a location of average temperature away from direct sunlight, radiant heat, outside walls, behind doors, air discharge grills, stairwells, or outside doors away from steam or water pipes, warm air stacks, unconditioned areas (no heating and no cooling), or sources of electrical interference Note: The TE-6800 Series sensor is shock and vibration resistant; however, be careful not to drop the unit or mount it where it could be exposed to excessive vibration. The following ambient operating conditions apply: Temperature: to F (0 to 55 C) Humidity: 0 to 95% Relative Humidity (RH), noncondensing; 86 F (0 C) maximum dew point To mount the sensor to the wall:. Use a /6 in. (.5 mm) hex wrench or T-000-9 hex-head adjustment tool to loosen the security screw on the top of the unit.. Insert a blade screwdriver into the slot next to the security screw location, and then carefully pry the top edge of the sensor assembly away from its mounting base. IMPORTANT: Do not remove the Printed Circuit Board (PCB). Removing the PCB voids the product warranty.. Pull out approximately 6 in. (5 mm) of cable from the wall, and insert the cable through the hole in the mounting base.

85-YIM-B-070. Align the mounting base on the wall, and use the base as a template to mark the location of the two mounting holes on the wall surface. Note: Make sure to position the mounting base correctly with the security screw located on the top edge of the base. 5. Secure the mounting base to the wall using the appropriate mounting hardware (field supplied). 6. Set DIP switch in LED OFF position (Figure ) and wire the unit as illustrated in Figure. See the Internal Wiring Diagrams and Setup and Adjustments sections for additional information. For models featuring a screw terminal block, wire the unit as illustrated in Figure. 7. Align the tabs on the bottom edge of the mounting base with the slots on the bottom edge of the sensor assembly, and carefully snap the assembly onto the mounting base. Keep wires as short as possible to minimize sensor error. Each 50 ft (76 m) run of 8 AWG wire or 50 ft (5 m) of AWG wire creates F (0.56 C) error for a nickel sensor due to wire resistance. To maintain less than F (0.56 C) error hold the total resistance of all sensor wiring below ohm. When wiring the TE-6800, do not run low voltage wiring in the same conduit as line voltage wiring or other conductors supplying highly inductive loads. Internal Wiring Diagrams Figure shows the internal wiring diagram and Figure shows the terminal block designations. The terminals are identified in Table. See the Setup and Adjustments section and Figure for an explanation of the Light-Emitting Diode (LED) and Push Button (PB) modes. Make connections pairing the following wires: sensor (Terminal and Terminal ) setpoint (Terminal and Terminal ) Note: Make sure to align the terminal block pins with the holes in the terminal block. 8. Use a /6 in. (.5 mm) hex wrench or T-000-9 hex-head adjustment tool to tighten the security screw and fasten the sensor assembly to the mounting base. Note: Shielding is not required. If used, follow the system controller s recommendations for grounding the shield. Wiring! CAUTION: Risk of Property Damage. Do not apply power to the system before checking all wiring connections. Short circuited or improperly connected wires may result in permanent damage to the equipment. IMPORTANT: Use copper conductors only. Make all wiring connections in accordance with local, national, and regional regulations. field-installed override push button jumper (Terminal and Terminal 6) Note: The Manual Override PB does not respond when the DIP switch positions are in the OFF position. Table : Terminal Block Wiring Terminal Signal Designation Temperature Sensor Temperature Sensor Setpoint Warmer/Cooler 5 6 (Manual Override) 7 8

