Selecting Explosion-Proof Motors And Variable-Frequency Drive Controllers For Hazardous Environmental Applications

Similar documents
EXPLOSION-PROOF MOTORS SINGLE PHASE

by Jim Phillips, P. E.

VALVCON. QX-Series ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

Installation & Maintenance Manual

Installation and Service Instructions for EX Series Explosion-proof Switches

Section 8. Application Manual for NEMA Motors. Special Information

TXB Series Explosion Proof

Model 5000 Level Controller

LIGHTING TOOLS RATED

Engineering Information. Solenoid Valves Principles of Operation. Solenoid Valves. Direct Acting Valves (Figures 1A, 1B)

Petroleum industries are dealing with different hazardous materials starting from storing, processing and distributing the petroleum products These he

EHB Series Explosion Proof Heavy Duty Belt Drive Exhaust Fans Data sheet

Catalog. Brochure. Baldor explosion proof AC and DC Motors. Catalog

Inverter User Manual

A. Fan motors and associated equipment shall be sized to operate at 110% of calculated loads and capacities.

SENSIT TKX INSTRUCTION MANUAL. Combustible Gas Leak Detector. Read and understand instructions before use.

Hybrid Motor Technology to Achieve Efficiency Levels Beyond NEMA Premium

HVA - BELT DRIVE WALL FANS Designed for heavy duty commercial and industrial exhaust applications.

Hazardous Location Enclosures INDEX. Hazardous Location Enclosures HAZ-2

Battery Power Inverters

BFG range BFGC range BFN range

SECTION MOTOR REQUIREMENTS for HVAC

2 Fluid Level Management

ER SERIES EXPLOSION-PROOF BRUSHLESS SERVO MOTOR INSTALLATION AND SERVICE MANUAL

FAN ENGINEERING. Integral AC Motor Selection and Application Guide For Fans

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

SKINNER Intrinsically Safe Series Four-Way

ENGINEERING DATA. Motor Performance Characteristics and Application Guidelines

SEWPCC UPGRADING/EXPANSION PROJECT BID OPPORTUNITY SECTION LOW-VOLTAGE AC INDUCTION MOTORS

ELECTROGALVANIZED ALUMINUM ACRYLIC PAINTED FERALOY IRON ALLOY

RGZESDI Inverter Duty AC Induction Motors

Industrial Motors. But first..servos!

Owner s Guide. DC TO AC Power Inverter

SECTION GENERAL MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

ELECTROGALVANIZED ALUMINUM ACRYLIC PAINTED FERALOY IRON ALLOY

FAN ENGINEERING. Motor Performance Characteristics and Application Guidelines

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

PRODUCT SPECIFICATIONS

SPECIFICATIONS - DETAILED PROVISIONS Section Vertical Hollowshaft Electric Motors C O N T E N T S

BFG range BFGC range BFN range

Owner s Manual. PowerVerterDC-to-AC Inverter

Flammability of Bakken Crude Oil: Dangerous. Rail Cargo Even When Empty. (by Dr. Gerard Macri, Expert Witness)

Sources of Ignition and Hazardous Area Classification Core

Application Information

Código de rotor bloqueado Rotor bloqueado, Letra de código. Rotor bloqueado, Letra de código

VLT SERIES. True Sine Wave AC Power Inverter. Owner s Manual. Owner s Manual D Rev.B

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

IMPORTANT SAFETY NOTICE

List Price. Mult. Sym. C Dim. Single Phase

1/4 thru 300 Hp NEMA 48 thru 449TY. List Price. Mult. Sym. C Dim. Single Phase

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

IT 318 SUPPLEMENTARY MATERIAL CHAPTER 4

VALVCON. V-Series. STANDARD ELECTRIC ACTUATORS With Speed Control/Timer Board (Option J ) Installation, Maintenance and Operating Instructions

ATEX LABELLING FOR MOTORS AND GEAR UNITS

Comfort. Description. Applications

Spark-ignited generator set

Comfort. Sewage Treatment Plants. Petrochemical Facilities, Oil Rigs. Unattended Pumping Stations. Chemical Storage and Handling Facilities

NEMA Premium Efficiency T-Frame Motors. Three-Phase, TEFC Enclosures RELIABILITY MATTERS

TYPICAL APPLICATIONS FOR EL SERIES EXPLOSION-PROOF MOTORS ARE WELL-SUITED TO MANY APPLICATIONS SUCH AS:

Maximum operating temperature for standard motors = 110 C. Shut down temperature in case of a malfunction = 115 C.

