P-SERIES VFD WITH BYPASS

Similar documents
Large Drive. Variable Speed Control is Just the Beginning. Franklin FastApp Firmware. Variable Speed Control NEMA. Standard Features (Enclosed Drives)

Submittal Data Information

Submittal Data Information

Molded Case Circuit Breakers

Delta Products VFD CP2000 Bypass Control Packages.

Symbol Input rating Symbol 2 Three-phase, 200 ~ 230V N 4 Three-phase, 380 ~ 480V. None. Loader. Graphic. Loader

UTS400 SELECTION GUIDE CATALOG NUMBERING [PRODUCT SELECTION] UTS400 NT ATU 400A 3P LL LSIS UL MCCB

2015 Fall Product Catalog ADVANCED CONTROLS & DRIVES

A200 NEMA Contactors and Starters A200

Sensorless Vector Drives

Varispeed E7. Varispeed E7. Varispeed. Varispeed E7. Varispeed E7. Varispeed E7 INVERTER SERIES

SYSDrive Frequency Inverter

Description 1/8-7.5HP

HVW701 HVAC Drive with By-Pass

Phoenix DX Sensorless AC Vector Drive. 3 HP to 3500 HP

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

ACW Molded-Case Circuit Breaker UL 489 Listed

RVS-DN Digital Reduced Voltage Motor Starter

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

GS2 Series - Introduction

J1000. Compact Inverter Series.

Data Sheet DIN Rail Miniature Circuit Breakers Ex9 Series - B1

Selection HP V Class V Class Input: 3 Phase Output Voltage: 3 Phase V at 60Hz Voltage Toleran

Shenzhen Sine Electric Co., Ltd.

Honeywell CORE Drive FEATURES APPLICATION SPECIFICATION DATA

ESW/PESW. Non-Combination Starters

SECTION MOTOR CONTROL

Constant torque, Constant power, Torque boost Six selectable pre-set patterns

Motors Automation Energy Transmission & Distribution Coatings UBW. Molded-Case Circuit Breaker UL 489 Listed

ACW. Molded-Case Circuit Breaker UL 489 Listed. ACW Catalog Number Sequence

AQUAVAR Intelligent Pump Controller TECHNICAL BROCHURE BCPAQIPC R2

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

MPW Series. MPW Catalog Number Sequence. Standard Features MPW U004

Application Description

Designed for ease of integration with automation systems

cor Long Run Experience

NB1 Miniature Circuit Breaker

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

USB Copy Unit COM ERR. Copy. RJ-45 / USB Adapter. Verify. Read LOCK YASKAWA JVOP-181. Remote Operator Extansion Cable. Communication Option Board

L300P Inverter Specifications

RVS-DX Digital Reduced Voltage Motor Starter

Contactors & Overload relays

RS232 Communications cable with PC ER M. RJ-45 / USB Adapter Remote Operator Extansion Cable. Communication Unit. Mounting Accesories

Metasol MC 4pole. Contactor. Overview 108 Table of specifications 110 Dimension 114. Contents

EPS-ECONOMY PUMP STARTER

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Low voltage circuit breakers

Technical Information

ADJUSTABLE FREQUENCY CONTROLS SENSORLESS VECTOR CONTROL. Dual Rating. Technologies Inc. mgitech.com NRTL/C CERTIFIED

MAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-

J1000 D E F I 1000 J1000 J1000 J1000 J1000

VS1PFB 230V, 50/60 Hz, 3-Phase

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

Selection Guide Motor Control Device Solutions

High performance Vector Control. Ratings. System configuration

Quick Start Guide of CV50- ControlVIT Series

ACW Molded-Case Circuit Breaker UL 489 Listed

HVAC-R Drive Products

JC-VSD FP Series II Drives Product Bulletin 1

AF40... AF96 3-pole contactors Technical data

VSD Series II Variable Speed Enclosed IntelliPass and IntelliDisconnect Drives

Technical Data Accessories MCBs Ex9B.

