Redundancy unit CP-C.1-A-RU Accessory for CP-C.1 range power supplies

Similar documents
Electronic overload relay EF65, EF96 and EF146

Thermal overload relay TF65 and TF96

Electronic overload relays EF205 and EF370

Mini contactors B6, BC6 with 3 pole

Thermal overload relay TF140DU and TF140DU-V1000

Manual motor starter magnetic only MO325

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

Manual motor starter MS116

Manual motor starter MS132

Manual motor starter MS132

Manual motor starter MS116

Manual motor starter MS132

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

249.1 m3/h m3/h 7.23 MW m3/h 50.0 m3/h

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

NF31E-.. / NFZ31E-.. Contactor Relays AC / DC Operated - with Screw Terminals

ZS35-PEN Screw Clamp Terminal Blocks Ground + Neutral

AF / AF38Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF30Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

ZS4-SF1-R Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with blown fuse indicator

AF / AF16Z pole Contactors AC / DC Operated - with Screw Terminals

ZS4-PE Screw Clamp Terminal Blocks Ground

DBL distribution blocks 3x1 pole

ZS6-D1-PE Screw Clamp Terminal Blocks Double deck with 1 ground circuit

ZS50-PE Screw Clamp Terminal Blocks Ground

ZK2.5-SP-4P PI-Spring Terminal Blocks Disconnect with plug - with test socket

ZS10-ST Screw Clamp Terminal Blocks Test disconnect with sliding link

ZS4-S Screw Clamp Terminal Blocks Disconnect with blade

ZS4-SF Screw Clamp Terminal Blocks For 5 x 20 fuses

ZS4-D-CH Screw Clamp Terminal Blocks Component holder

Solid State Relays, 3-phase

ZS6-S Screw Clamp Terminal Blocks Disconnect with blade

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

ZS4-T3 Screw Clamp Terminal Blocks Triple deck with 3 feed-through circuits

ZS10-S-R2 Screw Clamp Terminal Blocks Disconnect with lever

ZK2.5-D-CH PI-Spring Terminal Blocks Component holder

ZS4-SF1 Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses

QUINT-PS/24DC/24DC/ 5/CO

Selective main circuit breakers S 750 series Technical Data

ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket

ZS10-PE Screw Clamp Terminal Blocks Ground

DIN EN UL 508 / CSA 3RF A A 0 2

ABB i-bus KNX DG/S x DALI-Gateway Basic

ZS4-D2-S-T Screw Clamp Terminal Blocks Double deck with 1 disconnect circuit with test socket screws and 1 feed-through circuit

QUINT-PS/24DC/48DC/ 5

ZS4-PE Screw Clamp Terminal Blocks Ground

ZK2.5-SF-R PI-Spring Terminal Blocks For 5x20 fuses - with blown fuse indicator

ZK2.5-D1-PE PI-Spring Terminal Blocks Double deck with 1 ground circuit

QUINT-PS/24DC/24DC/20

ZS4-SF1-R Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with blown fuse indicator

ZK4-PE PI-Spring Terminal Blocks Ground

ZS10 Screw Clamp Terminal Blocks Feed-through

ZK2.5-SP PI-Spring Terminal Blocks Disconnect with plug - with test sockets

ZS35 Screw Clamp Terminal Blocks Feed-through

ZP2.5-PE Spring Terminal Block Ground

ZS4 Screw Clamp Terminal Blocks Feed-through

ZS6-4S Screw Clamp Terminal Blocks Feed-through with 4 connections

QUINT-PS/48DC/24DC/5. DC/DC converter with SFB technology, primaryswitched, input: 48 V DC, output: 24 V DC, output current: 5 A.

ZS6-3S Screw Clamp Terminal Blocks Feed-through with 3 connections

QUINT-PS/24DC/24DC/10

ZK2.5-PE-4P PI-Spring Terminal Blocks Ground with 4 connections

Models. Output current max.* Output Power max. Low Line : VAC High Line: VAC 24 VDC / 12 A 240 W. Back up battery

ZS6 Screw Clamp Terminal Blocks Feed-through

ZK2.5-4P PI-Spring Terminal Blocks Feed-through with 4 connections

Thermal Overload Relays

Features. LED Driver. RACT09 9 Watt. TRIAC Dimmable. Single Output RACT09- AC/DC Converter

ZK6 PI-Spring Terminal Blocks Feed-through

QUINT-PS/24DC/24DC/10/CO

SIRIUS 3RU2 Thermal Overload Relays

ABB i-bus KNX HIL/S , Hotel IP Link, Bundle

Manual motor starters Overview and benefits

Industrial Power Supplies

Safety Standards. Model Number:

ZK4-4P PI-Spring Terminal Blocks Feed-through with 4 connections

ZP2.5-4P Spring Terminal Block Feed-through

ZS6 Screw Clamp Terminal Blocks Feed-through

ZS4-SF1 Screw Clamp Terminal Block

ABB i-bus KNX Hotel IP Link, Bundle HIL/S , 2CDG110237R0011

ZK2.5-4P PI-Spring Terminal Blocks Feed-through with 4 connections

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

ZDP Pluggable Terminal Blocks Feed-through

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489

MINI MCR-SL-UI-UI(-SP)(-NC)

Uncompromising safety and comfort Miniature Circuit Breaker SU 200 M for branch circuit protection per UL and CSA

UZK12.071, UZO GENERAL DESCRIPTION 2. DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY MODULE BATTERY MODULE 12V, 7AH 1/9.

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.

NEW The new PROmax power supplies offer a wide range of robust solutions for demanding application requirements.

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.

Surge arrester POLIM-H..SD

UZK12.071, UZO DATA 1. GENERAL DESCRIPTION 4. MARKINGS 3. ORDER NUMBERS PASSIVE BATTERY MODULE BATTERY MODULE 12V, 7AH 1/9.

INDUSTRIAL POWER SUPPLIES SFL-SERIES

MS General Information Extended Product Type: MS

Surge arrester POLIM-C.. HD

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

Transcription:

Data sheet Redundancy unit -A-RU Accessory for range power supplies ABB s redundancy units are used to establish true redundancy which increases the availability of electrical systems significantly. 2CDC 271 001 V0018 Characteristics Decoupling of power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power supplies 2 integrated diodes for the decoupling of 2 switch mode power supplies up to 20 A Device with coated PCBA for harsh environments and with extended temperature range Various certifications and approvals (see overview, document no. 2CDC114098D0201) Ordering details Description 2 inputs each up to 20 A and 1 output up to 40 A Suitable for decoupling of two 24 V DC power supply units 28.5 V and 40 A PCBA Type Order code Weight (1 pc) kg (lb) uncoated -A-RU 1SVR360060R1001 1.04 (2.29) coated -A-RU-C 1SVR360060R2001 1.04 (2.29)

Functions 1 1 INPUT 1, 2: Terminals input 2CDC 271 001 V0018 2 2 Circuit diagram 3 OUTPUT ++/-- Terminals output 3 Application The redundancy unit A-RU provides decoupling of two power supply units. It provides automatic redundant power supply operation for critical applications. It has 2 inputs, each up to 20 A, and 1 output up to 40 A. Operating mode True redundancy with decoupling provided by the A-RU and A-RU-C Redundant circuits are used to increase the operational reliability and eliminate power supply outages. Events that can cause a power supply failure include: incorrect wiring, blown fuses, or failure of a single power supply. If a fault event occurs (called initial fault) in the first power supply circuit, power to all loads is then supplied by the second (redundant) power supply. For this reason, both power supplies must be sized to handle the total current requirement of all loads. The primary and the redundant power supplies are decoupled from one another by the A-RU unit. It automatically switches from the primary to the redundant supply after a fault. It decouples the output of the failed power supply from the redundant supply preventing the initial fault from shorting or compromising the redundant supplies output. In this way, uninterrupted supply of power to all loads is guaranteed. When available, the two power supplies should be connected to different input voltage phases, to avoid loss of power caused by a blown fuse on the primary side of the power supplies. True redundancy, I out I r + - L+ L- + - + - L+ L- INPUT 1 INPUT 2 I r 20 A -A-RU I r 20 A OUTPUT L N PE + + - - L N PE Load I out I r T a 60 C - max. 20 A T a 40 C - max. 30 A 2CDC 272 005 F0217 2 - Redundancy unit -A-RU Data sheet