Overview V10-T1-2 V10-T1-2 V10-T1-3 V10-T1-4 V10-T1-5 V10-T1-6 V10-T1-7 V10-T1-7 V10-T1-8

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

AC Adjustable Speed Drives (ASD s)

Thermal Protector (as applied to motors). Thermally Protected (as applied to motors).

VFD Best Practices: Getting the Most from Your VFD Investment

SECTION COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

SUBMERSIBLES INDEX. General Description and Notes UL Motors Single-Phase UL Approved Three-Phase UL Approved... 4

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

AC Induction Motors. Installation and operating instructions

Application Techniques. North American Standards, Configurations, and Ratings: Introduction to Motor Circuit Design

IMPROVING MOTOR SYSTEM EFFICIENCY WITH HIGH EFFICIENCY BELT DRIVE SYSTEMS

GUIDE FOR MICROGENERATION INTERCONNECTION TO CITY OF MEDICINE HAT ELECTRIC DISTRIBUTION SYSTEM

DC AC POWER INVERTER. LIV 10 / LIV 20 / LIV 30 User Manual

New Products for Integrated Electrical Systems/Questions and Answers/Resources. necdigest. Bringing a new level of electrical protection into the home

Compact Sine Inverter

PowerOhm Installation Manual for LG ATV Series Braking Modules

SECTION OWNER FURNISHED EQUIPMENT

High voltage flameproof induction motors The simplest solution for hazardous environments

Fans for ATEX EXPLOSIVE ATMOSPHERES

UPS Ratings-Not so Apparent

M T E C o r p o r a t i o n. MTE Series RL. Line/ load Reactors USER MANUAL PART NO. INSTR -011 REL MTE Corporation

Ballasts For High Intensity Discharge Lamps

VALVCON I-SERIES I6600 OPTION DN DEVICENET PROTOCOL

Three Phase Modifiable NEMA Horizontal Motors Accessories and Modifications

EDS / EFS Series Control Stations

254 Series Convector. Standard Construction Features

V Series 115 VAC AND 230 VAC STANDARD ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

Convector. Standard Construction Features

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

Inverter Speed Ratio Information

Design Standard. Electric Motors. Detailed specifications follow. PART 1 - GENERAL

SECTION VARIABLE FREQUENCY DRIVE UNITS

Technical Specification. RCS Electric Actuators with a ProfiBus Field Control and Communication Module

powerdriveinverters.com Owner s Guide Please Save for Future Reference 100 Watt DC to AC Power Inverter

powerdriveinverters.com Owner s Guide Please Save for Future Reference 300 Watt DC to AC Power Inverter

S150,S300 Series Pure Sine Wave Inverter User s Manual

FUSE TECHNOLOGY Ambient temperature

ACCUSENSE CHARGE SERIES ON/OFF BOARD FULLY AUTOMATIC BATTERY CHARGER

EL Series Explosion Proof Linear Actuators

powerdriveinverters.com Owner s Guide Please Save for Future Reference 150 Watt DC to AC Power Inverter

Transcription:

Selecting Explosion-Proof Motors And Variable-Frequency Drive Controllers For Hazardous Environmental Applications Application Solution Introduction Applying variable frequency power to explosion-proof motors in hazardous locations requires special considerations regarding UL 674, motor ratings and variable frequency drive characteristics to name a few. The attached paper (D-7154), originally published in Machine Design, highlights the issues important to the success of a XP motor operated on variable frequency drive power. It is an appropriate paper for the VLS drive application note guide.