Molded case circuit breakers

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

LIFT INVERTER SERIES L1000V DE ES FR IT 1000V L1000V L1000V L1000V L1000V

CI-tronic Soft Start Motor Controller Type MCI 25B with Brake

SINUS PENTA 2T/4T SINUS PENTA 2T/4T

RM B. Features. Drive Model Number Scheme. A RM6 Product Series

BAC Custom Engineered Controls

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

SIDERMAT Load break switches for power distribution from 250 to 1800 A with tripping function

MaxPak Plus Analog DC V S Drive

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

Datasheet VFD-CP2000. Type number key A B C S -XY VFD 007 CP 43. Option cards. Slot 3

VFD E Series. Features

SJ300 Inverter Specifications

1/2 thru 1.5 Hp 1/2 thru 3 Hp 2 thru 5 Hp 1 thru 10 Hp

C -5 to +55 (0.8 to 1.1Uc) Permissible o

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

CTi Automation - Phone: Fax: Web:

ROBICON W120 enclosed drive

CI-Tronic Soft start motor controller MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 40-3D and MCI 50-3 I-O

Data Sheet Manual Motor Starter Ex9S32 Series

Data Sheet Manual Motor Starter Ex9S32 Series

Motors Automation Energy Transmission & Distribution Coatings EDP11. Enclosed Drive Panel USA EDP11

SECTION MOTOR CONTROLLERS

MULTI LANGUAGE KEYPAD

D509E. Manual Motor - Starters

Meta Solution. Contactors and Overload relays

825-P Modular Protection System for motors Specification Guide

QUEENSLAND URBAN UTILITIES

ATyS t M - ATyS g M Automatic Transfer Switching Equipment from 40 to 160 A

Motors Automation Energy Transmission & Distribution Coatings. UMBW UL489 and UL1077 Thermal-Magnetic MCB

Technical Information

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

ACH550 VARIABLE FREQUENCY DRIVES FOR HVAC APPLICATIONS

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

150 B180 N B D A 8L. Enclosure Type. Input Line Voltage Open Type V AC, 3-phase, 50 and 60 Hz V AC, 3-phase, 50 and 60 Hz

Transcription:

P-SERIES VFD WITH BYPSS 1 40 HP (200~230 VC) 1 100 HP (380~480 VC), 3Ø Enclosed Bypass - UL Type 3R Standard Controls for Bypass & Local/Remote Operation Special Instructions: FETURES ND OPTIONS Compact vertical design preserves wall space Includes standard MMS disconnect, Hand/Off/ uto & VFD/Off/Bypass switches Fireman s override/smoke purge ready Choose from 2 or 3 contactor configurations UL 508C rating for maximum motor protection Optional Features Door mounted control options for manual speed potentiometer, LED pilot lights and more Input circuit breaker Optional installed input or output reactors Integrated electronic overload for full phase protection in bypass mode Panel space heaters available for ambient temperatures below 14 F variety of NEM rated enclosures to meet application requirements (Stainless, fiberglass, watertight, etc.) Weatherproof, white powdercoat Type 3R enclosure for rooftop and outdoor mounting.