Parallel operation for increased power Another operation mode of two power supplies in combination with a redundancy unit is to parallel and decouple them for increased power. The setup looks similar to the true redundant installation above but the field of application is different. Instead of redundancy the max. output current (limits see under the schematics) can be used to power up the loads. The redundancy module decouples both power supplies from each other to avoid that any electrical failure from one power supply circuit affects the other one. However, using the increased power also means there is no redundancy since if one supply fails the other one can not supply the load alone. Increased power, I out I r L+ L- + - + - L+ L- INPUT 1 INPUT 2 I r 10 A -A-RU I r 10 A L+ L- + - + - L+ L- INPUT 1 INPUT 2 I r = 20 A -A-RU I r = 20 A OUTPUT L N PE + + - - L N PE OUTPUT L N PE + + - - L N PE + - Load I out I r T a 60 C - max. 20 A T a 40 C - max. 30 A 2CDC 272 003 F0017 + - Load I out I r T a 60 C - max. 40 A T a 40 C - max. 60 A 2CDC 272 004 F0017 Mounting To mount the unit place the upper edge of the DIN rail adapter on the upper edge of the DIN rail holding the unit slightly tilted upwards as shown in the illustration. Then tilt the unit down until the latch snaps onto the DIN rail. 2CDC 273 002 F0015 Mounting positions Position 2 Position 4 Position 3 Position 1 Position 5 Position 7 2CDC 272 001 F0016 In order to ensure a sufficient convection in mounting position 1 and 7, the minimum distance to other modules must not be less than 25 mm in vertical direction and 25 mm in horizontal direction. For the derating of the output current, see the characteristic curve of temperature. Details for other mounting positions on request. Data sheet Redundancy unit -A-RU - 3

Mounting -A-RU in position 7 To mount the unit in position 7 remove the DIN rail adapter that is fastened with 4 screws and attach it on the side of the power supply. Screwdriver: Torx T10 Tightening torque: 0.7 w0.1 Nm 2CDC 273 005 F0015 2CDC 273 008 F0015 Demounting To release the unit pull the latching lever downwards with a screwdriver and press the upper side of the the latching lever down. The device can be unhinged from the DIN rail and removed. 2CDC 273 003 F0015 Electrical connection Input side [INPUT 1 + / INPUT 2 + ] Connect the input terminals, stripping length of the cable see technical data. For channel 1 left hand input terminals +, for channel 2 right hand input terminals +. Electrical connection Output side [OUTPUT ++ - ] Rate the lines for the maximum output current or provide a separate fuse protection. We recommend to choose the cable cross section as large as possible in order to minimize voltage drops. Observe the polarity. Connection diagram 2CDC 272 019 F0005 INPUT 1 +, Connection of the output of power supply unit 1 INPUT 2 +, Connection of the output of power supply unit 2 OUTPUT ++, Output for load 4 - Redundancy unit -A-RU Data sheet

Safety instructions and warnings In operation pay attention to: Do not modify the installation! Risk of electric arcs! Risk of burns: Depending on the operation conditions the housing can become hot. The device contains no user serviceable parts. In any case of device malfunction please send the unit back to manufacturer. The device must be installed by qualified persons only and in accordance with the specific national regulations (e. g. VDE, etc.). These devices are maintenance free chassis mounted units. Before any installation, maintenance or modification work: Read the operating and installation instructions carefully and completely! Disconnect the system from the supply network and protect against switching on! Before start of operation the following must be ensured: Power supply cables and unit must be sufficiently fused. Rate the output lines for the output current and connect them with the correct polarity. In order to ensure sufficient convection the distance to the other devices has to be considered. Attention! Improper installation/operation may impair safety of personnel and cause operational difficulties or destruction of the unit. Attention! Danger to life! Disconnect the system from the supply network before executing any works at the device and protect against switching on! The unit contains components with high stored energy and circuits with high voltage! Do not introduce any objects into the unit and do not open the unit. With some units of this range the output is capable of providing hazardous energy. Ensure that the service personnel is protected against inadvertent contact with parts carrying energy. Data sheet Redundancy unit -A-RU - 5

