Table of Contents. For latest version, visit:

Similar documents
SURE TRIP SLT-201 SECONDARY TEST SET

SURE-TRIP OEM RELACEMENT TRIP UNIT

SURE TRIP RETRO KITS

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

EPS/ELA-Series User Manual EPS/ELA 250W

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

ES52 Auto Start Engine Controller Installation and User Manual for the ES52 Auto Start Engine Controller.

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

5. OVERCURRENT RELEASE (OCR)

Guide for Primary Injection Testing WL Circuit Breakers. Document No. : 11-C

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

PORTABLE CURRENT SOURCE FOR CIRCUIT BREAKER AND MOTOR OVERLOAD TESTING INSTRUCTION MANUAL PI-250B. Release 1.0 April 5, 2013

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

ECU. Speed Switch Manual. Contents. ECU is a registered trademark of Engineering Concepts Unlimited Inc.

NO work shall be performed on an energized breaker.

Installation, Operation and Maintenance Manual

OnCommand Troubleshooting Guide Hayward Industries

ES52. Auto Start Engine Controller. Full Version. Installation and User Manual for the ES52 Auto Start Engine Controller.

AUTOMATIC 12 WAY HEAT TREATMENT CONSOLE

A. Submit manufacturer's literature and technical data before starting work.

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide

CABINET REEL OPERATING INSTRUCTIONS

BIGLA30-T/BIELA14-T Event Codes Quick Reference EXPLANATION CORRECTIVE ACTION PARTS TO CARRY ON SERVICE CALL

COOPER POWER SERIES. VFI tester operating instructions. Underground Distribution Switchgear MN285001EN

60 Series Engine Controls

Application Engineering

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual

Power Distribution System User s Manual. Model: PDS-100

USERS MANUAL MCD REMOTE OPERATOR

Combined Ventilation Controller RVWS-T-224HA

GENERAL REQUIREMENTS:

CCTV Rack Mount Power Supplies

DC Variable Speed Drive Panel

Rack Mount Power Supplies

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

Pure Sine Wave Inverter GP-HS1500. Owner s Manual

SECOND GENERATION Use this guide with unit serial number prefix beginning with BWF using Terra Power separator.

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

HT Dielectric Withstand Tester Volts AC Output 25mA Leakage Option

POWER SUPPLY MODEL XP-800. TWO AC VARIABLE VOLTAGES; 0-120V and 7A, PLUS UP TO 10A. Instruction Manual. Elenco Electronics, Inc.

DIESEL Engine Fire Pump Controllers Features

Senior Swing Control Box. Table of Contents

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

5. OVERCURRENT RELEASE (OCR)

U. Electric Golf Cart (egc) CHARGING PROCEDURE. California Roadster. HUMMER H3 egc. Cadillac Escalade egc

DC-Motor Controller. User Manual

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

GENERAL REQUIREMENTS:

Application Engineering

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

INOVA HIGHTECH Ltd. MEP 002/003 Auto Starter Manual

XENON POWER SUPPLY Watt

30A SMART ENERGY MANAGEMENT SYSTEM TM

OTEC Transfer switch open transition

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Advanced Test Equipment Rentals ATEC (2832)

Moulded case circuit breakers

Troubleshooting Bosch Proportional Valves

M440 MOTOR PROTECTION, EARTH FAULT LOCKOUT & MANAGEMENT RELAY VERSION 3.5 NINGI SERVICES (PTY) LTD

PARTS & SERVICE MANUAL

Visit our web site at AMR LS-3000, LS-3010 & LS-3020 BELT SLIP/SEQUENCE CONTROL INSTALLATION AND SETUP INSTRUCTIONS

RP-4000 Reserve Power Control

XENON POWER SUPPLY 4000 Watt Gladiator IV

PRODUCT INFORMATION BULLETIN

REVISION HISTORY REVISION HISTORY

GENSET CONTROL MODULE A121A / A241A

Fisher Pierce. Cable Accessories. Faulted Circuit Indicators. Series 1548 Overhead FCIs

Designed for ease of integration with automation systems

Protection and control VIP30, VIP35. Relays technical manual

PD-Series Ground Fault Circuit Protection

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

OPERATORS INSTRUCTION MANUAL CIRCUIT BREAKER TEST SET MODEL DDA-1600

Variable Regulated Voltage Power Supply Instruction Manual Model XP-605 / XP-752A

5001TCP SPEED CONTROLLER

320 to 327 M Series Low and Medium Voltage Motor Protection Relays

PowerView PV380-R2 Mechanical Configuration

ASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Transformer Protection

INSTRUCTION MANUAL MODEL CB-7120A CIRCUIT BREAKER

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

ARCHITECTURAL CONTROL SYSTEMS, INCORPORATED ST. LOUIS, MISSOURI

HWP Protection Board

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

ADDITIONAL INFORMATION. BE1-50/51B SELF POWERED TIME OVERCURRENT RELAY and RETROFIT KITS. FEATURES and APPLICATION Page 2

Transcription:

Table of Contents 1.0 Introduction... 1.0 Overview... 1 3.0 Test Set Controls... 6 3.1 Power... 6 3. Time Display... 6 3.3 Timer Clear Push Button... 6 3.4 Start Push Button and LED... 6 3.5 Stop Push Button... 6 3.6 Test Current display... 6 3.7 Current Preset Push Button... 7 3.8 Amp Coarse Adjust... 7 3.9 Amp Fine Adjust... 7 3.10 Phase Selector... 7 3.11 Frequency Selector... 7 3.1 Contrast Push Button... 7 3.13 Ground Fault Type Selector Switch... 7 3.14 4V Fuse / Fuseholder... 7 4.0 Operation... 10 4.1 Connecting to AC-PRO or AC-PRO-II... 10 4.1.1 AC-PRO-GR, Ground Return Trip Unit... 10 4. Select the Frequency... 10 4.3 Calculate Long Time (LT) Pick-Up Secondary Current... 10 4.4 Long Time (LT) Pick-Up Test... 11 4.5 Long Time (LT) Time Test... 11 4.6 Calculate Short Time (ST) Pick-Up Secondary Current... 1 4.7 Short Time (ST) Pick-Up Test... 1 4.8 Short Time (ST) Test... 13 4.9 Calculate Instantaneous (I) Pick-Up Secondary Current... 13 4.10 Instantaneous (I) Pick-Up Test... 14 4.11 Calculate Ground Fault (GF) Pick-Up Secondary Current... 14 4.1 Ground Fault (GF) Pick-Up Test... 15 4.13 Ground Fault (GF) Time Test... 15 4.14 AC-PRO Unbalance Testing... 15 4.15 Calculate Neutral Overload (NOL) Pick-Up Secondary Current... 16 4.16 Neutral Overload (NOL) Pick-Up Test... 16 4.17 Neutral Overload (NOL) Time Test... 17 5.0 Quick-Trip Testing... 0 5.1 Calculate Quick-Trip Instantaneous (QT-I) Pick-Up Secondary Current... 0 5. Quick-Trip Instantaneous (QT-I) Pick-Up Test... 0 5.3 Calculate Quick-Trip Ground Fault (QT-GF) Pick-Up Secondary Current... 1 5.4 Quick-Trip Ground Fault (QT-GF) Pick-Up Test... 1 6.0 Clearing Last Trip Data... 7.0 Error/Fault Conditions... 7.1 Current Error... 7. Thermal Limit... 7.3 Unexpected GF Trip... 8.0 Specifications... For latest version, visit: http://www.utilityrelay.com/side_bar/instruction_manuals.html www.utilityrelay.com

Figure 1: Test Set Exterior... Figure : Test Set Case Interior... 3 Figure 3: Test Set Cables... 4 Figure 4: Control Panel Overview... 5 Figure 5: AC-PRO Breaker Test Set Connections... 8 Figure 6: AC-PRO-II Breaker Test Set Connections... 9 Figure 7: AC-PRO Quick-Trip Testing Connections... 18 Figure 8: AC-PRO-II Quick-Trip Testing Connections... 19 Figure 9: AC-PRO Overload TCC... 4 Figure 10: AC-PRO Unbalance TCC & Ground Fault TCC... 5 Figure 11: AC-PRO Quick-Trip TCC... 6 Figure 1: AC-PRO-II Overload TCC... 7 Figure 13: AC-PRO-II Ground Fault TCC... 8 Figure 14: AC-PRO-II Quick-Trip TCC... 9 Figure 15: AC-PRO-II Neutral Overload TCC... 30 For latest version, visit: http://www.utilityrelay.com/side_bar/instruction_manuals.html www.utilityrelay.com

1.0 Introduction The Model B-9 Secondary Injection Test Set is a single-phase test set specifically designed for testing the operation of the AC-PRO and AC-PRO-II microcontroller based trip units manufactured by Utility Relay Company. The earlier version test set with the Red panel, can only be used to test the AC-PRO. It cannot be used to test the AC-PRO-II. The test set can test pick-up and time delays of the various protection functions by driving current into the trip unit on the secondary side of the CT circuit. The test set will test 60, 50, 40 or 5 Hertz AC-PRO trip units. (The AC-PRO-II can be set for either 50 Hertz or 60 Hertz). The test set will test the AC-PRO or AC-PRO-II trip system with the exception of the CTs and associated wiring harness..0 Overview The basic function of the test set is to deliver an accurate level of AC current directly to the trip unit under test and to verify the pick-up values and times required for the AC-PRO or AC-PRO-II to trip. The technician running the test will operate the Start (5), Stop (7), Clear (8) and Current Preset (13) push buttons, adjust the Amp Coarse (14) and Amp Fine (15) potentiometers (pots), and adjust the Phase (11) and Frequency (16) Selector switches. The two displays (6 & 1) are used to indicate elapsed time in seconds and test current in amps. Note: Numbers in parentheses refer to the labeled items in Figure 4. Please reference the AC-PRO and AC-PRO-II users manuals for complete trip unit instructions. Important: Secondary injection testing is not a substitute for primary injection testing that should be performed for any circuit breaker retrofit. www.utilityrelay.com Page 1

Rugged Construction for protection during operation, transport, and shipping Large Handles Telescoping Handle Copolymer Polypropylene Compound Padlock Provisions Chemical Resistant Durable Latches Replaceable Steel-Axle Wheels Figure 1: Test Set Exterior www.utilityrelay.com Page

Interior Panel Abbreviated Instruction Manual Long Time Test Chart Cable Storage Figure : Test Set Case Interior www.utilityrelay.com Page 3

Power Cord AC-PRO Test Set Harness Labeled For AC-PRO AC-PRO-II Test Set Harness Note: different connector Labeled For AC-PRO-II AC-PRO Test Set Harness for Breaker Test Port Labeled AC-PRO Test Set to Breaker Test Port Figure 3: Test Set Cables www.utilityrelay.com Page 4

1 19 18 17 3 4 5 6 7 8 9 10 11 1 13 14 15 16 1 Power Cable/Fuse Holder Power cable connector with main fuse. (10Vac 50/60Hz). Cooling Airflow Exhaust Cooling air for the test set exits via this filter opening (must not be blocked). 3 Power ON/OFF Switch 4 Start LED Illuminates when test current is flowing. 5 Start Push Button Starts test current flow and starts the timer. 6 Timer Display Displays elapsed time of test current flow in seconds. 7 Stop Push Button Stops test current flow and freezes the timer. 8 Clear Push Button Resets the timer to zero. 9 Contrast Push Button Hold this button in until the desired display contrast is reached. 10 Ground Fault Type Select Switch Selects between Standard Residual GF or Ground Return GF. 11 Phase Select Switch Selects one of the phases (A,B,C) or ground fault as the test current path. 1 Current Display Displays measured true RMS current and Current Preset value. 13 Current Preset Push Button When held, the current display indicates the setting of the Amp Coarse and Fine pots but does not send current to the trip unit. Figure 4: Control Panel Overview 14 Amp Coarse Pot Used to make large adjustments in current. 15 Amp Fine Pot Used to make small adjustments in current. 16 Frequency Select Switch This switch selects the AC frequency; 5, 40, 50 or 60 Hertz for AC-PRO. 50 or 60 Hertz for AC-PRO-II. 17 Cooling Airflow Intake Cooing air for the test set enters via this filter opening (must not be blocked). 18 AC-PRO or AC-PRO-II Test Harness Connector The trip unit connects to the test-set with the supplied wire harness via this connector. 19 4V Fuse / Fuseholder (fuse is rated 1A/50V, 3AG slow blow fuse) www.utilityrelay.com Page 5

