V46 and V47. Repair Parts and Service Instructions. Applications. Adjustments. Installation Guidelines

Similar documents
Manual Flushing. I nspection and Service

Installation Instructions. Applications. Installation. Part No , Rev. Issued May 9, 2011

V46 Series Pressure-Actuated Water-Regulating Valves

This valve is designed to modulate flow of water or glycol to a water cooled condenser on a refrigeration system. ice machines. Pressure Element Style

P70 Series MICRO-SET TM Pressure Controls for Refrigeration and Air Conditioning, 4-Wire, 2-Circuit Contact Block

P70, P72 and P170 Series Controls for High Pressure Applications

P70, P72, and P170 Series Controls for High Pressure Applications

P70, P72, and P170 Controls for Low Pressure Applications

V43xx and V243xx Series Repair Parts Kits

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

M Ball Valve Linkage Kit

M x Cast Iron Flanged Valve Linkage Kit for Mounting a Single M9000 Series Electric Actuator

A-4000 Series Oil Removal and Pressure-Reducing Stations and Air Compressor Accessories

F261 Series Fluid Flow Switches

F61 Series Standard Flow Switches

M x Series Valve Linkage Kits

M x Series Cast Iron Flanged Valve Linkage Kit for Tandem Mounting of M9000 Series Electric Actuators

LOW PRESSURE BALANCED VALVE DIAPHRAGM BALANCED

VG7000 Series Bronze Control Valves

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

Series V47 Temperature Actuated Modulating Valves

A11 Series Low Temperature Cutout Control

Technical Instructions

V-9502 Series Pneumatic Valve Actuator Positioners

Powers Controls 656 Powermite Valve with 3-inch Top Rebuilding

P66 Series Electronic Fan Speed Controls

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 )

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

TECHNICAL INSTRUCTIONS #11 REGULATOR Single Seat - Bronze Trim - Composition Disc

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1/2-1 )

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

PP1 Series Piping Packages for VG1000 Series Ball Valves

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

M Ball Valve Linkage Kit

M Valve Actuator Weather Shield Kit

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

VA-8020 Floating Valve Actuator

ONYX VALVE CO MODEL CAR, CAP-PFO Installation & Maintenance

M x Series Valve Linkage Kits

DeZURIK DR 125 ROTARY DIAPHRAGM ACTUATOR

User s Manual CM2-ALV nd edition

Model 8329 Table of Contents

VG7000 Valve Linkage for M100 Series Motor Actuators

Baumann Series Flexsleev Control Valve Instructions

Y20EBA Linkage Kit, M100 to Barber-Colman 1/2 to 1-1/4 Inch Valves

INSTALLATION & MAINTENANCE MODEL mm

TK-6024, TK-6124, TK-8024, TK-8124

VA-4233-GGx Series Electric Valve Actuators

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

INSTRUCTIONS FOR INSTALLATION, START-UP, AND OPERATION

Model Table of Contents. SERVICE & OPERATING MANUAL Original Instructions. Instructions Sheet:

Pilot-Operated Regulators

TYPE E Main Valve Sizes 3 /8 through 12

Air operated chassis pump

4 - Way Control 4 - Way Control 4 - Way Control with lock

KP-C Series. Close Coupled End Suction Centrifugal Pumps. Installation, Operation and Maintenance

USER INSTRUCTIONS. Installation Operation Maintenance. NAF Setball SF Ball Sector Valves. Experience In Motion FCD NFENIM A4 09/16

ONYX VALVE CO MODEL DAO-PFC Installation & Maintenance

VA-7450 Series. Electric Valve Actuators

HIGH PRESSURE CONTROL VALVE PISTON BALANCED

Valtek Spring Cylinder Linear Actuators

Mounting and operating instructions EB EN. Differential Pressure and Temperature Regulator with Flow Limiter Type 2479/2430 K

Cylinder and Valve: AirHawk II Air Mask

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves

ONYX VALVE CO MODEL DAO-PFO Installation & Maintenance

PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY

Technical Data TYPE T124 & T134 TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4512A

Replacing the Internal Oil Filter Elements for HS85 and OS 85 Screw Compressors

Installation Instructions

VG2000 Series Cast Iron Flanged Globe Valves

Maintenance Information

ONYX VALVE CO MODEL DAO-ADA Installation & Maintenance

CONTROL VALVES SINGLE PORTED CLASSES DL, DDL, DOS, DDOS

MK-6600 Series, MK-6800 Series, and MK-6911

OPERATION AND MAINTENANCE MANUAL 2-66 SERIES 2500 RESILIENT WEDGE GATE VALVE

Baumann Mikroseal Control Valve

CONTROL VALVES. Installation, Maintenance & Operating Instructions. Read these instructions carefully before installation or servicing.

