Now Available Sweat Connection. Belimo ZoneTight Zone Valves Technical Documentation

Similar documents
Z2 050 Q -J +CQB 24 -SR -L

LF24-SR US TF24-SR US TFX24 US LF24 US. B3 B Three-way Characterized Control Valve, Chrome Plated Brass Ball and Brass Stem

B2/B3 Series Characterized Control Valve, Non-Spring Return Actuator

B2 Series Characterized Control Valve, Non-Spring Return Actuator

G3 (D) 3-way Globe Valve, Bronze Trim

G7 (S) 3-way Mixing Flanged Globe Valve, Bronze or Stainless Steel Trim

P2050S-030, 1/2, Electronic Pressure Independent Valve Stainless Steel Ball and Stem, Female NPT Ends

PRESSURE INDEPENDENT CONTROL VALVES (epiv & PICCV )

pressure independent characterized control tm

PRESSURE INDEPENDENT CONTROL VALVES (PICCV& epiv)

G6 C(S)(LCS) 2-way Pressure Compensated Flanged Globe Valve

Pressure Independent Characterized Control Valves (PICCV)

Electronic Pressure Independent Valves (epiv)

Pressure Independent Characterized Control Valves (PICCV)

Technical Documentation Pressure Independent Characterized Control Valves (PICCV) Patented Effective December 2007

Pressure Independent Characterized Control Valves (PICCV)

7 ZONE VALVES. Applications

VA9203-AGx / VA9203-Bxx / VA9203-GGx

Electronic Pressure Independent Valves (epiv)

Technical Documentation Ball Valves

B278, 2-Way, Characterized Control Valve Stainless Steel Ball and Stem

B352, 3-Way, Characterized Control Valve Stainless Steel Ball and Stem

High temperature characterized control valves

Minimum 18 in-lb Torque

G765, 3-Way, Mixing Flanged Globe Valve

Minimum 18 in-lb Torque. Applications. TF Series At A Glance. TF Series Spring Return Direct Coupled Actuator. For damper areas up to 4.

High Performance Solutions. Belimo Pressure Independent Control Valves

Zone Valves and Parts (Honeywell)

Versatile and Powerful

Minimum 27 in-lb Torque

Simple Set COMMERCIAL. Pressure Independent Control Valves 2 Way 1/2-2 02/16/18 COMMERCIAL

G7100S, 3-Way, Mixing Flanged Globe Valve

G765, 3-Way, Mixing Flanged Globe Valve

Minimum 27 in-lb torque

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

Versatile and Powerful

G780, 3-Way, Mixing Flanged Globe Valve

2006 Product Range Overview. Belimo Project: One Bellevue Center, Seattle, Washington

M9206-GGx-2S Series Proportional Electric Spring Return Actuators

Minimum 90 in-lb Torque. Applications. NFB, NFX Series At A Glance. NFB and NFX Series Spring Return Direct Coupled Actuator

Pressure Independent Valves for Terminal Unit Applications

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

F6100HD, 4, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

FSAF24(-S) US, FSAF120(-S) US

F6150HD, 6, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

F6125HD, 5, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

LF Series At A Glance

F6250L, 10, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

ZG-JSL, ZG-JSLA Jackshaft Retrofit Linkage For AF, NF, LF, NMX and AMX Series Actuators

Electronic Pressure Independent Valve (epiv)

F6200L, 8, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

G7150D, 3-Way, Diverting Flanged Globe Valve

Spring Achieve System Balance Without All The Spin. PICCV. Complete Details Inside!

VE-S_15-32 Pressure Independent Balancing & Control Valves

F6 Series 2-Way, Victaulic Butterfly Valve

Pressure Independent Control Valve Applications for Building Automation, Temperature Controls, and HVAC Two-Way Chilled Water Hot Water

Installation, Operation and Maintenance. VA(M)S24-27 (T)-T Series Actuator

VBB/VBS Series Ball Valve Assemblies

ATT Series Adjustable PIC Valves 2 Way 1/2-1-1/2 ATT - AutoTouch Terminal

F6250L, 10, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

Features Globe Valve 2-Way & 3-Way Assembly Features:

LF Series Spring Return Direct Coupled Actuator

ES177B2(-S) Series Proportional Electric Spring Return Actuators

Selection Guide. Vx-2x13-5xx-9-xx Series Vx-2x13-8xx-9-xx Series VB-2x xx Series. Schneider Electric Ball Valve Assemblies

ATi Max Series. Pressure Independent Control Valves 2 Way 2-1/2-6

F6100HD, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

F6300L, 12, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

Stainless Steel Pilot Piston Solenoid Valve 2MS Series for High Temperature & High Pressure

Torque min. 35 in-lb, for control of air dampers

Butterfly Valves (BFV)

STC 2W Series Solenoid Valves

VRN Dynamic Pressure-Regulating Control Valves and Actuators

F6150HD, 6, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

TRF.. series spring return rotary actuators for CCV

Installation Instructions

Belimo is the Worldwide Leader in Fire and Smoke Actuation

STC 2P025 Series Solenoid Valve

MVN Rotary Valve Actuators FOR CONTROL BALL VALVES VBG (DN15 TO DN32)

Installation Instructions

VA9104-xGA-2S Series Electric Non-Spring Return Valve Actuators

Mount directly to 1.05 jackshafts. AF230 US (p. 02) AF230-S US (p. 20) AF24-S US (p. 18)

STC 2L Series Solenoid Valves

VA, VF, and VS Series Direct Mounted Globe Valve Assemblies. Application. Features

The Siemens 599 Series Ball Valve Portfolio simplifies installations and maximizes control usa.siemens.com/hvac

Hose Length Custom Length Supply Line Options Ball Valve w/ PT UBY Strainer w/ PT and BDV

F6100HD, 4, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

Characterized Port -CP Three-Way Ball Valves

Product Catalog. Precision Control DeltaPValves. guaranteed delta T 10-year warranty made in the USA

24/3000H-3PH 24/4500H-3PH 24/6000H-3PH

Overview of types. Characterised control valves, 3-way, with internal thread For closed cold and warm water systems

NV Direct Coupled Globe Valve Actuator

G6125C, 2-Way, Pressure Compensated Flanged Globe Valve

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

Product bulletin for: ST2 Ball valves with two-way and three-way BSPP threaded fittings

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

599 Series Zone Valve Bodies:

PIC-V Valve... 1 Unimizer (1/2 to 3 )... 2 Unimizer (4 to 6 )... 3 Automizer... 4 MVP Valve... 5

LMB24-3 (-S)(-T) On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 24 V

VA9104-xGA-1S Series Electric Non-Spring Return Valve Actuators

PUMP PRIMING INSTALLATION CHECK MOTOR ROTATION PUMP START-UP MOTOR REPLACEMENT DISASSEMBLY ELECTRICAL HOOKUP ASSEMBLY

Transcription:

Version 07_1_17 Now vailable Sweat Connection Belimo ZoneTight Zone Valves Technical Documentation

Table of Contents Overview.......................................... 3 QCV Nomenclature........................................ 5 PIQCV Nomenclature...................................... 7 Set-Up.......................................... 9 ccessories..........................................10 Flow Pattern..........................................11 Piping..........................................1 Field-Set djustment.......................................14 Installation..........................................15 Wiring..........................................16 Flow Verifi cation.........................................18 Troubleshooting.........................................1 Valve Specifi cation and Dimensions............................... ctuator Specifi cation......................................5 Flow Curves..........................................6 Terms and Conditions......................................8