3.0 Test Set Controls 3.4 Start Push Button and LED 5 4 A brief description of the operation of the various test set controls is given below. The numbers in parentheses refer to the labels in Figure 4. 3.1 Power 3 Power to the test set is controlled with the Power On-Off switch. An AC cord is supplied with the test set. The recommended AC power source is 10V AC at either 50 or 60 Hz. The 10 VAC receptacle also contains the 5 Amp, 50V, 5 x 0mm main power fuse. 3. Time Display The test set will measure the time elapsed while current is being delivered to the trip unit, and display the time on the Timer display. The displayed time is in seconds with 1/100 of a second resolution. The time will stop accumulating when a trip occurs or when the Stop (7) push button is pushed. The timer display is cleared when the Clear (8) push button is pushed. 3.3 Timer Clear Push Button The Clear (8) push button clears the Timer display. 6 8 The Start push button starts the test current flow to the trip unit and simultaneously starts the Timer (6). The green LED located above the Start push button indicates test current flow. 3.5 Stop Push Button The Stop push button stops the test current flow and simultaneously freezes the Timer (6). 3.6 Test Current display The Test Current display indicates the true RMS test current in amps, going to the AC-PRO or AC-PRO-II during a test. To determine the equivalent CT primary current: 1-Amp AC-PRO or AC-PRO-II multiply the test set current by the CT Primary rating set in the trip unit. For example: If the CT primary rating is 600 and the test current is 1.50 amps, then the equivalent primary current is: 1.50 x 600 = 900 amps primary 0.5 Amp Example multiply the test set current by the CT Ratio (CT Primary Rating CT Secondary Rating). For example: If the CT Primary Rating is 600, the CT Secondary Rating is 0.5A, and the test current is 0.75 amps, then the equivalent primary current is: 7 1 0.75 x (600 0.5) = 900 amps Note: If CT Secondary Rating is different than 1.0 or 0.5, use the 0.5 example above and replace 0.5 with the specific CT secondary rating. www.utilityrelay.com Page 6

3.7 Current Preset Push Button 13 3.11 Frequency Selector 16 While the Current Preset push button is pushed, the test set will display the current setting (from the Amp Coarse and Fine adjust pots) in the Current (1) display without actually driving any current to the trip unit. The sum of the Amp Coarse (14) and Fine (15) pots is displayed in the Current (1) display and is continually updated while the Current Preset switch is pushed. After the current pots are adjusted to the desired test current as seen on the display, release the Current Preset push button. The test set limits the current set point level to 1.00 amps. 3.8 Amp Coarse Adjust The Amps Coarse adjustment quickly changes the test current to the trip unit or the test Current Preset, with clockwise rotation increasing the value. 3.9 Amp Fine Adjust The Amps Fine adjustment slowly changes the test current to the trip unit or the test Current Preset, with clockwise rotation increasing the value. 3.10 Phase Selector The Phase Select selector switch is used to select which phase of the trip unit the test current is driven into. It selects between Phase A, Phase B, Phase C or Ground Fault (Neutral). 11 15 14 The Frequency selector switch is used to select the AC test current frequency. This is used to select either 5, 40, 50 or 60 Hz for AC-PRO. The selections for AC-PRO-II are 50 or 60 Hertz. 3.1 Contrast Push Button The Contrast push button changes the contrast of both the Timer (6) and Current (1) displays. The push button should be pushed until the desired contrast is seen in the displays. 3.13 Ground Fault Type Selector Switch The GF Type Selector switch selects between the standard "residual" ground fault trip unit and the special "ground return" ground fault trip unit. For AC-PRO, the option label on the front of the AC-PRO indicates if that trip unit is the special factory-configured "ground return" type, with a GR suffix in the trip unit part number. For AC-PRO-II, Ground Fault Type is a user setting. It can be set to Residual (standard) or Ground Return. Push the GF Type Selector switch so the correct type of ground fault is selected. Note: When the GF Type Switch is set to standard residual and Phase switch is set to A, B, or C, current is injected into the phase current input and returned through the neutral current input (to result in zero GF current). When the GF Type switch is set to ground return and Phase Switch is set to A, B, or C, current is injected into the Phase input only. 9 10 3.14 4V Fuse / Fuseholder 19 The main 4V fuse is accessible from the front panel. The fuse is rated 1A/50V max, type 3AG slow blow fuse. www.utilityrelay.com Page 7

D A C E AC-PRO on breaker B A) AC-PRO Test Set Harness B) Test Set Power Plug to AC-PRO C) Test Set AC-PRO Harness Main Connector D) Test Set AC-PRO Harness Actuator Connector E) Circuit Breaker Wiring Harness (previously connected to the AC-PRO) Figure 5: AC-PRO Breaker Test Set Connections www.utilityrelay.com Page 8

AC-PRO-II TM on breaker G H K F J F) AC-PRO-II Test Set Harness G) Test Set Power Plug to AC-PRO-II (Remove the cover (not pictured) to gain access to the connector) H) Test Set AC-PRO-II Harness Main Connector (Remove the wire guard (not pictured) to gain access to the connector) J) Test Set AC-PRO-II Harness Actuator Connector K) Circuit Breaker Wiring Harness (previously connected to the AC-PRO-II) Figure 6: AC-PRO-II Breaker Test Set Connections www.utilityrelay.com Page 9