J Flow Controls Model Numbering

Fisher 3024C Diaphragm Actuator

Type 644 and 645 Differential Pressure Pump Governors

NUMBER: S.M. REF.: Listed in Table ENGINE: EPA07 Series 60 DATE: October 2012 SUBJECT: REFERENCES TO THE TURBOCHARGER PURGE ROUTINE

Flare Valves 1/2 inch 2-Way and 3-Way

Split Body Valves with Bellows Seal Series Globe Valves Series Angle Valves Series Way-Valves

Installation, Operation and Maintenance Instructions Series 608 Ball Valve

M9000-3xx Series Weather Shield Enclosures

Integra Pneumatically Operated Diaphragm Valves with Position Indication Option

AV-8020 Series Floating Control Actuated Valve

A-4000 Series Oil Removal and Pressure Reducing Stations & Air Compressor Accessories

M100F Incremental Motor Actuator R81F Interface Board

DeZURIK R1 POWERRAC ACTUATOR ON 1/2-3" PEC ECCENTRIC VALVES

DeZURIK " BAW AWWA BUTTERFLY VALVES WITH EPOXY-RETAINED SEAT

B0123HF and B0123HE Pressure Regulators. B1279UL Air Filter

PNEUMATIC SLIDING VALVE

INSTRUCTION MANUAL. CR Series A/B

Installation Instructions

Temperature Sensor Series

User s Manual OM th edition

Operating & Maintenance Manual For Steam Conditioning Valve

Baumann Sanitary Angle Control Valve

Transcription:

Applications The V46 pressure-actuated and V47 temperatureactuated water-regulating valves are used for water-cooled condensers, bypass service on refrigeration systems, engine cooling, and various industrial applications. Installation Guidelines V46 and V47 Repair Parts and Service Instructions IMPORTANT: The V46 and V47 valves are intended to control liquid flow under normal operating conditions. Where failure or malfunction of the V46 and V47 valves could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices, such as supervisory or alarm systems or safety or limit controls, intended to warn of or protect against failure or malfunction of the V46 and V47 valves. Follow these guidelines to install the V46 and V47 valves. Flush liquid lines to remove filings, chips, and other foreign matter before connecting to the valve. Make liquid line connections so the flow through the valve is in the direction of the arrow on the body casting. Make sure that the bulb and capillary do not rub against any metal obstruction that can wear and damage the element. Tighten the connector and seal, if furnished with the closed tank connector by tightening the small gland nut on heavy tubing near the bulb. Refer to the QuickLIT website for the most up-to-date version of this document. Avoid mounting the valve where the bulb might be partly above operating liquid level or surrounded by an air pocket. Mount the valve vertically with the bellows facing downward.! Adjustments Part No. 24-8414-12, Rev. C Code No. LIT-121695 Issued March 4, 2014 Supersedes January 1, 1996 CAUTION: Risk of Environmental and Property Damage. Avoid sharp bends in the capillary tubes. Sharp bends can weaken or kink capillary tubes, which may result in refrigerant leaks or restrictions of flow. To raise the valve opening point on direct-acting valves, turn the adjusting screw counterclockwise. To lower the valve opening point, turn the range adjusting screw clockwise. See Figure 2. The closing point of the valve is not adjustable. Pressure-actuated valves close approximately 3 to 7 psi (21 to 48 kpa) below the opening point, and temperature-actuated valves close approximately 3 to 5 F (1.7 to 2.8 C) below the opening point. If the compressor operates in high ambient temperatures, head pressures may remain high enough during off cycles to prevent the valve from closing completely. In such instances, the opening point of the valve should be raised just enough to cause the valve to close during compressor standby periods. The opening of the valve raises the throttling point. The all-range pressure-actuated valve settings can be adjusted for both low pressure refrigerant ranges of R-134a and higher pressure refrigerant ranges of R-22 (R-502). V46 and V47 Repair Parts and Service Instructions 1