Overview Designed for maximum efficiency in tight spaces, Belimo s ZoneTight valve offering sets new design and performance standards for both pressure dependent and pressure independent zoning applications. ZoneTight Zone Valve (QCV) The ultra-compact QCV leads the way in Belimo s new generation of room and zone solutions. Equipped with a space-saving -way or 3-way ball valve and an electronic rotary actuator, the QCV has an installation height of just 4.33 inches (110 mm), available NPT or Sweat, and offers a number of benefits over conventional pressure dependent control valves, including: Belimo ball valve design with zero leakage eliminates energy loss. Self-cleaning ball valve technology provides superior clog resistance. Low power consumption up to 95% less than conventional zone valves. Field adjustable Cv value to meet your design requirements. ZoneTight Pressure Independent Zone Valve (PIQCV) The PIQCV offers all the advantages of a Pressure Independent Characterized Control Valve (PICCV) but in an ultra compact confi guration. The PIQCV combines a differential pressure regulator with a -way control valve to supply a specific fl ow for each degree of ball opening regardless of system pressure fluctuations. The valve performs the function of a balancing valve and control valve in one unit. Smallest pressure independent characterized ball valve in the market. ctuator runs at 0.3 W saving energy and transformer power. Flow is adjustable at the actuator and always perfectly balanced. Permits PIV installation in tight spaces. Pressure Flow PIQCV 3 1 3 4 ZoneTight Zone Valve Valve body Control valve (QCV) 1 4 9 6 5 7 8 ZoneTight Pressure Independent Zone Valve Valve body Control valve (PIQCV) 10 11 Regulator 1 Body NPT or Sweat 3 Stem Ball with profi le 1 Body End Cap 4 5 Stem Ball with profi le 7 8 Regulator Cap Regulator Body 4 Seat 3 PT Ports 6 Seat 9 Diaphragm 10 Regulator Shaft 11 Regulator Spring 3

Features ZoneTight Features Compact Design When faced with limited available mounting space, the Belimo ZoneTight valve s super-compact design helps maximize workable space and complements OEM valve compartment optimization. Ball Valve Technology Unlike short stroke globe valves with plug and seat design, the self-cleaning ball helps minimize energy losses caused by clogging (0% to B leakage) and eliminates seat leakage. The intuitive confi guration also allows for bi-directional fl ow (QCV) unlike traditional paddle style zone valves. In addition, equal percentage fl ow characteristic provides superior part load coil performance. ctuator with Patented Brushless DC Motor The brushless DC motor s power consumption when running is a mere 0.3W, 0.15W when holding, saving energy and transformer power. In addition to signifi cantly reducing energy costs, this helps eliminate failures due to stalled motors and prolongs actuator life. It also allows for more units to be powered by a single transformer. Snap Fit The QCV and PIQCV easily connects to the actuator allowing operators and technicians to install valves quickly, easily, and without the use of tools. This helps simplify commissioning and reduces labor costs. Field djustable Max Cv/Flow QCVs and PIQCVs can be quickly and easily fi eld adjusted to ensure that necessary design requirements are met and reduces inventory. Stem Extension for Insulation Unlike conventional zone valve actuators, which are normally covered by pipe insulation, the stem extension on QCVs and PIQCVs allows for easy actuator removal without damaging the surrounding insulation, helping simplify operation and maintenance activities. 4

Nomenclature QCV Nomenclature Z 050 Q S -J +CQB 4 -SR -L Valve Type Z = -way Z3 = 3-way ZoneTight Chrome Plated Brass Ball and Brass Stem Valve Size 050 = ½ 075 = ¾ Quick Connect Connection Type Blank = NPT S = Sweat Cv -way F = 1.4 J = 5.9 K = 9.8 3-way* E = 1 H =.7 J = 4.6 *On/off only. ctuator Type Non-Spring Return CQB CQKB Power Supply 4 = 4 VC/DC UP = 110-30 VC Control -3 = On/Off, Floating Point -SR = Modulating Input = -10 VDC Direction of Rotation -L = Open ( VDC) -R = Close ( VDC) -LL = Normally Open, Fail Open -RR = Normally Close, Fail Close -LR = Normally Open, Fail Close -RL = Normally Close, Fail Open -S = Built-in ux. Switch Ordering Example 1 Choose the valve actuator combination. Z050QS-J+CQB4-SR Choose set-up required Modulating Non-Spring Models L = Normally Open R = Normally Closed Models LL = Normally Open/Fail Open LR = Normally Open/Fail Closed RL = Normally Closed/Fail Open RR = Normally Closed/Fail Closed Refers to valve ports from inlet to outlet, per fl ow arrow. Set-Up -L Tagging (if needed) 3 Does order require tagging? Tagging: Valves may be tagged per customer specifi cation. ($10.00 charge per tag) Example: HU-1 FCU- Part number for tagging: 99981-00101 4 Complete Ordering Example: Z050QS-J+CQB4-SR-L 5

QCV Product Range Valve Nominal Size Type Suitable ctuators C v Inches DN [mm] -way 3-way Non- Spring Return 1.4* ½ 15 Z050Q-F 5.9* ½ 15 Z050Q-J NPT 9.8* ¾ 0 Z075Q-K 1 ½ 15 Z3050Q-E Sweat.7 ½ 15 Z3050Q-H 4.6 ¾ 0 Z3075Q-J 1.4* ½ 15 Z050QS-F 5.9* ½ 15 Z050QS-J 9.8* ¾ 0 Z075QS-K 1 ½ 15 Z3050QS-E.7 ½ 15 Z3050QS-H CQ Series CQK Series QCV Mode of Operation The ZoneTight Zone Valve (QCV) is operated by a rotary actuator. The actuators are controlled by a standard voltage for on/off control, a modulating signal, or 3-point control system which moves the ball of the valve to the position dictated by the control system. 4.6 ¾ 0 Z3075QS-J *Maximum fl ow. Max value can be field adjusted, see actuator instructions. Product Features The equal percentage characteristic of the flow is ensured by the design of the ball. This characteristic provides linear heating or cooling output from the coil improving energy efficiency and comfort. V max End Stop Positions V nom 1 3-3 4 4+ 5 5+ 6 N No end stop Z050Q(S)-F (½ ) 0.1 N/ 0. N/ N/ 0.4 N/ 0.6 0.8 1. 1.4 Z050Q(S)-J (½ ) 0.5 0.7 N/ 1. 1.7 N/.4 N/ 3 4.8 5.9 Z075Q(S)-K (¾ ) 0.5 1.0 N/ 1.5.3 N/ 3.3 N/ 4.6 6.6 9.8 ctuator Specifications Control type -3 on/off, fl oating point -SR modulating, -10 VDC Manual override use actuator to turn valve stem Electrical connection 3 ft. [1 m] cable with ½ conduit fitting screw terminals Power consumption CQ.. 0.3 W running, 1.5 W holding CQK.. 3 W running, 1 W holding CQ..UP 1.5 W running, 1.1 W holding Power supply 4 VC/DC (110-30 VC, UP) Transformer sizing CQ.. 0.6 V CQK.. 8 V CQ..UP V Valve Specifications Service Flow characteristic Controllable flow range chilled or hot water, 60% glycol equal percentage (-way) linear (3-way) 75 (-way), 90 (3-way) Sizes ½, ¾ End fi tting NPT female sweat Materials Body forged brass Ball chrome plated brass Stem brass Seats Tefl on PTFE O-rings EPDM (lubricated) Media temp. range 36 F to 1 F [ C to 100 C] Media temp. limit 50 F [10 C] Maximum allowable operating temperature 1 F [100 C] Body pressure rating 360 psi Close-off pressure 75 psi Maximum differential pressure ( P) 40 psi Leakage 0% Tefl on is a registered trademark of DuPont If temperature exceeds 1 F [100 C] operating range due to a boiler control failure the valve will safely contain the hot water but manufacturer s product warranty becomes invalid. 6