4.0 Operation The following describes the operation of the test set. Note: Letters in parentheses refer to the labeled items in Figure 5 and Figure 6. 4.1 Connecting to AC-PRO or AC-PRO-II The B-9 Test Set includes two Test Harnesses, one for AC-PRO and one for AC-PRO-II. The Test Harness (A) or (F) makes the connections from the test set to the trip unit (including power (B or G)). It also provides a connector for connection to the breaker harness (E) or (K) to allow the AC-PRO or AC-PRO-II to fire the breaker actuator and trip the breaker. See Figure 5 and Figure 6. While the Power (3) switch is in the off position (red LED in switch off): 1) Connect the round connector on the Test Harness (A) or (F) to the connector on the test set marked AC-PRO or AC-PRO-II (18). Twist the outer ring clockwise to fully seat and lock the connector. ) Remove the breaker wiring harness from the breaker harness connector on the trip unit (if installed on a breaker). For AC-PRO-II remove the wire guard (not pictured). 3) Connect the female ten-position terminal block connector (C) or (H) on the Test Harness to the trip unit. 4) AC-PRO: Connect the small round connector on the Test Harness (B) to the 4 VAC auxiliary power jack. AC-PRO-II: Connect the white rectangular connector on the Test Harness (G) to the 4VDC Aux Power input (after removing the connector cover). 5) Connect the previously removed breaker wiring harness connector to the male ten-position terminal block on the Test Harness Actuator Connector (D) or (J) (if installed on a breaker). 6) Once all connections are made the test set power can be turned on. The trip unit should also power up. 4.1.1 AC-PRO-GR, Ground Return Trip Unit When testing a special AC-PRO trip unit with "ground return" ground fault, or AC-PRO-II with Ground Fault Type set to Return, see Section 3.13. 4. Select the Frequency Select the desired frequency of operation using the Frequency (16) selector switch. This must match the trip unit frequency. 4.3 Calculate Long Time (LT) Pick-Up Secondary Current Calculate the secondary LT pick-up current (LTSPU) as follows: For 1-Amp AC-PRO or AC-PRO-II: LTSPU = LT Pick-Up CT Primary Rating Example: If the CT Primary rating is 1600 and the LT pick-up is 800 amps, then LTSPU = 800 = 0.50 amp 1600 Example: If the CT Primary rating is 1600 and the LT pick-up is 1600 amps, then LTSPU = 1600 = 1.00 amp 1600 For 0.5 Amp AC-PRO or AC-PRO-II: LTSPU = LT Pick-Up X 0.5 CT Primary Rating Example: If the CT Primary rating is 1600 and the LT Pick-Up is 800 amps, then LTSPU = 800 X 0.5 = 0.5 amp 1600 www.utilityrelay.com Page 10

Example: If the CT Primary rating is 1600 and the LT Pick-Up is 1600 amps, then LTSPU = 1600 X 0.5 = 0.50 amp 1600 Note: If CT Secondary Rating is different than 1.0 or 0.5, use the 0.5 example above and replace 0.5 with the specific CT Secondary Rating. Note: If Phase CT and Neutral CT do not have the same Secondary Rating (i.e. if both not 1-Amp), temporarily turn off Ground Fault Protection in the Trip Unit when performing Long Time, Short Time, and Instantaneous Tests. 4.4 Long Time (LT) Pick-Up Test To test the LT pick-up: 1) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots until the Current (1) display shows about 90% of the LT pick-up current (LTSPU) previously calculated. ) Set the Phase selector (11) to either Phase A, B or C. 3) Push the Start (5) button. 4) Increase the test current until the display on the AC-PRO or AC-PRO-II matches the programmed LT pick-up. The red pick-up LED on the AC-PRO or AC-PRO-II should be flickering or solidly on. The test set current should be within ±10% of LTSPU. 5) Push the Stop (7) button. 6) If desired, test the other two phases in the same way. 4.5 Long Time (LT) Time Test To test the LT time delay trip: 1) The first step is to select a test current. For example, three times the LT pick-up (3X on the TCC in Figure 9 or Figure 1). The desired test current is then 3 X LTSPU. Note, to accurately test the LT delay, the test current must be at least 110% of the LT pick-up. ) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots until the Current (1) display shows the test current calculated in step 1. Release the Current Preset (13) button. 3) Set the Phase selector (11) to either Phase A, B or C. 4) Push the Clear (8) button to reset the Timer (6) to zero. 5) Push the Start (5) button and quickly make any minor adjustments required to the Amp Fine (15) pot. The red pick-up LED should be on. AC-PRO should display OVERLOAD. AC-PRO-II should display the current value. 6) When the trip unit trips, the test set current will stop and the Timer (6) will freeze and display the total trip time. 7) Compare the trip time with the TCC in Figure 9 or Figure 1 for the LT time band setting in the AC-PRO or AC-PRO-II. The trip time can also be verified against the LT Test Chart on the inside panel of the test set case. The LT Test Chart is also available at: http://www.utilityrelay.com/pdfs/prod uct%0manuals/ac-pro_&_ac- PRO-II_LT_Trip_Times.pdf Verify that the trip unit saved the proper last trip data. 8) Repeat for the other two phases if desired. www.utilityrelay.com Page 11

4.6 Calculate Short Time (ST) Pick-Up Secondary Current Calculate the ST secondary pick-up current (STSPU) as follows: For 1-Amp AC-PRO or AC-PRO-II: STSPU = ST Pick-Up CT Primary Rating Example: If the CT Primary rating is 1600 and the ST pick-up is 6400 amps, then STSPU = 6400 = 4.00 amp 1600 For 0.5 Amp AC-PRO or AC-PRO-II: STSPU = ST Pick-Up X 0.5 CT Primary Rating Example: If the CT Primary rating is 1600 and the ST pick-up is 6400 amps, then STSPU = 6400 X 0.5 =.00 amp 1600 Note: If CT Secondary Rating is different than 1.0 or 0.5, use the 0.5 example above and replace 0.5 with the specific CT Secondary Rating. Note: If Phase CT and Neutral CT do not have the same Secondary Rating (i.e. if both not 1-Amp), temporarily turn off Ground Fault Protection in the Trip Unit when performing Long Time, Short Time, and Instantaneous Tests. 4.7 Short Time (ST) Pick-Up Test To test the ST pick-up: 1) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots to 90% of the calculated STSPU. ) Set the Phase selector (11) to either Phase A, B or C. 3) Push the Start (5) button but leave the test current on only long enough to see if a ST trip occurs. If the current is left on long enough a LT trip will occur. A ST trip should NOT occur. 4) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots to 110% of the calculated STSPU. 5) Push the Clear (8) button to reset the Timer (6) to zero. 6) Push the Start (5) button. A ST trip should occur. The test set current will stop and the Timer (6) will freeze displaying the trip time. 7) Verify that the trip unit saved the proper last trip data. 8) Repeat for the other two phases if desired. www.utilityrelay.com Page 1