Manual Flushing To clear any sediment that may accumulate, valves may be manually flushed by inserting screwdrivers under both sides of the main spring and lifting upwards to flush the valve. Manual flushing does not affect valve adjustments. Note: Parts supplied in the renewal kit replace both V46 and V47 Series valve assemblies. Assembly Inspection and Service To inspect and replace internal parts, follow the procedures in this section. After long periods of operation, the valve seat and rubber disc may become worn, pitted, or wiredrawn, preventing the valve from completely closing off, allowing leakage through the valve in the closed position, when the pressure and temperature is below the setpoint. Figure 2: Valve Components Servicing V46 and V47 2 in. and 2-1/2 in. Valve Figure 1: Manual Flushing IMPORTANT: To decrease the pressure in the sensing element on the V47 valves, cool the bulb by submerging it in ice water. Do not remove the bulb from the ice water until the element is ready to be reinstalled. Otherwise, the pressure increases in the sensing element, resulting in a valve that is hard to reassemble.! WARNING: Risk of Personal Injury. Shut off the liquid supply and relieve pressure in the line before servicing the valve. Contents of liquid lines could be under pressure and the release of liquid under pressure may cause severe personal injury. Figure 3: V46 and V47, 2 in. and 2-1/2 in. Valves 2 V46 and V47 Repair Parts and Service Instructions

! WARNING: Risk of Personal Injury. Protect eyes. Do not remove the two screws on the sides of the spring housing. Disassembly can cause a compressed spring to fly out and may result in serious eye injuries, blindness, or other severe injury. 1. Decrease the compression on the main spring by turning the range adjusting screw clockwise until it stops. Using excessive force to turn the screw beyond the stop point strips the thread. 2. Remove the four screws holding the spring housing and remove the entire housing assembly. See Figure 2. 3. Remove the valve assembly screw (Figure 3). 4. Remove the guide post and old diaphragms (Figure 3). 5. Remove the sensing element and the diaphragms between it and the valve body (Figure 3). 6. Pull the disc, disc retainer, and extension sleeve assembly from the valve (Figure 3). 7. Remove the old valve seat and replace it with the new valve seat (Figure 3). (A seat wrench is not provided for 2 and 2-1/2 in. valves. Use 1-1/2 and 1-15/16 in. hex stock, respectively.) 8. Replace the three diaphragms between the sensing element and valve body (Figure 4). 9. Replace the guide plate gasket and bellows sealing ring (Figure 4). 10. Assemble the sensing element to the valve body with the bellows push rod, new diaphragms, guide plate gasket, and bellows sealing ring in place. 11. Assemble the new disc, disc retainer, and extension sleeve. a. Apply a small amount of grease to the grooves on the bottom of the new extension sleeve and the top of the new disc retainer. Place one O-ring into each groove. b. Place the subassembly into the valve. 12. Place two new diaphragms on the spring housing end of the valve body. 13. Screw the valve assembly screw through the guide post and into the bellows push rod (Figure 3). 14. Place the spring housing assembly over the guide post and secure in place with the four housing screws. 15. Adjust the valve to desired opening point. Then manually flush the valve. See the Manual Flushing section. 16. Before leaving the installation, run the system through at least one complete operating cycle to be sure the valve is operating correctly. for pressure Figure 4: Guide Plate Gasket and Bellows Sealing Ring Identification Gasket V46 and V47 Repair Parts and Service Instructions 3