D-7154 The proper application of variable-frequency drive controller power to AC induction motors can be difficult even in relatively simple applications. When using a variable-frequency controller, the non-pure sine wave output power causes additional motor heating primarily because of harmonics and below base speed operation. Add to these issues a hazardous environment requiring an explosion-proof (XP) motor, and the selection of a suitable, as well as efficient, motor and variable-frequency controller combination is complicated even further. Hazardous locations are found in a wide range of industries, including petrochemical, textile, rubber making, agriculture, food processing and metalworking. The array of hazardous locations found in these industries has been defined by standards such as The National Electric Code (National Fire Prevention Association - NFPA 70). Refer to Figure 1. Because standard constant-speed explosion-proof motors are not designed for use with variable-frequency controllers in these potentially explosive applications, it is necessary to understand how these controllers affect motor performance. UL addresses this issue within its Hazardous Duty Motor Specification, UL 674, which defines the testing and marking that a motor manufacturer must adhere to in order to supply a listed motor package for hazardous environments, when powered by a variable-frequency controller. The multitude of motors and controllers - as well as the ability to purchase each as a separate product - and the numerous hazardous application variables, make it extremely difficult to select the right explosion-proof motor/controller combination for hazardous applications. How Variable-Frequency Affects Motors Understanding the affects of variable-frequency on motors (whether the application is hazardous or non-hazardous) sheds some light on this complicated selection process. As with general-purpose locations, there are many benefits to using variable-frequency controllers in applications requiring explosionproof motors. However, when variable-frequency power is applied to AC motors, it causes increased motor heating that must be considered. Depending on the manufacturer and the type of variablefrequency controller, the input voltage and current waveform to the motor will be distorted by varying degrees. This distortion can be mathematically represented in terms of harmonics. The harmonics produced by drive controllers result from the conversion of the original pure sine wave to a variablefrequency output produced by the drive. Harmonic currents create no useful torque at the motor shaft. They actually produce additional heating in the motor. Varying the speed of the motor shaft also affects a motor s cooling capacity unless a separate constant-volume air supply is provided. The amount of air flow through or over the motor decreases as the inverter lowers the motor s speed, decreasing the cooling capability of the motor. This decreased cooling capability, along with losses due to harmonics, combine to cause the motor to run hotter as its speed decreases. The application in which the motor will perform must also be considered. Different load types have different effects on the heating of motors powered by variable-frequency sources. Constant torque, variable torque, and constant horsepower all create motor heat in different ways. Constant torque requires the same amount of torque throughout the application speed range, causing the motor to get hotter as its speed decreases. Variable torque is often used with centrifugal load, in which the load actually drops off faster than the motor s speed, enabling the motor to run cooler (than it would at full-load, full speed) as its speed slows. However, the temperature rises again when the motor approaches stalled state. Constant horsepower enables the motor to run above its base speed; the torque goes down as the speed increases. To complicate the issue further, different types of variablefrequency controllers, such as Variable Voltage Input (VVI), Current Source Input (CSI) and Pulse Width Modulated (PWM), have different output voltage and current waveforms, and thus vary in the amount of heat they impose on a motor. Underwriters Laboratories (UL) recognizes the complexity of these variables and provides a UL listing for motors that will be used in a hazardous atmosphere with variable-frequency controllers.