4.8 Short Time (ST) Test To test the ST time delay trip: 1) The first step is to select a test current. For example, 150% of the ST pick-up. The desired test current is then 1.5 X STSPU. Note, to accurately test the ST delay, the test current must be at least 110% of the ST pick-up. ) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots until the Current (1) display shows the test current calculated in step 1. 3) Set the Phase selector (11) to either Phase A, B or C. 4) Push the Clear (8) button to reset the Timer (6) to zero. 5) Push the Start (5) button. 6) When the AC-PRO or AC-PRO-II trips, the test set current will stop and the Timer (6) will freeze displaying the trip time. 7) Compare the trip time with the TCC in Figure 9 or Figure 1 for the ST time band setting in the AC-PRO or AC-PRO-II. 8) Verify that the trip unit saved the proper last trip data. 9) Repeat for the other two phases if desired. 4.9 Calculate Instantaneous (I) Pick-Up Secondary Current Calculate Instantaneous secondary pick-up current (ISPU) as follows: For 1-Amp AC-PRO or AC-PRO-II: ISPU = I Pick-Up CT Primary Rating Example: If the CT Primary rating is 1600 and Instantaneous pick-up is 9600 amps, then: ISPU = 9600 = 6.00 amp 1600 For 0.5 Amp AC-PRO or AC-PRO-II: ISPU = I Pick-Up X 0.5 CT Primary Rating Example: If the CT Primary rating is 1600 and Instantaneous pick-up is 9600 amps, then: STSPU = 9600 X 0.5 = 3.00 amp 1600 Note: If CT Secondary Rating is different than 1.0 or 0.5, use the 0.5 example above and replace 0.5 with the specific CT Secondary Rating. Note: If Phase CT and Neutral CT do not have the same Secondary Rating (i.e. if both not 1-Amp), temporarily turn off Ground Fault Protection in the Trip Unit when performing Long Time, Short Time, and Instantaneous Tests. www.utilityrelay.com Page 13

4.10 Instantaneous (I) Pick-Up Test To test Instantaneous pick-up: 1) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots to 90% of the calculated ISPU. ) Set the Phase selector (11) to either Phase A, B or C. 3) Push the Start (5) button but leave the test current on only long enough to see if an I trip occurs. If the current is left on long enough a LT or ST trip will occur. If ST is on, it is best to temporarily turn it off. An I trip should NOT occur. 4) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots to 110% of the calculated ISPU. 5) Push the Clear (8) button to reset the Timer (6) to zero. 6) Push the Start (5) button. An I trip should occur. The test set current will stop and the Timer (6) will freeze displaying the trip time. 4.11 Calculate Ground Fault (GF) Pick-Up Secondary Current Calculate the GF secondary pick-up current (GFSPU) as follows: For 1-Amp AC-PRO or AC-PRO-II: GFSPU = GF Pick-Up CT Primary Rating Example: If the CT Primary rating is 1600 and the GF pick-up is 100 amps, then: GFSPU = 100 = 0.75 amp 1600 For 0.5 Amp AC-PRO or AC-PRO-II: GFSPU = GF Pick-Up X 0.5 CT Primary Rating Example: If the CT Primary rating is 1600 and the GF pick-up is 100 amps, then: GFSPU = 100 X 0.5 = 0.38 amp 1600 Note: If the Neutral CT Secondary Rating is different than 1.0 or 0.5, use the 0.5 example above and replace 0.5 with the specific Neutral CT Secondary Rating. 7) Verify that the AC-PRO or AC-PRO-II saved the proper last trip data. 8) Repeat for the other two phases if desired. www.utilityrelay.com Page 14

4.1 Ground Fault (GF) Pick-Up Test Verify that the Ground Fault Type (10) selector switch is in the correct position for the AC-PRO or AC-PRO-II being tested. To test the GF pick-up: 1) Set the Phase selector (11) switch to GF. ) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots to 90% of the calculated GFSPU. 3) Push the Start (5) button but leave the test current on only long enough to see if a GF trip occurs. A GF trip should NOT occur. 4) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots to 110% of the calculated GFSPU. 5) Push the Clear (8) button to reset the Timer (6) to zero. 6) Push the Start (5) button. A GF trip should occur. The test set current will stop and the Timer (6) will freeze displaying the trip time. 7) Verify that the trip unit saved the proper last trip data. 4.13 Ground Fault (GF) Time Test To test the GF time delay trip: 1) The first step is to select a test current. For example, 150% of the GF pick-up. The desired test current is then 1.5 X GFSPU. Note, to accurately test the GF delay, the test current must be at least 110% of the GF pick-up. ) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots until the Display (1) shows the test current calculated in step 1. 3) Set the Phase selector (11) to GF. 4) Push the Clear (8) button to reset the timer (6) to zero. 5) Push the Start (5) button. 6) When the trip unit trips, the test set current will stop and the Timer (6) will freeze displaying the trip time. 7) Compare the trip time with the TCC in Figure 10 or Figure 13 for the GF time band and I T settings in the AC-PRO or AC-PRO-II. 8) Verify that the trip unit saved the proper last trip data. 4.14 AC-PRO Unbalance Testing The AC-PRO Unbalance function cannot be tested with this test set. www.utilityrelay.com Page 15