Nomenclature PIQCV Nomenclature Z 050 Q P T -B +CQB 4 -SR -R Valve Type Z = -way ZoneTight Chrome Plated Brass Ball and Brass Stem Valve Size 050 = ½ 075 = ¾ Quick Connect Pressure Independent T = PT Port Flow Rate B = 0.9 GPM D =.0 GPM F = 4.3 GPM G = 9.0 GPM ctuator Type Non-Spring Return CQB CQKB Power Supply 4 = 4 VC/DC UP = 110-40 VC Control -3 = Floating Point -SR = Modulating Input = -10 VDC Direction of Rotation -L = Open ( VDC) -R = Close ( VDC) -LL = Normally Open, Fail Open -S = Built -in ux. Switch -RR = Normally Close, Fail Close -LR = Normally Open, Fail Close -RL = Normally Close, Fail Open Ordering Example 1 Choose the valve actuator combination. Z050QPT-B+CQB4-SR Choose set-up required. Modulating Non-Spring Models L = Normally Open R = Normally Closed Models LL = Normally Open/Fail Open LR = Normally Open/Fail Closed RL = Normally Closed/Fail Open RR = Normally Closed/Fail Closed Set-Up -R Re fers to valve ports from inlet to outlet, per fl ow arrow. Tagging (if needed) 3 Does order require tagging? Tagging: Valves may be tagged per customer specifi cation. ($10.00 charge per tag) Example: HU-1 FCU- Part number for tagging: 99981-00101 4 Complete Ordering Example: Z050QPT-B+CQB4-SR-R 7

PIQCV Product Range Valve Nominal Size Type Suitable ctuators GPM Inches DN [mm] -way NPT with PT ports 0.9* ½ 15 Z050QPT-B.0* ½ 15 Z050QPT-D 4.3* ½ 15 Z050QPT-F 9.0* ¾ 0 Z075QPT-G Non-Spring Return CQ Series *Maximum fl ow. Max value can be field adjusted, see actuator instructions. CQK Series PIQCV Clip Position for Flow djustment (GPM) 1 3 4 5 6 N No Clip Z050QPT-B N/ N/ N/ N/ 0.4 N/ 0.8 0.9 Z050QPT-D 0. 0.3 0.4 0.6 0.9 1.3 1.8.0 Z050QPT-F N/ 0.6 0.9 1.3 1.9.8 3.6 4.3 Z075QPT-G N/ 1.8.7 3.7 4.9 6.3 7.7 9.0 ctuator Runtime 30 sec. 37 sec. 43 sec. 49 sec. 55 sec. 6 sec. 68 sec. 75 sec. For additional intermediate settings see technical documentation or the ZoneTight fl ow capacity setting tool on www.zonetight.com or www.belimo.us. Mode of Operation The ZoneTight Pressure Independent Zone Valve (PIQCV) is a two-way valve which combines the functionality of a control valve and a pressure regulating valve, creating one precise product which is unaffected by pressure variations in a system. Product Features Constant flow regardless of pressure variations in the system at set degrees of ball opening. Maximizes chiller ΔT, preventing energizing additional chillers due to low ΔT. Simplifi ed valve sizing and selection, no C v calculations required. ctuator Specifications Control type -3 on/off, floating point -SR modulating, -10 VDC Manual override use actuator to turn valve stem Electrical connection 3 ft. [1 m] cable with ½ conduit fitting screw terminals Power consumption CQ.. 0.3 W running, 0. W holding CQK...5 W running, 0.5 W holding CQ..UP 1 W running, 0.7 W holding Power supply 4V (110-40 VC, UP) Transformer sizing CQ.. 0.6 V CQK.. 5 V CQ..UP V Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic equal percentage Controllable flow range 75 Sizes ½, ¾ End fitting NPT female Materials Body forged brass Ball stainless steel Stem stainless steel Seats Tefl on PTFE O-rings PTFE Spring stainless steel Media temp. range 36 F to 1 F [ C to 100 C] Media temp. limit 50 F [10 C] Maximum allowable operating temperature 1 F [100 C] PT ports Body pressure rating 360 psi Close-off pressure 00 psi Differential pressure (ΔP) range 5 to 50 psi Leakage 0% If temperature exceeds 1 F [100 C] operating range due to a boiler control failure the valve will safely contain the hot water but manufacturers product warranty becomes invalid. 8

Set-Up QCV ND PIQCV SET-UP- Specify Upon Ordering -WY VLVE 3-WY VLVE (QCV ONLY) NON-SPRING RETURN Stays in Last Position CQBUP-3 CQB4-3 CQB4-SR Power to brown wire (pin for -T versions) will drive valve CW. Power to blue wire (pin 3 for -T versions) will drive valve CCW. Power to red wire (pin for -T versions) will drive valve CW. Power to white wire (pin 3 for -T versions) will drive valve CCW. CQB4-SR-R: Normally closed, valve will open as voltage increases CQB4-SR-L: Normally open, valve will close as voltage increases Power to brown wire (pin for -T versions) will drive valve CW. Power to blue wire (pin 3 for -T versions) will drive valve CCW. Power to red wire (pin for -T versions) will drive valve CW. Power to white wire (pin 3 for -T versions) will drive valve CCW. CQKB4 CQKB4-S CQKB4-LL, CQKB4-S- LL: Normally open CCW, valve will drive closed when energized. ction: ctuator will fail open CCW upon power loss. CQKB4-RR, CQKB4-S- RR: Normally closed CW, valve will drive open when energized. ction: ctuator will fail closed CW upon power loss. One wire control for CW or CCW rotation. FIL-SFE CQKB4-SR CQKB4-SR-RL: Normally closed CW, valve will open as voltage increases. ction: Will fail open upon power loss. CQKB4-SR-LL: Normally open CCW, valve will close as voltage increases. ction: Will fail open upon power loss. CQKB4-SR-RR: Normally closed CW, valve will open as voltage increases. ction: Will fail closed upon power loss. CQKB4-SR-LR: Normally open CCW, valve will close as voltage increases. ction: Will fail closed upon power loss. 9

ccessories VLVE TYPE ZONETIGHT VLVE CCESSORIES Valves Z (-WY) Z3 (3-WY) ZCQB-FL Flow setter PIQCV QCV ZCQ-E QCV or PIQCV valve stem extension. Designed for chilled water service up to 104 F [40 C] media temperature PIQCV QCV FLOW ORIFICE FO15010 ½ Flow orifice for 1.0 GPM FO1505 ½ Flow orifice for.5 GPM FO15055 ½ Flow orifice for 5.5 GPM FO0100 ¾ Flow orifice for 10.0 GPM PIQCV QCV PIQCV QCV PIQCV QCV QCV RCHITECTURL COVER ZCQB-W Housing cover for CQ actuators (white) PIQCV QCV 10