SIZING INFORMTION TBLE P-Series VFD Bypass - 3-Phase, 200~230V Standard duty (VT) Bypass with Drive Isolation (3-Contactor Bypass Equivalent) 2-Contactor Bypass Line Reactor Options HP kw Rating UL Type 3R UL Type 3R Installed 3% Installed 5% Disconnect Part-Number Contactor Part-Number 1 1.9 CIE3-BYP001-P2/3 CIE3-BYP001-P2 VFD-KDR25L VFD-KDR25H CMS-32HI-6 MRC-9B 2 3 CIE3-BYP002-P2/3 CIE3-BYP002-P2 VFD-KDR27L VFD-KDR26H CMS-32HI-8 MRC-12B 3 4.6 CIE3-BYP003-P2/3 CIE3-BYP003-P2 VFD-KDR28L VFD-KDR28H CMS-32HI-13 MRC-12B 5 6.1 CIE3-BYP005-P2/3 CIE3-BYP005-P2 VFD-KDRB22L VFD-KDRB25H CMS-32HI-17 MRC-18B 7.5 5.5 CIE3-BYP007-P2/3 CIE3-BYP007-P2 VFD-KDRB23L VFD-KDRB26H CMS-32HI-26 MRC-50L 10 7.5 CIE3-BYP010-P2/3 CIE3-BYP010-P2 VFD-KDRD25L VFD-KDRD21H CMS-63HI-40 MRC-50L 15 11 CIE3-BYP015-P2/3 CIE3-BYP015-P2 VFD-KDRD24L VFD-KDRD22H CMS-63HI-50 MRC-50L 20 15 CIE3-BYP020-P2/3 CIE3-BYP020-P2 VFD-KDRD26L VFD-KDRC22H CMS-63HI-63 MRC-65L 25 18.5 CIE3-BYP025-P2/3 CIE3-BYP025-P2 VFD-KDRC22L VFD-KDRF28H CMS-100HI-75 MRC-75L 30 22 CIE3-BYP030-P2/3 CIE3-BYP030-P2 VFD-KDRF24L VFD-KDRF25H CMS-100HI-100 MRC-100L 40 30 CIE3-BYP040-P2/3 CIE3-BYP040-P2 VFD-KDRF25L VFD-KDRF26H UTS250NNU FTU MRC-130L P-Series VFD Bypass - 3-Phase, 380~480V Standard duty (VT) Bypass with Drive Isolation (3-Contactor Bypass Equivalent) 2-Contactor Bypass Line Reactor Options HP kw Rating UL Type 3R UL Type 3R Installed 3% Installed 5% Disconnect Part-Number Contactor Part-Number 1 2 CIE3-BYP001-P4/3 CIE3-BYP001-P4 VFD-KDR8L VFD-KDR8H CMS-32HI-2.5 MRC-9B 2 3.2 CIE3-BYP002-P4/3 CIE3-BYP002-P4 VFD-KDR1L VFD-KDR1H CMS-32HI-4 MRC-9B 3 4.8 CIE3-BYP003-P4/3 CIE3-BYP003-P4 VFD-KDR2L VFD-KDR2H CMS-32HI-6 MRC-9B 5 6.4 CIE3-BYP005-P4/3 CIE3-BYP005-P4 VFD-KDR3L VFD-KDR3H CMS-32HI-8 MRC-9B 7.5 5.5 CIE3-BYP007-P4/3 CIE3-BYP007-P4 VFD-KDR4L VFD-KDR4H CMS-32HI-13 MRC-12B 10 7.5 CIE3-BYP010-P4/3 CIE3-BYP010-P4 VFD-KDR5L VFD-KDR5H CMS-32HI-17 MRC-18B 15 11 CIE3-BYP015-P4/3 CIE3-BYP015-P4 VFD-KDRB2L VFD-KDRB2H CMS-63HI-26 MRC-22B 20 15 CIE3-BYP020-P4/3 CIE3-BYP020-P4 VFD-KDRB1L VFD-KDRC3H CMS-63HI-32 MRC-50L 25 18.5 CIE3-BYP025-P4/3 CIE3-BYP025-P4 VFD-KDRD1L VFD-KDRC1H CMS-63HI-40 MRC-50L 30 22 CIE3-BYP030-P4/3 CIE3-BYP030-P4 VFD-KDRD2L VFD-KDRE2H CMS-63HI-50 MRC-50L 40 30 CIE3-BYP040-P4/3 CIE3-BYP040-P4 VFD-KDRC1L VFD-KDRF4H CMS-63HI-63 MRC-65L 50 37 CIE3-BYP050-P4/3 CIE3-BYP050-P4 VFD-KDRF2L VFD-KDRF1H CMS-100HI-75 MRC-75L 45 CIE3-BYP0-P4/3 CIE3-BYP0-P4 VFD-KDRF4L VFD-KDRF2H CMS-100HI-90 MRC-85L 75 55 CIE3-BYP075-P4/3 CIE3-BYP075-P4 VFD-KDRF3L VFD-KDRH2H CMS-100HI-100 MRC-100L 100 75 CIE3-BYP100-P4/3 CIE3-BYP100-P4 VFD-KDRH3L VFD-KDRH1H UTS250NNU FTU MRC-150L Options Part Number VFD-RPL* VFD-BPL* VFD-FPL* VFD-SPD VFD-EOL Description Run Pilot Light (Green Standard) Bypass Pilot Light (mber Standard) Fault Pilot Light (Red Standard) Door Mounted Speed Potentiometer Solid-state Bypass Overload * Select 24V or 120V based on package control voltage. For UL Type 1 select 24V. For UL Type 3R & 12 select 120V. Part Number CI-BN-COM CI-LWP-COM CI-N2-COM VFD-BYP-R VFD-KPD/4X Description BCnet communication card Lonworks communication card N2 communication card Drive auto bypass with relay Door Mounted Keypad with Type 4X Cover