4.15 Calculate Neutral Overload (NOL) Pick-Up Secondary Current Calculate the secondary NOL pick-up current (NOLSPU) as follows: For 1-Amp AC-PRO or AC-PRO-II: NOLSPU = NOL Pick-Up CT Primary Rating Example: If the CT Primary rating is 1600 and the NOL pick-up is 800 amps, then NOLSPU = 800 = 0.50 amp 1600 Example: If the CT Primary rating is 1600 and the NOL pick-up is 1600 amps, then NOLSPU = 1600 = 1.00 amp 1600 For 0.5 Amp AC-PRO or AC-PRO-II: NOLSPU = NOL Pick-Up X 0.5 CT Primary Rating Example: If the CT Primary rating is 1600 and the NOL Pick-Up is 800 amps, then NOLSPU = 800 X 0.5 = 0.5 amp 1600 4.16 Neutral Overload (NOL) Pick-Up Test (AC-PRO-II only) To test the NOL pick-up: 1) Temporarily turn Ground Fault protection OFF in the trip unit. ) Confirm the GF Switch (10) is in the Ground Return GF position. 3) Confirm the Phase Select Switch (11) is in the GF position. 4) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots until the Current (1) display shows about 90% of the NOL pick-up current (NOLSPU) previously calculated. 5) Set the Phase selector (11) to GF. 6) Push the Start (5) button. 7) Increase the test current until the display on the AC-PRO-II matches the programmed NOL pick-up. The test set current should be within ±10% of NOLSPU. 8) Push the Stop (7) button. Example: If the CT Primary rating is 1600 and the NOL Pick-Up is 1600 amps, then NOLSPU = 1600 X 0.5 = 0.50 amp 1600 Note: If the Neutral CT Secondary Rating is different than 1.0 or 0.5, use the 0.5 example above and replace 0.5 with the specific Neutral CT Secondary Rating. www.utilityrelay.com Page 16

4.17 Neutral Overload (NOL) Time Test (AC-PRO-II only) To test the NOL time delay trip: 1) The first step is to select a test current. For example, three times the NOL pickup (3X on the TCC in Figure 15). The desired test current is then 3 X NOLSPU. Note, to accurately test the NOL delay, the test current must be at least 110% of the NOL pick-up. ) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots until the Current (1) display shows the test current calculated in step 1. Release the Current Preset (13) button. 3) The GF Switch (10) should still be in the Ground Return GF position and the Phase selector (11) should still be set to GF. 4) Push the Clear (8) button to reset the Timer (6) to zero. 5) Push the Start (5) button and quickly make any minor adjustments required to the Amp Fine (15) pot. The AC-PRO-II should display the current value. 6) When the trip unit trips, the test set current will stop and the Timer (6) will freeze and display the total trip time. 7) Compare the trip time with the TCC in Figure 15 for the NOL time band setting in the AC-PRO-II. 8) Verify that the trip unit saved the proper last trip data. www.utilityrelay.com Page 17

P Pole Plug into back of QT-Display QT-DISPLAY AC-PRO REMOTE DISPLAY MICRO-CONTROLLER BASED QUICK-TRIP ON OFF N PICK-UP PUSH TO ADJUST DISPLAY CONTRAST Plug into Jack in back of QT-DISPLAY SELF TEST OK QUICK-TRIP ON UTILITY RELAY COMPANY TM PUSH TO VIEW REVIEW LAST TRIP DATA AND SETTINGS Note: Quick-Trip Switch Lockable Guard is not shown Q M Plug into "QT Display" jack Red LED is "ON" with Quick-Trip turned ON AC TRIP UNIT L PICK-UP SELF TEST OK ENTER MENU UTILITY RELAY COMPANY Figure 7: AC-PRO Quick-Trip Testing Connections L) AC-PRO Trip Unit M) AC-PRO Test Set Harness N) AC-PRO Shielded Cable: 8/C Shielded cable with modular connectors P) QT-DISPLAY (for AC-PRO) Q) Quick-Trip ON/OFF Selector Switch (for AC-PRO) www.utilityrelay.com Page 18

U T R Quick-Trip Switch Arc Flash Hazard Reduction Switch Quick-Trip ON TM (only for use with AC-PRO-II trip unit) Quick-Trip ON Quick-Trip OFF Push To Verify Red LED is "ON" with Quick-Trip turned ON Note: Quick-Trip Switch Lockable Guard is not shown Plug into Jack on back of AC-PRO-II QT Switch R S Plug into "4VDC Aux Power" Connector" DISPLAY Plug into "QUICK-TRIP Connector" AC-PRO-II Figure 8: AC-PRO-II Quick-Trip Testing Connections R) AC-PRO-II Trip Unit S) AC-PRO-II Test Set Harness T) AC-PRO-II 4/C Quick-Trip cable U) AC-PRO-II Quick-Trip Switch www.utilityrelay.com Page 19

5.0 Quick-Trip Testing In order to test the Quick-Trip settings, the QT-DISPLAY (P) and Quick-Trip ON/OFF Selector switch (Q) must be connected as shown in Figure 7 or Figure 8. 5.1 Calculate Quick-Trip Instantaneous (QT-I) Pick-Up Secondary Current Calculate the QT-I secondary pick-up current (QT-ISPU) as follows: For 1-Amp AC-PRO or AC-PRO-II: QT-ISPU = QT-I Pick-Up CT Primary Rating Example: If the CT Primary rating is 1600 and the QT-I pick-up is 9600 amps, then: QT-ISPU = 9600 = 6.00 amp 1600 For 0.5 Amp AC-PRO or AC-PRO-II: QT-ISPU = QT-I Pick-Up X 0.5 CT Primary Rating Example: If the CT rating is 1600 and the QT-I pick-up is 9600 amps, then: QT-ISPU = 9600 X 0.5 = 3.00 amp 1600 Note: If CT Secondary Rating is different than 1.0 or 0.5, use the 0.5 example above and replace 0.5 with the specific CT Secondary Rating. Note: If Phase CT and Neutral CT do not have the same Secondary Rating (i.e. if both not 1-Amp), temporarily turn off Ground Fault Protection in the Trip Unit when performing Quick-Trip Instantaneous Tests. 5. Quick-Trip Instantaneous (QT-I) Pick-Up Test To test the QT-I pick-up: 1) AC-PRO: Connect the Quick-Trip Display (P) and the Quick-Trip ON/OFF Selector switch (Q) as shown in Figure 7. AC-PRO-II: Connect the AC-PRO-II Quick-Trip switch (U) as shown in Figure 8. ) Set the Quick-Trip ON/OFF Selector switch (Q) or (U) to ON. 3) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots to 90% of the calculated QT-ISPU. 4) Set the Phase selector (11) to either Phase A, B or C. 5) Push the Start (5) button but leave the test current on only long enough to see if a QT-I trip occurs. A QT-I trip should NOT occur. 6) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots to 110% of the calculated QT-ISPU. 7) Push the Clear (8) button to reset the Timer (6) to zero. 8) Push the Start (5) button. A QT-I trip should occur. The test set current will stop and the Timer (6) will freeze displaying the trip time. 9) Verify that the trip unit saved the proper last trip data. 10) Set the Quick-Trip ON/OFF Selector switch (Q) or (U) to OFF. 11) Push the Start (5) button but leave the test current on only long enough to see if a QT-I trip occurs. A QT-I trip should NOT occur. 1) Repeat for the other two phases if desired. www.utilityrelay.com Page 0