Flow Pattern QCV Flow Pattern QCV -way valves can be piped with fl ow entering and exiting either port. For on/off control of coil fl ow the QCV 3-way valve is piped with supply entering the bottom part. For a QCV 3-way switching application, pipe hot and cold supply water to either side ports and the appropriate seasonal supply water will exit the bottom port for regulation by another -way valve; typically installed in the return pipe. INLET OUTLET Side Side Bottom PIQCV Flow Pattern The PIQCV consists of a differential pressure regulator and a control valve. The control valve is throttled to match the fl ow command of the control signal. The differential pressure regulator holds the pressure drop across the ball of the valve. s system pressure changes, the differential pressure regulator moves in response to keep the fl ow stable. Pressure (P1) at the inlet PIQCV is high and pressure (P3) at the outlet is low. The differential pressure between (P1) and (P3) must be between 5-50 to achieve pressure independent fl ow. When differential pressure increases the regulator opening is decreased. When differential pressure decreases the regulator opening is increased. This allows for the constant pressure differential across the ball of the valve. P3 P3 P P1 11

Piping QCV Typical Piping -way Valve Piping Diagram 3-way Switching Valve Piping Diagram 3-way Diverting Valve Piping Diagram PIQCV Typical Piping PIQCVs are recommended to be installed on the return side of the coil. This diagram represents a typical application. Consult engineering specifi cation and drawings for project details. PT ports are recommended if not supplied on either side of the valve and the supply side of the heat transfer device to allow for pressure/fl ow measurement/calculation. H/C COIL FLOW IR VENT DRIN BELIMO PIQCV (TYP.) FLOW P/T PORT UNION CONNECTION (TYP.) P/T PORT FLOW P/T PORT STRINER (Optional) FLOW FLOW SHUT OFF VLVE SHUT OFF VLVE 1

Belimo ZoneTight Zone Valves Orientation QCV/PIQCV Orientation QCV and PIQCV assemblies can be installed in a vertical or horizontal arrangement, as long as the actuator is positioned to avoid water from dripping on the actuator.! QCV kg PIQCV kg >1 F PIQCV s should be installed with flow in the direction of the arrow on the valve body. If installed backwards, there could be damage to either the diaphragm or the regulator. The valve assembly can be installed in a vertical or horizontal arrangement. 360 90 90 90 90 800-543-9038 US 866-805-7089 CND 03-791-8396 LTIN MERIC / CRIBBEN 13

Belimo ZoneTight Zone Valves Field-Set djustment QCV/PIQCV Field-Set Flow Capacity djustment lign the clip to the notch scale found on the underside of the actuator to the corresponding flow in the table below. For 3-point floating control signals adjust the controller runtime parameter to match the runtime of the of the final clip position. For analog -10 VDC control signals see adaption instructions. For incremental notch settings refer to the flow graphs on page 5 or visit www.zonetight.com and put in your flow requirements to determine your notch position. QCV 1 1 V'max End Stop Positions Size Valve Model 1/" Z050Q(S)-F 0.1 1/" Z050Q(S)-J 0.5 0.7 1. 1.7 3/4" Z075Q(S)-K 0.5 1.0 1.5.3 30 37 43 49 Runtime (seconds) 3-3 4 4+ 0. 5 5+ 6 N No end stop 0.6 0.8 1. 1.4.4 3 4.8 5.9 3.3 4.6 6.6 9.8 6 68 75 0.4 41 51 55 PIQCV 58 1 1 Valve Model 1/" Clip Position for Flow djustment (GPM) 1 1+ + 3-3 0.1 Z050QPT-B Z050QPT-D - 0. 4-4 0. 0.3 0.6 Z050QPT-F 3+ 0.4 0.5 0.7 0.8 0.9 4+ 5-5 0.3 5+ 0.4 6-6 0.5 6+ N- N No Clip 0.6 0.7 0.8 0.9 0.6 0.7 0.8 0.9 1.0 1. 1.3 1.5 1.6 1.8.0 1.0 1.3 1.5 1.7 1.9..5.8 3.1 3.3 3.6 4.3 Valve Model 3/4" Z075QPT-G Runtime 30 33 1.6 1.8.1.4.7 3.0 3.3 3.7 4.0 4.4 4.9 5.3 5.8 6.3 6.7 7. 7.7 9.0 35 37 39 41 43 45 47 49 51 53 55 58 60 6 64 66 68 75 NPT Installation ZoneTight valves are provided with SME NPT female pipe treads for connection to threaded pipe. 800-543-9038 US 14 866-805-7089 CND 03-791-8396 LTIN MERIC / CRIBBEN 1 V'nom

Belimo ZoneTight Zone Valves Installation ctuator ttachment for QCV/PIQCV ttach the actuator to the valve body. lign the actuator guide pins to the valve bonnet openings and press down until a click is heard. To remove the actuator, grasp it with your hand and pull it away from the valve body. click 3 1 daption for Proportional ctuators For actuators with analog -10 VDC signal, after flow capacity adjustment has been field-set by moving the clip to a desired position, execute the adaption routine to scale the signal across the available travel. The actuator will travel first in one direction and stall, then will travel in the opposite direction and stall. Then it will travel to the commanded position of the control signal. When the actuator is powered for the first time the adaption routine will execute automatically. Execute the adaption function any time the clip position is changed. The adaption routine does not change the actuator speed, which is 75 seconds over 90 degree rotation. daption For actuators with On/Off or Floating Control input there is no adaption function or button. Proportional ctuators: CQB4-SR, CQB4-SR-L, CQB4-SR-R, CQKB4-SR, CQKB4-SR-LL, CQKB4-SR-RR, CQKB4-SR-LR, CQKB4-SR-RL On/Off, Floating Point ctuators: CQB4-3, CQBUP-3 On/Off ctuators: CQKB4, CQKB4-S Proportional ctuator Insulation On/Off, Floating Point ctuator Insulation should wrap the pipe and valve body but not the actuator. For chilled water applications use the stem extension kit accessory to raise the actuator above the valve body to provide space for insulation. kg >1 F 800-543-9038 US 866-805-7089 CND 03-791-8396 LTIN MERIC / CRIBBEN 15

Wiring Diagrams Wiring Diagrams 3 18 1 Provide overload protection and disconnect as required. Line Volts Blk Red Common + Hot ctuators may be connected in parallel. Power consumption and input impedance must be observed. 3 ctuators may also be powered by 4 VDC. 5 Only connect common to neg. (-) leg of control circuits. 7 500 (ZG-R01) converts the 4 to 0 m control signal to to 10 VDC. Functions 0% 100% Fail Position 100% Open S1 S 1 100 18 ctuators with plenum rated cable do not have numbers on wires; use color codes instead. On/Off, CQKB4-S-LL NO 100 One built-in auxiliary switch (1x SPST), for end position indication, interlock control, fan startup, etc. 3 5 7 18 Line Volts Blk Red Common + Hot Meets culus requirements without the need of an electrical ground connection WRNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Control Signal VDC/m 500 VDC Close Open 10 VDC Open Close Fail Position Wht 100% Open Y 1 Input, to 10V 3 5 7 18 Line Volts 3 18 Blk Common Red Hot + Line Volts Control Signal VDC/m 500 Blk Red Wht Common + Hot Y 1 Input, to 10V On/Off, CQKB4-RR Line Volts On/Off, CQKB4-LL Line Volts Functions 0% 100% Fail Position Functions 0% 100% Fail Position 100% Open 3 18 Blk Common Red Hot + 0% Close 3 18 Blk Common Red + Hot VDC Open 10 VDC Close Fail Position 0% Close Proportional, CQKB4-SR-LR Line Volts Control Signal VDC/m 500 VDC Close Close 10 VDC Open Open Fail Position Proportional, CQKB4-SR-RL Line Volts 3 5 7 18 Blk Red Wht 100% Open Common + Hot Y 1 Input, to 10V 3 5 7 18 Blk Red Common + Hot Control Signal VDC/m 500 Wht Y 1 Input, to 10V Functions 100% 1 100 VDC Close Close 0% 10 VDC Open Open Fail Position 0% Close S1 Fail Position 0% Close S On/Off, CQKB4-S-RR NO Proportional, CQKB4-SR-RR 16