Specification Table P-Series Bypass Specifications Output ratings Input ratings Operation Input signal Output signal Protective functions Operating environment Voltage (V) Three phase, 200~230V, Three phase, 380~480V Frequency (Hz) 0~120Hz Voltage (V) Three phase, 200~230V (-15%, +10%), Three phase, 380~480V (-15%, +10%) Frequency (Hz) 50~Hz (±5%) Input Power Factor <.95 from no load to full load Drive Efficiency >96% Control method V/F control, Sensorless vector control Frequency setting resolution Digital reference: 0.01Hz (below 99Hz) & 0.1Hz (100Hz and over); nalog reference: 0.06Hz at Hz Frequency setting accuracy Digital: 0.01% of maximum output frequency; nalog: 0.1% of maximum output frequency V/F ratio Linear, Square, User V/F Overload capacity 1 minute at 120%, 10 seconds at 150% (with inverse characteristic proportional to time) Torque boost uto, Manual (0~15%) Multi-function input terminals Total 8 inputs (programmable) nalog output 0~10V linear Operator control 32-character LCD keypad, Terminals, ModBus-RTU communication Optional, ProfiBus-DP, DeviceNet, F-Net, BCnet, LonWorks Frequency setting nalog: 0~10V, 4~20m, additional port for Sub-Board (0~10V); Digital: Keypad, Communication Start signal Forward, Reverse Multi-step operation Setting up to 17 speeds (using multi-function terminal) Multi-step accel/decel time Operational functions Emergency stop uto operation Jog Fault reset 0.1~00 seconds. Maximum 8 pre-defined steps using multi-function terminals DC braking, Frequency limit, Frequency jump, Second motor function, Slip compensation, Reverse rotation prevention, uto restart, Inverter bypass, uto-tuning, Dual PID control Stops output from inverter Operates from internal sequence by setting multi-function terminal (5 way x 8 step) Jog operation Resets fault signal when protective function is active Operational status Frequency detection, Overload alarm, Stall, Overvoltage, Undervoltage, Inverter overheat, Run, Stop, Constant speed, Speed search, Fault output, Inverter bypass, uto-operation sequence Indicator Output frequency, Output current, Output voltage, DC voltage, Output torque (output voltage: 0~10V) Overvoltage, Undervoltage, Overcurrent, Inverter overheat, Motor overheat, I/O phase loss, Fuse open, Trip Ground fault, External fault 1, 2, Option fault, Overload, Speed command loss, Hardware fault, Communication error, etc. larm Stall, Overload Temperature sensor fault mbient temperature -10 ~40 C (50 C when derated 20%) or 14 ~104 F (122 F when derated 20%) Storage temperature -20 ~65 C or -4 ~149.5 F Humidity Less than 95% Relative Humidity maximum (non-condensing) Vibration Below 5.9m²/sec (=0.6g) ltitude Below 1,000m (3,300ft): Derate VFD by 10% for every additional 1,000m pplication site Pollution degree 2. No corrosive gas, combustible gas, oil mist or dust

SUBMITTED EQUIPMENT SCHEDULE QTY Tag Configuration Part Number HP Voltage Enclosure Line Reactor Part Number natomy Control Options CIE3-BYP010-P4/3 HP Rating (Select Motor HP) Bypass Contactor Configuration Voltage Rating (P2 equates 200-230V) Enclosure Rating (Type 1 or 3R) VFD-RPL* VFD-FLT* VFD-HO Run Pilot Light (Green Standard) Fault Pilot Light (Red Standard) Hand/Off/uto Switch VFD-EOL Solid-State Bypass Overload VFD-SPD Door Mounted Speed Potentiometer VFD-KPD Door Mounted Keypad VFD-KPD/4X Door Mounted Keypad with Type 4X Cover CI-BN-COM BCnet Communication Card CI-LWP-COM Lonworks Communication Card CI-N2-COM N2 Communication Card

P-SERIES POWER CIRCUITS (1 75HP)

P-SERIES CONTROL WIRING (1 75HP)

P-SERIES POWER CIRCUITS (100HP)