5.3 Calculate Quick-Trip Ground Fault (QT-GF) Pick-Up Secondary Current Calculate the QT-GF secondary pick-up current (QT-GFSPU) as follows: For 1-Amp AC-PRO or AC-PRO-II: QT-GFSPU = QT-GF Pick-Up CT Primary Rating Example: If the CT Primary rating is 1600 and the QT-GF pick-up is 100 amps, then: QT-GFSPU = 100 = 0.75 amp 1600 For 0.5-Amp AC-PRO or AC-PRO-II: QT-GFSPU = QT-GF Pick-Up X 0.5 CT Primary Rating Example: If the CT Primary rating is 1600 and the QT-GF pick-up is 100 amps, then: GFSPU = 100 X 0.5 = 0.38 amp 1600 Note: If CT Secondary Rating is different than 1.0 or 0.5, use the 0.5 example above and replace 0.5 with the specific CT Secondary Rating. 5.4 Quick-Trip Ground Fault (QT-GF) Pick-Up Test Verify that the Ground Fault Type (10) selector switch is in the correct position for the AC-PRO or AC-PRO-II being tested. ) Set the Quick-Trip ON/OFF Selector switch (Q) or (U) to ON. 3) Set the Phase Selector (11) switch to GF. 4) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots to 90% of the calculated QT-GFSPU. 5) Push the Start (5) button but leave the test current on only long enough to see if a QT-GF trip occurs. A QT-GF trip should NOT occur. 6) Hold down the Current Preset (13) while adjusting the Amp Coarse (14) and Fine (15) pots to 110% of the calculated QT-GFSPU. 7) Push the Clear (8) button to reset the Timer (6) to zero. 8) Push the Start (5) button. A QT-GF trip should occur. The test set current will stop and the Timer (6) will freeze displaying the trip time. 9) Set the Quick-Trip ON/OFF Selector switch (Q) or (U) to OFF. 10) Push the Start (5) button but leave the test current on only long enough to see if a QT-GF trip occurs. A QT-GF trip should NOT occur. 11) Verify that the trip unit saved the proper last trip data. To test the QT-GF pick-up: 1) AC-PRO: Connect the Quick-Trip Display (P) and the Quick-Trip ON/OFF Selector switch (Q) as shown in Figure 7. AC-PRO-II: Connect the AC-PRO-II Quick-Trip switch (U) as shown in Figure 8. www.utilityrelay.com Page 1

6.0 Clearing Last Trip Data It is very important to clear the Last Trip Data from the trip unit after testing is complete. Leaving the Last Trip Data in the trip unit will later cause confusion for operating personnel. Follow the Instructions in the AC-PRO or AC-PRO-II trip unit Instruction Manual. 7.0 Error/Fault Conditions 7.1 Current Error The test set monitors the current level while a test is in progress. Should the current level be outside of the expected range, a current error will occur and the test set will stop current flow and display Current Error. To clear the current error the Clear (8) button must be pressed. After this, normal operation on the test set should be restored after the reason causing the error is corrected. The most likely causes for a "Current Error" are: 1) The trip unit is not powered up. ) There are loose connections in the test cable. 7. Thermal Limit 7.3 Unexpected GF Trip If a GF trip occurs when the Phase Selector (11) switch is NOT set to GF, the Ground Fault Type (10) selector switch may be incorrectly set to "Ground Return" instead of "Standard GF". 8.0 Specifications Dimensions:.1" L x 17.9" W x 10.4" D (560mm x 455mm x 65mm) Weight: 39 lbs (17.7 kg) Power Requirement: 10V, 3A Current output: Single-phase, 0-13A. Frequency: 5, 40, 50, or 60 Hertz Current Display: 0.01 Amp resolution Time Display: 0.01 Second resolution Case Information: IP67 Waterproof and Dust-proof Chemical Resistant Impact-resistant Construction Copolymer Polypropylene Compound As a protective feature, the test set will stop delivering current and display a Thermal Limit message if high levels of test current remain for a prolonged time period. The timeout for the thermal limit shutdown begins when any test current exceeds eight amps. If a thermal limit occurs it must be cleared by pressing the Clear (8) button. The test set will not allow a test to be restarted for about five seconds. Before restarting the test, verify that there are no loose connections. www.utilityrelay.com Page

This Page Intentionally Left Blank www.utilityrelay.com Page 3

AC-PRO & AC-PRO-II B-9 Secondary Injection Test Set Instruction Manual Rev 1.1 1000 1X X 4X 6X 10X 0X 1 Long Time (LT) Pick-Up 5A steps 0% to 100% of CT Rating (50A steps for CTs > 5000A) (0.5A steps for CTs < 5A) 30s LT Delay 0.5 sec. steps.0 to 30.0 sec. @ 600% LT Pick-Up 100 1 600% LT Pick-Up 150% ST Pick-Up 10.0s Short Time (ST) Pick-Up OFF & 100A steps 150% to 100% of LT Pick-Up (1000A steps for CTs > 5000A) (10A steps for CTs < 5A) SECONDS.40s I T ON.30s I 1 100% ST Pick-Up SECONDS 1.0s I T ON.15s I T ON T ON ST Delay with & without I T 1.5.10s I T ON.07s I T ON.40sec.30sec..0sec.15sec ST I T ON.10sec.1.07sec. ST I T OFF Instantaneous (I) Pick-Up OFF & 100A steps 150% to 100% of LT Pick-Up (1000A steps for CTs > 5000A) (10A steps for CTs < 5A) 150% I Pick-Up.01 1X 100% I Pick-Up X 4X 6X 10X 0X Current in Multiples of Long Time Pick-Up Figure 9: AC-PRO Overload TCC www.utilityrelay.com Page 4.