Wiring Diagrams Wiring Diagrams ctuators may be connected in parallel. Power consumption and input impedance must be observed. 3 ctuators may also be powered by 4 VDC. Line Volts 3 5 7 18 Blk Red Common + Hot 5 Only connect common to neg. (-) leg of control circuits. 7 500 (ZG-R01) converts the 4 to 0 m control signal to to 10 VDC. Control Signal VDC/m 500 Wht Y 1 Input, to 10V 18 ctuators with plenum rated cable do not have numbers on wires; use color codes instead. VDC Open 10 VDC Close Meets culus requirements without the need of an electrical ground connection WRNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. Proportional, CQB4-SR-L Line Volts 4 VC Transformer Control Signal VDC/m 500 3 5 7 18 Blk Red Wht Common + Hot Y 1 Input, to 10V VDC Close 10 VDC Open 4 VC Transformer 3 18 Proportional, CQB4-SR-R Line Volts Blk Common Red + Wht + Line Volts 110 to 30 VC 18 Blu Common Brn + Wht + On/Off, CQB4-3 Line Volts Functions 100% 0% Functions 0% 100% B B 3 18 1 Common + 3 + On/Off, CQBUP-3 Line Volts Functions 0% 100% Functions 100% 0% B B 18 Blu Common Brn + Wht + Floating Point, CQB4-3 Floating Point, CQBUP-3 17

Flow Verfication PIQCV Flow Verification and Commissioning Overview without Flow Orifice Device fter the actuator travel limit clip has been correctly located to position 1-7 (or removed) to match the maximum flow setting of the coil, the following procedures detail the flow verification and commissioning procedures for Pressure Independent Valves Quick Compact Valves (PIQCV). These procedures are not mandatory to ensure proper operation of PIQCV. PIQCVs are very different from pressure dependent control valves (standard control valves). Pressure variations in the system do not affect flow through the PIQCV. dditional flow regulating devices (e.g. circuit setters and automatic flow limiting devices) should not be used in conjunction with PIQCVs. This makes the Testing and Balancing (TB) or commissioning process much different from standard control valves. PIQCVs offer numerous maximum design flow values in each valve body size. It is important to note that the valve will travel to 90 degrees only when there is no end stop. External P/T ports allow for independent verifi cation of proper PIQCV operation. dditionally, these ports allow for future comprehensive troubleshooting and diagnosis. For proper and accurate fl ow verifi cation of the mechanical PIQCV, it is essential that the mechanical contractor install P/T ports, B & C as shown in Figure if the mechanical PIQCV body is not supplied with integrated ports. If the PIQCV includes integrated PT ports the mechanical contractor only needs to install P/T port. Mechanical PIQCV Pre-Flow Verification Checklist Verify that system is purged of air and fi lled to proper pressure. Verify that each PIQCV has the manufacturer s required operating differential pressure range across P/T ports B and C (or P1 and P3) as shown in fi g.. Verify proper pump operation per manufacturer s specifi cations. Verify proper supply water temperature is available and is at design temperature. Proper air fi lter maintenance has been completed. Fan belts are in proper working order. Heat transfer devices (coils) are clean. Strainers are clean. ll manual shutoff valves are open. ll bypass valves are closed. No automatic or manual balancing valves exist. If they do exist, they must be set fully open and locked to not interfere with the pressure independency function of the PIQCV. P/T port and P/T port B (or and P1) are used for measuring pressure differential across the coil (used to measure water P to equate to fl ow) or to measure water T across the coil. P/T port B and P/T port C (or P1 and P3) are used to measure P across the PIQCV assembly. PIQCVs must have 5 50 psid (11.5 ft. 115 ft. HO) (or per manufacturer s specifi cation) differential pressure within this range. Do not manually remove the actuator travel limit clip to fully open the valve to check for design fl ow or pressure. Valve shall be commanded to design fl ow position via analog or BMS (Building Management System) signal. The required operating differential pressure range is necessary to insure pressure independent operation of the PIQCV Note: The fl ow setter (ZCQB-FL) can be used to adjust the fl ow if the BMS is not available during the commissioning process. H/C COIL IR VENT FLOW BELIMO PIQCV (TYP.) P/T PORT B P1 P3 P/T PORT C FLOW SHUT OFF VLVE UNION CONNECTION (TYP.) FLOW DRIN P/T PORT FLOW STRINER (Optional) FLOW SHUT OFF VLVE 18

Flow Verification Procedures without Flow Orifice Device Procedure #1 (System Verifi cation) Total System Flow Method Verifi cation for PIQCV Cooling/Heating 1. Verify that the system is in proper working order. Depending on the valves used, check the items listed for PIQCV Pre-Flow Verification Checklists.. If diversity factor = 100%, command open all PIQCV s via the BMS system. Systems with less than 100% diversity need to have a number of valves closed to match design diversity. 3. Ensure that pumps are either manually commanded to suffi cient speed to provide proper differential pressure across all valves OR if pumps are under DDC pressure control ensure P setpoint is suffi cient to provide the above conditions. Verify total system fl ow in main return line is at system design fl ow rate using one of the following methods: Orifi ce, Venturi, Electronic fl ow meter, System-level Flow Device 1. Decrease the pump speed (or decrease P setpoint if under control) until a measureable fl ow decrease occurs.. Increase pump speed (or increase P setpoint if under control) slowly until design fl ow is reestablished. Make note of the resulting P. This will be the maximum system P operating setpoint. Note: If total fl ow does not match design fl ow then troubleshooting must be done to determine cause. This may involve verifying fl ows at the terminal level. Procedure # (Terminal Level Verifi cation) ir Delta T Method Verifi cation for PIQCV Cooling/Heating 1. Verify that the system is in proper working order. Depending on the valves used, check the items listed for PIQCV Pre-Flow Verification Checklists.. Ensure that water is at design temperature. 3. Ensure that terminal airfl ow is at design airfl ow rate (cfm). 4. Command open the PIQCV via analog or BMS control signal to maximum design fl ow position. (Do not manually open the PIQCV beyond the actuator travel limit clip position). 5. Reference approved engineering document containing design air temperature drop/rise for design conditions. 6. Measure coil inlet air temperature and coil discharge air temperature. 7. Difference between coil inlet air reading (ET) and coil discharge air reading (LT) should equal to or exceed design air delta T as shown on the contract documents. Procedure #3 (Terminal Level Verifi cation) Water Delta Method Verifi cation for PIQCV Cooling/Heating 1. Verify that the system is in proper working order. Depending on the valves used, check the items listed for PIQCV Pre-Flow Verification Checklists. Ensure that water is at design temperature.. Ensure that terminal airfl ow is at design fl ow rate (cfm) or water coil airfl ow is unencumbered. 3. Command open the PIQCV via analog or BMS control signal to maximum design fl ow position. (Do not manually open the PIQCV beyond the actuator travel limit clip position.) 4. Reference approved engineering document containing design water temperature drop/rise for design conditions. 5. Measure water temperature differential of coil by using P/T ports and B (or and P1) as referenced in Fig.. 6. Measured temperature differential should be equal to designed water temperature differential (EWT, LWT) as shown on the contract documents. Procedure #4 (Terminal Level Verifi cation) Coil P (Delta P) Method Verifi cation for PIQCV Cooling/Heating 1. Verify that the system is in proper working order. Depending on the valves used, check the items listed for PIQCV Pre-Flow Verification Checklists.. Command open the PIQCV via analog or BMS control signal to maximum design fl ow position. (Do not manually open the PIQCV beyond the actuator travel limit clip position.) 3. Ensure P across valve assembly between P/T ports B and C (or P1 and P3) as shown above in Fig. is within manufacturer s operating parameters. 4. Reference approved engineering document containing design coil water pressure drop (usually expressed in ft. of water) for design fl ow conditions. This value will be for the heating/cooling coil associated with corresponding PIQCV. 5. Measure coil P by using P/T ports and B (or and P1) as referenced in Fig.. 6. Formula to calculate fl ow is: ctual GPM = Design GPM x (Measured Coil P/Design Coil P) Note: Measured Coil P and Design Coil P must be expressed in the same engineering units (feet of water, inches of water, psi, etc.). 19