Classification Class I Class II Class III Group A Group B Group C Group D Group E Group F Group G Division 1 Division 2 Hazardous Environment Potentially explosive flammable gases or vapors in the air Combustible dust in the air Ignitable fibers or flyings (dust) in the air Acetylene Hydrogen, gases, or vapors of manufactured origin Ethyl-ether vapors, ethylene or cyclopropane Gasoline, hexane, naphtha, benzine, butane, propane, alcohol, acetone, benzol, lacquer, solvent vapors, or natural gas (methane) Conductive dust and metal dust: aluminum, magnesium - their commercial alloys, etc. Carbon black, coal, or coke dust Flour, starch, grain dusts Location where hazardous material exists (always or periodically) during operating conditions Location where hazardous material exists only in the case of fault situation (leaky valve, burst pipe, faulty equipment) Figure 1. Hazardous Classifications UL 674 and Hazardous Environments UL requires motor manufacturers to complete an extensive series of tests to measure motor performance and temperature rise when powered by different types of drives and when used in different hazardous environments. UL must witness these tests in all combinations for which the motor manufacturer seeks a UL listing. UL 674 defines the many requirements a hazardous-location motor muse meet, including those it must meet when operated on inverter power. The standard states that the motor must perform throughout the market frequency range and... be tested with each type of inverter with which the manufacturer specifies that the motor be used. UL 674 also defines the marking required on a metal nameplate for a hazardous-location motor to be operated on inverter power. To obtain the UL listing, the motor manufacturer must first submit to UL the speed/torque capabilities the manufacturer anticipates from the line of motors. UL also requires additional information such as the type of variable-frequency controller the motor will be used with (VVI, CSI, PWM, etc.); the motor s voltage, frequency and speed ranges; duty, surface temperature code; and hazardous location classifications in which the motor will be approved. UL then selects the test requirements to verify the motors will perform as expected. Testing for variable-frequency motors in hazardous environments consists of tests to verify the surface temperature of the motor will not exceed the listed temperature code under all operating conditions throughout the speed range. UL requires that the motor nameplate be marked to reflect its suitability for operation with an inverter. The specified speed range in hertz, the expected load type (e.g. constant torque, variable torque, or constant horsepower), as well as the hazardous location, Class, Group, temperature code (See Figure 2) and type of inverter (VVI, CSI, PWM) must be listed on the motor s nameplate or the auxiliary UL nameplate. The UL nameplate identifies the hazardous environment. Applying a motor outside the specified limits on the nameplate is a violation of the UL label. Therefore, a motor not specifically labeled for variablefrequency use may not be applied to those applications. Assuming the motor is already approved for sine wave explosionproof duty and has undergone the rigorous testing of frames and thermostat capabilities, the tests for variable-frequencies focus on motor surface temperature and are divided into two main hazardous environment classifications: Class I - Locations with flammable gases or vapors in levels that may ignite or explode (Groups C and D) Class II - Locations with combustible dust (Groups E, F, and G) See Figure 1 for complete UL and NEC Hazardous Area Class and Group classifications. As Figure 1 illustrates, hazardous environments are determined by the type of flammable gas, vapor, dust or fiber in the area. Hazardous areas are typically identified by the insurance underwriters. However, the National Fire Prevention Association s codes also provide guidelines for evaluating the environment.

T Code Max. Surface Temp. T1 450 o C (842 o F) T2 300 o C (572 o F) T2A 280 o C (536 o F) Class I, Group D w/caut. label T2B 260 o C (500 o F) T2C 230 o C (446 o F) T2D 215 o C (419 o F) Class I, Group D w/thermals T3 200 o C (392 o F) Class II, Groups E & F T3A 180 o C (356 o F) T3B 165 o C (329 o F) Class II, Group G T3C 160 o C (320 o F) Class I, Group C Figure 2. NEC Temperature Codes Figure 4 shows a typical hazardous environment application with and XP motor powered by a variable-frequency controller. The UL test procedures are different for each Class and Group hazardous location. When testing a motor/variable-frequency drive package for Class I environments, the manufacturer must prove the package will operate satisfactorily throughout the speed range and if the motor is overloaded the thermostats will take it off-line. This testing is performed in a clean-air environment. Testing for Class II, Groups E, F, and G is even more demanding of motor performance. These tests require the motor to be covered with dust (during the procedure), further affecting motor cooling capability. Upon completion of the test, the dust must not show any signs of charring caused by overheating. Matched XP Motors with Variable-Frequency Controllers Motors that are not listed for use with variable-frequency controllers, but UL listed for hazardous environments, are readily available off-the-shelf. Drives are readily available as well. Motor and drive packages are applied everyday to OEMs, distributors, manufacturers and end users. Many assumptions, however, and even erroneous rules of thumb are applied to the sizing of motors powered by variable-frequency controllers. Because of the vast differences among manufacturers variablefrequency controllers, as well as their affect on motors, these assumptions can lead users into trouble. For example, when using a 10 HP motor with a 10 HP controller - if applied over a wide speed range - the motor may overheat at lower speeds. Fortunately, few motors and controllers are ever applied to their non-hazardous environment, and are overheated for short periods of time, this may go undetected by the user. This is usually not the case for motors in hazardous locations. If misapplied, the thermostats will take the motor off-line. Also, any time a motor overheats, insulation life is decreased. Therefore, extra care should be taken to properly match motors and controllers in hazardous environments. Exceeding a motor s rated temperature at lower speeds, even for a short period of time, may cause the motor to become a hazard. The maximum surface temperature of the motor must remain below the autoignition temperature of the hazardous environment. Each remain beneath the limit. The temperature code defines the maximum motor surface temperature (See Figure 2). By packaging a variable-frequency controller with a UL Listed motor, which meets the requirements of UL 674, the user has an installation that not only meets regulations, but provides the required nameplate speed torque range. In other words, the package meets the regulations, and does not compromise performance. These standards cannot be met simply by installing thermostats in the motor windings that signal the controller, which feeds power to the motor, to shut down when the motor thermostats open. UL 674 test procedures specifically require that the thermostats be proven with the motor being tested. Factors such as thermostat location, temperature, tolerance and response time should be considered. In fact, if a motor/controller package is not properly matched, the motor s thermostat may simply trip because of its inability to perform the speed range function required, resulting in nuisance trips. You can begin to see the importance of properly matched motors and controllers when applied in hazardous environments. Nuisance tripping can lead to either very long, repeated start-ups