Technical data Data at T a = 25 C, U in = 230 V AC and rated values, unless otherwise indicated Type -A-RU -A-RU-C Input circuit - Supply circuit (+/+, -/-) Rated input voltage U in 24 V DC Input voltage range 10-28.5 V DC Rated input current I in per channel -25 C m T a m 60 C 20 A Maximum input current per channel -25 C m T a m 40 C 30 A -40 C m T a m 40 C - 30 A Transient overvoltage protection yes, varistor Output circuit (++/--) Rated output voltage U out 24 V DC Voltage drop input/output typ. 0.6 V, max. 0.9 V Rated output current I r -25 C m T a m 60 C 2 x 20 A or 1 x 40 A Max. output current (power reserve) -25 C m T a m 40 C 2 x 30 A or 1 x 60 A -40 C m T a m 40 C - 2 x 30 A or 1 x 60 A Derating of the output current 60 C < T a m 70 C 2.5 % per Kelvin temperature increase Resistance to reverse feed < 60 V General data Power loss input 2 x 20 A 23.0 W input 2 x 10 A 9.4 W input 2 x 5 A 4.1 W MTBF acc. to MIL 217 HDBK on request Dimensions see "Dimensional drawings" Material of housing cover / housing shell / front aluminium / zinc-coated sheet steel / plastic Mounting DIN rail (IEC/EN 60715), snap-on mounting Mounting position 1 and 7 Minimum distance to other units horizontal / vertical 25 mm (0.98 in) / 25 mm (0.98 in) Degree of protection (IEC/EN 60529) housing / terminals IP20 / IP20 Protection class (IEC/EN 61140) III Electrical connection - Input circuit / Output circuit Connecting capacity fine-strand with(out) wire end ferrule 2.5-10 mm 2 (12-8 AWG) rigid 2.5-16 mm 2 (12-6 AWG) Stripping length 10 mm (0.39 in) Tightening torque 1.2 Nm (10.5 lb.in) Recommended screw driver PH1 / Ø 4.0 x 0.8 mm (0.16 x 0.03 in) Environmental data Ambient temperature range operation -25 +70 C (-13... +158 F) -40 +70 C (-40...+158 F) rated load -25...+60 C (-13... +140 F) -40...+60 C (-40...+140 F) storage transportation -40 +85 C (-40...+185 F) -40 +85 C (-40...+185 F) Climatic class (IEC/EN 60721-3-1) storage 1K2 (-40...+85 C / -40...+185 F) Climatic class (IEC/EN 60721-3-2) transportation 2K2 (-40 +85 C / -40...+185 F) Climatic class (IEC/EN 60721-3-3) operation 3K3 (-25 +70 C / Damp heat, cyclic (IEC/EN 60068 2 30) -13...+158 F) test Db: 55 C, 2 cycles 3K3 (-40 +70 C / -40...+158 F) Vibration (IEC/EN 60068 2 6) test Fc: 10-58 Hz, amplitude ±0.15 mm, 58-150 Hz, 2 g, 10 sweep cycles each axis Shock, half sine (IEC/EN 60068 2 27) test Ea: 30 g, 6 ms, 3 pulses each axis; bump 20 g, 11 ms, 100 pulses each axis Coated PCBA no yes Gaseous corrosive environment withstand test (IEC/EN 60068-2-60) - testing method: 4 testing period: 21 days ambient conditions: 25 C, 75 % r.h. air/volume change rate per hour: 3-6 sample not energized during exposure gas concentrations acc. ISA-S71.04.2013 Harsh Group A, G3 IEC 60721-3.3 acc. 3C2/3C3 - H2S 100 ± 10 ppb - SO2/SO3 300 ± 20 ppb - Cl2 100 ± 10 ppb - NOx 1250 ± 20 ppb 6 - Redundancy unit -A-RU Data sheet

Type -A-RU -A-RU-C Isolation data Rated impulse withstand voltage U imp (EN 50178) input / housing 1.5 kv (1.2/50 µs) output / housing Pollution degree 2 Standards / Directives 1.5 kv (1.2/50 µs) Standards IEC/EN 61204 EMC Directive 2014/30/EU ATEX Directive - 2014/34/EU RoHS Directive 2011/65/EU Electrical safety IEC/EN 60950-1 Industrial control equipment / General Use Power Supplies UL 508 / CSA 22.2 No 107.1 Electromagnetic compatibility Interference immunity to electrostatic discharge IEC/EN 61000-4-2 Level 4, contact discharge 8 kv, air discharge 15 kv (criterion B) electrical fast transient / burst IEC/EN 61000-4-4 Level 3, DC mains inputs and output ±2 kv (criterion B) surge IEC/EN 61000-4-5 Level 1, DC mains inputs and output ±0.5 kv, input and output vs. PE ±1 kv (criterion B) Dimensions in mm [inches] 129.8 5.11" 126.8 4.99" 56.4 2.22" INPUT 1 INPUT 2 + - + - -A-RU - + + - OUTPUT 129.4 5.09" 2CDC 272 011 F0017 136.0 5.35" Data sheet Redundancy unit -A-RU - 7

Further Documentation Document title Document type Document number Electronic relays and controls Catalog 2CDC 110 004 C02xx Redundancy unit Instruction manual 1SVC 360 561 M0000 Additional information and notes on safety (ATEX) Instruction manual 1SVC 360 560 M9000 You can find the documentation on the internet at www.abb.com/lowvoltage -> Automation, control and protection -> Power supplies. CAD system files You can find the CAD files for CAD systems at http://abb-control-products.partcommunity.com -> Low Voltage Products & Systems -> Control Products -> Electronic Relays and Controls. 8 - Redundancy unit -A-RU Data sheet

Contact us ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2018 ABB All rights reserved Document number 2CDC 114 103 D0201 Rev. C (04.2018)