1 Belimo ZoneTight Zone Valves Flow Verfication Flow Verification with Flow Orifice Device Belimo fl ow orifi ce device has two pressure ports for fi eld P measurement with a manometer gauge. Connect manometer high pressure line to fl ow orifi ce red PT port; connect low pressure line to green PT port. Follow gauge instructions to verify connections. Take P reading in inches of water (w.c.) and transpose to the Flow Orifi ce line of the Flow Chart. From that point follow the corresponding chart line to the fl ow scale and determine the actual fl ow. Refer to fi eld-set procedure section on page 14 to adjust fl ow capacity to meet project requirements. Meter Readings, Water @ 70 F / 1 C FO15010 FO1505 FO15055 FO0100 FO15010 FO1505 FO15055 FO0100 FO15010 FO1505 FO15055 FO0100 Temperature Correction Factor: 155 F / 68 C = 1.01 x GPM 05 F / 96 C = 1.0 x GPM How to Determine Flow: 1. Enter the chart with the P (differential pressure) reading.. Go horizontally across to the size of the valve. 3. Go vertically up or down to read the GPM (flow). 0

Troubleshooting Problem Field Observations Possible Solution ctuator will not move. ctuators wires are connected. Verify the power supply and control signal are wired and operating correctly. ctuator does not modulate with the control signal as expected. Valve is yielding fl ow but cannot be commanded to the full fl ow setting Full fl ow is lower than expected. Desired fl ow cannot be reached. Flow measurements are not stable. Valve throttles to a different position than expected. Valve is partially open but will not move to a full open position with a full signal command. Clip may be in the wrong position. Valve is wide open. ir may be in the system. Remove the actuator from the valve body and use the actuator or a slotted screwdriver to move the valve stem to verify free rotation. For 3-point fl oating signals the actuator runtime is relative to the travel set by the clip. The controller runtime parameter may need to be adjusted to match the runtime of the actuator. For analog actuators the adaption function may have previously occurred to a lesser angle of rotation than now exits. Press the adaption button and the actuator will re-scale to the full travel set by the clip position. The clip may need to be adjusted to a greater angle of rotation to allow more fl ow, or removed to obtain maximum fl ow capacity. Refer to the fl ow commissioning instructions (page 18) for adjustment and verifi cation procedures. Increase the pump differential pressure to resolve low fl ow problems. Remove air from the system to solve the problem. 1

Chrome Plated Brass Ball, NPT Female Ends pplication The QCV zone valves are suited for large commercial buildings where higher close-off and the ability to change fl ow is desired. Common applications include unit ventilators, fan coil units, VV reheat coils, fi n tube casing, radiant panels and duct coils. The valve fi ts in space restricted areas and can be assembled without the use of tools. Dimensions -Way QCV Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic equal percentage (-way), linear (3-way) Controllable fl ow range 75 (-way), 90 (3-way) Size ½, ¾ Type of end fi tting NPT female ends Materials Body forged brass Ball chrome plated brass Stem brass Seats Tefl on PTFE O-rings EPDM (lubricated) Media temperature range 1 F to 1 F [-6 C to 100 C] Media temperature limit* 50 F [10 C] Max. allowable operating temp. 1 F [100 C] Body pressure rating 360 psi Close-off pressure 75 psi Maximum differential pressure ( P) 40 psi Leakage 0% *If temperature exceeds 1 F [100 C] operating range due to a boiler control failure the valve will safely contain the hot water but manufacturers product warranty becomes invalid. E Valve Nominal Size DN In. [mm] ½ Non-Spring 15 Return ¾ Non-Spring 0 Return ½ 15 ¾ Dimensions 3-Way Valve Nominal Size DN In. [mm] ½ Non-Spring 15 Return ¾ Non-Spring 0 Return ½ 15 E 0 F F D B Dimensions (Inches [mm]) B C D E F 4.5 [114] 4.5 [114] 4.5 [114] D.05 [5].4 [61].05 [5] B Dimensions (Inches [mm]) B C D E F 4.5 [114] 4.5 [114] 4.5 [114] 4.5 [114].05 [5].4 [61].05 [5].4 [61] 3.7 [83] 3.4 [86.9] 3.7 [83] 3.4 [86.9] 3.83 [97] 3.98 [101] 3.83 [97].71 [69].77 [70].71 [69].77 [70].71 [69].77 [70].71 [69] 1.88 [48] 0.94 [4] 0.94 [4] 1.88 [48] 1.0 [6] 1. [31] 1.0 [6] 1.88 [48] 0.94 [4] 0.94 [4] 1.88 [48] C 1.0 [6] 1. [31] 1.0 [6] C ¾ 0 4.5 [114].4 [61] 3.98 [101].77 [70] 1. [31] 1. [31]

Chrome Plated Brass Ball, Sweat Connection pplication The QCV zone valves are suited for large commercial buildings where higher close-off and the ability to change fl ow is desired. Common applications include unit ventilators, fan coil units, VV reheat coils, fi n tube casing, radiant panels and duct coils. The valve fi ts in space restricted areas and can be assembled without the use of tools. Dimensions -Way QCV Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic equal percentage (-way), linear (3-way) Controllable fl ow range 75 (-way), 90 (3-way) Size ½, ¾ Type of end fi tting sweat Materials Body forged brass Ball chrome plated brass Stem brass Seats Tefl on PTFE O-rings EPDM (lubricated) Media temperature range 36 F to 1 F [ C to 100 C] Media temperature limit* 50 F [10 C] Max. allowable operating temp. 1 F [100 C] Body pressure rating 360 psi Close-off pressure 75 psi Maximum differential pressure ( P) 40 psi Leakage 0% *If temperature exceeds 1 F [100 C] operating range due to a boiler control failure the valve will safely contain the hot water but manufacturers product warranty becomes invalid. E Valve Nominal Size DN In. [mm] ½ Non-Spring 15 Return ¾ Non-Spring 0 Return ½ 15 ¾ Dimensions 3-Way Valve Nominal Size DN In. [mm] ½ Non-Spring 15 Return ¾ Non-Spring 0 Return ½ 15 E 0 F F D B Dimensions (Inches [mm]) B C D E F 4.78 [1] 4.95 [16] 4.78 [1] D.6 [67].95 [75].6 [67] B Dimensions (Inches [mm]) B C D E F 4.78 [1] 4.95 [16] 4.95 [16] 4.78 [114].6 [67].95 [75].95 [75].6 [67] 3.14 [80] 3.8 [84] 3.8 [84] 3.14 [80] 3.14 [80] 3.8 [84] 3.14 [80].56 [66].64 [68].64 [68].56 [66].56 [65].64 [68].56 [65] 1.0 [6] 1. [31] 1. [31] 1.0 [6] 1.0 [6] 1. [31] 1.0 [6] 1.0 [6] 1. [31] 1. [31] 1.0 [6] C 1.0 [6] 1. [31] 1.0 [6] C ¾ 0 4.95 [16].95 [75] 3.8 [84].64 [68] 1. [31] 1. [31] 3