P-SERIES CONTROL WIRING (100HP)

COMPONENT SPECIFICTIONS The following section details the various components sizing and ratings. To locate your component part numbers for the EMS reference the sizing information table above. THREE POLE CONTCTORS 3-POLE CONTCTOR SPECIFICTIONS Type Frame Size Terminal Type Number of poles Rated operation voltage, Ue Rated insulation voltage, Ui Rated frequency Rated impulse withstand voltage, Uimp Max. operating rate in operating cycles per hour (C3) tmechanical Durability Electrical C-1, Thermal current kw 200/240V Current and power UL rating (50/Hz) kw 380/440V tc-3 500/550V kw kw Continuous current Single Phase Three Phase 110~120V HP 220~240V HP 200~208V HP 220~240V HP 440~4 80V HP 550~0V HP NEM size Weight MRC Size and weight Size (WxHxD) Weight MRD Size (WxHxD) uxiliary (standard) Side mount uxiliary Front mountt lbs in lbs in MRC-9 MRC-12B MRC-18B MRC-22B 22F Screw 3 pole 50/Hz 6kV 1800 operations per hour 15 mil. operations 2.5 mil. operations 25 25 40 40 2.5 11 4 9 4 7 4 6 3.5 13 5.5 12 7.5 12 7.5 9 4.5 18 7.5 18 7.5 13 7.5 9 5.5 22 11 22 15 20 15 18 25 25 32 32 0.5 0.75 1 2 1.5 2 3 3 2 3 5 7.5 3 5 7.5 7.5 5 7.5 10 10 7.5 10 15 15 00 0 0.73 lbs 1.77 x 2.89 x 3.39 in 1.12 lbs 1.77 x 2.89 x 4.63 in 1NO & 1NC M-1 C-2, C-4 MRC-50L MRC-65L 40F Screw 3 pole 1000V 50/Hz 8kV 1800 operations per hour 12 mil. operations 2 mil. operations 70 100 15 55 22 50 30 43 30 28 18.5 65 30 65 33 33 35 70 100 3 5 10 15 20 25 25 30 40 50 50 2 1.98 lbs 2.17 x 4.17 x 4.69 in 2.65 lbs 2.17 x 4.17 x 5.76 in M-1 C-2, C-4 *Minimum conduct current of auxiliary contactor is DC 17V 5m **10 max, Not motor duty rated.

3-POLE CONTCTOR SPECIFICTIONS (CONT.) Type Frame Size Terminal Type Number of poles Rated operation voltage, Ue Rated insulation voltage, Ui Rated frequency Rated impulse withstand voltage, Uimp Max. operating rate in operating cycles per hour (C3) tmechanical Durability Electrical C-1, Thermal current kw 200/240V Current and power UL rating (50/Hz) kw 380/440V tc-3 500/550V kw kw Continuous current Single Phase Three Phase 110~120V HP 220~240V HP 200~208V HP 220~240V HP 440~4 80V HP 550~0V HP NEM size Weight MRC Size and weight Size (WxHxD) Weight MRD Size (WxHxD) uxiliary (standard) Side mount uxiliary Front mountt lbs in lbs in MRC-75L MRC-85L MRC-100L 100F Lug 3 pole 1000V 50/Hz 6kV 1800 operations per hour 12 mil. operations 2 mil. operations 110 135 1 22 75 37 75 37 64 37 42 25 85 45 85 45 75 45 45 30 105 55 105 55 85 45 65 110 135 1 5 7.5 10 15 15 20 25 30 30 30 40 40 50 75 75 75 3 3.53 lbs 2.76 x 5.51 x 5.35 in 5.73 lbs 2.76 x 5.51 x 6.78 in 1NO & 1NC M-1 C-2, C-4 MRC-130L MRC-150L 150F Lug 3 pole 1000V 50/Hz 8kV 1800 operations per hour 5 mil. operations 1 mil. operations 1 210 37 130 130 90 55 45 150 75 150 70 100 50 1 210 10 15 20 25 40 40 40 50 5 100 75 75 4 5.29 lbs 3.74 x 622 x 5.13 in 1NO & 1NC M-1 C-2, C-4 MRC-185 225F Screw 3 pole 1000V 50/Hz 8kV 1800 operations per hour 5 mil. operations 1 mil. operations 230 55 185 90 185 110 180 110 120 230 15 30 150 125 11.91 lbs 5.43 x 7.99 x 7.29 in 1NO & 1NC M-1 C-2, C-4