Servicing V46 and V47 3/8 in. through 1-1/2 in. Valves IMPORTANT: To decrease the pressure in the sensing element on the V47 valve, cool the bulb by submerging it in ice water. Do not remove the bulb from the ice water until the element is ready to be reinstalled. Otherwise, the pressure increases in the sensing element, resulting in a valve that is hard to reassemble.! WARNING: Risk of Personal Injury. Protect eyes. Do not remove the two screws on the sides of the spring housing. Disassembly can cause a compressed spring to fly out and may result in serious eye injuries, blindness, or other severe injury. Note: Reverse-acting 3/8 in. valves do not require the ISO-loss washer. a. Slightly squeeze the spring housing assembly to remove the spring housing. b. Remove the range adjusting screw, spring, and valve spring guide (Figure 6). c. Clean off any excess grease on the valve spring guide. d. Place the new ISO-loss washer over the guide plate. e. Replace the valve spring guide, spring, range adjusting screw, and spring housing. ISO-loss Washer ISO-loss Washer Post Disc Stud Disc Cup Valve Disc Guide Plate Gasket Figure 5: V46 and V47 3/8 in. through 1-1/2 in. Valves 1. Decrease the compression on the main spring by turning the range adjusting screw clockwise until it stops. Using excessive force to turn the screw beyond the stop point strips the thread. 2. Remove the four screws holding the spring housing and remove the entire housing assembly. See Figure 2. 3. To improve the performance on 3/8 in. direct-acting valves, install the ISO-loss washer that is supplied with the 3/8 in. valve repair kit as follows: Figure 6: ISO-loss Washer 4. Remove the seat guide post (Figure 5). 5. Remove the rubber diaphragms (Figure 5). 6. Turn the disc stud counterclockwise to remove the valve stem assembly (Figure 5). 7. Remove the sensing element, bellows push rod, and diaphragms. See Figure 8. 8. Using the seat wrench supplied with the kit, remove the old valve seat and replace it with the new valve seat (Figure 5). 9. Assemble the new valve stem, disc, disc cup, and disc stud, and place into the valve body (Figure 5). 10. On 1 in. and larger pressure valves and all temperature valves, replace the guide plate gasket and bellows sealing ring (Figure 8). 11. If servicing a V47 or V46 valve other than low flow, place new diaphragms on the sensing element end of the valve stem assembly. Use two diaphragms on 3/8 in., 1/2 in., and 3/4 in. valves and three diaphragms on 1 in. and larger valves. Screw the diaphragm into place with the bellows push rod. Attach the sensing element to the valve body. See Figure 5. 4 V46 and V47 Repair Parts and Service Instructions

12. If servicing a low flow valve, place the stem washer and new diaphragms on the sensing element end of the valve stem assembly. Use two diaphragms on 3/8 in., 1/2 in., and 3/4 in. valves and three diaphragms on 1 in. and larger valves. Screw the diaphragm into place with the bellows push rod. Attach the sensing element to the valve body. See Figure 7. 15. Adjust the valve to desired opening point. Then manually flush the valve. See the Manual Flushing section. 16. Before leaving the installation, run the system through at least one complete operating cycle to be sure the valve is operating correctly. Post Disc Stud Disc Cup ISO-loss Washer Valve Disc Guide Plate Gasket for pressure Gasket Figure 7: Low Flow Valves 13. Place two new diaphragms on the spring housing side of the valve body. Screw into place with the seat guide post (Figure 7). 14. Place the spring housing assembly over the seat guide post and secure in place with the four housing screws. Figure 8: Guide Plate Gasket and Bellows Sealing Ring Identification V46 and V47 Repair Parts and Service Instructions 5

Renewal Kits Table 1: Renew Kits Individual Part Description Commercial Type: V46A, V46D, V47A, V47N Maritime and Navy Type: V46B, V46C Diaphragm Kits for All Types Seat Guide Post 1 1 1 1 1 1 1 1 1 1 1 Disc Stud 1 1 1 1 1 1 1 1 1 1 1 Disc Cup (Retainer) 1 1 1 1 1 1 1 1 1 1 1 Valve Disc 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Valve Seat 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Valve Stem 1 1 1 1 1 1 1 1 1 1 1 Rubber Diaphragm 1 4 4 4 4 5 5 5 5 4 4 4 5 5 5 5 5 Guide Plate Gasket 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Bellows Sealing Ring 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Valve Assembly Screw 1 1 1 Guide Post 1 1 1 Valve Disc Retainer 1 1 1 Extension Sleeve 1 1 1 Seat Wrench 1 1 1 1 1 1 1 1 1 1 1 Sensing Element Contact Application Engineering at (414)-524-5535 Stem Washer 1 ISO-loss Washer 2 1 1 1 O-ring Seals 2 2 1. 3/8, 1/2, and 3/4 in. valves require two diaphragms on the spring end and two diaphragms on the sensing element end. One through 2-1/2 in. valves require two diaphragms on the spring end and three diaphragms on the sensing element end. 2. Reverse acting 3/8 in. valves do not require an ISO-loss washer. Building Efficiency 507 E. Michigan Street, Milwaukee, WI 53202 Johnson Controls and PENN are registered trademarks of Johnson Controls, Inc. in the United States of America and/or other countries. All other trademarks used herein are the property of their respective owners. Copyright 2014 by Johnson Controls, Inc. All rights reserved. 6 V46 and V47 Repair Parts and Service Instructions Published in U.S.A. www.johnsoncontrols.com