Belimo ZoneTight Pressure Independent Zone Valves Stainless Steel Ball, NPT Female Ends pplication The PIQCV zone valves with its pressure independent technology are suited for large commercial buildings where higher close-off and dynamic balancing is required. Common applications include unit ventilators, fan coil units, VV reheat coils, fin tube casing, radiant panels and duct coils. The valve fits in space restricted areas and can be assembled without the use of tools. PIQCV Dimensions Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic equal percentage Controllable fl ow range 75 Size ½ Type of end fi tting NPT female ends Materials Body forged brass Ball stainless steel Stem stainless steel Stem packing EPDM (lubricated) Seats Tefl on PTFE O-rings PTFE Seat o-rings EPDM Spring stainless steel Media temperature range 36 F to 1 F [ C to 100 C] Media temperature limit* 50 F [10 C] Max. allowable operating temp. 1 F [100 C] PT ports included Body pressure rating 360 psi Close-off pressure 00 psi Differential pressure ( P) range 5 to 50 psi Leakage 0% *If temperature exceeds 1 F [100 C] operating range due to a boiler control failure the valve will safely contain the hot water but manufacturers product warranty becomes invalid. Valve Nominal Size DN In. [mm] ½ Non-Spring 15 Return ¾ Non-Spring 15 Return ½ ¾ E 15 15 F D Dimensions (Inches [mm]) B C D E F 4.71 [10] 5.11 [130] 4.71 [10] 5.11 [130] 3.74 [95] 4.63 [118] 3.74 [95] 4.63 [118] 4.07 [104] 5.17 [13] 4.07 [104] 5.17 [13] B 3.31 [80] 3.65 [93] 3.31 [80] 3.65 [93].3 [57].55 [65].3 [57].55 [65] 1.03 [7] 1.5 [39] 1.03 [7] 1.5 [39] C 4

Non-Spring Return and ctuator Series Operation The ZoneTight Zone Valves (QCV, PIQCV) are operated by rotary actuators. The actuators are controlled by a standard voltage for on/off control, proportional signal, or 3-point control system which move the ball of the valve to the position dictated by the control system. Non-Spring Return CQ.., CQ..UP ctuators CQK.. ctuator Specifications Power supply 4V (110-30 VC, UP series) Manual override use actuator or slotted screwdriver to turn valve stem Power consumption CQ... 0.3 W running, 0. W holding CQK....5 W running, 0.5 W holding CQ..UP 1.0 W running, 0.7 W holding Transformer sizing CQ... 0.6 V CQK... 5 V CQ..UP V Electrical connection 3 ft., 18 G, plenum rated cable ½ conduit connector Overload protection Non-Spring Return electronic throughout 0 to 90 rotation electronic throughout full stroke Operation range Y on/off ngle of Rotation 90, adjustable with mechanical stop Position Indication pointer Running Time (Motor) 75 seconds Running Time () 60 seconds Humidity 5 to 95% RH non-condensing mbient Temperature Range +35 F to +104 F [+1.7 C to +40 C] Storage Temperature Range -40 F to +176 F [-40 C TO +80 C] Housing NEM, IP40, UL enclosure type Housing Material UL94-5V culus acc. to UL60730-1/--14, CN/CS gency Listings E60730-1:0, CE acc. to 004/108/EC and 006/95/EC Noise Level (Motor) <35 db () Servicing maintenance free Quality Standard ISO 9001 Weight Non-Spring Return 0.44 lb [0. kg] 3.6 lbs [1.6 kg] Quality standard ISO 9001 gency listings UL 60730-1/-14, -18, CE according to 004/108/EC and 006/95/EC 5

Flow Curves Valve Flow Charts Two notch positions exist between numbered notches for fi eld-set clip positioning to obtain maximum fl ow capacity. Refer to charts and set the clip as needed. QCV Flow Curves ctuator Runtime (Seconds) 30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 6 64 66 68 75 1.6 1.4 1.4 1. 1.1 1. 1.0 0.9 Cv 0.8 0.8 0.7 0.6 0.6 0.5 0.4 0.4 0.3 0. 0.1 0. 0.0 1 3 4 5 6 N (Default) Clip in Notch Position Removed Z050Q-F Flow Capacity ctuator Runtime (Seconds) 30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 6 64 66 68 75 6.5 5.9 6.0 5.5 5.0 4.8 4.5 4.3 3.8 4.0 Cv 3.4 3.5 3.0 3.0.6.4.5.1 1.9.0 1.7 1.5 1.5 1.3 1. 1.0 0.9 1.0 0.6 0.7 0.5 0.5 0.0 1 3 4 5 6 N Removed (Default) Clip in Notch Position Z050Q-J Flow Capacity ctuator Runtime (Seconds) 30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 6 64 66 68 75 11.0 10.0 9.5 9.0 8.0 7.0 6.6 Cv 5.8 6.0 5.1 5.0 4.5 4.0 4.0 3.0.0 0.5 0.7 0.8 1.0 1.0 1.1 1.3 1.5 1.7.0.3.5.9 3.3 3.7 0.0 1 3 4 5 6 N (Default) Clip in Notch Position Removed Z050Q-K Flow Capacity 6

Flow Curves PIQCV Flow Curves ctuator Runtime (Seconds) ctuator Runtime (Seconds) 1.0 30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 6 64 66 68 75.3 30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 6 64 66 68 75 0.9 0.9.0.0 0.8 0.7 0.8 1.8 1.6 1.8 0.7 0.6 1.5 1.3 1.5 0.6 GPM 0.5 0.4 0.3 0. 0.1 0.1 0. 0.3 0.4 0.5 GPM 1.3 1.0 0.8 0.5 0. 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1. 0.0 0.0 1 3 4 5 6 N (Default) Removed 1 3 4 5 6 N (Default) Removed Clip in Notch Position Clip in Notch Position Z050QP(T)-B Flow Capacity Z050QP(T)-D Flow Capacity ctuator Runtime (Seconds) ctuator Runtime (Seconds) 4.5 30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 6 64 66 68 75 4.3 9.5 30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 6 64 66 68 75 9.0 4.0 8.5 3.6 7.7 3.5 3.3 7.5 7. 3.1 6.7 3.0 GPM.5..5.8 6.5 GPM 5.5 4.9 5.3 5.8 6.3.0 1.5 1.0 0.5 0.6 0.7 0.8 0.9 1.0 1.3 1.5 1.7 1.9 4.5 3.5.5 1.5 1.1 1.3 1.6 1.8.1.4.7 3.0 3.3 3.7 4.0 4.4 0.0 0.5 1 3 4 5 6 N Removed 1 3 4 5 6 N Removed Clip in Notch Position Z050QP(T)-F Flow Capacity (Default) Clip in Notch Position Z050QP(T)-G Flow Capacity (Default) 7