Date COMPONENT SPECIFICTIONS The following section details the various components sizing and ratings. To locate your component part numbers for the EMS reference the sizing information table above. UTS CIRCUIT BREKER MOLDED CSE CIRCUIT BREKER SPECIFICTIONS UTS Series (FMU) Frame size Rated current ln Number of poles Rated operational voltage, Ue UL interupting rating C 50/Hz Reference standard V k 120V 240V 480V 0V UTS250 250F 128-1, 1-200, 200-250 3 0 NU 65 35 18 UL489 vailable breaker types djustable-thermal, fixed-magnetic, FMU ccessories Weight 3-pole lbs (kg) Basic dimension, WxHxD 3-Pole X - uxiliary switch L - larm switch SHT - Shunt trip UVT - Undervoltage trip EHU - Extended rotary handle FH - Flange handle PL, PHL - Locking devices (removable, fixed) MIT - Mechanical interlock device 4.49lbs (2.04kg) 4.13 x 7.48 x 3.44in (105 x 190 x 87.5mm)

COMPONENT SPECIFICTIONS The following section details the various components sizing and ratings. To locate your component part numbers for the EMS reference the sizing information table above. (MCP) DISCONNECT Frame Size Part # 32F 63F 100F Rated operational current Ie () Magnetic release operating current () Branch Motor Protection (UL508) 1-phase [HP] (50/Hz) 3-phase [HP] (Hz) KIC Ratings [k] 115V 230V 200V 230V 4V 575V 240V 480V 0V CMS-32HI-2.5 2.5 32.5-1/6 1/2 1/2 1 1.5 100 50 10 CMS-32HI-4 4 52 1/8 1/3 3/4 3/4 2 3 100 50 10 CMS-32HI-6 6 78 1/4 1/2 1 1.5 3 5 100 50 10 CMS-32HI-8 8 104 1/3 1 2 2 5 5 100 50 10 CMS-32HI-10 10 130 1/2 1.5 2 3 5 7.5 100 50 10 CMS-32HI-13 13 169 1/2 2 3 3 7.5 10 100 50 10 CMS-32HI-17 17 221 1 3 3 5 10 15 100 50 10 CMS-32HI-22 22 286 1.5 3 5 7.5 15 20 100 30 10 CMS-32HI-26 26 338 2 3 7.5 7.5 15 20 100 30 10 CMS-63HI-26 26 338 2 3 7.5 7.5 15 20 100 50 10 CMS-63HI-32 32 416 2 5 7.5 10 20 30 100 50 10 CMS-63HI-40 40 520 3 7.5 10 10 30 30 100 50 10 CMS-63HI-50 50 650 3 10 15 15 30 40 100 50 10 CMS-63HI-63 63 819 5 10 20 20 40 100 50 10 CMS-63HI-65 65 845 5 10 20 20 40 100 50 10 CMS-100H-75 75 975 5 15 20 25 50 100 50 10 CMS-100H-90 90 1170 7.5 20 25 30 75 100 50 10 ssociated product part numbers can be found in the Sizing Information Table.

ENCLOSURE DIMENSIONS UL Type 3R Dimensions UL Type 3R P-Drive Bypass H x W x D ( x B x C) B C CIE3-BYP001-P2/3 ~ CIE3-BYP015-P2/3 CIE3-BYP001-P4/3 ~ CIE3-BYP015-P4/3 CIE3-BYP020-P2/3 CIE3-BYP020-P4/3 ~ CIE3-BYP025-P4/3 CIE3-BYP025-P2/3 CIE3-BYP030-P2/3 CIE3-BYP030-P4/3 ~ CIE3-BYP040-P4/3 CIE3-BYP050-P4/3 ~ CIE3-BYP075-P4/3 CIE3-BYP040-P2/3 CIE3-BYP100-P4/3 36.5 x 26 x 16.56 41.5 x 29 x 16.56 46.5 x 29 x 16.56 51.5 x 34 x 20.6 56.5 x 39 x 20.6 * Contact Franklin Control Systems or visit www.franklin-controls.com for larger bypass dimensions