Figure 10: AC-PRO Unbalance TCC & Ground Fault TCC www.utilityrelay.com Page 5

1000 0% 40% 60% 100% 00%.1 0% 40% 60% 100% 00% Minimum possible Instantaneous (I) Pick-Up or R Quick-Trip Instantaneous (QT I) Pick-Up Allowance for 3-Phase power-up time 100 10 0% QT GF Pick-Up R Quick-Trip Ground Fault Pick-Up (QT GF Pick-Up) OFF & 10A steps 0% to 00% of CT Rating (100A Max) (100A steps for CTs > 5000A) (1A steps for CTs < 5A) SECONDS.01 0% 40% 60% 100% 00% Current in Percent of CT Rating Instantaneous Allowance for 3-Phase Power-Up Time For Very Low QT-I Settings 5 1X X 4X 6X 10X 0X SECONDS 1 00% QT GF Pick-Up 1 R Quick-Trip Instantaneous (QT I) Pick-Up 100A steps 150% to 100% of LT Pick-Up (1000A steps for CTs > 5000A) (10A steps for CTs < 5A).5 150% QT I Pick-Up Allowance for 1-Phase power-up time SECONDS 100% QT I Pick-Up.1.1.01 0% 40% 60% 100% 00% Current in Percent of CT Rating Quick-Trip R Ground Fault Time Current Curve.01 1X X 4X 6X 10X 0X Current in Multiples of Long Time Pick-Up Quick-Trip R Instantaneous Time Current Curve Figure 11: AC-PRO Quick-Trip TCC www.utilityrelay.com Page 6

AC-PRO & AC-PRO-II B-9 Secondary Injection Test Set Instruction Manual Rev 1.1 1000 1X X 4X 6X 10X 0X 1000 Long Time (LT) Pick-Up 5A steps (0.5A steps for CTs < 5A) CT Secondary Rating 0.5A and above 0% to 100% of CT Rating CT Secondary Rating below 0.5A 50% to 100% of CT Rating 100 30s LT Delay 0.5 sec. steps.0 to 30.0 sec. @ 600% LT Pick-Up 100 600% LT Pick-Up 150% ST Pick-Up.0s 10 10 Short Time (ST) Pick-Up OFF & 100A steps 150% to 100% of LT Pick-Up (10A steps for CTs < 5A) SECONDS.40s I T ON.30s I 100% ST Pick-Up SECONDS 1.0s I T ON.15s I T ON T ON ST Delay with & without I T 1.5.10s I T ON.07s I T ON.40sec.30sec.5.0sec.15sec ST I T ON.10sec.1.07sec.1 ST I T OFF Instantaneous (I) Pick-Up OFF & 100A steps 150% to 100% of LT Pick-Up (10A steps for CTs < 5A) 150% I Pick-Up.01 1X 100% I Pick-Up Instantaneous Override (I-OVRD) @ 100% of CT Rating (if applicable) X 4X 6X 10X 0X Current in Multiples of Long Time Pick-Up Figure 1: AC-PRO-II Overload TCC www.utilityrelay.com Page 7.01 AC-PRO-II O.L. Rev 1.01 01/15/015

1000 0% 40% 60% 100% 00% 100 10 0% GF Pick-Up Ground Fault (GF) Pick-Up OFF & 10A steps (1A steps for CTs < 5A) 100A Max CT Secondary Rating 0.5A and above 0% to 00% of CT Rating CT Secondary Rating below 0.5A 50% to 00% of CT Rating CT ratios over 4000 100A only (requires VDM or 4VDC) SECONDS SECONDS 1.50s.40s GF I T ON 00% GF Pick-Up GF Delay with & without I T.5.30s.0s.50sec.40sec.50sec.10s I T ON.30sec.0sec GF ends at 1xCT.1.10sec GF I T OFF.01 0% 40% 60% 100% 00% Current in Percent of CT Rating AC-PRO-II G.F. Rev 1.0 05/1/015 Figure 13: AC-PRO-II Ground Fault TCC Note: 0.5 sec GF delay setting does not comply with IEEE C37.17. www.utilityrelay.com Page 8

1000 0% 40% 60% 100% 00% 100 10 0% QT GF Pick-Up R Quick-Trip Ground Fault Pick-Up (QT GF Pick-Up) OFF & 10A steps (1A steps for CTs < 5A) 100A max CT Secondary Rating 0.5A and above 0% to 00% of CT Rating CT Secondary Rating below 0.5A 50% to 00% of CT Rating CT ratios above 4000 100A only (requires VDM or 4VDC) 5 1X X 4X 6X 10X 0X SECONDS 1 00% QT GF Pick-Up 1 R Quick-Trip Instantaneous (QT I) Pick-Up 100A steps 150% to 100% of LT Pick-Up (10A steps for CTs < 5A).5 150% QT I Pick-Up SECONDS 100% QT I Pick-Up.1.1 QT-GF ends at 1 x CT Rating.01 0% 40% 60% 100% 00% Current in Percent of CT Rating Quick-Trip R Ground Fault Time Current Curve.01 1X X 4X 6X 10X 0X Current in Multiples of Long Time Pick-Up Quick-Trip R Instantaneous Time Current Curve AC-PRO-II Q.T. Rev 1.0 01/15/015 Figure 14: AC-PRO-II Quick-Trip TCC www.utilityrelay.com Page 9

1000 100% 00% 500% 1000% Neutral Overload (NOL) Pick-up 5A steps for CTs > 5A 0.5A steps for CTs < 5A Neutral CT Secondary Rating 0.5A and above 0% to 00% of CT Rating Neutral CTs Secondary Rating below 0.5A 50% to 00% of CT Rating 30s NOL Delay 0.5 sec. steps.0 to 30.0 sec. @ 600% NOL Pick-Up 100.0s 600% NOL Pick-Up 10 SECONDS NOL ends at 100% of CT Rating. 1.5.1 100% 00% 500% 1000% Current in Percent of NOL Pick-Up AC-PRO-II NOL Rev 1. 07/14/015 Figure 15: AC-PRO-II Neutral Overload TCC www.utilityrelay.com Page 30

T P I L B

T P I L B

* I A C P R O T S * I ACPROTS Chagri n Fal l s,oh 4403 Phone:888. 89. 864 www. ut i l i t yrel ay. com