Though it is potentially dangerous and not recommended, it is nonetheless common practice to apply standard, totally-enclosed fan-cooled (TEFC) motors or, in some cases, open dripproof motors to a Division 2 environment. The key criteria for motors applied in a Division 2 motor include no sparking or arcing devices and the surface temperature of the motor must not exceed the maximum temperature allowed by the temperature code. Figure 3. Reliance Motor Nameplate and UL Listed Nameplate or hazardous situations, should someone decide to bypass the thermostat. Overheating and nuisance tripping can also occur if the inverter is adjusted improperly. Cautionary Label explosion-proof motors are also available for hazardous environments. These motors are used only in a Class I, Group D environment and do not require a thermostat. Their insulation system is designed to be the thermostat and will fail before the surface temperature of the motor reaches the hazardous environment limit. Nuisance tripping in this case means replacing the entire motor. Hence, care must be taken to ensure the inverter is not misadjusted and the motor/drive package is properly matched. With the explosion-proof motor, the only surface exposed to the environment is the outside surface of the motor. The design of the motor is such that any explosion within the motor will be contained by the motor enclosure. However, with a Class 1, Division 2 motor, the internal surfaces (rotor, stator, space heaters, etc.) must not exceed the temperature code of the hazardous material. Fans must be made of non-sparking material and thermostats must be hermetically sealed. In the case of motors applied on variable-frequency controllers, the actual internal temperature - especially the rotor temperature - can neither be accurately measured nor predicted. Nor can it be protected from exceeding the allowable temperature. If the drive A Look at Division 2 Hazardous Environments As shown in Figure 1, UL and NEC classifications include Class, Group and Division categories. Class groupings define the actual physical form of the combustible material; Groups further subdivide the classes. Divisions, however, define the degree of exposure to hazardous material. Division 1 - Location where hazardous material exists (always or periodically) during operating conditions. Division 2 - Location where hazardous material exists only in the case of a fault situation (leaky valve, burst pipe, faulty equipment). Figure 4.

is improperly adjusted, especially at the lower frequencies, motor slip may increase. When this occurs, the bulk of the motor heating occurs in the rotor. It is therefore recommended that motors applied to variable-frequency for Division 2 applications be fully-labeled explosion-proof Division 1 motors, thereby eliminating the rotor as a potential heat source problem. The Canadian Standards Association (CSA) provides a listing for motors in Division 1 and 2 environments but currently doesn t recognize motors for use on variable-frequency power. matching drive controllers with motors for hazardous-duty applications not only helps ensure meeting industry standards, it also improves motor performance. To be UL approved for inverter application, the motor nameplate must specify the type of inverter for which the motor is suitable, the application characteristics and the frequency range. Conclusion It is essential for users to recognize the importance of selecting and installing properly matched motor/drive packages for hazardous applications. Few manufacturers provide UL-approved explosion-proof motors for use on variable-frequency controllers in Division 1 Environments. None have UL approval for Division 2. It is important to note that standard fixed-frequency explosionproof motors are not designed for use with all variable-speed controllers. One should work with a manufacturer that complies with UL 674 and understands the considerations to be weighed and followed when using explosion-proof motors and variablefrequency controllers in hazardous environments. Properly NOTE: This material is not intended to provide operational instructions. Appropriate Reliance Electric Drives instruction manuals precautions should be studied prior to installation, operation, or maintenance of equipment. Publication D-7736 September 2000 2000 Rockwell International Corporation All Rights Reserved Printed in USA