Terms and Conditions of Sale and Warranty I. General 1.1. The following Terms and Conditions of Sale ( Terms ) apply to the sale of products described in this Product Guide ( Products ). s used herein, Seller or Belimo refers to Belimo ircontrols (US) Inc., or Belimo ircontrols (CN) Inc., Belimo ircontrols (L) Inc., or Belimo utomation G as applicable, and Client refers to the individual or business entity that purchases the Products from Seller. These Terms shall apply unless the parties mutually agree to different terms and memorialize such agreement in writing signed by both Client and Seller. In case Seller s delivery includes Software and accompanying documentation, the terms of the license agreement are applicable in addition to these Terms. However, in case of disputes arising out of the Software, the license agreement shall prevail. II. III. IV. Price.1. The Seller s price for Products (the Price ) is net, F.O.B. Point of Origin, and is calculated in US currency for sales made by Belimo ircontrols (US), Inc. and calculated in Canadian currency for sales made by Belimo ircontrols (CN) Inc., and Brazilian currency for sales made by Belimo utomation G to Clients in Brazil... The Price, unless otherwise agreed upon, does not include freight and packaging (wooden crates, pallets, etc), the costs of which will be charged to Client at cost for each shipment and shall be payable with payment of the Price..3. Orders for Products with a net value of less than US $300 (CN $300) will be subject to a US $0 (CN $0) handling fee (the Handling Fee ). The Handling Fee will not be charged for orders of Products with a net value equal to or greater than US $300 (CN $300) or for Products ordered through Seller s ecommerce ordering system at: www.belimo.com..4. Seller reserves the right to make partial deliveries of orders of Products, each of which deliveries may be invoiced separately by Seller..5. The Price does not include charges for wiring diagrams, installation, and commissioning, which will be charged to Client separately and will be payable on demand. Payment 3.1. Invoices are payable in US currency for sales made by Belimo ircontrols (US), Inc., in Canadian currency for sales made by Belimo ircontrols (CN) Inc. and in Brazilian currency for sales made by Belimo utomation G on behalf of Brazil. Invoices are due no later than 30 days from the date of invoice, without any deductions. 3.. If Client maintains an outstanding balance for 45 days or more after the date of invoice, Client may be subject to restricted shipments of Products. Client may also be required to pay for all future deliveries of Products on a cash-on-delivery or approved credit card only basis. Title and Risk 4.1. Title to all Products shall remain with Seller and shall not pass to Client until Seller has received full payment for the Products. V. Damage or Loss in Transit 5.1. Seller assumes no liability for damage or loss of shipment of Products, which risk shall at all times remain with the carrier. ll shipments must be unpacked and examined by Client immediately upon receipt. ny external evidence of loss or damage must be noted on the freight bill accompanying the shipment of Products or carrier s receipt and signed by the carrier s agent at the time of delivery. Failure to do so will result in the carrier s refusal to honor any claim relating to damage of Products. Client must also notify Seller within 5 days of such damage by providing Seller with a copy of the freight bill or damage report so that Seller can file a claim for loss or damage in transit with the carrier. If the damage does not become apparent until the shipment is unpacked, Client must make a request for inspection by the carrier s agent and file with the carrier within 15 days after receipt of product and notify Seller of the same. VI. Delivery 6.1. Seller undertakes to make every attempt to adhere to its stated delivery parameters and to make a timely delivery of the Products but does not guarantee any delivery specifications. Each contract entered into for the purchase of Products is not cancelable nor is Seller liable for any direct or indirect losses that may arise, for any reason whatsoever, due to Seller s failure to meet any stated or assumed delivery schedules. VII. Inventory Overstock 7.1. If Client has an overstock of Product inventory, such Products received by Client cannot be returned unless and until: (i) Client alerts Seller that it intends to return some overstock of Products, (ii) Seller agrees to accept such return, (iii) Client obtains a Return Material uthorization ("RM") number from Seller for such return of such Products, and (iv) Client follows all return instructions provided by the Seller. The RM number must be clearly written on the outside of all packaging for any returned overstock of Products. 7.. Only such Products returned in original packaging and shipped to Seller at Client's cost may be accepted for return under this Section. Client is also responsible for payment of a restocking charge for all returned overstocked Products in an amount no less than 0% of the invoice value of the Products ("Restocking Charges"). Returns that result from Seller errors and not overstocking will be credited in full and will not be subject to Restocking Charges. 7.3 ny Product received damaged or showing evidence of having been installed will be refused or assessed a higher restocking charge. Custom kits designed to a Client's unique specifications are not returnable. 7.4 If Client requests product to be returned to them, the Client will be responsible for return shipping charges. See specific product literature for exclusions or exceptions. VIII. Limited Warranty VIII. 5-year Limited Warranty 8.1. Products that are listed in this Product Guide as carrying a 5-year warranty to a location in the United States, Canada, or Latin merica shall carry a 5-year warranty. The 5-year warranty is unconditional for the first two years from the date of sale of the Products to Client. fter the first two years from the date of Sale, the warranty coverage shall not apply to damage to Products not resulting from normal wear and tear (e.g. negligence, misuse, or failure to maintain). Product specific terms of warranty with regard to warranty period or conditions of warranty may apply to certain specified Products as stated in the documentation for those Products. VIII.B -year Conditional Warranty 8.. Products that are listed in this Product Guide as carrying a -year warranty to a location in the United States, Canada, or Latin merica shall carry a -year warranty. The -year warranty is conditional from the date of sale of the Products to Client, and the warranty coverage shall not apply to damage to Products not resulting from normal wear and tear (e.g. negligence, misuse, or failure to maintain). Product specific terms of warranty with regard to warranty period or conditions of warranty may apply to certain specified Products as stated in the documentation for those Products. VIII.C Limitations 8.3. Seller s warranties hereunder shall be be null and void in the event of any: (a) modification or unauthorized repairs of Products by Client; (b) unauthorized incorporation or integration of Products into or with Client s equipment; (c) use of Products in an unauthorized manner; or (d) damage to Products not caused by Seller. VIII. D. Remedies 8.4 If a defect arises and a Return Material uthorization ( RM ) is issued as provided in Section 8.5, Seller will, at its option and to the extent permitted by law, either (1) repair the Product at no charge, using new or refurbished replacement parts or () replace the Product with a new Product. In the event of such a defect, to the extent permitted by law, these are Client s sole and exclusive remedies. 8.5 Products received by Client cannot be returned unless: (i) Client alerts Seller that it intends to return such Products, (ii) Seller agrees to accept the return of such Products, (iii) Client obtains a RM number from Seller for the return of such Products, and (iv) Client follows all return instructions provided by the Seller. Client shall promptly notify Seller of Products alleged defect and provide Seller with other evidence and documentation reasonably requested by Seller. The RM number must be clearly written on the outside of all packaging for any returned Products. Only Products returned to the proper location as instructed by Seller and identified with an RM number will be considered for credit. 8