85-YIM-B-070 Setpoint RTD Manual Override Button Temperature Sensor Temperature Sensor Setpoint Warmer/Cooler Setpoint 5 6 Field-installed jumper to enable manual override push button Internal wiring diagram with DIP switches set as shown on the right, LED Mode = OFF and manual override push button enabled. O N Figure : Terminal Block Wiring Designations (LED OFF Mode and Manual Override PB Enabled) Figure : Terminal Block Location and Wiring Setup and Adjustments Controller Configuration Switch A DIP switch configures the TE-6800 Series sensor for use with the desired controller by enabling or disabling the manual override PB and the LED. To change the controller mode, use the three position DIP switch located on the lower right side of the PCB (Figure ). LED MODE DIP switch in the default position. OFF KEY: O N ON Switch is in up position (ON) NO PB Switch is in down position (OFF) REMOVING THE CIRCUIT BOARD VOIDS WARRANTY Note: Read switch positions from left to right. Figure : DIP Switch Positions! CAUTION: Risk of Property Damage. Do not use switch settings other than those shown in Figure. Using other switch settings may cause incorrect controller operation or damage to the element, controller, and/or controlled equipment. Warmer/Cooler Setpoint and No Setpoint Models For the Warmer/Cooler Setpoint and No Setpoint models, the factory default is the LED Mode: ON. The DIP switch positions enable/disable the functions listed in Table : Temperature Setpoint Adjust the setpoint using the setpoint adjustment dial. Rotate clockwise to raise the temperature. Rotate counterclockwise to lower the temperature.

85-YIM-B-070 Table : LED Mode and Functions LED Functions Switch Positions Mode Enabled Disabled OFF Sensor, PB LED Switch positions are OFF, ON, and OFF. The LED remains off at all times. ON LED, Sensor, PB --- Switch positions are factory-set ON, OFF, and ON. The controller determines the LED mode. NO PB Sensor LED and PB All switch positions are OFF. LED is off, and the PB does not function. Troubleshooting TE-6800 Series Temperature Sensors are recommended for use only with York digital controllers. If the TE-6800 Series sensor is not functioning properly, use the following troubleshooting procedures:. Check that the TE-6800 Series sensor is mounted in a location indicative of the space temperature (for example, away from drafts or sunlight).. Check the wiring and verify that it is correct.. Check the override status at the System Manager or Zone Controller (Temporary Occupancy mode versus Unoccupied mode). Technical Specifications YCCS TE-6800 Series Temperature Sensors (Part of ). Check the setpoint settings. 5. Replace the TE-6800 if the troubleshooting suggestions fail to remedy the problem. Repair Information Do not field repair the TE-6800 temperature sensors. Keep the air vents clean and free from dust or obstruction. If the TE-6800 Temperature Sensor fails to operate within its specifications, replace the unit. For a replacement sensor, contact the nearest Source representative. Nickel Sensor Temperature Sensor:,000 ohm thin-film nickel Temperature Coefficient: Approximately ohms per F (5. ohms per C ) Reference Resistance:,000 ohms at 70 F ( C) Accuracy: ±0. F at 70 F (±0.8 C at C) Setpoint Range Single Adjustment: Warmer/Cooler, -5 to 5 F Resistance: Nominal.5k ohm Sensor Response Time One time constant: 0 minutes at 0 feet per minute airflow Field Connections Terminal Block: Screw type terminals for 8 to AWG wire Manual Override Integral momentary push button (DIP switch selectable) Ambient Operating Conditions to F (0 to 55 C) 0 to 95% RH, noncondensing; 86 F (0 C) maximum dew point Ambient Storage Conditions -0 to 60 F (-0 to 7 C) 0 to 95% RH, noncondensing; 86 F (0 C) maximum dew point Mounting Style Includes base and hardware for surface mounting. Materials White thermoplastic Dimensions (H x W x D) -/ x -/ x -7/6 in. (8 x 8 x 6 mm)

YCCS TE-6800 Series Temperature Sensors (Part of ) Shipping Weight lb (0.5 kg) Compliance United States UL Listed File E070 CCS PAZX, Under UL 96, Energy Management Equipment Canada UL Listed, File E070 CCN PAZX7, Under CAN/CSA C. No. 05, Signal Equipment Europe CE Mark, EMC Directive 00/08/EC; EN600-6- (00) Generic Emission Standard for Residential and Light Industry EN600-6- (00) Generic Immunity Standard for Heavy Industrial Environment Australia and New Zealand C-Tick Mark, Australia/NZ Emissions Compliant Subject to change without notice. Printed in U.S.A. Copyright 00 by Johnson Controls, Inc. All rights reserved. 85-YIM-B-070 Ref: 07 Supersedes: 85-YIM-A-0808, Ref: -009- Johnson Controls Unitary Products 5005 York Drive Norman, OK 7069